Questions and Answers – W25G1V‐18‐R‐0030
Q1. It was indicated that a sprinkler head needs to be relocated. What is the system, water, dry or chemical? Does the government want engineered drawings for this application or are we moving the head to accommodate the tank?
A1. The system is wet. Engineered drawings are not required, we just require the head to be moved in order to accommodate the tank.
Q2. At the walk‐through it was indicated that the contractor would have access to the Government Crane to set the equipment and steel due to the difficult location, is this correct?
A2. The crane will be available for use. The contractor shall provide evidence of training in the safe use of an overhead crane prior to use of equipment.