2024.05.24 HANGAR 21 FALL PROTECTION UPGRADES_REV 1.pdf
PDF 2 MB Posted
- Solicitation number
- W50S6L-24-Q-0013
About this file
This document appears to be a set of engineering plans and specifications for upgrading the fall protection system in Hangar 21 at Joint Base Elmendorf-Richardson (JBER) in Alaska. The plans detail the installation of new trolley beams, hangers, and rail supports to provide a fall arrest system compliant with ANSI Z359.6 standards.
The related federal contract opportunity is for the inspection, testing, repair, and certification of the Hangar 21 fall protection system. The contractor will be responsible for managing all aspects of maintaining the continuous and safe operations of the fall protection equipment. The scope includes, but is not limited to, the required inspection, testing, and certification of the system. This opportunity is being solicited by the Alaska Army National Guard.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LEGEND:
REUSE (E) L HANGERS
NEW HANGERS THAT ATTACH TO BOTTOM CHORD OF (E) JOIST GIRDER
NEW BTWN TRUSS BOTTOM CHORD HANGERS
(E) L HANGERS
H
SC
J G
H
SC
J G
H
SC
J G
H
SC
J G
H
SC
J G
HR1
HR1
HR2
HR1
HR1
HR2
HR1
HR1
HR2
HR1
HR1
HR2
HR1
HR1
HR2
HR1
HR1
HR2
W x7
W x7
W x7
W x7
W x5
W x5
W x5
W x5
W x5
W24x76 W12x35 W12x35 W12x35 W24x76 W24x76
HR2 HR2 HR2 HR2 HR2 HR2
W14x43 RAIL SUPPORT
BEAM CENTERED ON GRID
BELOW
W14x43 RAIL SUPPORT
BEAM CENTERED ON GRID
BELOW
W14x43 RAIL SUPPORT
BEAM EAST OF GRID
BELOW
W14x43 RAIL SUPPORT
BEAM CENTERED ON GRID
BELOW
ROOF DECKING SPAN, TYP,
FOR DECK LAYOUT, SEE S161
CRANE RAIL
BY CRANE
MFR, BELOW
CRANE RAIL
BY CRANE
MFR, BELOW
CRANE RAIL
SUPPORT BY
CRANE MFR,
@ EA JOIST
GIRDER, TYP
LADDER
11 12 14 15 1913 20 21171613.1 18
HR1
HR1
HR2
HR2
C C
H J
G
C C
H J
G -S
P1
C C
H J
G
C C
H J
G -S
P1
C C
H J
G -S
P2
HR1
HR1
HR2
HR1
HR1-SP1
HR2
HR1
HR1
HR2
HR2
HR1
HR1
HR2
HR1
HR1
HR2
W x5
W x5
W x5
W x5
W x5
W24x76 W24x76 W12x35 W12x35 W24x76 W24x76
W 8x
L3x3x5/16
L3x3x5/16
HR1
HR1-SP2
HR1-SP1
HR1-SP3
HR1-SP2
HR1-SP3
HR1-SP2
HR1-SP2
HR1-SP1
HR1-SP1
3 4 5 6 9 1110
M
L
P
R
T
U
X
1.1 2 7 8
H R
H R
H R
H R
H R
H R
H R
H R
H R
H R
ACCESS
PLATFORM
RAIL BELOW
ACCESS
PLATFORM
RAIL BELOW
W12x35 W12x35
W12x35 W12x35
W12x35 W12x35 W12x35 W12x35
W12x35W12x35
W12x26 W12x26
W x3
W x3
W x3
W x3
W x3
W x3
W x3
W x3
W x3
W x3
W x3
W x3
W12x35 W12x53
W12x35 W12x35
W12x26 W12x26 W12x26
W12x35W12x35
W12x26 W12x26
W12x35W12x35
W12x26 W12x26
W12x35W12x35
W12x26
W12x35W12x53 W12x53 W12x53 W12x53 W12x53
W x6
W x6
W x6
W24x146 W24x146 W24x146
ROOF DECKING SPAN, TYP,
FOR DECK LAYOUT
W33x201 W/ 19
(3/4") CAMBER
W33x201 W/ 19
(3/4") CAMBER
W33x201 W/ 19
(3/4") CAMBER
W x1
W x1
W x1
W x1
W x1
W x1
W x1
W x1
W x1
W x1
W x1
W x1
W
P
EL
(6
7' -0
W P
EL
(6 7'
-0
W
P
EL
(6
7' -0
W P
EL
(6 7'
-0
W
P
EL
(6
7' -0
W P
EL
(6 7'
-0
W
P
EL
(6
7' -0
W P
EL
(6 7'
-0
W
P
EL
(6
7' -0
W P
EL
(6 7'
-0
W
P
EL
(6
7' -0
W P
EL
(6 7'
-0
RAIL SUPPORT,
4- EQ SP @ EA
W33x120
X
Z
BB
DD
EE
FF
H R
H R
H R
H R
H R
H R
H R
H R
H R
H R
H R
H R
W12x26
W x8
W x8
W12x26
W12x35W12x35
W12x35 W12x35
W x3
W x3
W x3
W x3
W12x35W12x35
W12x35W12x35
W x3
W x3
W12x35W12x35
W12x35 W12x35
W x3
W12x35W12x35
W12x35 W12x35
W x3
W12x35W12x35
W12x35 W12x35
W x3
W12x35W12x35
W12x35 W12x35
W24x146 W24x146 W24x131 W24x146
W33x201 W/ 19
(3/4") CAMBER
W33x201 W/ 19
(3/4") CAMBER
W33x201 W/ 19
(3/4") CAMBER
W33x201 W/ 19
(3/4") CAMBER
W x1
W x1
W x1
W x1
W x1
W x1
W x1
W x1
W
P
EL
(6
7' -0
W P
EL
(6 7'
-0
W
P
EL
(6
7' -0
W
P
EL
(6
7' -0
W
P
EL
(6
7' -0
W
P
EL
(6
7' -0
W
P
EL
(6
7' -0
")RAIL SUPPORT,
4- EQ SP @ EA
W33x120
CRANE RAIL
BY CRANE
MFR, BELOW
ROOF DECKING SPAN, TYP,
FOR DECK LAYOUT
CRANE RAIL
SUPPORT BY
CRANE MFR,
@ EA JOIST,
TYP
CRANE RAIL
BY CRANE
MFR, BELOW
LADDER
S-501
DOUBLE W10x39 TROLLEY
BEAMS FOR C-17 WINGS, TYP
S-501
COPED DOUBLE W8x21
TROLLEY BEAMS AT C-17
TAIL
14'-1"
33'-11"
3'- 0"
'-0
'-0
'-0
'-0
'-0
7'-
07 8"
3'- 0"
'-0
'-0
'-0
'-0
8'- 0"
'-0
3'-
0"
6'-0"
(E) DRAFT CURTAIN,
(NOTE 1)
33'-11" 6'-4"
1'-8" (TYP)
CL W8 TO CL W8
DOUBLE W8x21 TROLLEY
BEAMS ABOVE FUSELAGE
WORK POINT
33'-11"33'-11"6'-4"
DOUBLE W10x39 TROLLEY
BEAMS FOR C-130 WINGS
DOUBLE W10x39 TROLLEY
BEAMS FOR C-130 WINGS
1'- 8"
(TY
P)
CL
W
TO
C L W
PENETRATION THROUGH (E)
DRAFT CURTAIN (NOTE 2)
5'-0"
PENETRATION THROUGH (E)
DRAFT CURTAIN (NOTE 2)
S-502
S-502
SIM
(E) JOIST GIRDER
(E) JOIST GIRDER
5'- 7"
38'-6 1 2 "
38'-6 1 2 " 5'-0"
DOUBLE W10x39 TROLLEY
BEAMS AT C-17 WING, TYP
T.O.S. EL= 48' - 7 5/8"
WORK POINT
38'-6 1 2"
38'-6 1 2"
5'-0"
S-502
38'-3"
38'-3"
38'-3"
38'-3"
5'-0"
1'- 8"
(TY
P)
CL
W
TO
C L W
1'-8" (TYP)
CL W8 TO CL W8
3'-0"
14'-0"
11'-10"
14'-1"
3'-0"
14'-0" 11'-10"
1'- 6"
CL
W
8 T O
W8
S-502
TYP OF 4
S-502
TYP OF 4
TYP
OF 6
SIM, ELEVATIONS
DIFFER
TYP OF 7
DOUBLE W8x21 TROLLEY
BEAMS ABOVE FUSELAGE
T.O.S. EL= 47' - 9 3/4"
S-501
(E) FOAM
GENERATOR
IN ALCOVE
(E) FOAM
GENERATOR
IN ALCOVE
7'-
7 8"
6'- 9"
TROLLEY BEAM DISCONTINUITY @
(E) OVERHEAD BRIDGE CRANE
'-1
11 4"
'-0
3 4"
S-503
S-503
S-503
S-503
SCALE:
S-101
FALL PROTECTION LAYOUT PLAN
1/16" = 1'-0"
SHEET NOTES:
1. (E) DRAFT CURTAIN IS CONSTRUCTED OF 18 GAUGE STEEL AND DESCENDS 5'-2" BELOW (E) PAINT BOOTH CEILING.
PENETRATIONS WHERE W8 TROLLEY BEAMS PASS THROUGH (E) DRAFT CURTAIN SHALL BE FULLY PATCHED WITH MINERAL
WOOL AND/OR FIRESTOP SEALANT (HILTI CFS-S SIL GG, OR EQUAL).
2. T.O. (E) SLAB EL = 0'-0".
3. FALL ARREST SYSTEM COMPLIES WITH ANSI Z359.6. SEE SHEET S-503 FOR GENERAL NOTES.
4. THE HSC HANGAR BAY HAS OVERHEAD BRIDGE CRANES. THE USER'S FALL PROTECTION PLAN SHALL INCLUDE OPERATIONAL PROCEDURES TO PREVENT CONFLICT BETWEEN THE FALL ARREST ATTACHMENTS AND THE (E) OVERHEAD CRANES.
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
1 2 3 4 5
2 3 4 5 ph 907.276.6664
800 F Street Anchorage, AK 99501 www.coffman.com AECC249
AIR NATIONAL
GUARD JOINT
BASE
ELMENDORF-RICHARDSON
RE-ISSUED FOR
CONSTRUCTION
HANGAR 21 FALL
ARREST SYSTEM
REPLACEMENT
01/05/2024
231472
01-05-24 IFC0
FALL
PROTECTION
LAYOUT PLAN
S-101
BMH
DRB
0 4 8 12 16 24 32 48 1/16"=1'-0"
05-24-24 RE-IFC1
R EG IS T ER ED P R O F E S S IO NA L ENGINEER
No. SE 13701
MATTHEW C. STIELSTRA
May 24, 2024 http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com
(E) 2L8x8 JOIST GIRDER
BOTTOM CHORD
(4) 1/2"Ø A325 BOLTS SPACED AT
BEAMS' GAUGE, TYPICAL
W8 TROLLEY BEAMS
1'-8"
(E) W6x25x1'-5"
W10x39x2'-2"
1'-1" 1'-1"
3/16 3
EL = 49'-2"
EL = 47'-9 3/4"
W8 T.O.S.
1/2"Ø BOLT EA SIDE FOR WEB
SPACED AT W6 BEAM GAUGE, TYP
2",TYP
(E) VACANT BOLT HOLES FROM
(E) TROLLEY BEAM DEMO
(E) BOLTS TRUSS WEB PLATE
(E) TRUSS BOTTOM
CHORD
W8 TROLLEY BEAM
S-501
1'-6"
W8 TROLLEY BEAMS
HANGER PL3/8
BEAM
HANGER
PLATE
BEAM
HANGER
PLATE
VERIFY1"1"1
2"
1 2"
1" 2"
1"
1 2"
TRUSS WEB PL7/8x3x1'-0"
41 4"
3/16 3/16
3/16
3/16 EACH SIDE
HANGER PL3/8
TAB PL 3/8x2x0'-4-1/2" CENTER ON
AND ALIGN WITH TROLLEY BEAM
WEB (2) 5/8" DIAM A325 BOLTS
(E) TRUSS BOTTOM CHORD
(FIELD VERIFY SIZE)
END PL 3/8
3/16
3/16 EACH SIDE
L2-1/2x2-1/2x1/4 WHEEL STOP EACH
SIDE WITH (1) 1/2" DIAM A307 BOLT
NOTE 1
4"
3/16 2
3/16 2 EACH SIDE
L2x2x1/4 DIAGONAL BRACE
EACH SIDE UP TO NEAREST
TOP CHORD WEB NODE
PJP EACH SIDE AT JOINTS
G
TROLLEY END CONDITION SHOWN. AT
INTERMEDIATE SUPPORTS COPED W8 TROLLEY
BEAM, TAB PLATE AND HANGER PLATE SHALL
BE MIRRORED ABOUT JOIST CENTERLINE.
1'-8"
EQ
8" 11
8"
EQ
(E) W12x22 CEILING GRID FRAMING
(E) L HANGER FRAMING FROM (E)
FALL PROTECTION SYSTEM. "U"
SHAPE SHOWN OCCURS ON BOTH
SIDES OF (E) W12. BOTTOM OF "U" IS
(E) L5x3x3/8 LLV.
W16x26x2'-11
4", TYP OF 2 NEAR SIDE
AND FAR SIDE @ EACH (E) "U"
SHAPE HANGER.
(2) 1/2"Ø BOLTS THROUGH (E) HOLES
IN (E) L5x3
(4) 1/2"Ø BOLTS @ EACH W8-W16
CONN. CENTER BOLTS ON BEAM
FLANGE FLATS
W8 TROLLEY BEAMS PER PLAN
EL = 40'-5"
EL = 38'-7 1/2"
SCALE:
S-501
TROLLEY BEAM CONNECTION DETAIL @ CCH FUSELAGE
1-1/2" = 1'-0"
SCALE:
S-501
TROLLEY BEAM CONNECTION DETAIL @ HSC HANGAR FUSELAGE
1-1/2" = 1'-0" SCALE:
S-501
COPED TROLLEY BEAMS TRUSS BOTTOM CHORD CONN. PLAN
3" = 1'-0"
SCALE:
S-501
COPED TROLLEY BEAMS ELEVATION
3" = 1'-0"
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
1 2 3 4 5
2 3 4 5 ph 907.276.6664
800 F Street Anchorage, AK 99501 www.coffman.com AECC249
AIR NATIONAL
GUARD JOINT
BASE
ELMENDORF-RICHARDSON
RE-ISSUED FOR
CONSTRUCTION
HANGAR 21 FALL
ARREST SYSTEM
REPLACEMENT
01/05/2024
231472
01-05-24 IFC0
TROLLEY BEAM
DETAILS
S-501
RJP
MCS
0 1' 2' 1 1/2"=1'-0"
6"
3"=1'-0" 12"6"0 3" 9"
05-24-24 RE-IFC1
SHEET NOTES:
1. ALL TROLLEY BEAMS SHALL HAVE A L4x4x1/4"x0'-4 1/2"
WHEEL STOP ON EACH SIDE OF THE WEB, ATTACHED
WITH (1) 1/2" DIAM. A307 BOLT, UNO.
R EG IS T ER ED P R O F E S S IO NA L ENGINEER
No. SE 13701
MATTHEW C. STIELSTRA
May 24, 2024 http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com
TOS EL=38'-7 1/2"
1'-8"
10" 10"
TOS EL=39'-5 3/8"
1'- 8"
3/16
3 TOP EDGES
TYP OPTION 1
OPTION 2: (3) 1/2"Ø
THRU-BOLTS BOTTOM
FLANGE OF W10 TO TOP
FLANGE OF W8
WORK POINT
W10 PER PLAN, TYP
W8 PER PLAN
1'-8"
W6x20x2'-4"
W10 TROLLEY
BEAMS PER PLAN
8'- 1 7
/8"
(E) JOIST GIRDER (JG) BOTTOM
CHORD (2L8x8x3/4).
NOTE: (E) JG IS NOT PERPENDICULAR
TO TROLLEY BEAMS @ C-17 WINGS
AS SHOWN. REFER TO PLAN.
EL=39'-5 3/8"
S-502
CAULK PENETRATION PER
NOTE 2 ON S-101 (SIM)
(4) 3/4"Ø BOLTS @ EACH
W6-W10 CONN. CENTER BOLTS
ON BEAM FLANGE FLATS
S-502
WT16.5x59x1'-0"
AT CONTRACTOR OPTION FABRICATOR
MAY CONSTRUCT WT FROM 3/8" PLATE
WITH 1/4" FILLET WELD IN LIEU OF
STANDARD WT16.5 AS SHOWN.
EL=47'-7 1/4"±
EL=41'-5 1/4"
L4x4x1/4 W/ U-BOLT
PIPE 3 X-STRONG
1/4
WT16.5
(E) 2L8x8 JOIST GIRDER
BOTTOM CHORD
1"
FIELD VERIFY
3/16 2
EA END
OF WT
1/2"Ø THRU-BOLTS
PIPE 3
11 8" 11 2"
3" 11 2"
(E) W12x22 PAINT
BOOTH CEILING
FRAMING
(E) W12x22 PAINT
BOOTH CEILING
FRAMING
U-BOLT CENTERED
ON L4x4 VERT LEG
PIPE 3
L4x4 W/ ENDS
BEARING
ON (E) W12
VA
RI
ES
(1
0'- 0"
M
IN
3/16 TYP
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
1 2 3 4 5
2 3 4 5 ph 907.276.6664
800 F Street Anchorage, AK 99501 www.coffman.com AECC249
AIR NATIONAL
GUARD JOINT
BASE
ELMENDORF-RICHARDSON
ISSUED FOR
CONSTRUCTION
HANGAR 21 FALL
ARREST SYSTEM
REPLACEMENT
01/05/2024
231472
REG IS T ER ED P R O F E S S I O NA L ENGINEERJan 05, 2024 No. SE13701
MATTHEW C. STIELSTRA
01-05-24 IFC0
TROLLEY BEAM
DETAILS
S-502
RJP
MCS
SCALE:
S-502
CCH TROLLEY BEAM INTERSECTION
1" = 1'-0"
0 1 2 3 1"=1'-0"
SCALE:
S-502
TROLLEY BEAM HANGER DETAIL @ CCH WINGS (C-130 SHOWN, C-17 SIM)
1" = 1'-0"
SCALE:
S-502
WT TO (E) BOTTOM CHORD DETAIL
1" = 1'-0" SCALE:
S-502
HANGER BRACING DETAIL @ CCH WINGS
1" = 1'-0" http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com AutoCAD SHX Text A
AutoCAD SHX Text K
AutoCAD SHX Text A
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text
AutoCAD SHX Text
TH
AutoCAD SHX Text S
(4) 1/2"Ø A325 BOLTS SPACED AT
BEAMS' GAUGE, TYPICAL
W10 TROLLEY BEAMS
1'-8"
W6x25x2'-4"
FIELD WELD TO (E)
JG ABOVE PER 2/E9
EL = 48' - 7 5/8"
W10 T.O.S.
(E) JOIST GIRDER (JG)
BOTTOM CHORD (2L8x8x3/4)
NOTE: (E) JG IN NOT PERPENDICULAR
TO TROLLEY BEAMS AS SHOWN.
REFER TO PLAN AND DETAIL.
EL = 49' - 2"
W10 T.O.S.
S-503
(4) 1/2"Ø A325 BOLTS SPACED AT
W10 GAUGE, TYPICAL
W10 TROLLEY BEAMS
1'-8"
S-503
(E) JOIST GIRDER (JG)
BOTTOM CHORD (2L8x8x3/4)
NOTE: (E) JG IN NOT PERPENDICULAR
TO TROLLEY BEAMS AS SHOWN.
REFER TO PLAN AND DETAIL.
EL = 50' - 3"
WIDE FLANGE CONSTRUCTED OF
PL 1/2. FIELD WELD TOP FLANGE
TO (E) JG ABOVE 2/E9
STIFFENER PL 1/2, TYP
EA SIDE OF WEB
EL = 48' - 7 5/8"
W10 T.O.S.
1'- 73 8"
PL 1/2x6 1/8x2'-4"
1/4TYP
1'-8"
PLAN VIEW
W-BEAM THAT ATTACHES
TO UNDERSIDE OF JG
BOTTOM CHORD
CL W10 TROLLEY
BEAMS (BELOW)
L8x8x3/8 JG
BOTTOM CHORD
3/16 3
3/16 3
1813.112 19
OPP HAND
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
1 2 3 4 5
2 3 4 5 ph 907.276.6664
800 F Street Anchorage, AK 99501 www.coffman.com AECC249
AIR NATIONAL
GUARD JOINT
BASE
ELMENDORF-RICHARDSON
RE-ISSUED FOR
CONSTRUCTION
HANGAR 21 FALL
ARREST SYSTEM
REPLACEMENT
01/05/2024
231472
01-05-24 IFC0
TROLLEY BEAM
DETAILS
S-503
RJP
MCS
SCALE:
S-503
HSC HANGAR WING TROLLEY BEAM CONNECTION DETAIL @ GL 12 & GL 19
1 1/2" = 1'-0"
0 1' 2' 1 1/2"=1'-0"
6"
SCALE:
S-503
HSC HANGAR WING TROLLEY BEAM CONNECTION DETAIL @ GL 13.1 & GL 18
1 1/2" = 1'-0"
SCALE:
S-503
HSC HANGAR WING TROLLEY BEAM CONNECTION DETAIL
1 1/2" = 1'-0"
FALL ARREST SYSTEM GENERAL NOTES:
THE HANGAR 21 ACTIVE FALL PROTECTION SYSTEM IS A FALL ARREST SYSTEM PER ANSI Z359.6. EXCEPTIONS HAVE NOT BEEN MADE TO THE STANDARD.
ANY CHANGES TO THE FALL ARREST SYSTEM MAY ONLY BE DONE BY A QUALIFIED PERSON.
EACH TROLLEY BEAM IS EQUIPPED WITH A SINGLE TROLLEY ANCHOR. ONLY ONE (1) USER AT A TIME IS PERMITTED FOR EACH TROLLEY ANCHOR, BUT ALL TROLLEY ANCHORS MAY BE USED SIMULTANEOUSLY FOR A MAXIMUM OF SIX (6) USERS IN THE CORROSION CONTROL BAY AND TEN (10) USERS IN THE HSC BAY. THE MAXIMUM ARREST FORCE IS 1800
POUNDS PER ANSI Z359.6 SECTION 5.3.1.1.1.
TROLLEY ANCHORS HAVE BEEN DESIGNED FOR THE MAXIMUM ARREST FORCE OF 1800 POUNDS WITH A SAFETY FACTOR OF TWO FOR A 3600 POUND ANCHOR DESIGN LOAD.
THE FOLLOWING BASIS OF DESIGN EQUIPMENT IS USED WITH THE TROLLEY BEAMS:
1. TROLLEY ANCHOR BY 3M DBI SALA, MODEL 2103143. EQUIVALENT PRODUCTS SHALL BE ANSI Z359.18 CERTIFIED AND MAY ONLY BE SUBSTITUTED BY A QUALIFIED PERSON.
2. SELF-RETRACTING DEVICES (SRD) SHALL BE 3M DBI SALA SMART-LOCK SELF-RETRACTING DEVICE, MODEL 3503878. EQUIVALENT PRODUCTS SHALL BE ANSI Z359.14 CLASS 1
CERTIFIED AND MAY ONLY BE SUBSTITUTED BY A QUALIFIED PERSON.
3. SNAP HOOKS AND CARABINERS SHALL BE SELF-CLOSING / SELF-LOCKING BY DBI SALA OR APPROVED EQUIVALENT THAT COMPLIES WITH ANSI Z359.1 AND COMPATIBLE WITH
THE SRD.
EQUIPMENT SHALL BE INSPECTED BY THE USER PRIOR TO EACH USE - FOLLOW MANUFACTURER INSTRUCTIONS.
THE SYSTEM SHALL BE INSPECTED ANNUALLY BY A COMPETENT PERSON.
THE SYSTEM SHALL BE RE-CERTIFIED EVERY FIVE YEARS BY A COMPETENT PERSON.
AFTER A FALL EVENT, THE EFFECTED PORTIONS OF THE SYSTEM SHALL NOT BE USED UNTIL INSPECTED BY A COMPETENT PERSON.
AFTER HEAVY USE, INSPECTION AND/OR RE-CERTIFICATION FREQUENCY CAN BE INCREASED IF DEEMED APPROPRIATE BY A COMPETENT PERSON.
THE SYSTEM WAS NOT DESIGNED FOR RESCUE. THE SYSTEM WOULD NEED TO BE RE-QUALIFIED WITH POTENTIALLY DIFFERENT TROLLEY ANCHORS TO BE USED FOR RESCUE
WITHOUT LIMITATION.
05-24-24 RE-IFC1
R EG IS T ER ED P R O F E S S IO NA L ENGINEER
No. SE 13701
MATTHEW C. STIELSTRA
May 24, 2024 http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com
| Sheets and Views |
| S-101 FALL PROTECTION LAYOUT PLAN |
| S-501 TROLLEY BEAM DETAILS |
| S-503 TROLLEY BEAM DETAILS |
File details come from the government source that posted it. Updated .