W50S6S22Q0012 - Q and A.docx
DOCX document 710 KB Posted
- Attached to
- Bldg. 12 Compressor
- Solicitation number
- W50S6S22Q0012
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 1 - Statement of Need.pdf | ||
| Attachment 2 - CERT of 52.204-24 25 26.pdf | ||
| RFQ W50S6S22Q0012.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W50S6S22Q0012 - Bldg. 12 Compressor – Q & A
Q1. The existing compressor is tank mounted. Do you need a vertical tank to be included with the install?
A1. Yes, vendor to include Tank.
Q2. If so, can the housekeeping pad in front of the existing compressor be used to install the dryer and tank?
A2. Yes, Original Compressor had filter/dryer installed in front of 3’ x 8’ concrete pad.
Q3. Is there a forklift available onsite or should we provide that?
A3. No, vendor is responsible to provide a forklift and operator. Please refer to Statement of Need: ‘Section 3 - Project Scope’ and ‘Section 9 - Government Furnished Materials/Equipment’.
Note: Doorway entrance to compressor area approximately 71” Wide x 83” Tall.
image1.tmp
File details come from the government source that posted it. Updated .