VASOW100 STATEMENT OF WORK (ATTACHED).docx
DOCX document 17 KB Posted
- Attached to
- M1DA--CAT Generator PMI -New Requirement
- Solicitation number
- 36C26224Q0277
About this file
This statement of work outlines requirements for replacing a diesel particulate filter controller on an emergency generator at a Veterans Affairs medical center. The contractor will provide all labor, equipment, transportation and parts to remove the existing controller and replace it with a new unit that meets the generator manufacturer's specifications. The technician performing the work must have at least five years of experience working on similar generator systems. After replacement, the generator must be load tested for two hours at its rated capacity while monitoring operating parameters. The contractor must be certified to service the generator make and model, have direct access to replacement parts, and at least ten years of experience working on comparable emergency power systems. The period of performance is approximately 90 to 105 days at the West Los Angeles VA Medical Center.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 52.212-1 INSTRUCTIONS TO OFFERORS-COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES.docx | DOCX document | |
| 36C26224Q0277.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
?.## STATEMENT OF WORK
STATEMENT OF WORK (SOW)
As of November 21, 2023
1. PROJECT: VAWLA Emergency Medical Air Compressor Pumps Purchase and replacement.
2. OBJECTIVE: Prospective Contractor to provide all parts, materials and labor required to replace Distilled Particulate Filter (DPF) controller on CAT 200KVA unit/emergency power generator located at building 304, on the West Los Angeles Veterans Affairs facility (WLAVA). WLAVA is located at 11301 Wilshire Blvd. Los Angeles CA 90073.
3. SCOPE: DPF Controller to be replaced shall meet the manufacturer requirements and specifications for CAT engine to meet AQMD requirements.
4. Program Point of Contact: To Be Determined
Name:
Section:
Address:
Phone Number:
Fax Number:
E-Mail Address:
5. TASK SPECIFICATIONS: The Contractor shall provide all necessary labor, equipment, transportation, and related items to provide, remove and replace DPF for CAT engine powering 200KVA generator for building 304 WLAVA medical center. Contractor to provide service must be licensed to work on CAT emergency power standby generators. Technicians to perform the repair must have at least 5 years’ experience working on CAT engines and their DPF systems. After replacement of DPF controller technician must load bank the unit for 2 hours at the nameplate load rating capacity. Technician must take and record readings of engine oil pressure, engine temperature, fuel pressure, and generator voltage/ amperage readings. No additional work / costs incurred that are not specifically listed in the Statement of Work are authorized without written approval by contracting officer. Pre-approval of replacement or unknown parts/costs must be obtained from the Contracting Officer prior to any work being performed.
6. Contractor Requirements:
a) Contractor shall be certified to perform service and maintenance to CAT Engine driven generator sets.
b) Contractor shall have a direct line to CAT engine/generator parts.
c) Contractor must have a minimum of 10 years recorded experience working with CAT emergency power generator sets at least 200KVA rating.
d) Contractor must have all required certifications to work on CAT emergency power generators and be able to access any data and parts required to change out DPF controller and test to confirm repair is complete.
7. Security Requirements: Contractor shall be granted access to work areas via COR or assigned VA personnel.
8. Government-Furnished Equipment / Government-Furnished Information: NONE
9. Place of Performance: WLAVA Medical Center
10. Period of Performance: Approximately 90-105 Days
11. Delivery Schedule: N/A
File details come from the government source that posted it. Updated .