Attachment C.1 Construction Drawings Volume 1

21 MB Posted

Attached to
Upgrade Electrical Distribution, 5kV to 15kV, Building 100 NRM 663-15-102 CON
Solicitation number
VA26016R0001
Issued by

About this file

VA260-16-R-0001 Attachments

Text of this file

NORTH

600 Stewart St., Ste 1400 Seattle, Washington 98101

Tel 206.267.1700 Fax 206.267.1701

SAZAN # 269-1507

600 Stewart St., Ste 1400 Seattle, Washington 98101

Tel 206.267.1700 Fax 206.267.1701

SAZAN # 269-1507

GENERAL DATE

CIVIL

ARCHITECTURAL

STRUCTURAL

ELECTRICAL

MECHANICAL

ELECTRICALDATE DATE

DRAWING LIST NOTE:

600 Stewart St., Ste 1400 Seattle, Washington 98101

Tel 206.267.1700 Fax 206.267.1701

SAZAN # 269-1507

600 Stewart St., Ste 1400 Seattle, Washington 98101

Tel 206.267.1700

WORKING LIMITS

Seattle, Washington 98101

Tel 206.267.1700 Fax 206.267.1701

SAZAN # 269-1507

33301 9th Avenue South, Suite 300

Federal Way, Washington 98003-2600

(206) 431-2300 Fax: (206) 431-2250

Seattle, Washington 98101

Tel 206.267.1700 Fax 206.267.1701

SAZAN # 269-1507

33301 9th Avenue South, Suite 300

Federal Way, Washington 98003-2600

(206) 431-2300 Fax: (206) 431-2250

TEMPORARY EROSION/SEDIMENT CONTROL NOTES:

GENERAL NOTES:

33301 9th Avenue South, Suite 300

Federal Way, Washington 98003-2600

(206) 431-2300 Fax: (206) 431-2250

600 Stewart St., Ste 1400 Seattle, Washington 98101

Tel 206.267.1700

S75-LA

S & L PAD MOUNT

TRANSFORMER

TRANSFORMER

33301 9th Avenue South, Suite 300

Federal Way, Washington 98003-2600

(206) 431-2300 Fax: (206) 431-2250

600 Stewart St., Ste 1400 Seattle, Washington 98101

Tel 206.267.1700 Fax 206.267.1701

SAZAN # 269-1507

NOTES:

S75-LA

TRANSFORMER

S & L PAD MOUNT

TRANSFORMER

33301 9th Avenue South, Suite 300

Federal Way, Washington 98003-2600

(206) 431-2300 Fax: (206) 431-2250

600 Stewart St., Ste 1400 Seattle, Washington 98101

Tel 206.267.1700 Fax 206.267.1701

SAZAN # 269-1507

PHASING NOTES:

OVERFLOW BYPASS (TYP.)

BELOW INLET GRATE DEVICE

DRAINAGE GRATE

~ RECTANGULAR GRATE

SHOWN RETRIEVAL SYSTEM (TYP.)

BELOW INLET GRATE DEVICE

OVERFLOW BYPASS

DRAINAGE GRATE

GRATE FRAME

SEDIMENT AND DEBRIS

FILTERED

WATER

SECTION VIEW

ISOMETRIC VIEW

5" MAX.

TRIM

1. SIZE THE BELOW INLET GRATE DEVISE (BIGD) FOR THE STORM WATER STRUCTURE IT WILL SERVICE.

2. THE BIGD SHALL HAVE A BUILT-IN HIGH-FLOW RELIEF SYSTEM (OVERFLOW BYPASS).

3. THE RETRIEVAL SYSTEM MUST ALLOW REMOVAL OF THE BIGD WITHOUT SPILLING THE COLLECTED MATERIAL.

4. PERFORM MAINTENANCE IN ACCORDANCE WITH STANDARD SPECIFICATION 8-01.3(15).

TWO 1" DIAM. RODS

(SEE NOTE 4)

10" 12" 14"

28,275

50,265

4,440 9,995

17,770

39,985 54,425 71,085

2,405

38,470 19,615 15,015

9,855

5,54511,030 7,660

2,4654,905 2,760 3,000

10,000

4" 6" 8"

16"

3,140 7,070

12,565 19,635

38,485

27,770

5,410 9,620

15,030 21,640 29,455 7,545

3,850

1,385 6151,225

MUCK, PEAT, ETC.

SOFT CLAY

SAND

SAND AND GRAVEL

HARD SHALE

1,000 2,000

4,000

1. CONTRACTOR TO PROVIDE BLOCKING ADEQUATE TO WITHSTAND FULL TEST PRESSURE.

2. DIVIDE THRUST BY SAFE BEARING LOAD TO DETERMINE REQUIRED AREA (IN SQUARE FEET) OF CONCRETE TO DISTRIBUTE LOAD.

3. AREAS TO BE ADJUSTED FOR OTHER PRESSURE CONDITIONS.

4. PROVIDE TWO 1" MINIMUM DIAMETER RODS ON VALVES UP THROUGH 10" DIAMETER. VALVES LARGER THAN 10" REQUIRE

SPECIAL TIE ROD DESIGN

PLAN VIEW

DEAD END

OFFSET

(USE COLUMNS B~E)

BEND

PLAN VIEW

PLUGGED TEE

(USE COLUMNS B)

PROFILE VIEW

VALVE

(USE COLUMNS A)

PLAN VIEW

TEE

PLAN VIEW

UNBALANCED CROSS

(USE COLUMNS A)

PLAN VIEW

PLUGGED CROSS

(USE COLUMNS B)

PLAN VIEW

PLUGGED CROSS

(USE COLUMNS A)

SIZE

TEST

(PSI)

THRUST AT FITTINGS IN POUNDS

TEE AND

DEAD

ENDS

11.25°

BEND

22.5°

BEND

45°

BEND

90°

BEND

A B C D E

SOIL TYPE SAFE BEARING LOAD

(PSI)

PIPE ZONE BACKFILL

(SEE NOTE 1)

GRAVEL BACKFILL FOR

PIPE ZONE BEDDING

(SEE NOTE 2)

FOUNDATION LEVEL

P

IP

E Z

O N

E

TRENCH WIDTH

(SEE NOTE 3)

6" 6"

85% O.D.

(SEE NOTE 4)

15% O.D.

DUCTILE IRON PIPE

GRAVEL BACKFILL FOR

PIPE ZONE BEDDING

(SEE NOTE 2)

FOUNDATION LEVEL

P

IP

E Z

O N

E

TRENCH WIDTH

(SEE NOTE 3)

6" 6"

O .D

THERMOPLASTIC PIPE

SECTION AA

PLAN VIEW

A A

33301 9th Avenue South, Suite 300

Federal Way, Washington 98003-2600

(206) 431-2300 Fax: (206) 431-2250

600 Stewart St., Ste 1400 Seattle, Washington 98101

Tel 206.267.1700

1.8 2.3

2.4 3.0

2.9 3.6

3.4 4.2

3.8 108 4.8

4.2 147 5.3

4.6 192 5.8

2.8

10"

12"

14"

16"

17"

17"

17"

17"

17"

17"

20"

24"

3.7

250 17" 4.5

139 5.2

200 5.8

6.5

7.1

24"

1" 27"

30"

8" THREAD 6"

8"

4"

6"

8"

5/8"

5/8"

5/8"

5/8"

5/8"

7/8" 5/8" 3/4"

5/8" 7/8"

1 1/8"

11.25^ 22.5^ 45^ 11.25^ 22.5^ 45^ 11.25^ 22.5^ 45^ 11.25^ 22.5^ 45^ 11.25^ 22.5^ 45^ 11.25^ 22.5^ 45^ 11.25^ 22.5^ 45^

FOUR TIE RODS

WITH TURNBUCKLES

THREAD 6"

TWO TIE RODS

WITH TURNBUCKLES

Steel tie rods to be heavily coated with asphalt after installation.

DIMENSION TABLE

PIPE

DIAM.

TEST

PRESSURE

(PSI)

BEND

ANGLE

CONCRETE

VOLUME

(FT )

CUBE

SIZE

(FT)

TIE ROD

DIAM.

TIE ROD

EMBENMENT

DIMENSION TO

FINISH FACE OR

AS NOTED.

SURFACE

SLOPE

NORTH ARROW

PROJECT NORTH

(SEE CIVIL FOR

TRUE NORTH)

DRAWING REVISION NEW SPOT ELEV

WINDOW TYPE -

REF WINDOW SCH

DOOR TAG

WINDOW TAG

CALLOUT

DRAWING NUMBER

DRAWING NUMBER

EXTERIOR ELEVATION

DOOR NUMBER -

REF DOOR SCH

SHEET NUMBER

EXISTING SPOT ELEV

ELEVATION TAG

KEYNOTE

BUILDING

SECTION

WALL SECTION

SHEET NUMBER

ROOM TAG

(E) 98.75'

1"

98.75'

ROOM NUMBER

1/4:12

SLOPE

Room name

150 SF

SYMBOLS AND FILL PATTERNS

EARTH

GRAVEL

ASPHALT

METAL - STEEL

MASONRY - CONCRETE BLOCK

WOOD - FINISH

*WOOD - CONTINUOUS

INSULATION - BATT

INSULATION -

RIGID

INSULATION - ACOUSTICAL

WOOD - PLYWOOD

GYPSUM WALL BOARD

GLASS

WOOD - PARTICLE BOARD

METAL - ALUMINUM

CONCRETE

MASONRY - BRICK

SAND

*WOOD - BLOCKING

INSULATION -

SEMI RIGID

W1

A101

SIM

A3.00

FINISH TAG

P01

AC

GROUP

ASSEMBLY

STUD SIZE

MODIFIER

WALL TAG

CEILING HEIGHT ABOVE

FINISHED FLOOR- ALL

CEILINGS 9'-0" UNLESS

OTHERWISE NOTED.

CEILING MATERIAL

CEILING TAG

1t

9'-0"

CP-1

INTERIOR ELEVATION

DRAWING NUMBER

A101

SIM

A101

SIM

NAME

ELEVATION

A101

1 1

SHEET NUMBER

REVISION NUMBER

GENERAL NOTES

CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TO

PROCEEDING WITH THE WORK.

DIMENSIONS TAKE PRECEDENCE OVER DRAWINGS. DO NOT SCALE DRAWINGS.

NOTIFY THE ARCHITECT OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH THE

WORK.

CONTRACTOR IS RESPONSIBLE FOR CONSTRUCTION MEANS AND METHODS.

CONTRACTOR IS RESPONSIBLE FOR VERIFICATION AND COORDINATION OF

SUBCONTRACTOR'S WORK, COMPLIANCE WITH THE DRAWINGS AND SPECIFICATIONS,

ACCURATE LOCATION OF STRUCTURAL MEMBERS, AND OPENINGS FOR MECHANICAL,

ELECTRICAL, AND MISCELLANEOUS EQUIPMENT.

CONTRACTOR SHALL VERIFY DIMENSIONS AND CLEARANCES FROM MANUFACTURER

PRIOR TO THE CONSTRUCTION AND INSTALLATION OF ALL EQUIPMENT, FURNISHINGS,

AND ACCESSORIES.

CONTRACTOR IS RESPONSIBLE FOR THE COMPLETE SECURITY OF THE SITE DURING

CONSTRUCTION AND UNTIL PROJECT COMPLETION.

CONTRACTOR SHALL LOCATE AND PROTECT EXISTING UTILITIES, WHETHER INDICATED

IN DRAWINGS OR NOT.

PROVIDE BACKING, BLOCKING, OR STRAPPING AS REQUIRED FOR GRAB BARS,

SHELVING, EQUIPMENT, HANDRAILS, ACCESSORIES, AND CABINETS.

COORDINATE LOCATIONS OF IN-WALL ITEMS TO AVOID BACK TO BACK

INSTALLATION.

ALL SAFETY GLAZING SHALL BE PERMANENTLY LABELED WITH THE MANUFACTURER'S

NAME AND TEST APPROVAL INFORMATION.

SEE STRUCTURAL FOR REQUIRED SPECIAL INSPECTIONS.

SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL ELECTRICAL AND

EQUIPMENT INFORMATION.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

A

ACOUS ACOUSTICAL

ACT ACOUSTICAL TILE

A.D AREA DRAIN

ADJ ADJUSTABLE

AFF ABOVE FINISH FLOOR

AGGR AGGREGATE

AL ALUMINUM

APPROX APPROXIMATE

ARCH ARCHITECTURAL

ASPH ASPHALT

B

BCS BABY CHANGING STATION

BD BOARD

BITUM BITUMINOUS

BLDG BUILDING

BLK BLOCK

BLKG BLOCKING

BR BUMPER RAIL

BW BLANKET WARMER

C

CAB CABINET

CB CATCH BASIN

CER CERAMIC

CI CAST IRON

CG CORNER GUARD

CPT CARPET

CR CHAIR RAIL

CENTERLINE

CLO CLOSET

CLR CLEAR

CJ CONTROL JOINT

COL COLUMN

CONC CONCRETE

CONSTR CONSTRUCTION

CONT CONTINUOUS

CORR CORRIDOR

D

DBL DOUBLE

DEPT DEPARTMENT

DF DRINKING FOUNTAIN

DET DETAIL

DIA DIAMETER

DIM DIMENSION

DISP DISPENSER

DN DOWN

DWR DRAWER

DS DOWNSPOUT

DWG DRAWING

E

E EAST

(E) EXISTING

EA EACH

EJ EXPANSION JOINT

ELEC ELECTRICAL

ELEV ELEVATION

EMER EMERGENCY

ENCL ENCLOSURE

EP ELECTRICAL PANEL

EQ EQUAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXP EXPOSED

EXT EXTERIOR

F

FA FIRE ALARM

FD FLOOR DRAIN

FDN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FHC FIRE HOSE CABINET

FIN FINISH

FL FLOOR

FC FACE OF CONCRETE

FF FACE OF FINISH

F/O FACE OF

FS FACE OF STUDS

FT FOOT/ FEET

FTG FOOTING

FURR FURRING

FUT FUTURE

G

GA GAUGE

GALV GALVANIZED

GB GRAB BAR

GL GLASS

GND GROUND

GR GRADE

GWB GYPSUM WALL BOARD

H

H.B HOSE BIB

HC HOLLOW CORE

HDWD HARDWOOD

HDWR HARDWARE

HM HOLLOW METAL

HORIZ HORIZONTAL

HT HEIGHT

HW HARDWARE

I

IBC INTERNATIONAL BUILDING CODE

ID INSIDE DIAMETER

INSUL INSULATION

INT INTERIOR

J

JAN JANITOR

JT JOINT

L

LAB LABORATORY

LAM LAMINATE

LAV LAVATORY

LT LIGHT

M

MAX MAXIMUM

MECH MECHANICAL

MEMB MEMBRANE

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MIR MIRROR

MISC MISCELLANEOUS

MO MASONRY OPENING

MTD MOUNTED

MUL MULLION

N

N NORTH

(N) NEW

NIC NOT IN CONTRACT

NS NURSE STATION

NTS NOT TO SCALE

O

OA OVERALL

OC ON CENTER

OCC OCCUPANT

OD OUTSIDE DIAMETER

OFCI OWNER FURNISHED,

CONTRACTOR INSTALLED

OFOI OWNER FURNISHED,

OWNER INSTALLED

OPNG OPENING

OPP OPPOSITE

ORD OVERFLOW ROOF DRAIN

P

PL PLASTIC LAMINATE

PT PAINT

R

(R) RELOCATE

RAD RADIUS

RB RUBBER BASE

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REF REFRIGERATOR

REFER REFERENCE

REQ REQUIRED

RM ROOM

RO ROUGH OPENING

S

S SOUTH

SCW SOLID CORE WOOD

SCD SEAT COVER DISPENSER

SCH SCHEDULE

SD SOAP DISPENSER

SDS SOLID SURFACE

SECT SECTION

SF SQUARE FOOT/ FEET

SHT SHEET

SIM SIMILAR

SND SANITARY NAPKIN DISPENSER

SNR SANITARY NAPKIN RECEPTACLE

SPT SPECIMEN PASS THROUGH

SQ SQUARE

SS SOLID SURFACE

SST STAINLESS STEEL

STA STATION

STC SOUND TRANSMISSION CLASS

STD STANDARD

STL STEEL

STRUCT STRUCTURAL

SUSP SUSPENDED

SV SHEET VINYL

SYM SYMMETRICAL

T

TB TOWEL BAR

TBD TO BE DETERMINED

TC TOP OF CURB

TEL TELEPHONE

T&G TONGUE AND GROOVE

THK THICK

TOP TOP OF PAVEMENT

TPD TOILET PAPER DISPENSER

TV TELEVISION

TOW TOP OF WALL

TYP TYPICAL

U

UL UNDERWRITERS LABORATORY

UNF UNFINISHED

UNO UNLESS NOTED OTHERWISE

V

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

W

W WEST

W/ WITH

WC WATER CLOSET

WD WOOD

WF WINDOW FILM

W/O WITHOUT

WP WATERPROOF

WPR WALL PROTECTION

WRB WEATHER RESISTANT BARRIER

CL

ABBREVIATIONS

600 Stewart St., Ste 1400 Seattle, Washington

98101 Tel 206.267.1700

Fax 206.267.1701

SAZAN #

100% CONSTRUCTION DOCUMENTS

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management

663-15-102

1660 South Columbian Way, Seattle, WA 98108

VA PUGET SOUND HEALTH CARE SYSTEM

UPGRADE SEATTLE ELECTRICAL

DISTRIBUTION FROM 5kV TO 15kV

01-19-2016

VAPAHCS PLANNING AND ENGINEERING

o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

269-1507

R. DAVID FRUM

STATE OF WASHINGTON

REGISTERED7043

ARCHITECT

1402 Third Avenue Suite 200 Seattle, WA 98101

TEL: 206/ 652-0722

FAX: 206/ 652-0720 -N

O T F

O R

C O

N S

TR

U

C

TIO

N

P R

ELI

M

IN

AR

Y

S A L U S

A R C H

IT

E C T U R E

IN

C

O P Y R

IG

H T

Proj. Number

/1

/2

:5

:3

P

M

15327

GENERAL NOTES, SYMBOLS, ABBREVIATIONS &

FINISH CODE

100-A001

-ARCHITECTURAL-

100-A101 SERVICE YARD PLAN AND DETAILS

100-A102 ENERGY PLANT PLAN

100-A103 SUBSTATION B PLAN

100-A104 ELECTRICAL ROOM C PLAN

100-A200 ELEVATIONS

100-AE400 OPENING SCHEDULE, DETAILS AND PARTITIONS

-ARCHITECTURAL DEMOLITION-

100-AD101 ARCHITECTURAL DEMOLITION PLAN SERVICE YARD

100-AD102 ARCHITECTURAL DEMOLITION PLAN ENERGY PLANT

100-AD103 ARCHITECTURAL DEMOLITION PLAN SUBSTATION B

100-AD104 ARCHITECTURAL DEMOLITION PLAN ELECTRICAL ROOM C

-ARCHITECTURAL GENERAL-

100-A001 GENERAL NOTES, SYMBOLS, ABBREVIATIONS & FINISH CODE

100-A002 ARCHITECTURAL AREA OF WORK OVERVIEW

100-A003 FIRE AND LIFE SAFETY PLANS

REINF. TURF FIRE LANE

R

EIN

F.

TU

R F

FIR

E

LA

N E

D O O R

D O O R

GO

V' T

D T

BL

DG

BL

DG

.1

EN

ER

GY

PL

AN

T

PA

TIO

EN

GR

'G

NURSING TOWER

NURSING

BLDG.100

HOME

SH

OP

S

SO. SNOQUALMIE ST.

SO. ALASKA ST.

COLUM

BIAN W

AY SO.

B E A C O N

A V E

S O

SE

RV

IC

E

CO

UR

T

GOLF DRIVE

HILL DRIVE

EN

TR

AN

CE

L

OO

P

NO

RT

H

DR

IV

E

SOUTH DRIVE

SO

U

TH

D

RI

VE

M

ED

IA

R D.

EAST LOOP RD.

E A S T

L O O P

R D

LOT "G"

LOT "A"

LOT "B"

LOT"D"LOT "C"

S .C .I

ROOF TOP

PATIO

LOT "F"

SE

RV

IC

E

CO

UR

T

LOT "E"

DAV

Rehab

Training

17 Spots

FI

SH

ER

H O U

SE

C

RE

D

IT

U N

IO

N

GO

V' T./

SR

VC

R

AD

TH

ER

AP

Y

BLDG.100

S .C .I

ENLARGE EXISTING SERVICE YARD ENCLOSURE.

SEE 100-AD101 AND 100-A101

MODIFICATIONS TO EXISTING SWITCHGEAR ROOMS,

GENERATOR ROOM AND REACTOR ROOM TO

ACCOMMODATE NEW EQUIPMENT. CONFIRM EXISTING

SECURITY DOOR HARDWARE AND UPGRADE AS REQUIRED.

SEE 100-AD102 AND 100-A102

MODIFICATIONS TO EXISTING ELECTRICAL ROOM B

TO ACCOMMODATE NEW/ ADDITIONAL EQUIPMENT.

CONFIRM EXISTING SECURITY DOOR HARDWARE

AND UPGRADE AS REQUIRED.

SEE 100-AD103 AND 100-A103

TEMPORARY REMOVAL OF LOUVERS IN ELECTRICAL ROOM

C TO REPLACE/ ADD EQUIPMENT. CONFIRM EXISTING

SECURITY DOOR HARDWARE AND UPGRADE AS REQUIRED.

SEE 100-AD104 AND 100-A104

ELECTRICAL ROOM C

SERVICE YARD

ENERGY PLANT

SUBSTATION B

600 Stewart St., Ste 1400 Seattle, Washington

98101 Tel 206.267.1700

Fax 206.267.1701

SAZAN #

100% CONSTRUCTION DOCUMENTS

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management

663-15-102

1660 South Columbian Way, Seattle, WA 98108

VA PUGET SOUND HEALTH CARE SYSTEM

UPGRADE SEATTLE ELECTRICAL

DISTRIBUTION FROM 5kV TO 15kV

01-19-2016

VAPAHCS PLANNING AND ENGINEERING

o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

269-1507

R. DAVID FRUM

STATE OF WASHINGTON

REGISTERED7043

ARCHITECT

1402 Third Avenue Suite 200 Seattle, WA 98101

TEL: 206/ 652-0722

FAX: 206/ 652-0720 -N

O T F

O R

C O

N S

TR

U

C

TIO

N

P R

ELI

M

IN

AR

Y

S A L U S

A R C H

IT

E C T U R E

IN

P Y R

IG

H T

Proj. Number

/1

/2

:5

:3

P

M

15327

ARCHITECTURAL AREA OF WORK OVERVIEW

100-A002

1" = 60'-0"1

ARCHITECTURAL AREA OF WORK OVERVIEW PLAN

ROLL DOWN FIRE

SHUTTER (E)

ROLL DOWN FIRE

SHUTTER (E)

ROLL DOWN FIRE

SHUTTER (E)

U P

E.

W

53'-10"

7'-2" 6'-4 1/2"

SUBSTATION "A"

MAIN SERVICE SWITCHGEAR

R O L L

D O W N

F

IR

E

S H U T T E R

(E

R O L L

D O W N

F

IR

E

S H U T T E R

(E

D N

U P

L O U V E R

L O U V E R

C O M P A C T O R

C O M P A C T O R

T R A S H

C A R D B O A R D

A C C E S S

C O R R

ID

O R

L

IN

K

A B O V E

D O O R

F D

RAISED WOOD WALKWAY

W/ METAL DECK

V E R T

IC

A L

L A D D E R

C M P A C T O R

C O N T R O L

GENERAL NOTES

LEGEND

FIRE EXTINGUISHER

EXIT SIGN LOCATION -

COORDINATE WITH

ELECTRICAL

FE

X'-X"

3 HOUR WALL-VERIFY IN FIELD

EGRESS TRAVEL DISTANCE

THESE PLANS ARE INTENDED TO

SHOW THE FIRE AND LIFE SAFETY

SYSTEM FOR THE FLOOR AREAS

SHOWN.

THE CONTRACTOR SHALL BE

RESPONSIBLE FOR VERIFYING THAT

ALL TRADES ARE THOROUGHLY

FAMILIAR AND COMPLY WITH THE

REQUIREMENTS LISTED IN THE "FIRE

AND LIFE SAFETY STANDARDS"

(FLSS).

ALL RATED ASSEMBLIES SHALL BE

CONSTRUCTED TO PREVENT THE

MOVEMENT OF FLAME OR GASSES

PER CODE.

INSTALL RATED ENCLOSURES FOR

ALL RECESSED ITEMS IN RATED

WALLS PER CODE.

ALL PENETRATIONS THROUGH RATED

ASSEMBLIES IN AREAS OF WORK

SHALL BE FIRESTOPPED OR SEALED

PER CODE.

THE CONTRACTOR SHALL FIELD

VERIFY THE CONDITION OF THE

EXISTING FLSS SYSTEMS IN THE

AREAS OF WORK THAT MAY

REQUIRE UPDATING. AREAS INCLUDE

(BUT ARE NOT LIMITED TO) THE

FOLLOWING:

1.

2.

3.

4.

5.

6.

A.

B.

C.

D.

EXIT SIGNS INDICATED ON FIRE AND

LIFE SAFETY PLAN ARE FOR

REFERENCE ONLY. SEE ELECTRICAL

DOCUMENTS FOR EXACT EXIT SIGN

LOCATIONS.

INDICATED FIRE RATINGS BASED ON

RECORD DRAWINGS. CONFIRM

RATINGS PRIOR TO CONSTRUCTION.

7.

8.

CONTRACTOR TO VERIFY THAT

ALL EXISTING PENETRATIONS OF

RATED ASSEMBLIES WHICH ARE

EXPOSED TO VIEW DURING

CONSTRUCTION ARE COMPLIANT

WITH CODE REQUIREMENTS.

CONTRACTOR TO EXTEND ANY

EXISTING WALL (WITHIN THE AREA

OF WORK) TO STRUCTURE WHICH

IS REQUIRED BY FLSS, BUT

DOES NOT PRESENTLY EXIST.

CONTRACTOR TO VERIFY THAT

ALL DUCTWORK PENETRATIONS

THROUGH RATED ASSEMBLIES ARE

EQUIPPED WITH FIRE AND/ OR

SMOKE DAMPERS AS REQUIRED

BY CODE.

CONTRACTOR TO VERIFY THAT

THE FIRE ALARM, EMERGENCY

LIGHTING, AND EMERGENCY

POWER IN THE AREA OF WORK

CONFORMS TO THE FLSS

"ELECTRICAL STANDARDS"

SECTION FOR THE OCCUPANCY

TYPE INDICATED ON THE FLSS

PLANS.

MAIN

SWITCHGEAR

BE-101

EMERGENCY

GENERATOR

BE-103

EMERGENCY

SWITCHGEAR

BE-102

REACTOR ROOM

BE-108

1 1/2HR

DOOR

RAISED SLAB EDGE

FE FE

FE

1 1/2HR

DOOR

SUBSTATION B

BD-115

FE

3-HR ROLL

DOWN FIRE

SHUTTER

FE

3HR

DOOR

3HR

DOOR

CODE REVIEW FOR "AREA OF WORK"

VA PUGET SOUND HEALTH CARE SYSTEM UPGRADE

SEATTLE ELECTRICAL DISTRIBUTION FROM 5KV TO 15KV

UNITED STATES

1660 S COLUMBIAN WAY, SEATTLE, WA 98108

162404-9193

POR GL 5 & OF SE 1/4 OF SW 1/4 LY WLY OF

BEACON AVE & NELY OF COLUMBIAN WAY & NLY OF

SNOQUALMIE ST LESS BEG AT NW COR THOF TH E 580

FT TH S 14-05-15 W 942.98 FT TH N 42-19-47 W

532.34 FT TH N TO BEG

-VA ARCHITECTURAL DESIGN MANUAL

-JAN 2015 VA PHYSICAL SECURITY DESIGN MANUAL

-2012 SEATTLE BUILDING CODE

-NFPA 101, 220, 37

FULLY SPRINKLERED (EXISTING)

YES (EXISTING)

205255 NET SF

EMERGENCY GENERATOR - 2,354 NET SF (EXISTING)

SUBSTATION B - 1,895 (EXISTING)

PROJECT NAME:

OWNER:

ADDRESS:

PARCEL NUMBER:

LEGAL DESCRIPTION:

CODES:

FIRE PROTECTION:

FIRE ALARM SYSTEM:

EXISTING BUILDING:

AREA OF WORK:

AREA OF WORK IS F-1 (EXISTING)

II-A (EXISTING)

75 FT (100 FT WITH SPRINKLER)

3 HR (EXISTING)

2012 SEATTLE BUILDING CODE

OCCUPANCY:

CONSTRUCTION TYPE:

MAX COMMON PATH OF

TRAVEL:

(1014.3)

BUILDING SEPARATION:

INDUSTRIAL POWER PLANT (EXISTING)

TYPE II 2,2,2 (EXISTING)

NFPA 101, 220

OCCUPANCY:

CONSTRUCTION TYPE:

NFPA 37 -INSTALLATION AND AND USE OF STATIONARY COMBUSTION

ENGINES AND GAS TRUBINES

3-5.1.2 ROOMS CONTAINING COMBUSTION ENGINES LOCATED WITHIN

STRUCTURES SHALL HAVE AT LEAST 2-HOURS FIRE RESISTANCE

RATING.

600 Stewart St., Ste 1400 Seattle, Washington

98101 Tel 206.267.1700

Fax 206.267.1701

SAZAN #

100% CONSTRUCTION DOCUMENTS

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management

663-15-102

1660 South Columbian Way, Seattle, WA 98108

VA PUGET SOUND HEALTH CARE SYSTEM

UPGRADE SEATTLE ELECTRICAL

DISTRIBUTION FROM 5kV TO 15kV

01-19-2016

VAPAHCS PLANNING AND ENGINEERING

o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

269-1507

R. DAVID FRUM

STATE OF WASHINGTON

REGISTERED7043

ARCHITECT

1402 Third Avenue Suite 200 Seattle, WA 98101

TEL: 206/ 652-0722

FAX: 206/ 652-0720 -N

O T F

O R

C O

N S

TR

U

C

TIO

N

P R

ELI

M

IN

AR

Y

S A L U S

A R C H

IT

E C T U R E

IN

P Y R

IG

H T

Proj. Number

/1

/2

:5

:3

P

M

15327

FIRE AND LIFE SAFETY PLANS

100-A003

1/8" = 1'-0"1

ENERGY PLANT FIRE AND LIFE SAFETY PLAN

1/8" = 1'-0"2

SUBSTATION B FIRE AND LIFE SAFETY PLAN

D T

BL

DG

BL

DG

.1

EN

ER

GY

PL

AN

T

PA

TIO

EN

GR

'G

NURSING TOWER

NURSING

BLDG.100

HOME

SH

OP

S

SE

RV

IC

E

CO

UR

T

SO

U

TH

D

RI

VE

LOT "G"

ROOF TOP

PATIO

LOT "F"

SE

RV

IC

E

CO

UR

T

FI

SH

ER

H O U

SE

C R E

DI

T U N

IO

N

GO

V'T ./S

RV

C.

RA

D

TH

ERA

PY

BLDG.100

D O O R

D O O R

GO

V' T

KEY PLAN

AREA OF WORK

PORTABLE

PORTABLEBUILDING

UJW

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

EXISTING PARTITION TO BE REMOVED

EXISTING PARTITION

LEGEND

HAZARDOUS MATERIAL REMOVAL IS

NOT WITHIN THE SCOPE OF THESE

DOCUMENTS. VETERANS

ADMINISTRATION WILL BE

RESPONSIBLE FOR REMOVING

HAZARDOUS MATERIAL FROM THE

AREA OF WORK. NOTIFY VETERANS

ADMINISTRATION OF ANY

HAZARDOUS MATERIAL FOUND IN

THE AREA OF WORK DURING

CONSTRUCTION.

CONTRACTOR SHALL VERIFY LIMITS

OF DEMOLITION WORK.

THIS DRAWING IDENTIFIES ONLY

MAJOR WORK FOR DEMOLITION AND

REMOVAL. ALL AREAS OF

DEMOLITION SHALL BE CLEARED OF

ALL ITEMS MAJOR AND MINOR TO

RECEIVE INSTALLATION OF NEW

CONSTRUCTION AND FINISHES.

SEE STRUCTURAL, MECHANICAL

AND ELECTRICAL DRAWINGS FOR

ADDITIONAL DEMOLITION

INFORMATION.

CONTRACTOR SHALL VERIFY ALL

EXISTING DIMENSIONS, MEMBER

SIZES AND CONDITIONS PRIOR TO

COMMENCING WORK. ALL

DIMENSIONS OF EXISTING

CONSTRUCTION ARE INTENDED AS

GUIDELINES ONLY AND MUST BE

VERIFIED. REPORT ANY

DISCREPANCIES BETWEEN

DIMENSIONS FOUND IN FIELD AND

DIMENSIONS ON DRAWINGS TO

ARCHITECT.

LOCATE ALL WIRES, PIPES,

UTILITIES, STRUCTURAL MEMBERS,

ETC. PRIOR TO ANY DEMOLITION.

CUTTING OF ANY ITEM WHICH IS

NOT PART OF THIS PROJECT SHALL

BE REPAIRED BY THE CONTRACTOR

AT NO ADDITIONAL COST TO THE

OWNER, INCLUDING ANY TESTING

OR SPECIAL OBSERVATION TO

CORRECT THE PROBLEM.

PATCH AND PAINT WALLS, FLOORS,

AND SUBFLOOR TO MATCH

EXISTING WHERE WORK HAS

DISTURBED EXISTING CONDITIONS.

ALL EXISTING FINISHES ARE TO BE

PROTECTED FROM DAMAGE.

DAMAGED AREAS SHALL BE

REPAIRED AT NO COST TO THE

OWNER.

PROTECT OPENING(S) DURING

CONSTRUCTION WHEN DEMOLISHING

FIRE RATED ASSEMBLIES (WALLS,

DOORS, ETC.) MEET ASSEMBLIES

ORIGINAL FIRE RATING.

D.12

D.13

D.14

D.18

600 Stewart St., Ste 1400 Seattle, Washington

98101 Tel 206.267.1700

Fax 206.267.1701

SAZAN #

100% CONSTRUCTION DOCUMENTS

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management

663-15-102

1660 South Columbian Way, Seattle, WA 98108

VA PUGET SOUND HEALTH CARE SYSTEM

UPGRADE SEATTLE ELECTRICAL

DISTRIBUTION FROM 5kV TO 15kV

01-19-2016

VAPAHCS PLANNING AND ENGINEERING

o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

269-1507

R. DAVID FRUM

STATE OF WASHINGTON

REGISTERED7043

ARCHITECT

1402 Third Avenue Suite 200 Seattle, WA 98101

TEL: 206/ 652-0722

FAX: 206/ 652-0720 -N

O T F

O R

C O

N S

TR

U

C

TIO

N

P R

ELI

M

IN

AR

Y

S A L U S

A R C H

IT

E C T U R E

IN

P Y R

IG

H T

Proj. Number

/1

/2

:5

:4

P

M

15327

ARCHITECTURAL DEMOLITION PLAN SERVICE

YARD

100-AD101

-KEYNOTES-

D.12 REMOVE TREE. SEE OWNER FOR

POSSIBLE RE-LOCATION INSTRUCTIONS.

D.13 REMOVE PORTABLES FROM AREA OF

WORK. COORDINATE WITH OWNER.

D.14 REMOVE WALLS, FOOTINGS, SLAB AND

FENCING SYSTEM AS INDICATED PER

PHASING REQUIREMENTS. COORDINATE

WITH STRUCTURAL, ELECTRICAL AND

CIVIL.

D.18 DEMOLISH EXISTING STAIR AS REQUIRED

IN PREPARATION FOR NEW WORK.

COORDINATE WITH STRUCTURAL AND

CIVIL.

D T

BL

DG

BL

DG

.1

EN

ER

GY

PL

AN

T

PA

TIO

EN

GR

'G

NURSING TOWER

NURSING

BLDG.100

HOME

SH

OP

S

SE

RV

IC

E

CO

UR

T

SO

U

TH

D

RI

VE

LOT "G"

ROOF TOP

PATIO

LOT "F"

SE

RV

IC

E

CO

UR

T

FI

SH

ER

H O U

SE

C R E

DI

T U N

IO

N

GO

V'T ./S

RV

C.

RA

D

TH

ERA

PY

BLDG.100

D O O R

D O O R

GO

V' T

KEY PLAN

AREA OF WORK

1/8" = 1'-0"1

TRANSFORMER YARD DEMO PLAN - ARCHITECTURAL

ROLL DOWN FIRE

SHUTTER (E)

ROLL DOWN FIRE

SHUTTER (E)

ROLL DOWN FIRE

SHUTTER (E)

U P

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

EXISTING PARTITION TO BE REMOVED

EXISTING PARTITION

LEGEND

HAZARDOUS MATERIAL REMOVAL IS

NOT WITHIN THE SCOPE OF THESE

DOCUMENTS. VETERANS

ADMINISTRATION WILL BE

RESPONSIBLE FOR REMOVING

HAZARDOUS MATERIAL FROM THE

AREA OF WORK. NOTIFY VETERANS

ADMINISTRATION OF ANY

HAZARDOUS MATERIAL FOUND IN

THE AREA OF WORK DURING

CONSTRUCTION.

CONTRACTOR SHALL VERIFY LIMITS

OF DEMOLITION WORK.

THIS DRAWING IDENTIFIES ONLY

MAJOR WORK FOR DEMOLITION AND

REMOVAL. ALL AREAS OF

DEMOLITION SHALL BE CLEARED OF

ALL ITEMS MAJOR AND MINOR TO

RECEIVE INSTALLATION OF NEW

CONSTRUCTION AND FINISHES.

SEE STRUCTURAL, MECHANICAL

AND ELECTRICAL DRAWINGS FOR

ADDITIONAL DEMOLITION

INFORMATION.

CONTRACTOR SHALL VERIFY ALL

EXISTING DIMENSIONS, MEMBER

SIZES AND CONDITIONS PRIOR TO

COMMENCING WORK. ALL

DIMENSIONS OF EXISTING

CONSTRUCTION ARE INTENDED AS

GUIDELINES ONLY AND MUST BE

VERIFIED. REPORT ANY

DISCREPANCIES BETWEEN

DIMENSIONS FOUND IN FIELD AND

DIMENSIONS ON DRAWINGS TO

ARCHITECT.

LOCATE ALL WIRES, PIPES,

UTILITIES, STRUCTURAL MEMBERS,

ETC. PRIOR TO ANY DEMOLITION.

CUTTING OF ANY ITEM WHICH IS

NOT PART OF THIS PROJECT SHALL

BE REPAIRED BY THE CONTRACTOR

AT NO ADDITIONAL COST TO THE

OWNER, INCLUDING ANY TESTING

OR SPECIAL OBSERVATION TO

CORRECT THE PROBLEM.

PATCH AND PAINT WALLS, FLOORS,

AND SUBFLOOR TO MATCH

EXISTING WHERE WORK HAS

DISTURBED EXISTING CONDITIONS.

ALL EXISTING FINISHES ARE TO BE

PROTECTED FROM DAMAGE.

DAMAGED AREAS SHALL BE

REPAIRED AT NO COST TO THE

OWNER.

PROTECT OPENING(S) DURING

CONSTRUCTION WHEN DEMOLISHING

FIRE RATED ASSEMBLIES (WALLS,

DOORS, ETC.) MEET ASSEMBLIES

ORIGINAL FIRE RATING.

6' - 0"

EMERGENCY

GENERATOR

BE-103

D.4

D.1 D.2D.2

D.3

D.6 D.7

D.8D.9

D.10

VERIFY

6"

D.8

D.11

D.3

D.4D.4

D.5 D.5

D.17D.17 D.17D.17

600 Stewart St., Ste 1400 Seattle, Washington

98101 Tel 206.267.1700

Fax 206.267.1701

SAZAN #

100% CONSTRUCTION DOCUMENTS

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management

663-15-102

1660 South Columbian Way, Seattle, WA 98108

VA PUGET SOUND HEALTH CARE SYSTEM

UPGRADE SEATTLE ELECTRICAL

DISTRIBUTION FROM 5kV TO 15kV

01-19-2016

VAPAHCS PLANNING AND ENGINEERING

o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

269-1507

R. DAVID FRUM

STATE OF WASHINGTON

REGISTERED7043

ARCHITECT

1402 Third Avenue Suite 200 Seattle, WA 98101

TEL: 206/ 652-0722

FAX: 206/ 652-0720 -N

O T F

O R

C O

N S

TR

U

C

TIO

N

P R

ELI

M

IN

AR

Y

S A L U S

A R C H

IT

E C T U R E

IN

P Y R

IG

H T

Proj. Number

/1

/2

:5

:4

P

M

15327

ARCHITECTURAL DEMOLITION PLAN ENERGY

PLANT

100-AD102

D T

BL

DG

BL

DG

.1

EN

ER

GY

PL

AN

T

PA

TIO

EN

GR

'G

NURSING TOWER

NURSING

BLDG.100

HOME

SH

OP

S

SE

RV

IC

E

CO

UR

T

SO

U

TH

D

RI

VE

LOT "G"

ROOF TOP

PATIO

LOT "F"

SE

RV

IC

E

CO

UR

T

FI

SH

ER

H O U

SE

C R E

DI

T U N

IO

N

GO

V'T ./S

RV

C.

RA

D

TH

ERA

PY

BLDG.100

D O O R

D O O R

GO

V' T

KEY PLAN

AREA OF WORK

1/8" = 1'-0"1

MAIN ELECTRICAL & GENERATOR ROOMS

RE-LOCATE OVERHEAD

PIPE TO PROVIDE

ADEQUATE CLEARANCE

FOR NEW

DOOR/EQUIPMENT

INSTALL.

CLEARANCE ISSUE

-KEYNOTES-

D.1 REMOVE EXISTING DOOR, FRAME,

HARDWARE AND ALL APPURTENANCES.

SEE OWNER FOR SALVAGE

INSTRUCTIONS.

D.2 REMOVE EXISTING LOUVERS. SEE

OWNER FOR SALVAGE INSTRUCTIONS.

D.3 REMOVE AND RE-INSTALL LOUVERS AS

REQUIRED PER NEW EQUIPMENT

INSTALLATION.

D.4 REMOVE EXISTING CURBS FROM

EMERGENCY GENERATOR ROOM BE-103

AS INDICATED.

D.5 REMOVE EXISTING CURBS AT EXTERIOR

PARTITION OF EMERGENCY GENERATOR

ROOM AS INDICATED IN PREPARATION

FOR NEW DOOR LOCATIONS. PRIOR TO

COMMENCING DEMOLITION VERIFY NEW

DOOR LOCATIONS ON SHEET 100-A102.

D.6 RE-LOCATE OVERHEAD PIPE TO

PROVIDE ADEQUATE CLEARANCE FOR

NEW DOOR/EQUIPMENT INSTALL. SEE

2/100-AD102 AND MECHANICAL.

D.7 RE-LOCATE WALL MOUNTED PANEL.

COORDINATE WITH ELECTRICAL.

D.8 EXTENT OF DEMOLISHED WALL IN

PREPARATION FOR NEW DOOR SIZE AND

LOCATION. COORDINATE RE-LOCATION

OF WALL MOUNTED EQUIPMENT WITH

ELECTRICAL. COORDINATE SAW CUT

LOCATION WITH STRUCTURAL. SEE NOTE

D.9 REMOVE EXISTING DOOR, FRAME,

HARDWARE AND ALL APPURTENANCES.

PREPARE OPENING FOR NEW DOOR AND

IN-FILL AS REQUIRED TO MATCH

EXISTING WALL AND RATING.

COORDINATE WITH STRUCTURAL. SEE

NOTE 9. SEE OWNER FOR SALVAGE

INSTRUCTIONS.

D.10 REMOVE EXISTING DOOR, FRAME,

HARDWARE AND ALL APPURTENANCES.

PREPARE OPENING FOR NEW DOOR AS

REQUIRED. VERIFY EXTENT OF

DEMOLITION WITH NEW DOOR

REQUIREMENTS. COORDINATE WITH

STRUCTURAL. SEE NOTE 9. SEE OWNER

FOR SALVAGE INSTRUCTIONS.

D.11 IF STAIR IS REMOVED BY CONTRACTOR

FOR PHASING REQUIREMENTS, PATH OF

EGRESS MUST BE MAINTAINED AT ALL

TIMES. REPLACE STAIR TO ORIGINAL

LOCATION UPON COMPLETION OF NEW

EQUIPMENT INSTALL. COORDINATE

REMOVAL WITH STRUCTURAL.

D.17 EXTENT OF DEMOLISHED CURB IN

PREPERATION FOR NEW DOOR.

R

L L

D O W N

F

IR

E

S H U T T E R

(E

R O L L

D O W N

F

IR

E

S H U T T E R

(E

D N

U P

L O U V E R

L O U V E R

C O M P A C T O R

C O M P A C T O R

T R A S H

C A R D B O A R D

A C C E S S

C O R R

ID

O R

L

IN

K

A B O V E

D O O R

TO

M

EZ

AB

O

VE

F D

RAISED WOOD WALKWAY

W/ METAL DECK

V E R T

IC

A L

L A D D E R

C M P A C T O R

C O N T R O L

D.15

D.16

D.16

D.10

D.8

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

EXISTING PARTITION TO BE REMOVED

EXISTING PARTITION

LEGEND

HAZARDOUS MATERIAL REMOVAL IS

NOT WITHIN THE SCOPE OF THESE

DOCUMENTS. VETERANS

ADMINISTRATION WILL BE

RESPONSIBLE FOR REMOVING

HAZARDOUS MATERIAL FROM THE

AREA OF WORK. NOTIFY VETERANS

ADMINISTRATION OF ANY

HAZARDOUS MATERIAL FOUND IN

THE AREA OF WORK DURING

CONSTRUCTION.

CONTRACTOR SHALL VERIFY LIMITS

OF DEMOLITION WORK.

THIS DRAWING IDENTIFIES ONLY

MAJOR WORK FOR DEMOLITION AND

REMOVAL. ALL AREAS OF

DEMOLITION SHALL BE CLEARED OF

ALL ITEMS MAJOR AND MINOR TO

RECEIVE INSTALLATION OF NEW

CONSTRUCTION AND FINISHES.

SEE STRUCTURAL, MECHANICAL

AND ELECTRICAL DRAWINGS FOR

ADDITIONAL DEMOLITION

INFORMATION.

CONTRACTOR SHALL VERIFY ALL

EXISTING DIMENSIONS, MEMBER

SIZES AND CONDITIONS PRIOR TO

COMMENCING WORK. ALL

DIMENSIONS OF EXISTING

CONSTRUCTION ARE INTENDED AS

GUIDELINES ONLY AND MUST BE

VERIFIED. REPORT ANY

DISCREPANCIES BETWEEN

DIMENSIONS FOUND IN FIELD AND

DIMENSIONS ON DRAWINGS TO

ARCHITECT.

LOCATE ALL WIRES, PIPES,

UTILITIES, STRUCTURAL MEMBERS,

ETC. PRIOR TO ANY DEMOLITION.

CUTTING OF ANY ITEM WHICH IS

NOT PART OF THIS PROJECT SHALL

BE REPAIRED BY THE CONTRACTOR

AT NO ADDITIONAL COST TO THE

OWNER, INCLUDING ANY TESTING

OR SPECIAL OBSERVATION TO

CORRECT THE PROBLEM.

PATCH AND PAINT WALLS, FLOORS,

AND SUBFLOOR TO MATCH

EXISTING WHERE WORK HAS

DISTURBED EXISTING CONDITIONS.

ALL EXISTING FINISHES ARE TO BE

PROTECTED FROM DAMAGE.

DAMAGED AREAS SHALL BE

REPAIRED AT NO COST TO THE

OWNER.

PROTECT OPENING(S) DURING

CONSTRUCTION WHEN DEMOLISHING

FIRE RATED ASSEMBLIES (WALLS,

DOORS, ETC.) MEET ASSEMBLIES

ORIGINAL FIRE RATING.

600 Stewart St., Ste 1400 Seattle, Washington

98101 Tel 206.267.1700

Fax 206.267.1701

SAZAN #

100% CONSTRUCTION DOCUMENTS

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management

663-15-102

1660 South Columbian Way, Seattle, WA 98108

VA PUGET SOUND HEALTH CARE SYSTEM

UPGRADE SEATTLE ELECTRICAL

DISTRIBUTION FROM 5kV TO 15kV

01-19-2016

VAPAHCS PLANNING AND ENGINEERING

o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

269-1507

R. DAVID FRUM

STATE OF WASHINGTON

REGISTERED7043

ARCHITECT

1402 Third Avenue Suite 200 Seattle, WA 98101

TEL: 206/ 652-0722

FAX: 206/ 652-0720 -N

O T F

O R

C O

N S

TR

U

C

TIO

N

P R

ELI

M

IN

AR

Y

S A L U S

A R C H

IT

E C T U R E

IN

P Y R

IG

H T

Proj. Number

/1

/2

:5

:4

P

M

15327

ARCHITECTURAL DEMOLITION PLAN SUBSTATION

B

100-AD103

1/8" = 1'-0"1

DEMO PLAN - SUBSTATION B

D T

BL

DG

BL

DG

.1

EN

ER

GY

PL

AN

T

PA

TIO

EN

GR

'G

NURSING TOWER

NURSING

BLDG.100

HOME

SH

OP

S

SE

RV

IC

E

CO

UR

T

SO

U

TH

D

RI

VE

LOT "G"

ROOF TOP

PATIO

LOT "F"

SE

RV

IC

E

CO

UR

T

FI

SH

ER

H O U

SE

C R E

DI

T U N

IO

N

GO

V'T ./S

RV

C.

RA

D

TH

ERA

PY

BLDG.100

D O O R

D O O R

GO

V' T

KEY PLAN

AREA OF WORK

-KEYNOTES-

D.8 EXTENT OF DEMOLISHED WALL IN

PREPARATION FOR NEW DOOR SIZE AND

LOCATION. COORDINATE RE-LOCATION

OF WALL MOUNTED EQUIPMENT WITH

ELECTRICAL. COORDINATE SAW CUT

LOCATION WITH STRUCTURAL. SEE NOTE

D.10 REMOVE EXISTING DOOR, FRAME,

HARDWARE AND ALL APPURTENANCES.

PREPARE OPENING FOR NEW DOOR AS

REQUIRED. VERIFY EXTENT OF

DEMOLITION WITH NEW DOOR

REQUIREMENTS. COORDINATE WITH

STRUCTURAL. SEE NOTE 9. SEE OWNER

FOR SALVAGE INSTRUCTIONS.

D.15 SAW CUT OPENING IN WALL AS

REQUIRED FOR NEW MECHANICAL

LOUVER. SEE SHEET 100-A200

ELEVATIONS FOR REFERENCE.

COORDINATE RE-LOCATION OF WALL

MOUNTED EQUIPMENT WITH ELECTRICAL.

COORDINATE SAW CUT LOCATION WITH

STRUCTURAL. SEE NOTE 9

D.16 EXTENT OF DEMOLISHED WALL IN

PREPARATION FOR NEW MECHANICAL

LOUVER. COORDINATE SAW CUT

LOCATION WITH STRUCTURAL.

3-

HR

R

OL

L

UP

ST

EE

L

DO

OR

3-

HR

R

OL

L

UP

ST

EE

L

DO

OR

F.

E.

F.

E.

F.

E.

F.

E.

F.

E.

F.

E.

F .E .C

LO

UV

ER

DN

DN

U P

TY

PI

C

AL

TA

NK

TY

PI

C

AL

C

ON

C

PI

ER

IN

FI

LL

W

AL

L

FD

F.

D.

F.

D.

F.

D.

F.

D.

F.

D.F.

D. F.

D.

F.

D.

D N

C

UR

TA

IN

SM

OK

E

U P

A F P B

M A T C H L

IN

E

SUBSTATIO

N "C

ES

SE

N

TI

AL

"C

ES

SE

N

TI

AL

"C

" F R

O N

T

EN

D

D.3D.3

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

EXISTING PARTITION TO BE REMOVED

EXISTING PARTITION

LEGEND

HAZARDOUS MATERIAL REMOVAL IS

NOT WITHIN THE SCOPE OF THESE

DOCUMENTS. VETERANS

ADMINISTRATION WILL BE

RESPONSIBLE FOR REMOVING

HAZARDOUS MATERIAL FROM THE

AREA OF WORK. NOTIFY VETERANS

ADMINISTRATION OF ANY

HAZARDOUS MATERIAL FOUND IN

THE AREA OF WORK DURING

CONSTRUCTION.

CONTRACTOR SHALL VERIFY LIMITS

OF DEMOLITION WORK.

THIS DRAWING IDENTIFIES ONLY

MAJOR WORK FOR DEMOLITION AND

REMOVAL. ALL AREAS OF

DEMOLITION SHALL BE CLEARED OF

ALL ITEMS MAJOR AND MINOR TO

RECEIVE INSTALLATION OF NEW

CONSTRUCTION AND FINISHES.

SEE STRUCTURAL, MECHANICAL

AND ELECTRICAL DRAWINGS FOR

ADDITIONAL DEMOLITION

INFORMATION.

CONTRACTOR SHALL VERIFY ALL

EXISTING DIMENSIONS, MEMBER

SIZES AND CONDITIONS PRIOR TO

COMMENCING WORK. ALL

DIMENSIONS OF EXISTING

CONSTRUCTION ARE INTENDED AS

GUIDELINES ONLY AND MUST BE

VERIFIED. REPORT ANY

DISCREPANCIES BETWEEN

DIMENSIONS FOUND IN FIELD AND

DIMENSIONS ON DRAWINGS TO

ARCHITECT.

LOCATE ALL WIRES, PIPES,

UTILITIES, STRUCTURAL MEMBERS,

ETC. PRIOR TO ANY DEMOLITION.

CUTTING OF ANY ITEM WHICH IS

NOT PART OF THIS PROJECT SHALL

BE REPAIRED BY THE CONTRACTOR

AT NO ADDITIONAL COST TO THE

OWNER, INCLUDING ANY TESTING

OR SPECIAL OBSERVATION TO

CORRECT THE PROBLEM.

PATCH AND PAINT WALLS, FLOORS,

AND SUBFLOOR TO MATCH

EXISTING WHERE WORK HAS

DISTURBED EXISTING CONDITIONS.

ALL EXISTING FINISHES ARE TO BE

PROTECTED FROM DAMAGE.

DAMAGED AREAS SHALL BE

REPAIRED AT NO COST TO THE

OWNER.

PROTECT OPENING(S) DURING

CONSTRUCTION WHEN DEMOLISHING

FIRE RATED ASSEMBLIES (WALLS,

DOORS, ETC.) MEET ASSEMBLIES

ORIGINAL FIRE RATING.

600 Stewart St., Ste 1400 Seattle, Washington

98101 Tel 206.267.1700

Fax 206.267.1701

SAZAN #

100% CONSTRUCTION DOCUMENTS

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management

663-15-102

1660 South Columbian Way, Seattle, WA 98108

VA PUGET SOUND HEALTH CARE SYSTEM

UPGRADE SEATTLE ELECTRICAL

DISTRIBUTION FROM 5kV TO 15kV

01-19-2016

VAPAHCS PLANNING AND ENGINEERING

o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

269-1507

R. DAVID FRUM

STATE OF WASHINGTON

REGISTERED7043

ARCHITECT

1402 Third Avenue Suite 200 Seattle, WA 98101

TEL: 206/ 652-0722

FAX: 206/ 652-0720 -N

O T F

O R

C O

N S

TR

U

C

TIO

N

P R

ELI

M

IN

AR

Y

S A L U S

A R C H

IT

E C T U R E

IN

P Y R

IG

H T

Proj. Number

/1

/2

:5

:4

P

M

15327

ARCHITECTURAL DEMOLITION PLAN ELECTRICAL

ROOM C

100-AD104

1/8" = 1'-0"1

DEMO PLAN - ELECTRICAL ROOM C

D T

BL

DG

BL

DG

.1

EN

ER

GY

PL

AN

T

PA

TIO

EN

GR

'G

NURSING TOWER

NURSING

BLDG.100

HOME

SH

OP

S

SE

RV

IC

E

CO

UR

T

SO

U

TH

D

RI

VE

LOT "G"

ROOF TOP

PATIO

LOT "F"

SE

RV

IC

E

CO

UR

T

FI

SH

ER

H O U

SE

C R E

DI

T U N

IO

N

GO

V'T ./S

RV

C.

RA

D

TH

ERA

PY

BLDG.100

D O O R

D O O R

GO

V' T

KEY PLAN

AREA OF WORK

-KEYNOTES-

D.3 REMOVE AND RE-INSTALL LOUVERS AS

REQUIRED PER NEW EQUIPMENT

INSTALLATION.

W

100-A200

CURB - COORDINATE

WITH STRUCTURAL & CIVIL

16' - 3 1/2"

36' - 3"

50'

2"160.8°

14' - 5"10' - 5"

100-A101

100-A101

100-A101

11'

7" 100-A101

TYP

100-A101

1'

- 4

TYP

160.8°

CMU WALL - SEE STRUCTURAL

PL 3/4" WELD TO HSS-SEE STRUCTRAL

COORDINATE BOLTED CONNECTION TO

CURB WITH ELECTRICAL GROUNDING

REQUIREMENTS AND STRUCTURAL.

HSS 4"x4"x1/4" FRAME WITH GROUND SMOOTH

MITERED CORNERS-PAINTED (TYP)

1 1/2" SQUARE STEEL BARS WELDED TO

STEEL TUBING. (TOP, BOTTOM & MID RAIL)

GRIND SMOOTH AND PAINT. (TYP)

CMU WALL

SEE STRUCTRAL

CURB- SEE STRUCTURAL AND CIVIL

EXP ANCHORS-SEE STRUCTRAL

160.8°

CHAMFER END OF CMU WALL FOR

FLAT PARALLEL EDGE FENCE

SUPPORT

4 1/2" x 4 7/8" x 1/4"

STEEL CHANNEL

1" MAX GROUT FOR

PLUMBING CMU

3/4" DIAM(TYP)-SEE STRUCTRAL

9"

1"

TYP

1 1

/2"

4" x 3" x 1/4" HSS FRAME WITH

GROUND SMOOTH MITERED CORNERS-

PAINTED (TYP)

2 5/8" X 3 1/2" X 1/4" STEEL CHANNEL

EXP ANCHORS-SEE STRUCTRAL

2 5/8" X 3" X 1/4" STEEL CHANNEL

STEEL CHANNELS WELDED TOGETHER

-SEE STRUCTRAL

E Q

E Q

1 1/2" SQUARE STEEL BARS

WELDED TO STEEL TUBING.

(TOP, BOTTOM & MID RAIL)

GRIND SMOOTH AND PAINT.

CONTINUOUS STEEL HINGE.

WELD TO GATE AND CHANNEL-SEE STRUCTRAL

7/8

1" MAX GROUT FOR

PLUMBING CMU

PL 1/2"

COORDINATE BOLTED CONNECTION TO

CURB WITH ELECTRICAL GROUNDING

REQUIREMENTS AND STRUCTURAL.

HSS 2"x4"x1/4" FRAME WITH GROUND

SMOOTH MITERED CORNERS-PAINTED (TYP)

WELD TO PL 3/4"-SEE STRUCTRAL

1 1/2" SQUARE STEEL BARS WELDED TO HSS.

(TOP, BOTTOM & MID RAIL) GRIND SMOOTH

AND PAINT. (TYP)

CURB

E Q

E Q

8"

TYP

3"

SQ

TYP 3/4" DIAM(TYP)-SEE STRUCTRAL

TYP

1 1

/2"

CONT CONC CAP

TOOLED EDGES

16" CMU BLOCK

CONCRETE FILL

1/4"x2"x2" STEEL ANGLE

WELDED TO HEAD OF FRAME

W/ 5/8" DIAM HOLE FOR

BOLTED CONNECTION TO

ADJACENT FENCE PANEL

-SEE STRUCTRAL

HSS FENCING FRAME

GENERAL NOTES

SEE STRUCTRAL FOR CMU WALL

CONSTRUCTION DETAILS.

ALL DIMENSIONS TO FACE OF

FINISH UNLESS NOTED

OTHERWISE.

SEE MECHANICAL AND ELECTRICAL

FOR ADDITIONAL INFORMATION.

PROTECT OPENING(S) DURING

CONSTRUCTION WHEN

DEMOLISHING FIRE RATED

ASSEMBLIES (WALLS, DOORS, ETC.)

MEET ASSEMBLIES ORIGINAL FIRE

RATING.

SEE ELECTRICAL FOR REQUIRED

FENCE AND GATE GROUNDING

DETAILS.

SEAL WELD ALL AROUND ALL HSS

CONNECTIONS.

ALL STEEL FRAMING AND BASE

PLATES AT CURB TO BE PAINTED.

1.

2.

3.

4.

5.

6.

7.

HSS 4"x3"x1/4" FRAME W/ GROUND

SMOOTH MITERED CORNERS-PAINTED (TYP)

1 1/2" SQUARE STEEL BARS

WELDED TO HSS.

(TOP, BOTTOM & MID RAIL)

GRIND SMOOTH AND PAINT.

2 5/8" X 3 1/2" X 1/4" STEEL CHANNEL

CONTINUOUS STEEL HINGE.

WELD TO GATE AND CHANNEL-SEE STRUCTRAL

CURB-SEE STRUCTRAL

EXP ANCHORS-SEE STRUCTRAL

CMU WALL-SEE STRUCTRAL

M

IN3

2 1/4" 4" SPACING (TYP)

2 5/8" X 3" X 1/4" STEEL CHANNEL

STEEL CHANNELS WELDED TOGETHER,

GROUND SMOOTH AND PAINTED (TYP)

1" MAX GROUT FOR

PLUMBING C4

600 Stewart St., Ste 1400 Seattle, Washington

98101 Tel 206.267.1700

Fax 206.267.1701

SAZAN #

100% CONSTRUCTION DOCUMENTS

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management

663-15-102

1660 South Columbian Way, Seattle, WA 98108

VA PUGET SOUND HEALTH CARE SYSTEM

UPGRADE SEATTLE ELECTRICAL

DISTRIBUTION FROM 5kV TO 15kV

01-19-2016

VAPAHCS PLANNING AND ENGINEERING

o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

269-1507

R. DAVID FRUM

STATE OF WASHINGTON

REGISTERED7043

ARCHITECT

1402 Third Avenue Suite 200 Seattle, WA 98101

TEL: 206/ 652-0722

FAX: 206/ 652-0720 -N

O T F

O R

C O

N S

TR

U

C

TIO

N

P R

ELI

M

IN

AR

Y

S A L U S

A R C H

IT

E C T U R E

IN

P Y R

IG

H T

Proj. Number

/1

/2

:5

:3

P

M

15327

SERVICE YARD PLAN AND DETAILS

100-A101

1/8" = 1'-0"1

SERVICE YARD PLAN - ARCHITECTURAL

D T

BL

DG

BL

DG

.1

EN

ER

GY

PL

AN

T

PA

TIO

EN

GR

'G

NURSING TOWER

NURSING

BLDG.100

HOME

SH

OP

S

SE

RV

IC

E

CO

UR

T

SO

U

TH

D

RI

VE

LOT "G"

ROOF TOP

PATIO

LOT "F"

SE

RV

IC

E

CO

UR

T

FI

SH

ER

H O U

SE

C R E

DI

T U N

IO

N

GO

V'T ./S

RV

C.

RA

D

TH

ERA

PY

BLDG.100

D O O R

D O O R

GO

V' T

KEY PLAN

AREA OF WORK

1 1/2" = 1'-0"2

SERVICE YARD FENCE POST CONNECTION AT CMU WALL

3" = 1'-0"7

SERVICE YARD PERSONNEL GATE CONNECTION

1 1/2" = 1'-0"3

SERVICE YARD FENCE POST FOOTER - (TYP)

3" = 1'-0"5

CMU WALL CAP - SERVICE YARD (TYP)

3" = 1'-0"4

SERVICE YARD FENCE POST HEADER - (TYP)

3" = 1'-0"6

SERVICE YARD GATE DETAIL

SUBSTATION "A"

MAIN SERVICE SWITCHGEAR

ROLL DOWN FIRE

SHUTTER (E)

ROLL DOWN FIRE

SHUTTER (E)

ROLL DOWN FIRE

SHUTTER (E)

U P

GENERAL NOTES

SEE PARTITION TYPES SHEET FOR

LEGEND AND CONSTRUCTION

ASSEMBLIES.

ALL DIMENSIONS TO FACE OF

FINISH UNLESS NOTED

OTHERWISE.

SEE MECHANICAL AND ELECTRICAL

FOR ADDITIONAL INFORMATION.

PROTECT OPENING(S) DURING

CONSTRUCTION WHEN DEMOLISHING

FIRE RATED ASSEMBLIES (WALLS,

DOORS, ETC.) MEET ASSEMBLIES

ORIGINAL FIRE RATING.

INDICATION OF GENERATORS AND

HOUSE KEEPING PADS ARE FOR

REFERENCE ONLY. SEE

STRUCTURAL AND ELECTRICAL.

1.

2.

3.

4.

5.

LEGEND

ACOUSTICAL WALL TREATMENT

REACTOR ROOM

BE-108

MAIN

SWITCHGEAR

BE-101

EMERGENCY

SWITCHGEAR

BE-102

EMERGENCY

GENERATOR

BE-103

103A 103B

103C108

100-A200

2' - 2"

20' - 5"17' - 8"17' - 2" EQ EQ EQ EQ

SOUND

CHAMBER-A

SOUND

CHAMBER-B

SOUND

CHAMBER-C

A.2 A.2A.2

A.3 A.3A.3

FIXED

LEAF

OPERABLE

LEAF

A.1 A.4A.4A.4A.4

A.5

A.6 A.6

600 Stewart St., Ste 1400 Seattle, Washington

98101 Tel 206.267.1700

Fax 206.267.1701

SAZAN #

100% CONSTRUCTION DOCUMENTS

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management

663-15-102

1660 South Columbian Way, Seattle, WA 98108

VA PUGET SOUND HEALTH CARE SYSTEM

UPGRADE SEATTLE ELECTRICAL

DISTRIBUTION FROM 5kV TO 15kV

01-19-2016

VAPAHCS PLANNING AND ENGINEERING

o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

269-1507

R. DAVID FRUM

STATE OF WASHINGTON

REGISTERED7043

ARCHITECT

1402 Third Avenue Suite 200 Seattle, WA 98101

TEL: 206/ 652-0722

FAX: 206/ 652-0720 -N

O T F

O R

C O

N S

TR

U

C

TIO

N

P R

ELI

M

IN

AR

Y

S A L U S

A R C H

IT

E C T U R E

IN

P Y R

IG

H T

Proj. Number

/1

/2

:5

:3

P

M

15327

ENERGY PLANT PLAN

100-A102

D T

BL

DG

BL

DG

.1

EN

ER

GY

PL

AN

T

PA

TIO

EN

GR

'G

NURSING TOWER

NURSING

BLDG.100

HOME

SH

OP

S

SE

RV

IC

E

CO

UR

T

SO

U

TH

D

RI

VE

LOT "G"

ROOF TOP

PATIO

LOT "F"

SE

RV

IC

E

CO

UR

T

FI

SH

ER

H O U

SE

C R E

DI

T U N

IO

N

GO

V'T ./S

RV

C.

RA

D

TH

ERA

PY

BLDG.100

D O O R

D O O R

GO

V' T

KEY PLAN

AREA OF WORK

1/8" = 1'-0"1

ENERGY PLANT

-KEYNOTES-

A.1 INFILL TO MATCH EXISTING PARTITION,

FINISHES AND FIRE RATING.

A.2 METAL WALL, CURB BELOW AND DOOR

- SEE MECHANICAL AND STRUCTURAL.

A.3 HOUSEKEEPING PAD SEE STRUCTURAL.

A.4 INSTALL 1" THICK SOUND ABSORPTIVE

TREATMENT OVER APPROXIMATELY 50%

OF THE AVAILABLE WALL AND CEILING

SURFACES AS INDICATED. COORDINATE

WITH WALL MOUNTED EQUIPMENT.

BEGIN WALL COVERING 3'-0" AFF.

A.5 FINISH FLOOR WITH COLD

FLUID-APPLIED WATERPROOFING. RUN

UP WALL 4" AFF.

A.6 CURB SEE STRUCTURAL.

D N

U P

L O U V E R

L O U V E R

C O M P A C T O R

C O M P A C T O R

T R A S H

C A R D B O A R D

A C C E S S

C O R R

ID

O R

L

IN

K

A B O V E

D O O R

TO

M

EZ

AB

O

VE

F D

V E R T

IC

A L

L A D D E R

C M P A C T O R

C O N T R O L

SUBSTATION B

BD-115

100-A200 2

3-HR ROLL DOWN FIRE

SHUTTER

115A

V E R

IF

Y

A.1

3-HR ROLL

DOWN FIRE

SHUTTER (E)

3-HR ROLL

DOWN FIRE

SHUTTER (E)

100-AE400

TYP

115B(E)

GENERAL NOTES

SEE PARTITION TYPES SHEET FOR

LEGEND AND CONSTRUCTION

ASSEMBLIES.

ALL DIMENSIONS TO FACE OF FINISH

UNLESS NOTED OTHERWISE.

SEE MECHANICAL AND ELECTRICAL

FOR ADDITIONAL INFORMATION.

PROTECT OPENING(S) DURING

CONSTRUCTION WHEN DEMOLISHING

FIRE RATED ASSEMBLIES (WALLS,

DOORS, ETC.) MEET ASSEMBLIES

ORIGINAL FIRE RATING.

COORDINATE AND VERIFY

MECHANICAL AND ELECTRICAL

EQUIPMENT SIZES (SEE MECHANICAL

AND ELECTRICAL)

1.

2.

3.

4.

5.

600 Stewart St., Ste 1400 Seattle, Washington

98101 Tel 206.267.1700

Fax 206.267.1701

SAZAN #

100% CONSTRUCTION DOCUMENTS

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management

663-15-102

1660 South Columbian Way, Seattle, WA 98108

VA PUGET SOUND HEALTH CARE SYSTEM

UPGRADE SEATTLE ELECTRICAL

DISTRIBUTION FROM 5kV TO 15kV

01-19-2016

VAPAHCS PLANNING AND ENGINEERING

o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

269-1507

R. DAVID FRUM

STATE OF WASHINGTON

REGISTERED7043

ARCHITECT

1402 Third Avenue Suite 200 Seattle, WA 98101

TEL: 206/ 652-0722

FAX: 206/ 652-0720 -N

O T F

O R

C O

N S

TR

U

C

TIO

N

P R

ELI

M

IN

AR

Y

S A L U S

A R C H

IT

E C T U R E

IN

P Y R

IG

H T

Proj. Number

/1

/2

:5

:3

P

M

15327

SUBSTATION B PLAN

100-A103

D T

BL

DG

BL

DG

.1

EN

ER

GY

PL

AN

T

PA

TIO

EN

GR

'G

NURSING TOWER

NURSING

BLDG.100

HOME

SH

OP

S

SE

RV

IC

E

CO

UR

T

SO

U

TH

D

RI

VE

LOT "G"

ROOF TOP

PATIO

LOT "F"

SE

RV

IC

E

CO

UR

T

FI

SH

ER

H O U

SE

C R E

DI

T U N

IO

N

GO

V'T ./S

RV

C.

RA

D

TH

ERA

PY

BLDG.100

D O O R

D O O R

GO

V' T

KEY PLAN

AREA OF WORK

1/8" = 1'-0"1

SUBSTATION B

-KEYNOTES-

A.1 INFILL TO MATCH EXISTING PARTITION,

FINISHES AND FIRE RATING.

3-

HR

R

OL

L

UP

ST

EE

L

DO

OR

3-

HR

R

OL

L

UP

ST

EE

L

DO

OR

F.

E.

F.

E.

F.

E.

F.

E.

F.

E.

F.

E.

F .E .C

LO

UV

ER

DN

DN

U P

TY

PI

C

AL

TA

NK

TY

PI

C

AL

C

ON

C

PI

ER

IN

FI

LL

W

AL

L

FD

F.

D.

F.

D.

F.

D.

F.

D.

F.

D.F.

D. F.

D.

F.

D.

D N

C

UR

TA

IN

SM

OK

E

U P

A F P B

M A T C H L

IN

E

SUBSTATIO

N "C

ES

SE

N

TI

AL

"C

ES

SE

N

TI

AL

"C

" F R

O N

T

EN

D

D.3D.3

ELECTRICAL

ROOM C

BC-102

GENERAL NOTES

SEE PARTITION TYPES SHEET FOR

LEGEND AND CONSTRUCTION

ASSEMBLIES.

ALL DIMENSIONS TO FACE OF

FINISH UNLESS NOTED

OTHERWISE.

SEE MECHANICAL AND ELECTRICAL

FOR ADDITIONAL INFORMATION.

PROTECT OPENING(S) DURING

CONSTRUCTION WHEN DEMOLISHING

FIRE RATED ASSEMBLIES (WALLS,

DOORS, ETC.) MEET ASSEMBLIES

ORIGINAL FIRE RATING.

INDICATION OF GENERATORS AND

HOUSE KEEPING PADS ARE FOR

REFERENCE ONLY. SEE

STRUCTURAL AND ELECTRICAL.

1.

2.

3.

4.

5.

LEGEND

ACOUSTICAL WALL TREATMENT

600 Stewart St., Ste 1400 Seattle, Washington

98101 Tel 206.267.1700

Fax 206.267.1701

SAZAN #

100% CONSTRUCTION DOCUMENTS

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management

663-15-102

1660 South Columbian Way, Seattle, WA 98108

VA PUGET SOUND HEALTH CARE SYSTEM

UPGRADE SEATTLE ELECTRICAL

DISTRIBUTION FROM 5kV TO 15kV

01-19-2016

VAPAHCS PLANNING AND ENGINEERING

o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

269-1507

R. DAVID FRUM

STATE OF WASHINGTON

REGISTERED7043

ARCHITECT

1402 Third Avenue Suite 200 Seattle, WA 98101

TEL: 206/ 652-0722

FAX: 206/ 652-0720 -N

O T F

O R

C O

N S

TR

U

C

TIO

N

P R

ELI

M

IN

AR

Y

S A L U S

A R C H

IT

E C T U R E

IN

P Y R

IG

H T

Proj. Number

/1

/2

:5

:4

P

M

15327

ELECTRICAL ROOM C PLAN

100-A104

D T

BL

DG

BL

DG

.1

EN

ER

GY

PL

AN

T

PA

TIO

EN

GR

'G

NURSING TOWER

NURSING

BLDG.100

HOME

SH

OP

S

SE

RV

IC

E

CO

UR

T

SO

U

TH

D

RI

VE

LOT "G"

ROOF TOP

PATIO

LOT "F"

SE

RV

IC

E

CO

UR

T

FI

SH

ER

H O U

SE

C R E

DI

T U N

IO

N

GO

V'T ./S

RV

C.

RA

D

TH

ERA

PY

BLDG.100

D O O R

D O O R

GO

V' T

KEY PLAN

AREA OF WORK

1/8" = 1'-0"1

ELECTRICAL ROOM C

-KEYNOTES-

D.3 REMOVE AND RE-INSTALL LOUVERS AS

REQUIRED PER NEW EQUIPMENT

INSTALLATION.

GENERAL NOTES

SEE MECHANICAL, PLUMBING, AND

ELECTRICAL DRAWINGS FOR WALL

PENETRATIONS AND ITEMS TO BE

ACCOMODATED ON THE EXTERIOR.

SEE SHEET 100-A101 FOR FENCE

AND GATE MOUNTING DETAILS.

1.

2.

100-A101

TYP

100-A200

(T Y P

(E) LOUVER SYSTEM

4' - 0"10"

2' - 10"

100-AE400

TYP

100-AE400

TYP

(E) PANEL SYSTEM ABOVE

LOUVERS TO REMAIN

S E E

S T R U C T U R A L

C U R B

ACTIVE

LEAF

INACTIVE

LEAF

ACTIVE

LEAF

INACTIVE

LEAF

V E R

IF

Y

(E

L=NEW LOUVER

P=NEW PANEL

P P P P P

PPPPPPPP

P

PP

L L L L L L L L L L L L L L L L L L L

100-AE400

TYP

100-AE400

TYP

100-AE400

TYP

100-AE400

TYP

ALLIGN NEW JOINTS

WITH EXISTING (TYP)

CURB GATE HASP WELDED

TO FRAME

(LOCK TO BE

PROVIDED BY SCL)

4"

GATE PANEL

4' - 9"

GATE PANEL

4' - 9"1"

4" 4"4"

4"x4"x1/4" STEEL TUBE FRAME (TYP)

100-A200

100-A200

A B B B B B A

100-A200

ANGLED WALL UNROLLED FOR CLARITY

CURB

5' - 6 1/2"

4"

2"x4"x1/4" HSS

FRAME (TYP)

2"

4"x4"x1/4" HSS

FRAME (TYP)

CURB

5' - 4 1/2"

2" 2"

2"x4"x1/4" HSS

FRAME (TYP)

4"x4"x1/4" HSS

FRAME (TYP)

4' - 9"

4" 4"

4"x4"x1/4"

HSS FRAME

2"x4"x1/4"

HSS FRAME

WELD 4"x4"x1/4" HSS TO

ADJACENT FENCE FRAME

AND STEEL CHANNEL

-SEE STRUCTRAL

600 Stewart St., Ste 1400 Seattle, Washington

98101 Tel 206.267.1700

Fax 206.267.1701

SAZAN #

100% CONSTRUCTION DOCUMENTS

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management

663-15-102

1660 South Columbian Way, Seattle, WA 98108

VA PUGET SOUND HEALTH CARE SYSTEM

UPGRADE SEATTLE ELECTRICAL

DISTRIBUTION FROM 5kV TO 15kV

01-19-2016

VAPAHCS PLANNING AND ENGINEERING

o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

269-1507

R. DAVID FRUM

STATE OF WASHINGTON

REGISTERED7043

ARCHITECT

1402 Third Avenue Suite 200 Seattle, WA 98101

TEL: 206/ 652-0722

FAX: 206/ 652-0720 -N

O T F

O R

C O

N S

TR

U

C

TIO

N

P R

ELI

M

IN

AR

Y

S A L U S

A R C H

IT

E C T U R E

IN

P Y R

IG

H T

Proj. Number

/1

/2

:5

:4

P

M

15327

ELEVATIONS

100-A200

1/4" = 1'-0"1

SERVICE YARD WEST

1/4" = 1'-0"2

SUBSTATION B EXTERIOR

1/4" = 1'-0"5

ENERGY PLANT

1/2" = 1'-0"3

SERVICE YARD GATE

1/2" = 1'-0"6

METAL FENCE END PANEL (A)

1/2" = 1'-0"7

METAL FENCE PANEL (B)

ACTIVE

LEAF

INACTIVE

LEAF

1/2" = 1'-0"4

SERVICE YARD PERSONNEL GATE

HOLLOW METAL

FACTORY FINISH

METAL

PAINT

DOOR SEAL (THREE SIDES)

SOLID CORE

SOLID GROUT FRAME

STEEL

1 1/2 HOUR U.L RATED DOOR ASSEMBLY

3 HOUR U.L RATED DOOR ASSEMBLY

DOOR SCHEDULE ABBREVIATIONS

GENERAL NOTES

COORDINATE FRAME SIZES WITH WALL THICKNESS AT NEW AND

EXISTING CONDITIONS.

PROVIDE SAFETY GLAZING WHERE REQUIRED BY BUILDING CODE.

SEE VA STANDARD SECURITY DOOR TYPES FOR LOCATION OF

HARDWARE AND APPLICABLE APPURTENANCES.

1.

2.

3.

DOOR SCHEDULE NOTES

EXISTING DOOR TO REMAIN. CONTRACTOR TO VERIFY EXISTING

DOOR IS EQUIPED WITH CURRENT STANDARD SECURITY DOOR

HARDWARE AND UPGRADE AS REQUIRED.

OPERATION AT ALL TIMES

- OUTSIDE LEVER ALWAYS RIGID

- KEY RETRACTS LATCHBOLT FROM EXTERIOR

- INSIDE LEVER RETRACTS LATCH BOLT AT ALL TIMES

- DOOR MONITOR ALARMED AT CENTRAL MONITORING STATION

NORMAL DAYTIME OPERATION

- FREE OPERATION FROM EITHER SIDE

AFTER HOURS OPERATION

- EXTERIOR LEVER INOPERATIVE

- CARD READER ON EXTERIOR RELEASES ELECTRIC STRIKE

OR MAGNETIC LOCK

- DELAYED ACTION AND ALARMED OPERATION FROM INTERIOR

- DOOR CONTACT ALARMED TO CENTRAL MONITORING

VERIFY DOOR SIZE PROVIDES ADEQUATE CLEARANCE FOR

EQUIPMENT INSTALL PRIOR TO PURCHASE.

A.

B.

C.

D.

HARDWARE SETS - TO BE VERIFIED BY VA

HW-1 CARD READER

CLOSER

CONTINUOUS HINGE

DOOR CONTACT

FLUSH BOLTS

MORTISE LOCK (ANSI F07 STOREROOM)

IDS AUDIBLE AND REMOTE ALARM

HM

FF

MTL

PT

S3

SC

SGF

STL

1 1/2HR

3HR

HW-2 CARD READER

CLOSER

CONTINUOUS HINGE

DEADBOLT

DOOR CONTACT

ELECTRIC STRIKE

EXIT DEVICE (FIRE EXIT HW)

AUTOMATIC FLUSH BOLTS

HOLD OPEN ALARM

MAGNETIC LOCK

MORTISE LOCK (ANSI F04 ENTRY)

FAIL SAFE

AUTO DROP SEAL

HW-3 CARD READER

CLOSER

CONTINUOUS HINGE

DEADBOLT

DOOR CONTACT

ELECTRIC STRIKE

EXIT DEVICE (FIRE EXIT HW)

AUTOMATIC FLUSH BOLTS

HOLD OPEN ALARM

MAGNETIC LOCK

MORTISE LOCK (ANSI F04 ENTRY)

FAIL SAFE

REQUEST…

This is the start of the file's text. The full file is on GovTribe.

Other files

File Type Posted
VA260-16-R-0001-A00008001.pdf PDF
VA260-16-R-0001-A00008002.docx DOCX document
VA260-16-R-0001-A00008000.docx DOCX document
VA260-16-R-0001-A00007003.xlsx XLSX spreadsheet
VA260-16-R-0001-A00007002.pdf PDF
VA260-16-R-0001-A00007001.pdf PDF
VA260-16-R-0001-A00007004.doc DOC document
VA260-16-R-0001-A00007005.docx DOCX document
VA260-16-R-0001-A00007000.docx DOCX document
VA260-16-R-0001-A00006001.pdf PDF
VA260-16-R-0001-A00006000.docx DOCX document
VA260-16-R-0001-A00005005.pdf PDF
VA260-16-R-0001-A00005004.pdf PDF
VA260-16-R-0001-A00005002.pdf PDF
VA260-16-R-0001-A00005003.pdf PDF
VA260-16-R-0001-A00005001.pdf PDF
VA260-16-R-0001-A00005000.docx DOCX document
VA260-16-R-0001-A00004005.pdf PDF
VA260-16-R-0001-A00004001.pdf PDF
VA260-16-R-0001-A00004003.pdf PDF
VA260-16-R-0001-A00004004.pdf PDF
VA260-16-R-0001-A00004002.pdf PDF
VA260-16-R-0001-A00004000.docx DOCX document
VA260-16-R-0001-A00003009.pdf PDF
VA260-16-R-0001-A00003002.pdf PDF
VA260-16-R-0001-A00003010.docx DOCX document
VA260-16-R-0001-A00003012.pdf PDF
VA260-16-R-0001-A00003011.pdf PDF
VA260-16-R-0001-A00003001.pdf PDF
VA260-16-R-0001-A00003003.pdf PDF
VA260-16-R-0001-A00003000.docx DOCX document
VA260-16-R-0001-A00003004.pdf PDF
VA260-16-R-0001-A00003007.pdf PDF
VA260-16-R-0001-A00003006.pdf PDF
VA260-16-R-0001-A00003005.pdf PDF
VA260-16-R-0001-A00003008.pdf PDF
VA260-16-R-0001-A00002001.pdf PDF
VA260-16-R-0001-A00002000.docx DOCX document
VA260-16-R-0001-A00002002.pdf PDF
VA260-16-R-0001-A00002003.pdf PDF
VA260-16-R-0001-A00001000.docx DOCX document
VA260-16-R-0001-A00001006.pdf PDF
VA260-16-R-0001-A00001005.pdf PDF
VA260-16-R-0001-A00001004.pdf PDF
VA260-16-R-0001-A00001002.pdf PDF
VA260-16-R-0001-A00001001.pdf PDF
VA260-16-R-0001-A00001003.pdf PDF
Attachment F Past Performance Questionnaire —
Attachment B Construction Specifications —
Copy of Attachment E Price Schedule Breakdown —