QUESTIONS AND ANSWERS – SHOREHAM TANK SYSTEM
QUESTION 1. My supplier has advised me the UPS you specified for the Omntec system, can be a 15 minute or 48 hour supply. Obviously the latter is more expensive. Please advise which one will be required
ANSWER: The 48 hour supply should be utilized
QUESTION 2. Where inside the Admin & OMS buildings will the new Omntec units be located. Can I assume on the inside of the exterior wall for each? Running conduits thru the buildings can get expensive.
ANSWER: Location of new Omntec units be located where the current inoperable systems are. Existing conduit is already in place and will be used.
QUESTION 3. Where will these units "tie- into" the Army network. Is there a central computer station? Where is this located in each building
ANSWER: Existing conduit is already in place and will be used. These will not be tied into any network, they are stand-alone
QUESTION 4. Can you please let me know where I can find drawings & specs for this job?
ANSWER: Map was already posted to FEDBIZOPPS. Site Visit is May 14 at 9AM at the Kerry P. Heim USARC. Contact SFC Alejandro Cuevasvargas 661-910-3494 who will be onsite. If you can’t make this site visit please contact the Contract Specialist, Ellen Widelitz, 609-562-2384