This document includes an equipment schedule and drawings for a solar photovoltaic project at the North Las Vegas VA Medical Center. Key details include specifications for three medium voltage transformers ranging from 225 to 2000 kVA to step up voltage from 12.47 kV to 480V. Drawings show the installation of new medium voltage switchgear and conduits to interconnect the transformers and distribute power to various buildings. The project involves the Department of Veterans Affairs and aims to fulfill requirements under the VISN 21 Las Vegas Energy Savings Performance Contract solicitation to implement energy savings measures at the North Las Vegas VA facility.

VA701-17-R-0092 00002 Q15_PV801_Overall Power Plan.pdf

View the file

Other files

File Type Posted
VA701-17-R-0092-00002044.pdf PDF
VA701-17-R-0092-00002000.docx DOCX document
VA701-17-R-0092-00002024.pdf PDF
VA701-17-R-0092-00002015.xlsx XLSX spreadsheet
VA701-17-R-0092-00002045.pdf PDF
VA701-17-R-0092-00002031.pdf PDF
VA701-17-R-0092-00002032.pdf PDF
VA701-17-R-0092-00002007.xlsx XLSX spreadsheet
VA701-17-R-0092-00002022.xlsx XLSX spreadsheet
VA701-17-R-0092-00002009.xlsx XLSX spreadsheet
VA701-17-R-0092-00002025.pdf PDF
VA701-17-R-0092-00002001.doc DOC document
VA701-17-R-0092-00002040.xlsx XLSX spreadsheet
VA701-17-R-0092-00002051.pdf PDF
VA701-17-R-0092-00002037.xlsx XLSX spreadsheet
VA701-17-R-0092-00002006.xlsx XLSX spreadsheet
VA701-17-R-0092-00002011.xlsx XLSX spreadsheet
VA701-17-R-0092-00002049.pdf PDF
VA701-17-R-0092-00002005.pdf PDF
VA701-17-R-0092-00002003.pdf PDF
VA701-17-R-0092-00002026.pdf PDF
VA701-17-R-0092-00002029.pdf PDF
VA701-17-R-0092-00002021.xlsx XLSX spreadsheet
VA701-17-R-0092-00002028.pdf PDF
VA701-17-R-0092-00002012.xlsx XLSX spreadsheet
VA701-17-R-0092-00002043.pdf PDF
VA701-17-R-0092-00002008.xlsx XLSX spreadsheet
VA701-17-R-0092-00002050.pdf PDF
VA701-17-R-0092-00002035.pdf PDF
VA701-17-R-0092-00002048.pdf PDF
VA701-17-R-0092-00002018.xlsx XLSX spreadsheet
VA701-17-R-0092-00002004.pdf PDF
VA701-17-R-0092-00002042.pdf PDF
VA701-17-R-0092-00002016.xlsx XLSX spreadsheet
VA701-17-R-0092-00002017.xlsx XLSX spreadsheet
VA701-17-R-0092-00002010.xlsx XLSX spreadsheet
VA701-17-R-0092-00002014.xlsx XLSX spreadsheet
VA701-17-R-0092-00002013.xlsx XLSX spreadsheet
VA701-17-R-0092-00002034.pdf PDF
VA701-17-R-0092-00002046.pdf PDF
VA701-17-R-0092-00002027.pdf PDF
VA701-17-R-0092-00002019.xlsx XLSX spreadsheet
VA701-17-R-0092-00002020.xlsx XLSX spreadsheet
VA701-17-R-0092-00002047.pdf PDF
VA701-17-R-0092-00002023.xlsx XLSX spreadsheet
VA701-17-R-0092-00002030.pdf PDF
VA701-17-R-0092-00002041.pdf PDF
VA701-17-R-0092-00002036.pdf PDF
VA701-17-R-0092-00002033.pdf PDF
VA701-17-R-0092-00002038.xlsx XLSX spreadsheet
Show 40 more

Latest 50 of 165 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EQUIPMENT SCHEDULE - MV

IDTYPEMANUFACTURERMODELQUANTITYCURRENT AND

VOLTAGE RATINGOCPD AT EACHNOTES

G1

TRANSFORMER

(XFM-1 & 2)

CG POWER OR

EQUIVALENT1500KVA212.47kV GND WYE /

480V WYE

(3) OIL IMMERSED 80A

FUSES ON 12.47KV SIDE

DEAD-FRONT RADIAL FEED

CONFIGURATION PER VA

SPECIFICATIONS

G2

TRANSFORMER

(XFM-4)

CG POWER OR

EQUIVALENT2000KVA112.47kV GND WYE /

480V WYE

(3) OIL IMMERSED 100A

FUSES ON 12.47KV SIDE

DEAD-FRONT RADIAL FEED

CONFIGURATION PER VA

SPECIFICATIONS

G3

TRANSFORMER

(XFM-3)

CG POWER OR

EQUIVALENT225KVA112.47kV GND WYE /

480V WYE

(3) OIL IMMERSED 15A

FUSES ON 12.47KV SIDE

DEAD-FRONT RADIAL FEED

CONFIGURATION PER VA

SPECIFICATIONS

MEXISTING

MANHOLE--3--MANHOLE FOR MV RUN

NSWITCHGEARSQUARE D-115KV-RATED, 600AFUSED, VISIBLE, LOCKABLE

DISCONNECT SWITCH

NV ENERGY REQUIRES

GENERATION METER. VA

DOES NOT INTEND TO

RECOGNIZE RENEWABLE

ENERGY CREDITS

OPROTECTIVE

RELAYSEL751A OPTION (73)1--

INSTALL PTs AT

CUSTOMER'S SWITCHGEAR

ON THE NV ENERGY SIDE

OF THE BREAKER

PEXISTING MAIN

SWITCHGEAREATON

VACCLAD-W

SWITCHGEAR

ASEMBLY

112.47KV, 1200A,

1200A MAIN SET TO 240A TRIP

USE EXISTING, DEDICATED

SPARE BREAKER FOR PV

INTERCONNECTION.

QMINI POWER

ZONE

SQUARE D

OR EQUIV.TBD1480V-120VAC, 1KVA,

XXAINTERNAL PROTECTION

MINI-POWER ZONE TO

POWER MONITORING

EQUIPMENT AND REVERSE

POWER RELAY

MEDIUM VOLTAGE WIRE AND CONDUIT SCHEDULE

RUN #CONDUITCONDUCTORSNEUTRALGROUNDNOTES

1(N) (1) 3-1/2" PVC_40(N) (3) 2/0 AWG COPPER 15KV,

MV-105, 133%--

(1) 2 AWG Cu, 15KV, MV-105, 133%

2(E) (1) 6" SPARE (N) (3) 2/0 AWG COPPER 15KV,

MV-105, 133%--

(1) 2 AWG Cu, 15KV, MV-105, 133%

ROUTE NEW

CONDUCTORS

THROUGH EXISTING

SPARE CONDUIT

3(E) (1) 6" SPARE(E) (3) 500 KCMIL COPPER, 15KV,

MV105, 133%--

(1) 1/0 AWG Cu, 15KV, MV-105, 133%

EXISTING 500MCM

FROM MH-N7 TO MH-N1

TO MS-1

4(N) (1) 4" PVC_40(N) (3) 2/0 KCMIL COPPER, 15KV,

MV-105, 133%--

(1) 2 AWG Cu, 15KV, MV-105, 133%

5(N) (1) 5" PVC_40(E) (3) 500 KCMIL COPPER 15KV,

MV105, 133%--

(1) 1/0 AWG Cu, 15KV, MV-105, 133%

6(N)(1) 4" PVC_40(N)(3) 4/0 KCMIL COPPER, 15 KV,

MV-105, 133%--

(1) 1/0 AWG Cu, 15KV, MV-105, 133%

7(E)(1) 6" PVC_40(N)(3) 4/0 KCMIL COPPER, 15KV,

MV-105, 133%--

(1) 1/0 AWG Cu, 15KV, MV-105, 133%

P

SWG

GEN MTR

MTR

M

N12

G3

XFM-3

HV FUSE

G2

XFM-4

HV FUSE

G1

XFM-2

HV FUSE

SWITCH

M

N1

G1

XFM-1

HV FUSE

M

N7

M

N7

Q

XF

MAIN

EXISTING MAIN SWITCHGEAR (MS-1)

POINT OF PV INTERCONNECTION

"PCC"

AT EXISTING SPARE BREAKER

SET OVERCURRENT TO 241A

PER NV ENERGY SYSTEM IMPACT STUDY

DATED 2.18.16

SWITCHGEAR TO COMBINE PV XFM OUTPUTS

INCLUDES

GENERATION METER

VISIBLE, LOCKABLE SWITCH

REVERSE POWER RELAY

ROUTE THRU

EXISTING MANHOLE TO

NEW MV SWITCHGEAR

EXISTING

NV ENERGY METER

RELAY (SEL 751A)

POWER IN

RLY FDBK

12.47k:120V PTs

1200:5 CTs

PHASE 7 (LOT D) (PNL-7.1)

PHASE 3 (LOT B) (PNL-4)

PHASE 4 (LOT C) (PNL-4)

PHASE 8 (GND-MNT) (PNL-G1.1)

PHASE 9 (GND-MNT) (PNL-G2.1)

PHASE 10 (TANKS) (PNL-T.1)

TO GRID

N

O

PHASE 2A (LOT A) (PNL-3)

PHASE 2B (LOT A) (PNL-3)

PHASE 6 (LOT E) (PNL-3)

S

(N) 2-WAY SPLICE

CONNECT XFM-1 TO (E)

500KCMIL CONDUCTORS

S

(N) 3-WAY SPLICE

CONNECT XFM-1AND XFM-3 TO

(E) 500KCMIL CONDUCTORS

INPUTS

(2)4 (1)5

OUTPUT

(1)6

EXISTING

POWER IN

PANEL "X"

CB-X

(1)15A/1P BRKR TO POWER SEL 751(A)

(1)15A/1P BRKR TO POWER SHARK 100

(1)15A/1P BRKR TO POWER MEDIA CENTER

F H

FH

FH

FH

F H

F H

FH

FH

F H

FH

F H

FH

FH

F H

F H

F H

FH

F H

FH

F H

F H

FH

OFFICE OF

CONSTRUCTION AND

FACILITIES

MANAGEMENT

C

R

PROJECT NUMBER

DATEDESCRIPTION

THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF

REC SOLAR COMMERCIAL CORPORATION.

CONTRACTOR

REC SOLAR

810 FIERO LANE, SUITE 200

SAN LUIS OBISPO, CA 93401

PH (805) 477-3970

FX (805) 540-6040

(844) REC SOLARSHEET NUMBER

PROJECT MANAGER

PROJECT ENGINEER

ASSOCIATE ENGINEER

CHECKED BY

EDCBA

PV801 6

PROJECT

EDCBA

ENGINEERCLIENT

SHEET TITLE

DATE

R

PROJECT NUMBER

REVDATEDESCRIPTION

THE INFORMATION IN THIS DRAWING IS CONFIDENTIAL AND PROPRIETARY. ANY REPRODUCTION, DISCLOSURE, OR USE THEREOF IS PROHIBITED WITHOUT THE WRITTEN CONSENT OF

REC SOLAR COMMERCIAL CORPORATION.

CONTRACTOR

REC SOLAR

810 FIERO LANE, SUITE 200

SAN LUIS OBISPO, CA 93401

PH (805) 477-3970

FX (805) 540-6040

(844) REC SOLARSHEET NUMBER

PROJECT MANAGER

PROJECT ENGINEER

ASSOCIATE ENGINEER

CHECKED BY

EDCBA

PROJECT

EDCBA

14 ENGINEERCLIENT

SHEET TITLE

DATE11/14/2016

VALV.14580.EPC

BOB FISHER

JESSICA KENDRICK

ZORAN IVANCEVIC

RECORD SET

NORTH LAS VEGAS SOLAR PV PROJECT

6900 NORTH PECOS RD

NORTH LAS VEGAS, NV 89086

CONTRACT NUMBERVA701-14-C-0045

CLIENT CONTACTCLIENT NAME

CONTRACTING

OFFICER (CO)SEAN KAMINSKI

REPRESENTATIVE

(COR)DREW DOWNEN

CONTRACT

SPECIALIST (CS)SCOTT ELIAS

100% SET

8/25/15STRUT SWAP

1/26/16NV ENERGY COMMENTS

02/24/16RELOCATE XMF-3

3/04/162ND NV ENERGY COMMENT

05/25/16ADD SWB-5 TO XMF-4

11/14/16RECORD SET

05/29/15

OVERALL POWER PLAN

MEDIUM VOLTAGE

NTS

MEDIUM VOLTAGE SITE DISTRIBUTION

NTS

ELECTRICAL SINGLE LINE - MEDIUM VOLTAGE

ANTS

EXISTING FACILITY SERVICE

NTS

PROTECTION ELEMENTS - SEL 751A

NTS

INSTRUMENT POWER

3A

LEGEND

-WIRE LABEL

F

PPP1

EQUIPMENT ID PER

EQUIPMENT SCHEDULE

EQUIPMENT SYMBOL

EQUIPMENT LABEL

REFERRED TO IN PLANS

KEY MAP

(E) MH-N12

(E) MH-N7

(E ) M

H -N

XFM-1

"G1"

XFM-2

"G1"

XFM-3

"G3"

XFM-4

"G2"

(NEW 480VAC

SWITCHBOARD TO

INTERCEPT FEEDS

CURRENTLY

PULLED TO XFM-4

PAD)

(N) CONDUIT BY REC

(N) WIRE BY BRE

(E) SPARE CONDUIT

(N) WIRE

(N) CONDUIT

(N) WIRE

(E) SPARE CONDUIT

(E) SPARE WIRE

(N) CONDUIT

(N) WIRE

(E) SPARE CONDUIT

(E) SPARE WIRE

INTO MS-1

(E) MS-1

(N) CONDUIT

(N) WIRE

(N) 3-EA 2-WAY

SPLICE

(N) MV SWG

(INSIDE (E) FENCE)

(N) CONDUIT

(N) WIRE

(FROM MV SWG TO MH-N1)

NOTE:

FOR OVERALL TRENCH & BORE ROUTE

SEE SHEET PV300

** SEE SHEET PV801A FOR

EXISTING FACILITY SERVICE**

(E) MH-N

(E) MH

(E) MH

(E) MH

(E) MH

(N) 3-EA 3-WAY

SPLICE

EXACT

ROUTE

TBD

(N) MH

NOTES:

NOTE 1:PULL (3) 500MCM FROM MS-1

TO MH-N1

NOTE 2:PULL SLACK AT SE CORNER LOT

`'D' MH FOR 3-WAY SPLICE.

NOTE 3:PULL SLACK AT MH-N7 FOR

2-WAY SPLICE.

OUTSIDE

BUILDING 2

BUILDING 2

ELECTRICAL ROOM

OUT TO CARPORTSNORTH EAST CORNER

OF PROPERTY