W50S6S22Q0012 - Bldg. 12 Compressor – Q & A

Q1. The existing compressor is tank mounted. Do you need a vertical tank to be included with the install?

A1. Yes, vendor to include Tank.

Q2. If so, can the housekeeping pad in front of the existing compressor be used to install the dryer and tank?

A2. Yes, Original Compressor had filter/dryer installed in front of 3’ x 8’ concrete pad.

Q3. Is there a forklift available onsite or should we provide that?

A3. No, vendor is responsible to provide a forklift and operator. Please refer to Statement of Need: ‘Section 3 - Project Scope’ and ‘Section 9 - Government Furnished Materials/Equipment’.

Note: Doorway entrance to compressor area approximately 71” Wide x 83” Tall.