VA701-17-R-0092-00002002.pdf
PDF Posted
- Solicitation number
- VA70117R0092
About this file
This document includes an equipment schedule and drawings for a solar photovoltaic project at the North Las Vegas VA Medical Center. Key details include specifications for three medium voltage transformers ranging from 225 to 2000 kVA to step up voltage from 12.47 kV to 480V. Drawings show the installation of new medium voltage switchgear and conduits to interconnect the transformers and distribute power to various buildings. The project involves the Department of Veterans Affairs and aims to fulfill requirements under the VISN 21 Las Vegas Energy Savings Performance Contract solicitation to implement energy savings measures at the North Las Vegas VA facility.
VA701-17-R-0092 00002 Q15_PV801_Overall Power Plan.pdf
View the file
Other files
Show 40 more
Latest 50 of 165 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EQUIPMENT SCHEDULE - MV
IDTYPEMANUFACTURERMODELQUANTITYCURRENT AND
VOLTAGE RATINGOCPD AT EACHNOTES
G1
TRANSFORMER
(XFM-1 & 2)
CG POWER OR
EQUIVALENT1500KVA212.47kV GND WYE /
480V WYE
(3) OIL IMMERSED 80A
FUSES ON 12.47KV SIDE
DEAD-FRONT RADIAL FEED
CONFIGURATION PER VA
SPECIFICATIONS
G2
TRANSFORMER
(XFM-4)
CG POWER OR
EQUIVALENT2000KVA112.47kV GND WYE /
480V WYE
(3) OIL IMMERSED 100A
FUSES ON 12.47KV SIDE
DEAD-FRONT RADIAL FEED
CONFIGURATION PER VA
SPECIFICATIONS
G3
TRANSFORMER
(XFM-3)
CG POWER OR
EQUIVALENT225KVA112.47kV GND WYE /
480V WYE
(3) OIL IMMERSED 15A
FUSES ON 12.47KV SIDE
DEAD-FRONT RADIAL FEED
CONFIGURATION PER VA
SPECIFICATIONS
MEXISTING
MANHOLE--3--MANHOLE FOR MV RUN
NSWITCHGEARSQUARE D-115KV-RATED, 600AFUSED, VISIBLE, LOCKABLE
DISCONNECT SWITCH
NV ENERGY REQUIRES
GENERATION METER. VA
DOES NOT INTEND TO
RECOGNIZE RENEWABLE
ENERGY CREDITS
OPROTECTIVE
RELAYSEL751A OPTION (73)1--
INSTALL PTs AT
CUSTOMER'S SWITCHGEAR
ON THE NV ENERGY SIDE
OF THE BREAKER
PEXISTING MAIN
SWITCHGEAREATON
VACCLAD-W
SWITCHGEAR
ASEMBLY
112.47KV, 1200A,
1200A MAIN SET TO 240A TRIP
USE EXISTING, DEDICATED
SPARE BREAKER FOR PV
INTERCONNECTION.
QMINI POWER
ZONE
SQUARE D
OR EQUIV.TBD1480V-120VAC, 1KVA,
XXAINTERNAL PROTECTION
MINI-POWER ZONE TO
POWER MONITORING
EQUIPMENT AND REVERSE
POWER RELAY
MEDIUM VOLTAGE WIRE AND CONDUIT SCHEDULE
RUN #CONDUITCONDUCTORSNEUTRALGROUNDNOTES
1(N) (1) 3-1/2" PVC_40(N) (3) 2/0 AWG COPPER 15KV,
MV-105, 133%--
(1) 2 AWG Cu, 15KV, MV-105, 133%
2(E) (1) 6" SPARE (N) (3) 2/0 AWG COPPER 15KV,
MV-105, 133%--
(1) 2 AWG Cu, 15KV, MV-105, 133%
ROUTE NEW
CONDUCTORS
THROUGH EXISTING
SPARE CONDUIT
3(E) (1) 6" SPARE(E) (3) 500 KCMIL COPPER, 15KV,
MV105, 133%--
(1) 1/0 AWG Cu, 15KV, MV-105, 133%
EXISTING 500MCM
FROM MH-N7 TO MH-N1
TO MS-1
4(N) (1) 4" PVC_40(N) (3) 2/0 KCMIL COPPER, 15KV,
MV-105, 133%--
(1) 2 AWG Cu, 15KV, MV-105, 133%
5(N) (1) 5" PVC_40(E) (3) 500 KCMIL COPPER 15KV,
MV105, 133%--
(1) 1/0 AWG Cu, 15KV, MV-105, 133%
6(N)(1) 4" PVC_40(N)(3) 4/0 KCMIL COPPER, 15 KV,
MV-105, 133%--
(1) 1/0 AWG Cu, 15KV, MV-105, 133%
7(E)(1) 6" PVC_40(N)(3) 4/0 KCMIL COPPER, 15KV,
MV-105, 133%--
(1) 1/0 AWG Cu, 15KV, MV-105, 133%
P
SWG
GEN MTR
MTR
M
N12
G3
XFM-3
HV FUSE
G2
XFM-4
HV FUSE
G1
XFM-2
HV FUSE
SWITCH
M
N1
G1
XFM-1
HV FUSE
M
N7
M
N7
Q
XF
MAIN
EXISTING MAIN SWITCHGEAR (MS-1)
POINT OF PV INTERCONNECTION
"PCC"
AT EXISTING SPARE BREAKER
SET OVERCURRENT TO 241A
PER NV ENERGY SYSTEM IMPACT STUDY
DATED 2.18.16
SWITCHGEAR TO COMBINE PV XFM OUTPUTS
INCLUDES
GENERATION METER
VISIBLE, LOCKABLE SWITCH
REVERSE POWER RELAY
ROUTE THRU
EXISTING MANHOLE TO
NEW MV SWITCHGEAR
EXISTING
NV ENERGY METER
RELAY (SEL 751A)
POWER IN
RLY FDBK
12.47k:120V PTs
1200:5 CTs
PHASE 7 (LOT D) (PNL-7.1)
PHASE 3 (LOT B) (PNL-4)
PHASE 4 (LOT C) (PNL-4)
PHASE 8 (GND-MNT) (PNL-G1.1)
PHASE 9 (GND-MNT) (PNL-G2.1)
PHASE 10 (TANKS) (PNL-T.1)
TO GRID
N
O
PHASE 2A (LOT A) (PNL-3)
PHASE 2B (LOT A) (PNL-3)
PHASE 6 (LOT E) (PNL-3)
S
(N) 2-WAY SPLICE
CONNECT XFM-1 TO (E)
500KCMIL CONDUCTORS
S
(N) 3-WAY SPLICE
CONNECT XFM-1AND XFM-3 TO
(E) 500KCMIL CONDUCTORS
INPUTS
(2)4 (1)5
OUTPUT
(1)6
EXISTING
POWER IN
PANEL "X"
CB-X
(1)15A/1P BRKR TO POWER SEL 751(A)
(1)15A/1P BRKR TO POWER SHARK 100
(1)15A/1P BRKR TO POWER MEDIA CENTER
F H
FH
FH
FH
F H
F H
FH
FH
F H
FH
F H
FH
FH
F H
F H
F H
FH
F H
FH
F H
F H
FH
OFFICE OF
CONSTRUCTION AND
FACILITIES
MANAGEMENT
C
R
PROJECT NUMBER
DATEDESCRIPTION
THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF
REC SOLAR COMMERCIAL CORPORATION.
CONTRACTOR
REC SOLAR
810 FIERO LANE, SUITE 200
SAN LUIS OBISPO, CA 93401
PH (805) 477-3970
FX (805) 540-6040
(844) REC SOLARSHEET NUMBER
PROJECT MANAGER
PROJECT ENGINEER
ASSOCIATE ENGINEER
CHECKED BY
EDCBA
PV801 6
PROJECT
EDCBA
ENGINEERCLIENT
SHEET TITLE
DATE
R
PROJECT NUMBER
REVDATEDESCRIPTION
THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF
REC SOLAR COMMERCIAL CORPORATION.
CONTRACTOR
REC SOLAR
810 FIERO LANE, SUITE 200
SAN LUIS OBISPO, CA 93401
PH (805) 477-3970
FX (805) 540-6040
(844) REC SOLARSHEET NUMBER
PROJECT MANAGER
PROJECT ENGINEER
ASSOCIATE ENGINEER
CHECKED BY
EDCBA
PROJECT
EDCBA
14 ENGINEERCLIENT
SHEET TITLE
DATE11/14/2016
VALV.14580.EPC
BOB FISHER
JESSICA KENDRICK
ZORAN IVANCEVIC
RECORD SET
NORTH LAS VEGAS SOLAR PV PROJECT
6900 NORTH PECOS RD
NORTH LAS VEGAS, NV 89086
CONTRACT NUMBERVA701-14-C-0045
CLIENT CONTACTCLIENT NAME
CONTRACTING
OFFICER (CO)SEAN KAMINSKI
REPRESENTATIVE
(COR)DREW DOWNEN
CONTRACT
SPECIALIST (CS)SCOTT ELIAS
100% SET
8/25/15STRUT SWAP
1/26/16NV ENERGY COMMENTS
02/24/16RELOCATE XMF-3
3/04/162ND NV ENERGY COMMENT
05/25/16ADD SWB-5 TO XMF-4
11/14/16RECORD SET
05/29/15
OVERALL POWER PLAN
MEDIUM VOLTAGE
NTS
MEDIUM VOLTAGE SITE DISTRIBUTION
NTS
ELECTRICAL SINGLE LINE - MEDIUM VOLTAGE
ANTS
EXISTING FACILITY SERVICE
NTS
PROTECTION ELEMENTS - SEL 751A
NTS
INSTRUMENT POWER
3A
LEGEND
-WIRE LABEL
F
PPP1
EQUIPMENT ID PER
EQUIPMENT SCHEDULE
EQUIPMENT SYMBOL
EQUIPMENT LABEL
REFERRED TO IN PLANS
KEY MAP
(E) MH-N12
(E) MH-N7
(E ) M
H -N
XFM-1
"G1"
XFM-2
"G1"
XFM-3
"G3"
XFM-4
"G2"
(NEW 480VAC
SWITCHBOARD TO
INTERCEPT FEEDS
CURRENTLY
PULLED TO XFM-4
PAD)
(N) CONDUIT BY REC
(N) WIRE BY BRE
(E) SPARE CONDUIT
(N) WIRE
(N) CONDUIT
(N) WIRE
(E) SPARE CONDUIT
(E) SPARE WIRE
(N) CONDUIT
(N) WIRE
(E) SPARE CONDUIT
(E) SPARE WIRE
INTO MS-1
(E) MS-1
(N) CONDUIT
(N) WIRE
(N) 3-EA 2-WAY
SPLICE
(N) MV SWG
(INSIDE (E) FENCE)
(N) CONDUIT
(N) WIRE
(FROM MV SWG TO MH-N1)
NOTE:
FOR OVERALL TRENCH & BORE ROUTE
SEE SHEET PV300
** SEE SHEET PV801A FOR
EXISTING FACILITY SERVICE**
(E) MH-N
(E) MH
(E) MH
(E) MH
(E) MH
(N) 3-EA 3-WAY
SPLICE
EXACT
ROUTE
TBD
(N) MH
NOTES:
NOTE 1:PULL (3) 500MCM FROM MS-1
TO MH-N1
NOTE 2:PULL SLACK AT SE CORNER LOT
`'D' MH FOR 3-WAY SPLICE.
NOTE 3:PULL SLACK AT MH-N7 FOR
2-WAY SPLICE.
OUTSIDE
BUILDING 2
BUILDING 2
ELECTRICAL ROOM
OUT TO CARPORTSNORTH EAST CORNER
OF PROPERTY
File details come from the government source that posted it. Updated .