6C-168 - DEMO
SCALE =
" =1'-0"
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg.
of
Building Number
Project Number
Office of
Construction and Facilities
Management
6587 HAMILTON AVENUE
PITTSBURGH, PENNSYLVANIA 15206
PH: 412.287.7333 FAX: 412.287.7334
www.ae-works.com
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECTS/ENGINEERS:
Revisions:
Date
6 " o n e e i g h t h i n c o e f o t o n e q u a r t e r i n o t t h r e e e i g h t h s i n o t o n e h a l f i n o t t h r e e q u a r t e r s i n o t o n e i n o t o n e a d a l f i n o t t h r e e i n c h e s o t
100% CONSTRUCTION DOCUMENTS
NORTH
10 NORTH GREENE STREET BALTIMORE, MD 21201
Upgrade Public and Staff Restrooms 512-12-118
04 / 30 / 14
6C153, 6C159 - DEMO
SCALE =
" =1'-0"
6D153 - DEMO
SCALE =
" =1'-0"
6C103, 6C108, 6C123 - DEMO
SCALE =
" =1'-0"
6C138, 6C140 - DEMO
SCALE =
" =1'-0"
6D114, 6D115 - DEMO
SCALE =
" =1'-0"
6A101, 6A102, 6B104A, 6B104B, 6B104C & 6B104D - DEMO
SCALE =
" =1'-0" SCALE =
" =1'-0"
6A111, 6A112 - DEMO
SCALE =
" =1'-0"
6A121A, 6A123, 6A142B - DEMO
SCALE =
" =1'-0"
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg.
of
Building Number
Project Number
Office of
Construction and Facilities
Management
6587 HAMILTON AVENUE
PITTSBURGH, PENNSYLVANIA 15206
PH: 412.287.7333 FAX: 412.287.7334
www.ae-works.com
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECTS/ENGINEERS:
Revisions:
Date
6 " o n e e i g h o t o n e q u a r t e r i n o t t h r e e e i g h t h s i n o t o n e h a l f i n o t t h r e e q u a r t e r s i n o t o n e i n o t o n e a l f i n o t t h r e e i n c h e o t
100% CONSTRUCTION DOCUMENTS
NORTH
10 NORTH GREENE STREET BALTIMORE, MD 21201
Upgrade Public and Staff Restrooms 512-12-118
04 / 30 / 14
8D-100 - DEMO
SCALE =
" =1'-0"
7D-100D - DEMO
SCALE =
" =1'-0"
7A-104 PENTHOUSE (FLOOR LEVEL) - DEMO
SCALE =
" =1'-0"
7A-104 PENTHOUSE (UPPER LEVEL) - DEMO
SCALE =
" =1'-0"
7C-100 PENTHOUSE (FLOOR LEVEL) - DEMO
SCALE =
" =1'-0"
7C-100 PENTHOUSE (UPPER LEVEL) - DEMO
SCALE =
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg.
of
Building Number
Project Number
Office of
Construction and Facilities
Management
6587 HAMILTON AVENUE
PITTSBURGH, PENNSYLVANIA 15206
PH: 412.287.7333 FAX: 412.287.7334
www.ae-works.com
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECTS/ENGINEERS:
Revisions:
Date
6 " o n e e i g h o t o n e q u a r t e r i n o t t h r e e e i g h t h s i n o t o n e h a l f i n o t t h r e e q u a r t e r s i n o t o n e i n o t o n e a l f i n o t t h r e e i n c h e o t
100% CONSTRUCTION DOCUMENTS
NORTH
10 NORTH GREENE STREET BALTIMORE, MD 21201
Upgrade Public and Staff Restrooms 512-12-118
04 / 30 / 14
BD102A - NEW WORK
SCALE =
" =1'-0"
BD104A & BD104B - NEW WORK
SCALE =
" =1'-0"
BD109A & BD109B - NEW WORK
SCALE =
" =1'-0"
BB100A - NEW WORK
SCALE =
" =1'-0"
BD122 & BD124 - NEW WORK
SCALE =
" =1'-0"
BA101 & BA102 - NEW WORK
SCALE =
" =1'-0"
BA109A - NEW WORK
SCALE =
" =1'-0"
BB142 & BB144 - NEW WORK
SCALE =
" =1'-0"
BA114, BA116, BA118B, BA118D, BA121I & BA121J - NEW WORK
SCALE =
SCALE =
" =1'-0"
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg.
of
Building Number
Project Number
Office of
Construction and Facilities
Management
6587 HAMILTON AVENUE
PITTSBURGH, PENNSYLVANIA 15206
PH: 412.287.7333 FAX: 412.287.7334
www.ae-works.com
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECTS/ENGINEERS:
Revisions:
Date
6 " o n e e i g h o t o n e q u a r t e r i n o t t h r e e e i g h t h s i n o t o n e h a l f i n o t t h r e e q u a r t e r s i n o t o n e i n o t o n e a l f i n o t t h r e e i n c h e o t
100% CONSTRUCTION DOCUMENTS
NORTH
10 NORTH GREENE STREET BALTIMORE, MD 21201
Upgrade Public and Staff Restrooms 512-12-118
04 / 30 / 14
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
1C115 & 1C116 - NEW WORK 1C179B & 1C179E - NEW WORK 1B111, 1B115A & 1B115C - NEW WORK
1B102 & 1B103 - NEW WORK
1A101 - NEW WORK 1A102 - NEW WORK
1A107 & 1A109 - NEW WORK1B168 & 1B169 - NEW WORK
1B155 & 1B156 - NEW WORK
2C126A & 2C128A - NEW WORK
SCALE =
" =1'-0"
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg.
of
Building Number
Project Number
Office of
Construction and Facilities
Management
6587 HAMILTON AVENUE
PITTSBURGH, PENNSYLVANIA 15206
PH: 412.287.7333 FAX: 412.287.7334
www.ae-works.com
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECTS/ENGINEERS:
Revisions:
Date
6 " o n e e i g h o t o n e q u a r t e r i n o t t h r e e e i g h t h s i n o t o n e h a l f i n o t t h r e e q u a r t e r s i n o t o n e i n o t o n e a l f i n o t t h r e e i n c h e o t
100% CONSTRUCTION DOCUMENTS
NORTH
10 NORTH GREENE STREET BALTIMORE, MD 21201
Upgrade Public and Staff Restrooms 512-12-118
04 / 30 / 14
2C144 - NEW WORK
SCALE =
" =1'-0"
2C158 - NEW WORK
SCALE =
" =1'-0"
2C111 & 2C112 - NEW WORK
SCALE =
" =1'-0"
2D104 & 2D107 - NEW WORK
SCALE =
" =1'-0"
2D144A, 2D165, 2D166 & 2D168A - NEW WORK
SCALE =
" =1'-0"
2A101, 2A102, 2B104 & 2B105 - NEW WORK
2D134A - NEW WORK
SCALE =
" =1'-0"
2D138 - NEW WORK
SCALE =
" =1'-0"
2B129 & 2B131 - NEW WORK
SCALE =
" =1'-0"
2B126 - NEW WORK
SCALE =
" =1'-0"
2A110 - NEW WORK
SCALE =
" =1'-0"
2A117 - NEW WORK
SCALE =
" =1'-0"
SCALE =
SCALE =
" =1'-0"
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg.
of
Building Number
Project Number
Office of
Construction and Facilities
Management
6587 HAMILTON AVENUE
PITTSBURGH, PENNSYLVANIA 15206
PH: 412.287.7333 FAX: 412.287.7334
www.ae-works.com
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECTS/ENGINEERS:
Revisions:
Date
6 " o n e e i g h o t o n e q u a r t e r i n o t t h r e e e i g h t h s i n o t o n e h a l f i n o t t h r e e q u a r t e r s i n o t o n e i n o t o n e a l f i n o t t h r e e i n c h e o t
100% CONSTRUCTION DOCUMENTS
NORTH
10 NORTH GREENE STREET BALTIMORE, MD 21201
Upgrade Public and Staff Restrooms 512-12-118
04 / 30 / 14
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
3C122 & 3C123 - NEW WORK 3C108 & 3C109 - NEW WORK 3D131 & 3B142A - NEW WORK 3D136 - NEW WORK
3D125B & 3D125C - NEW WORK 3D115 & 3D116 - NEW WORK
3A101, 3A102, 3B221B, 3B221C, 3B221D,3B221E - NEW WORK
3B202A & 3B206 - NEW WORK 3A116 & 3A120A - NEW WORK
4C136, 4C149A, 4C149B, 4C150A, 4C150B, 4C151A, 4C 151B - NEW WORK
SCALE =
" =1'-0"
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg.
of
Building Number
Project Number
Office of
Construction and Facilities
Management
6587 HAMILTON AVENUE
PITTSBURGH, PENNSYLVANIA 15206
PH: 412.287.7333 FAX: 412.287.7334
www.ae-works.com
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECTS/ENGINEERS:
Revisions:
Date
6 " o n e e i g h o t o n e q u a r t e r i n o t t h r e e e i g h t h s i n o t o n e h a l f i n o t t h r e e q u a r t e r s i n o t o n e i n o t o n e a l f i n o t t h r e e i n c h e o t
100% CONSTRUCTION DOCUMENTS
NORTH
10 NORTH GREENE STREET BALTIMORE, MD 21201
Upgrade Public and Staff Restrooms 512-12-118
04 / 30 / 14
4C109 - NEW WORK
SCALE =
" =1'-0"
4D101A & 4D103L - NEW WORK
SCALE =
" =1'-0"
4D145 - NEW WORK
SCALE =
" =1'-0"
4D125B - NEW WORK
SCALE =
" =1'-0"
4B184 - NEW WORK
SCALE =
" =1'-0"
4A101, 4A102 & 4A102B - NEW WORK
SCALE =
" =1'-0"
4B206A & 4B207A - NEW WORK
SCALE =
" =1'-0"
4A136 & 4A157 - NEW WORK
SCALE =
" =1'-0"
4A117 & 4A118 - NEW WORK
SCALE =
" =1'-0"
4A143 & 4A169 - NEW WORK
SCALE =
" =1'-0"
4D147A - NEW WORK
SCALE =
" =1'-0"
4D134 - NEW WORK
SCALE =
" =1'-0"
4B191A - NEW WORK
SCALE =
" =1'-0"
4A4149 - NEW WORK
SCALE =
5C109, 5C110, 5C111A - NEW WORK
SCALE =
" =1'-0"
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg.
of
Building Number
Project Number
Office of
Construction and Facilities
Management
6587 HAMILTON AVENUE
PITTSBURGH, PENNSYLVANIA 15206
PH: 412.287.7333 FAX: 412.287.7334
www.ae-works.com
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECTS/ENGINEERS:
Revisions:
Date
6 " o n e e i g h o t o n e q u a r t e r i n o t t h r e e e i g h t h s i n o t o n e h a l f i n o t t h r e e q u a r t e r s i n o t o n e i n o t o n e a l f i n o t t h r e e i n c h e o t
100% CONSTRUCTION DOCUMENTS
NORTH
10 NORTH GREENE STREET BALTIMORE, MD 21201
Upgrade Public and Staff Restrooms 512-12-118
04 / 30 / 14
2 3
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
SCALE =
" =1'-0"
5C148A, 5C149A, 5C153 - NEW WORK 5C139, 5C166A - NEW WORK
5C164A, 5C164B & 5C164C - NEW WORK
5C163, 5C163D, 5D121A - NEW WORK 5D131, 5D132 - NEW WORK
5A101, 5A102, 5A103, 5A104,5A181, 5A182, 5B221B, 5B202 & 5B206 - NEW WORK 5A177C - NEW WORK 5A139, 5A154 & 5A164 - NEW WORK 5A123 - NEW WORK
5B221C, 5B221D,5B221E - NEW WORK
6C-168 - NEW WORK
SCALE =
" =1'-0"
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg.
of
Building Number
Project Number
Office of
Construction and Facilities
Management
6587 HAMILTON AVENUE
PITTSBURGH, PENNSYLVANIA 15206
PH: 412.287.7333 FAX: 412.287.7334
www.ae-works.com
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECTS/ENGINEERS:
Revisions:
Date
6 " o n e e i g h o t o n e q u a r t e r i n o t t h r e e e i g h t h s i n o t o n e h a l f i n o t t h r e e q u a r t e r s i n o t o n e i n o t o n e a l f i n o t t h r e e i n c h e o t
100% CONSTRUCTION DOCUMENTS
NORTH
10 NORTH GREENE STREET BALTIMORE, MD 21201
Upgrade Public and Staff Restrooms 512-12-118
04 / 30 / 14
6C153, 6C159 - NEW WORK
SCALE =
" =1'-0"
6D153 - NEW WORK
SCALE =
" =1'-0"
6C103, 6C108, 6C123 - NEW WORK
SCALE =
" =1'-0"
6C138, 6C140 - NEW WORK
SCALE =
" =1'-0"
6D114, 6D115 - NEW WORK
SCALE =
" =1'-0"
6A101, 6A102, 6B104A,6B104B, 6B104C, 6B104D - NEW WORK
SCALE =
" =1'-0"
6A111, 6A112 - NEW WORK
SCALE =
" =1'-0"
6A121A, 6A123, 6A142B - NEW WORK
SCALE =
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg.
of
Building Number
Project Number
Office of
Construction and Facilities
Management
6587 HAMILTON AVENUE
PITTSBURGH, PENNSYLVANIA 15206
PH: 412.287.7333 FAX: 412.287.7334
www.ae-works.com
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECTS/ENGINEERS:
Revisions:
Date
6 " o n e e i g h o t o n e q u a r t e r i n o t t h r e e e i g h t h s i n o t o n e h a l f i n o t t h r e e q u a r t e r s i n o t o n e i n o t o n e a l f i n o t t h r e e i n c h e o t
100% CONSTRUCTION DOCUMENTS
NORTH
10 NORTH GREENE STREET BALTIMORE, MD 21201
Upgrade Public and Staff Restrooms 512-12-118
04 / 30 / 14
8D-100 - NEW WORK
SCALE =
" =1'-0"
7D-100D - NEW WORK
SCALE =
" =1'-0"
7A-104 PENTHOUSE (FLOOR LEVEL) - NEW WORK
SCALE =
" =1'-0"
7A-104 PENTHOUSE (UPPER LEVEL) - NEW WORK
SCALE =
" =1'-0"
7C-100 PENTHOUSE (FLOOR LEVEL) - NEW WORK
SCALE =
" =1'-0"
7C-100 PENTHOUSE (UPPER LEVEL) - NEW WORK
SCALE =
FIRE DAMPER DETAIL
1-1/2"X1-1/2"X 14 GAUGE MOUNTING
ANGLES W/ 1/4" BOLTS, 1/2" LONG
(TYP.)
BREAK AWAY POINT
FIRE DAMPER
SHEET METAL
DUCTWORK
DISTANCE OF FIRE
DAMPER PLUS 1",
MINIMUM 4" (TYP. OF
BOTH SIDES)
METAL SLEEVE OF
GAUGE GREATER
THAN OR EQUAL TO
GAUGE OF DUCT
LINTEL BY .1 C.
ACCESS DOOR
DISTANCE TO SUIT
ACCESS DOOR
FIRE WALL OR FLOOR
NOTES:
1. TYPICAL FOR ALL HORIZONTAL AND VERTICAL DUCT PENETRATIONS.
2. ALL CONNECTION POINTS WILL BE SEALED AIR TIGHT. PROVIDE INSULATION ON BOTH SIDES OF AIR CONDITIONING
DUCTWORK.
3. INSTALL DAMPERS WHERE FIRE DAMPERS ARE SHOWN ON DRAWINGS
4. INSTALL PER NFPA PAMPHLET NO 90A AND PER LOCAL CODES
5. EXTERNAL DUCT INSULATION SHALL STOP AT WALL
6. INFILL ANY WALL, VOID OPENINGS AROUND FRAMES WITH SUITABLE MATERIAL TO MAINTAIN FIRE RATING
RETAINING ANGLE - DO NOT
SECURE TO WALL OR FLOOR
PROVIDE, CLEARANCE ON TOP
AND SIDES FOR EXPANSION
S-TYPE CONNECTION
SEAL AIR TIGHT
CONNECTING DUCTWORK ROUND,
OVAL, OR RECTANGULAR
SEE PLANS
DUCT ACCESS DOOR
LABELED "FIRE DAMPER ACCESS"
SLEEVE
FIRE DAMPER UL
RATED
WALL
FIRE DAMPER FRAME
MIN 1" OVER LAP
DISTANCE OF FIRE DAMPER PLUS 1",
MINIMUM 4" (TYPICAL BOTH SIDES)
MAIN DUCT
D-3/4" D HEEL R
BRANCH DUCT
BALANCING DAMPER (BD)
MINIMUM OF 1 DUCT DIA.
FROM MAIN DUCT
3/4" D THROAT
RADIUS
STRAIGHT
EXTEND DAMPER
HANDLE CLEAR OF
INSULATION
NOTE: MAY BE USED ANYWHERE
MAIN DUCT
BALANCING DAMPER (BD)
MINIMUM OF 1 DUCT DIA.
FROM MAIN DUCT
BRANCH DUCT
W
EXTEND DAMPER
HANDLE CLEAR OF
INSULATION
L
L=W/4 (4" MIN.)
NOTE:
USE ONLY AT LAST TAKEOFF BEFORE OUTLETS & THEN ONLY WHERE
RECTANGULAR RUNOUTS ARE INDICATED ON DRAWINGS
US DUCT GAUGE
SPIRAL LONGITUDINAL
US FITTING GAUGE
SPIRAL LONGITUDINAL
ROUND GALVANIZED STEEL
DUCTWORK SCHEDULE
DUCT DIA
3"-14"
15"-26"
27"-36"
37"-50"
51"-60"
4" BEADED SLEEVE
4" BEADED SLEEVE
4" BEADED SLEEVE
1-1/2" X 1-1/2" X 3/16" RT-2
1-1/2" X 1-1/2" X 3/16" RT-2A
LONGITUDINAL OR SPIRAL SEAM
BEADED SLEEVE JOINT
RT1
SLEEVE JOINTS ARE
PERMITTED ON ROUND DUCT
UP THROUGH 30" DIA.
MITERED ELBOWS SHALL HAVE A MINIMUM CENTERLINE RADIUS OF 1 1/2 TIMES THE
DUCT DIAMETER AND CONFORM AS FOLLOWS:
NUMBER OF MITERED PIECES
90 DEG
60 DEG
45 DEG
SEAMS SHALL BE LOCK AND PRESS OR SNAPLOCK.
NON-EXTRUDING
GASKET OR
SEALANT
3/8" FLANGE
5/16" DIA. BOLTS AT MAXIMUM
7" INTERVALS
1-1/2" X 1-1/2" X 1/8"
MINIMUM ANGLE
RT-2A COMPANION FLANGE (WELD
TO DUCT)
VAN STONE FLANGE JOINT
RT-2
FLANGED JOINTS ARE
REQUIRED ABOVE 30" DIA.
PROVIDE GIRTH REINFORCING
AT 72" CENTERS ON DUCT SIZES
37" THROUGH 50"
+10" W.C.HIGH PRESSURE (AHU TO AIR CONTROL VALVE (ACV))
MEDIUM PRESSURE (AHU TO VAV)
LOW PRESSURE (DOWNSTREAM OF ACV/VAV)
LOW PRESSURE EXHAUST
+3" W.C.
-3" W.C.
SYSTEM TYPE
DUCT PRESSURE CLASS
(SMACNA)
SEAL CLASS MAX. LEAKAGE
A
A
A
A
1%
1%
1%
1%
NOTE: STANDARDS SHALL APPLY TO FLEXIBLE DUCTWORK, FITTINGS, FLEXIBLE CONNECTIONS, AND ASSOCIATED ACCESSORIES FOR THE APPROPRIATE STANDARDS
SCHEDULED.
DUCT CONSTRUCTION SCHEDULE
W
W1
NOTES:
1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS
DETAILED BY SMACNA.
2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS
VANE TYPE REGARDLESS OF W DIMENSION.
3. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" RADIUS, 1 1/2"
MAXIMUM SPACE BETWEEN VANES AND A 3/4" TRAILING EDGE.
4. WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" VANES SHALL BE
DOUBLE VANE TYPE.
NOTES:
1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
2. ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED
AS RECOMMENDED BY SMACNA.
3. FOR R < 1-1/2 W, VANES SHALL BE USED.
R SHALL
EQUAL OR
BE
GREATER
THAN W.
W
R
STANDARD RADIUS OR LONG
RADIUS ELBOW
R SHALL
EQUAL OR
BE
GREATER
THAN 1/3W.
R SHALL
EQUAL OR
BE
GREATER
THAN 1/6W.
SHORT RADIUS ELBOW WITH
ONE VANE
SHORT RADIUS ELBOW WITH
TWO VANES
W W
2/3 W
1/2 W
VANE
VANER
R
1/ W
1/6 W
1/ W
NOTE:
1. UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL
APPLY.
M
AX
M
AX
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEW
TYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
M
AX
M A X
E Q U
IP
M E N T
M A X
M A X
AIR
FLOW
AIR
FLOW
NOTE:
1. UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
BRANCH DUCT TAKE-OFF PLAN VIEW
W
1/4 W
OR 4" MIN.
MAIN SUPPLY DUCT
PROVIDE VOLUME DAMPER
A
IR
F
LO
W
AIR
FLOW
SUPPLY REGISTER TAKE-OFF PLAN VIEW
AIR
FLOW
AIR
FLOW
VOLUME EXTRACTOR; ADJUSTABLE FROM
FULLY CLOSED POSITION TO CFM NOTED
ON FLOOR PLANS
ADJUSTABLE
METAL ROD OR
LINKAGE
TOP REGISTER
MAIN
SUPPLY
DUCT
SEE FLOOR PLAN FOR
SPLIT DIMENSION
MAIN
SUPPLY
DUCT
TURNING VANES
AIR
FLOW
AIR
FLOW
A
IR
F
LO
W
PROVIDE
VOLUME
DAMPER
AIR SPLIT DUCT TAKE-OFF PLAN VIEW
SUPPLY REGISTER OR
BRANCH DUCT
PLAN VIEW PLAN VIEW
(ALTERNATE VIEW)
SMACNA FIGURE 4-6
45° LEED IN
RIGID DUCT TO AIR
TERMINAL UNIT.
F
LO
W
MAIN SUPPLY
FLOW
MAIN SUPPLY
FLOW
ROUND SHEET
METAL DUCT
RIGID DUCT TO AIR
TERMINAL UNIT.
45° M A X "D"
CLOSE OPENING AT
CORNERS.
SEAL ALL JOINTS AS
SPECIFIED.
W
L= W /4 M
IN
PLAN VIEW
AIR
FLOW
AIR
FLOW
MAIN EXHAUST OR RETURN
W
BRANCH DUCT
PROVIDE VOLUME
DAMPER AT EACH
BRANCH DUCT
1/4W OR 4" MIN.
NOTES:
1. DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR MULTI-
BLADE DAMPERS & ROUND DAMPERS.
SIDE ELEVATION SECTION
HANDLE WITH
LOCKING QUADRANT
INSIDE END BEARING
1/8"CLEARANCE ALL
AROUND
DAMPER BLADE
INSULATION STAND-
OFF
DUCT
INSULATION SEE
SPECIFICATION
STIFFEN BLADE AS
REQUIRED
OUTSIDE END BEARING
1/2" ROUND ROD PIN
NOTES:
1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.
2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.
3. SEE SMACNA 2005, FIGURE 9-15
ACCESS DOOR
ACCESS PANEL
SECTION "B-B"
SECTION "A-A"
INSULATION
GASKET
DUCT
INSULATION
"A"
"A"
HANDLE INSIDE
NEOPRENE GASKET
CASING
FLEXIBLE WASHER
FACTORY FABRICATED
LATCH/HANDLE
1-1/2" MIN.
INSULATION
"B" "B"
COVER WITH HANDLE AND
CHAIN RETAINER
GASKETED AND PRESSURE
SEALED
ROUND OR FLAT
OVAL DUCT
SECTION
HOUSING WELDED TO
DUCT SECTION
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
1-1/2" MIN. TO 3" MAX. INSTALLED. 6"
NOMINAL WITH MATERIAL TAUT
1-1/2"1/2"1/2"
WASHER
FLANGED CONNECTION ON
FAN SIDE
FLEXIBLE MATERIAL AS
SPECIFIED
1"X1/8" BAND IRON
BOLT ON 4" CENTERS
1" FLANGE & HEM
FLEXIBLE
MATERIAL AS
SPECIFIED
RIVET ON 4"
CENTERS
DUCT
SHEET METAL SCREWS ON 12"
CENTERS
WASHER
FLANGED
CONNECTION ON
FAN SIDE
1-1/2" MIN. TO 3" MAX. INSTALLED. 6"
NOMINAL WITH MATERIAL TAUT
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
DUCT
1 1/2" POCKET SLIP
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.ALTERNATE
POSITION OF
BOLT
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg. of
Building Number
Project Number
Office of Construction and Facilities Management
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
NORTH
FULLY SPRINKLERED
A
B
C
D
E
F
Revisions: Date0
6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
6587 Hamilton Avenue Pittsburgh, Pennsylvania 15206 Ph: 412.287.7333 Fax: 412.287.7334 www.ae-works.com
AE Works Project Number:
ARCHITECTS/ENGINEERS:
AE works
SEAL
K ey plan
AB
C D
Upgrade Public and Staff Restrooms 512-12-118
SPL CJC
10 NORTH GREENE STREET BALTIMORE,
MD 21201
M501
MECHANICAL DETAILS
04 / 30 / 14 158121 12040
100% CONSTRUCTION DOCUMENTS
NOT TO SCALE
FIRE DAMPER DETAIL
NOT TO SCALE
TYPICAL BRANCH CONNECTION
NOT TO SCALE
DUCTWORK SCHEDULE
NOT TO SCALE
(VA) DUCTWORK SQUARE VANE ELBOWS
NOT TO SCALE
(VA) DUCTWORK RADIUS ELBOWS
NOT TO SCALE
(VA) DUCTWORK TRANSITIONS (W/EQUIP MOUNTED IN DUCT)
NOT TO SCALE
(VA) SUPPLY DUCTWORK TAKE-OFFS
NOT TO SCALE
(VA) SUPPLY DUCT TAKEOFF - AIR TERMINAL UNIT
NOT TO SCALE
(VA) EXHAUST/RETURN BRANCH DUCT
NOT TO SCALE
(VA) VOLUME DAMPER
NOT TO SCALE
(VA) ACCESS PANEL & DOOR DETAIL
NOT TO SCALE
(VA) ACCESS SECTION FOR ROUND/OVAL DUCT
NOT TO SCALE
(VA) FLEXIBLE DUCT CONNECTIONS
LAY-IN CEILING DIFFUSER INSTALLATION
GYP BOARD CEILING DIFFUSER INSTALLATION
FOR GYPSUM BOARD CEILING INSTALLATION, LOCATE VOLUME
DAMPER IMMEDIATELY UPSTREAM OF DIFFUSER DROP OR AT
TAP COLLAR. SUCH THAT VOLUME DAMPER AT TAP CAN BE
ACCESSED FROM DIFFUSER OPENING IN CLG.
D D
BRANCH DUCTCLOSED END OF
BRANCH DUCT
OBD
DIFFUSER
FLEXIBLE DUCTWORK
TAP COLLAR
CEILING
GYP-BOARD
FRAME
VOLUME DAMPER
AIR FLOW
USE CONICAL TAP WHERE DUCT SIZE &
ELEVATION PERMITS, OTHERWISE USE
CYLINDRICAL TAP
CLOSED END OF
BRANCH DUCT
OBD
DIFFUSER
FLEXIBLE DUCTWORK
TAP COLLAR
USE CONICAL TAP WHERE DUCT SIZE &
ELEVATION PERMITS, OTHERWISE USE
CYLINDRICAL TAP
BRANCH DUCT
VOLUME DAMPER
NOTE:
1. ALL FLEXIBLE DUCTWORK SHALL BE UL-181 CLASS 1 RATED.
LAY-IN FRAME
CEILING
D D D D
VOLUME DAMPER
AIR FLOW
MAXIMUM RIGIDITY CLASS ON MINIMUM GAUGE DUCT
MAX. DUCT DIMENSION MAX LENGTH 5' REINFORCEMENT (ANGLE SIZE) TRANSVERSE JOINT
NONE
NONE
NONE
NONE
NONE
NONE
NONE
1-1/2"X 1-1/2"X 1/8"
1-1/2"X 1-1/2"X 3/16"
2"X 2"X 1/4"
A-26
A-24
B-24
C-24
D-22
F-22
H-20
J-18
L-18
L-18
MINIMUM RIGIDITY CLASS SHEET METAL GAUGE
10"-12" (UP TO 10')
13"-18" (UP TO 10')
19"-24"
25"-30"
31"-42"
43"-54"
55"-60"
61"-84"
85"-96"
97" UP
RECTANGULAR DUCT REINFORCEMENT
1. AIRSIDE CONTRACTOR SHALL INDICATE UP TO 2 TRANSVERSE JOINTS TO BE USED FOR EACH RESPECTIVE DUCT SIZE RANGE. JOINTS SHALL BE SELECTED FROM SMACNA HVAC DUCT CONSTRUCTION STANDARDS TABLES 1-11, 1-12 AND 1-13. TYPE T-1 DRIVE SLIPS ACCEPTABLE AS CLASS A JOINT
REINFORCEMENT FOR UP TO 18" MAX. DUCT DIMENSIONS.
2. WHERE CONTRACTOR WISHES TO EMPLOY TIE ROD REINFORCEMENT OPTIONS IN ADDITION TO THAT REQUIRED ABOVE, DETAILS SHALL BE
SUBMITTED.
JOINT T-1, FLAT DRIVE SLIP:
USE GAUGE NOT LESS THAN TWO GAUGES LIGHTER THAN DUCT GAUGE,
WITH 24 GAUGE MINIMUM. SEE QUALIFICATION AS CLASS A
REINFORCEMENT ABOVE. FLANGE SHALL BE OVERLAPPED AND RIVETED
AT CORNERS.
JOINT T-2, STANDING CORNER DRIVE SLIP:
FASTEN STANDING PORTIONS WITHIN 2" FROM EACH END AND
ELSEWHERE AT 8" OR LESS INTERVALS. 4" W.G. MAX. 30" MAX. LENGTH AT
4" W.G. 36" LENGTH AT 3" W.G. FLANGE SHALL BE OVERLAPPED AND
RIVETED AT CORNERS.
JOINT T-13, STANDING S, BAR REINFORCED:
FASTEN AS ON JOINT T-10. THE STANDING PORTION OF THIS CLEAT MAY
BE FORMED PER ILLUSTRATION T-11 TO HOLD FLAT BAR. FASTEN THE BAR
STOCK TO THE CONNECTOR AT ENDS AND INTERMEDIATE POSITIONS. 4"
W.G. MAXIMUM.
JOINT T-14, STANDING S, ANGLE REINFORCED:
FASTEN AS ON JOINT T-10. THE ANGLE MUST BE FASTENED TO THE
CONNECTOR OR THE DUCT WALL.
JOINT T-17, POCKET LOCK:
USE ON ALL FOUR SIDES OF THE DUCT. A 7/8" FLANGE IS USED FOR 1"
HIGH LOCK; 1-1/4" FLANGE FOR 1-1/2" LOCK. BUTTON PUNCH WITHIN 2" OF
CORNER AND AT 6" INTERVALS. 3" W.G. MAXIMUM. FLANGE SHALL BE
OVERLAPPED AND RIVETED AT CORNERS.
JOINT T-18, POCKET LOCK, FLAT BAR REINFORCED:
FASTEN AS ON JOINT T-17. 3" W.G. MAXIMUM.
JOINT T-19, POCKET LOCK, ANGLE REINFORCED:
FASTEN AS ON JOINT T-17. FASTEN ANGLE TO DUCT WITHIN 2" OF CORNER
AND AT 12" MAXIMUM SPACING. LOCK NEED NOT BE FASTENED TO THE
BACKUP ANGLE. 3"W.G. MAXIMUM.
JOINT T-22, COMPANION ANGLE:
VAN STONE TYPE (WITH 3/8" FLANGE ON DUCT). ANGLES MUST HAVE
WELDED CORNERS AND BE TACK WELDED, RIVETED, BOLTED OR SCREWED
TO THE DUCT WALL AT 12" MAXIMUM SPACING CENTERS BEGINNING AND
ENDING WITH FASTENERS AT CORNERS. BOLT SCHEDULE, BOLTS MUST BE
5/16" MINIMUM DIAMETER AT 6" MAXIMUM SPACING ON 4" W.G. OR LOWER
PRESSURE CLASS AND 4" MAXIMUM SPACING ON HIGHER PRESSURES.
EXCEPTION: 4" MAXIMUM SPACING MUST BE USED ON 1/8" THICK ANGLES
AT 4" W.G.
JOINT T-22, ALTERNATE FLANGE STYLE:
THE JOINT MAY BE FORMED WITHOUT THE 3/8" FLANGE IF THE DUCT IS HELD 1/8"
BACK FROM THE VERTICAL FACE OF THE ANGLE AND TACK WELDED TO THE FLANGE
ALONG THE EDGE OF THE DUCT. THE ANGLE IS OTHERWISE FASTENED NORMALLY.
PLACE SEALANT BETWEEN ANGLE AND DUCT OR SEAL WELD. IF THE FACES OF
FLANGES WILL FLUSH, THICK CONSISTENCY SEALANT MAY BE USED IN LIEU OF
GASKET. OTHERWISE, USE GASKET SUITABLE FOR SPECIFIC SERVICE AND FIT UP
UNIFORMLY TO AVOID PROTRUDING INSIDE THE DUCT.
JOINT T-23, FORMED FLANGE:
THE JOINT IS FORMED FROM TWO STANDING SEAM POCKETS, NORMAL POSITION OR
REVERSED. FULL FACE GASKETS ARE REQUIRED. GASKET MUST NOT PROTRUDE
INTO INTERIOR OF DUCT. CORNERS REQUIRE SPECIAL PIECES FOR CLOSURE
ADDED AS SHOWN IN ILLUSTRATIONS. USE BOLTS AT 6" MAXIMUM SPACING: 1/4"
MINIMUM DIAMETER ON 3" W.G. OR LESS: 5/16" MINIMUM OVER 3" W.G. STATIC.
JOINT T- 24, FORMED FLANGE:
MATING FLANGES ARE FORMED ON THE ENDS OF THE DUCT IN DOUBLE FLANGE
STYLE TO CREATE A TEE SHAPE WHEN ASSEMBLED. 0.064" MINIMUM THICKNESS
STEEL CORNER PIECES WITH 3/8" MINIMUM DIAMETER BOLTS SHALL BE USED TO
CLOSE CORNERS. 1/4" BY 1/2" MINIMUM SIZE GASKETS OF SUITABLE DENSITY AND
RESILIENCY SHALL BE CONTINUOUS AROUND THE JOINT AND SHALL BE LOCATED
TO FORM AN EFFECTIVE SEAL. MATING FLANGES SHALL BE LOCKED TOGETHER BY 6"
LONG CLIPS LOCATED WITHIN 6" OF EACH CORNER AND ALSO SPACED AT
CENTERS NOT EXCEEDING 15" FOR 3" W.G. OR LESS STATIC PRESSURE, NOR
EXCEEDING 12" FOR 4", 6" AND 10" W.G.
CORNER
HAMMERED
OVER
DRIVE SLIP T-1
DRIVE SLIP
T-1 OR T-2
CORNER CLOSURES - SLIPS AND DRIVERS
FIGURE A
OPEN HEM FOR
DRIVE SLIP
5/ 8" M
IN
BUTT OF STANDING S TYPE
CONNECTIONS FIGURE B
WHEN USING FLAT OR
STANDING SLIPS ON ALL
FOUR SIDES SEAL
CORNERS
CORNER CLOSURES - FLANGES
(A) (B) (C)
CONTINUOUS GASKET TO
EFFECTIVELY SEAL FLANGES
AND CORNERS
0.064" MINIMUM CORNER
PIECES WITH 3/8" MINIMUM
BOLT
(D)
(E)
(F)
NUMBER OF SEAMS AND
LOCATION VARIES WITH JOINT
TYPE. SHEET STOCK AND
ASSEMBLY PLANS.
SEAM LOCATIONS
FLANGE T-24
FLANGE T-23
SECURELY ATTACH
ADDITIONAL METAL CLIPS ON
FLANGES AT 15" MAXIMUM
CENTERS
6"
6"
MINIMUM
LENGTH OF ALL
CLIPS
WELD IN CORNER
PIECE & FLUSH UP
MAY BE OMITTED AT
2" W.G. AND LESS
L-1 - PITTSBURGH LOCK POCKET DEPTH
BETWEEN 1/4" & 5/8"
L-3 - GROOVED SEAM (FLAT LOCK AND
PIPE LOCK)
L-4 - STANDING SEAM
NOTE:
ALL SEAMS SHALL BE MADE AIRTIGHT BY
USE OF DUCT SEALANT
FASTEN AT
ENDS
1" SEAM UP TO 42"
1-1/2" SEAM ABOVE 42"
8"
GENERAL FLEXIBLE DUCTWORK NOTES:
1. USE OF FLEXIBLE DUCTWORK SHALL BE RESTRICTED TO CONNECTIONS BETWEEN THE VAV/CV AIR TERMINAL UNITS AND THE MEDIUM OR HI PRESSURE SUPPLY DUCT AND CONNECTIONS BETWEEN SUPPLY
DIFFUSERS AND THE LOW PRESSURE SUPPLY AIR DUCTWORK.
2. USE OF FLEXIBLE DUCTWORK IN EXPOSED AREAS IS PROHIBITED.
3. MAXIMUM LENGTH OF FLEXIBLE DUCTWORK SHALL BE 5'-0".
4. DO NOT PENETRATE FIREWALLS AND INTERSTITIAL DECKS WITH FLEX. DUCTS.
CONICAL TEE
CONICAL 45 DEG. LATERAL
CONICAL 90 DEG. CROSS
45 DEG. LATERAL CROSS
REDUCING CONICAL TEE
REDUCING CONICAL 45 DEG. LATERAL
REDUCING CONICAL 90 DEG. CROSS
REDUCING 45 DEG. LATERAL CROSS
LO-LOSS TEE
45 DEG. LATERAL
LOLOSS 90 DEG. CROSS
REDUCING LO-LOSS TEE
REDUCING 45 DEG. LATERAL
REDUCING LOLOSS 90 DEG. CROSS
CONCENTRIC
TRANSITION WYE BRANCH
ECCENTRIC
TRANSITION
SADDLE CONICAL TEE TAP PERMITTED
ONLY WHERE BRANCH DIA. IS LESS THAN
2/3 OF MAIN DIA.
FIRESTOP
SEALANT PER
SPECIFICATIONS
DUCT OR PIPE
NOTE:
NO SMOKE DAMPERS IN EXISTING SUPPLY/RETURN/EXHAUST
AIR DUCT WORK PER VA FIRE SAFETY CODE VARIANCE
DUCT DIA
UP TO 26"
32"
50"
56"
62"
80"
92"
104"
ROD
1/4"
1/4"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
1" X 1" X 1/8"
1-1/2" X 1-1/2" X 1/8"
1-1/2" X 1-1/2" X 1/8"
1-1/2" X 1-1/2" X 3/16"
1-1/2" X 1-1/2" X 1/4"
2" X 2" X 3/16"
2-1/2" X 2-1/2" X 3/16"
2-1/2" X 2-1/2" X 1/4"
MINIMUM ANGLE
MINIMUM ANGLE/ROD SIZES FOR TRAPEZE HANGERS
* FOR SINGLE DUCT SUPPORT, FOR "GANGED" OR STACKED DUCT SUBMIT DETAIL OF HANGER SUPPORT
FOR APPROVAL. MINIMUM 1 HANGER PER 5'-0" SECTION.
DIAMETER
1-10"
11-18"
19-24"
25-36"
37-50"
51-60"
61-84"
MAX. SPACING
10'
10'
10'
10'
10'
10'
10'
WIRE DIAMETER
(1) 12 GA.
(2) 12 GA. OR (1) 8 GA.
(2) 10 GA.
(2) 8 GA.
ROD STRAP
1/4"
1/4"
1/4"
3/8"
(2) 3/8"
(2) 3/8"
(2) 3/8"
1" X 22 GA.
1" X 22 GA.
1" X 22 GA.
1" X 20 GA.
(2) 1" X 20 GA.
(2) 1" X 18 GA.
(2) 1" X 16 GA.
MINIMUM HANGER SIZES FOR ROUND DUCT
24" MAX
UNLESS FOOT STRAP IS PLACED
UNDER A BOTTOM
REINFORCEMENT
SCREWS
1" MIN.
STRAP HANGERS LOAD RATED
FASTENERS
HANGER
BAND OF SAME SIZE AS
HANGER STRAP
36" DIA.
MAX.
24" DIA.
MAX.
LOWER HANGER ATTACHMENTS
TRAPEZE HANGERS
L
HANGERS MUST NOT
DEFORM DUCT SHAPE
HANGER RODS
OR STRAPS
BAND ONE HALF-ROUND MAY BE USED
IF DUCT IS MAINTAINED.
W
2" 2"
ROD
UPPER ATTACHMENT DEVICES
STRAP HANGER OR
HANGER ROD (NOT
SHOWN)
EXPANSION SHIELD
CONCRETE ANCHOR
NOTE: NOT PERMITTED IN
METAL ROOF DECK.
WASHER
METAL DECK
CONCRETE
FLOOR SLAB
NOTE:
EXPANSION SHIELD ANCHORS ARE PERMITTED IN SHEAR
ONLY. DO NOT INSTALL VERTICALLY.
FRICTION CLAMP OR
CADDY CLAMP
NUT & BOLT
STRAP HANGER OR
ALL THREAD ROD
HANGER ROD
RETAINING CLIP
6AC - CLAMP W/ RETAINING CLIP
6BC - CLAMP W/ LOCK NUT(OPTIONAL)
STRAP
HANGER
WASHER MAY BE OMITTED
WITH 100 LB. MAX. LOAD ON
22 GA STRAP WHEN FOLDED.
BENT ALL THREAD
HANGER ROD
SLOT IN DECK
HANGER STRAP
BOLT, PIN OR SCREW
PENETRATION
NUTS AND WASHERS
BOTH SIDES OF ANGLE
(TYP)
STRUCTURAL JOIST
1" BOLT AND NUT
W/ 2 1/2" WASHER.
1/2" THREADED ROD (TYP)
VAV BOX
1 1/4 X 1 1/4 X
3/16" ANGLE IRON
SUPPORTS
STRAINER & BLOW OFF VALVE
BALL VALVE (TYP)
MODULATING CONTROL VALVE (A.T.C.)
CALIBRATED BALANCING VALVE
HWR
HWS
MANUAL
VENT
UNION (TYP)
3/4" DRAIN LINESUPPLY
AIR
REHEAT COIL
DUCT TRANSITION AS
REQ'D TO COIL
FLEX DUCT
CONNECTION
1" ACOUSTICAL LINING
VAV TERMINAL UNIT
FLEX DUCT
CONNECTION
AIR
INLET
UN-INSULATED EXHAUST DUCT
INSULATED SUPPLY/RETURN DUCT
20 GAGE GALVANIZED
STEEL COLLAR (EXPOSED
ONLY). SECURE TO WALL
ON 6 INCH CENTERS
(MINIMUM 4 FASTENERS
PER SIDE).
20 GAGE GALVANIZED
STEEL COLLAR (EXPOSED
ONLY). SECURE TO WALL
ON 6 INCH CENTERS
(MINIMUM 4 FASTENERS
PER SIDE).
CMU WALL
GROUT
2"x2"x1/4" TACK WELDED
OR RIVETED TO SLEEVE
DUCT
1" CLEARANCE BETWEEN
20 GAGE GALVANIZED
STEEL SLEEVE
CMU WALL
GROUT
2"x2"x1/4" TACK WELDED
OR RIVETED TO SLEEVE
DUCT
1" CLEARANCE BETWEEN
20 GAGE GALVANIZED
STEEL SLEEVE
SHEET METAL SCREWS 4" ON CENTER
1 1/2"x1 1/2"x1/8" ANGLE INSTALL ON
BOTH LONG DIMENSION SIDES OF
DUCT. FOR DUCTS OVER 60" USE
2"x2"x1/8" ANGLE.
HOLE IN STRUCTURAL FLOOR
DUCT RISER
SEAL HOLE WITH
FIREPROOFING MATERIAL
AFTER DUCT INSTALLATION
DUCT RISER - SEE FLOOR
PLANS FOR SIZES
EXTEND ANGLE 3" [75mm]
BEYOND DUCT
0.5 INCH WG TO 2 INCHES WG DUCT RISER SUPPORT
DUCT RISER - SEE FLOOR
PLANS FOR SIZES
SEAL HOLE WITH
FIREPROOFING MATERIAL
AFTER DUCT INSTALLATION
2 INCH WG TO 4 INCHES WG DUCT RISER SUPPORT
HOLE IN STRUCTURAL FLOOR
DUCT RISER
FLOOR
FLOOR
2"x2"x1/4" ANGLE
INSTALL ON BOTH
LONG DIMENSION
SIDES OF DUCT.
ARRANGE RISER SO
REINFORCER
TRANSVERSE JOINT
IS AT RISER
SUPPORT POINT
EXISTING AHU
INTERNAL CONTROLLER
VAV BOX
H
C
INTERNAL
CONTROLLER
H W S
H W R
T
THERMOSTAT
120V/1 (DIV. 26)
DDC
CONTROL
PANEL
NOTE:
1. ALL COMPONENTS ARE TO BE
COMPATIBLE WITH THE EXISTING
JOHNSON CONTROLS METASYS
SYSTEM.
EXTERIOR WALL
THERMOSTAT WITH
INSULATING BASE
ELECTRICAL JUNCTION BOX
SECURE TO WALL W/ (4)
SCREW ANCHORS
1" PVC STAND-OFF
NOTE:
ALL THERMOSTATS WILL
BE HARD WIRED TYPE
AND SHALL TIE INTO DDC
BUILDING MANAGEMENT
SYSTEM.
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg. of
Building Number
Project Number
Office of Construction and Facilities Management
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
NORTH
FULLY SPRINKLERED
A
B
C
D
E
F
Revisions: Date0
6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
6587 Hamilton Avenue Pittsburgh, Pennsylvania 15206 Ph: 412.287.7333 Fax: 412.287.7334 www.ae-works.com
AE Works Project Number:
ARCHITECTS/ENGINEERS:
AE works
SEAL
K ey plan
AB
C D
Upgrade Public and Staff Restrooms 512-12-118
SPL CJC
10 NORTH GREENE STREET BALTIMORE,
MD 21201
M502
MECHANICAL DETAILS
04 / 30 / 14 158122 12040
100% CONSTRUCTION DOCUMENTS
NOT TO SCALE
CEILING DIFFUSER INSTALLATION
NOT TO SCALE
RECTANGULAR DUCT REINFORCEMENT
NOT TO SCALE
CORNER CLOSURES
NOT TO SCALE
LONGITUDINAL SEAMS - RECT. DUCT NOT TO SCALE
GENERAL FLEXIBLE DUCTWORK NOTES
NOT TO SCALE
PERMISSIBLE ROUND / SPIRAL FITTINGS
NOT TO SCALE
DUCT/PIPE PENETRATION THRU SMOKE WALL
NOT TO SCALE
DUCT HANGER SCHEDULE
NOT TO SCALE
DUCT HANGERS
NOT TO SCALE
VAV TERMINAL SUPPORT DETAIL
NOT TO SCALE
VAV TERMINAL W/REHEAT COIL
NOT TO SCALE
DUCT PENETRATION
NOT TO SCALE
DUCT RISER SUPPORTS
NOT TO SCALE
VAV BOX/AHU CONTROL DIAGRAM
NOT TO SCALE
WALL MOUNTED THERMOSTAT
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg.
of
Building Number
Project Number
Office of
Construction and Facilities
Management
6587 HAMILTON AVENUE
PITTSBURGH, PENNSYLVANIA 15206
PH: 412.287.7333 FAX: 412.287.7334
www.ae-works.com
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECTS/ENGINEERS:
Revisions:
Date
6 " o n e e i g h o t o n e q u a r t e r i n o t t h r e e e i g h t h s i n o t o n e h a l f i n o t t h r e e q u a r t e r s i n o t o n e i n o t o n e a l f i n o t t h r e e i n c h e o t
100% CONSTRUCTION DOCUMENTS
NORTH
10 NORTH GREENE STREET BALTIMORE, MD 21201
Upgrade Public and Staff Restrooms 512-12-118
04 / 30 / 14
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg.
of
Building Number
Project Number
Office of
Construction and Facilities
Management
6587 HAMILTON AVENUE
PITTSBURGH, PENNSYLVANIA 15206
PH: 412.287.7333 FAX: 412.287.7334
www.ae-works.com
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
ARCHITECTS/ENGINEERS:
Revisions:
Date
6 " o n e e i g h o t o n e q u a r t e r i n o t t h r e e e i g h t h s i n o t o n e h a l f i n o t t h r e e q u a r t e r s i n o t o n e i n o t o n e a l f i n o t t h r e e i n c h e o t
100% CONSTRUCTION DOCUMENTS
NORTH
10 NORTH GREENE STREET BALTIMORE, MD 21201
Upgrade Public and Staff Restrooms 512-12-118
04 / 30 / 14
THIS IS A STANDARD SYMBOL LIST. ALL SYMBOLS MAY NOT APPEAR ON THIS PROJECT.
ABOVE GRADE/SLAB HOMERUN (MIN #12AWG WIRE)
FIRE ALARM
ABOVE FINISHED GRADE AFG
MANUFACTURER ASSOCIATION
FA
UON
SCHED/SCH
SWGR
SWBD
XFMR
TELE
REFL
REC/RECPT
REQ'D
N/A
WEATHERPROOF WP
DISCONNECT
DIAMETER
DOWNLIGHT
DISTRIBUTION PANEL
ELECTRIC WATER COOLER
EMERGENCY
EXHAUST FAN
EQUIPMENT
EXPLOSION PROOF
ELECTRICAL CONTRACTOR
ELECTRICAL
ELEVATOR
EACH
DRAWING
DECIBEL
COPPER
XP
EQIP
EF
EC
ELEV
E/EMER
ELEC
EWC
EA
DNLT
DWG
DISC
DP
DB
DIA
CU
ASYMMETRIC
AUTOMATIC TRANSFER SWITCH
APPROXIMATELE(LY)
CIRCUIT BREAKER
COMMUNICATION
CABLE TELEVISION
CLOSED CIRCUIT TELEVISION
BELOW FINISHED CEILING
CIRCUIT
CONDUIT
CEILING
BREAKER
AMPERE
BATTERY
CIR/CKT
COMM
C
CCTV
CB
CATV
CLG
BKR
A/AMP
BATT
BFC
APPROX
ASY
ATS
MANUAL TRANSFER SWITCH
MECHANICAL CONTRACTOR
METAL-CLAD CABLE
MISCELLANEOUS
MOTOR CONTROL CENTER
MOUNTING HEIGHT
MOUNTED
MEDIUM VOLTAGE
METAL HALIDE
MANUFACTURER
MANHOLE
MCC
MISC
MCC
MTD
MTG HT
MH
MC
MV
MFR
MH
MTS
MAIN DISTRIBUTION PANEL
LIGHTING
LOW VOLTAGE
MAIN CIRCUIT BREAKER
MAIN LUGS ONLY
LIGHT EMITTING DIODE
KILOVAR (REACTANCE)
KILOVOLT AMPERE
KILOWATT HOUR METER
LIGHT
KILOWATT
LTG
MCB
MDP
MLO
LED
LV
KVAR
KVA
KWH
KW
LT
UNLESS OTHERWISE NOTED
UNINTERRUPTIBLE POWER SUPPLY
UNDERWRITER'S LABORATORIES
WATT
VOLT
W
V
UPS
UL
SWITCHBOARD
TELEPHONE
TRANSFORMER
SWITCHGEAR
TYPICAL
SCHEDULE
SWITCH
TYP
SW
GROUND FAULT INTERRUPTER
HIGH INTENSITY DISCHARGE
JUNCTION BOX
ISOLATED GROUND
HORSEPOWER
INCANDESCENT
HIGH POWER FACTOR
HEATING VENTILATING AIR CONDITIONING
HERTZ
HP
INCAN
JB
IG
HZ
HVAC
HPF
HID
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
GENERAL CONTRACTOR
FULL LOAD AMPERES
FOOTCANDLES
GENERATOR
GROUND
FLUORESCENT
FIXTURE
FLOOR
GC
GFI
GEN
GND/G
FLA
FT
FACP
FAAP
FLOUR
FIXT
FL
RIGID GALVANIZED STEEL CONDUIT
ROOM
RAPID START
RECEPTACLE
REFLECTOR
REQUIRED
PULL BOX
RM
RGS
RS
PB
NATIONAL ELECTRIC CODE
NOT IN CONTRACT
NORMALLY OPENED
NOT AVAILABLE/NOT APPLICABLE
ON CENTER
NOT TO SCALE
PANEL
NIGHT LIGHT
PNL
NTS
OC
NIC
NL
NO
NEC
NEMA
ABOVE FINISHED FLOOR
ABBREVIATIONS
AFF
NATIONAL ELECTRIC
RECEPTACLES, FURNITURE FEEDS
THE ABOVE MOUNTING ELEVATIONS ARE TO CENTER OF DEVICE AND SHALL BE ADHERED TO UNLESS
SPECIFICALLY NOTED OR DETAILED OTHERWISE ON THE DRAWINGS AND/OR SPECIFICATIONS.
IN FLOOR JUNCTION BOXES FLUSH TO
FINISHED FLOOR (FF)
IN MASONRY CONSTRUCTION THE MOUNTING HEIGHTS SHALL BE USED FOR REFERENCE TO THE NEAREST
BLOCK OR BRICK COURSING.
COORDINATE THE INSTALLATION AND MOUNTING ELEVATIONS OF ALL EQUIPMENT, DEVICES, CONTROLS AND APPURTENANCES WITH ARCHITECT AND ALL AFFECTED TRADES PRIOR TO INSTALLATION. DOCUMENT
ALL MOUNTING ELEVATIONS FOR ALL EQUIPMENT, DEVICES,
CONTROLS AND APPURTENANCES AT THE TIME OF SHOP DRAWING SUBMITTAL.
3.
2.
1.
0'-0"
1'-5" A.F.F.
STANDARD MOUNTING HEIGHTS
RECESSED LIGHTING FIXTURES, CEILING
MOUNTED RECEPTACLES, INDICATING LIGHTS,
ETC.
CEILING
ELECTRICAL SYMBOLS LEGEND
GENERAL ELECTRICAL INSTALLATION NOTES:
RECESSED MOUNTED TROFFER, (1X4, 2X2, 2X4)
FX = FIXTURE TYPE (REFER TO LIGHTING FIXTURE SCHEDULE FOR DETAILS)
LED EXIT SIGN, AND BATTERY BACKUP.
CEILING MOUNTED OR WALL MOUNTED OCCUPANCY SENSOR, DUAL TECHNOLOGY
OCCUPANCY SENSOR POWER PACK, INSTALL IN A JUNCTION BOX ABOVE WALL
SWITCH.
DAYLIGHT SENSOR OR ON/OFF PHOTOCELL
DUPLEX RECEPTACLE IN A 4" SQUARE BOX WITH PLASTER RING (IN DRYWALL)
SINGLE GANG BOX IN MASONRY.
XX: WP=WEATHERPROOF, SS=SURGE SUPPRESSOR, GFI= GROUND FAULT
INTERRUPTER, TR=TAMPER RESISTANT
SINGLE RECEPTACLE IN A 4" SQUARE BOX WITH PLASTER RING (IN DRYWALL)
SINGLE GANG. BOX IN MASONRY.
COMBINATION POKE THRU DEVICE W/ (2) DUPLEX RECEPTACLES
(REFER TO ET SERIES DRAWINGS FOR # OF DATA OUTLETS)
WALL SWITCH, CONTROL: X=
3: 3 WAY
4: 4 WAY
P: PILOT LIGHT
M: MOTOR SWITCH
T: DIGITAL TIMER SWITCH,
LV: LOW VOLTAGE (REFER TO LIGHTING DETAILS FOR BUTTON TYPES)
OS=WALL SWITCH OCCUPANCY SENSOR - SINGLE BUTTON DUAL TECH
NON-FUSED DISCONNECT SWITCH
VARIABLE FREQUENCY DRIVE
SINGLE PHASE MOTOR CONNECTION
XX=HORSE POWER
ABOVE COUNTER DEVICES, GFI RECEPTACLES IN
RESTROOMS.
3'-6" A.F.F.
WALL SWITCHES, THERMOSTATS, CONTROL DEVICES,
TO CENTER OF BOX
4'-0" A.F.F.
TOP OF PANELBOARDS (<6'-0" TALL)6'-0" A.F.F.
TOP MOST PORTION OF OPERATING HANDLE OF
DISCONNECT SWITCHES / CIRCUIT BREAKERS
6'-6" A.F.F.
WALL MOUNTED LIGHTS IN STAIRS, MECH ROOMS,
ETC.
7'-0" A.F.F.
DRAWING KEYNOTE
EQUIPMENT TAG
REVISION TRIANGLE WITH REVISION CLOUD
GROUND PER NATIONAL ELECTRIC CODE
JUNCTION BOX - WALL MOUNTED
JUNCTION BOX - CEILING OR EQUIPMENT MOUNTED
BATTERY PACK EMERGENCY LIGHT
XX
X
XX
XX
J
J
DS
OS OS
X X
FX
FX
FX-Y
EX
EX
PP
SPECIAL RECEPTACLE IN A 4" SQUARE BOX WITH
NEMA CONFIGURATION INDICATED.50A
VFD
INDICATED MOUNTED ABOVE COUNTERTOP (REFER TO STANDARD
MOUNTING HEIGHTS DETAIL ON THIS SHEET)
ELECTRICAL DEMOLITION ABBREVIATIONS
EXISTING TO REMAIN - DEVICE SHALL REMAIN IN WORKING ORDER.
REMOVE AND REPLACE WITH NEW - EXISTING BACKBOX AND WIRING SHALL REMAIN, RECONNECT NEW DEVICE TO EXISTING CIRCUIT.
REMOVE AND RELOCATE - DISCONNECT DEVICE, MODIFY AND EXTEND FEED TO NEW LOCATION.
REMOVE COMPLETLY - REMOVE DEVICE, CONDUIT, AND WIRING BACK TO SOURCE.
ETR
RN
RR
RC
EXISTING TO REMAIN
NEW WORK
DEMOLITION
XX
DOUBLE GANG BACKBOX W/ SINGLE GANG DEVICE RING. 1 1/4" EMT
CONDUIT W/ PULL STRING TO ABOVE ACCESSIBLE CEILING
X
PUSHBUTTON:
E=EMERGENCY STOP, A=AUTO DOOR PUSH BUTTON
ELECTRICAL EQUIPMENT TAG:
X= DEVICE TYPE (PANELBOARD,TRANSFORMER,SWITCHBOARD)
Y= DEVICE NAME
X - Y
RECEPTACLE TAG:
X= PANEL NAME
Y= CIRCUIT NUMBER
X
Y
S
SURFACE MOUNTED ELECTRICAL PANELBOARD
RECESSED MOUNTED ELECTRICAL PANELBOARD
N E
W
E X
IS
T
IN
G
N E
W
E X
IS
T
IN
G
ADA INSTALLATION GUIDLINES
34"
46"
MAX.
(NOTE #2)
44"
MAX.
(FOR 20-25")
(NOTE #2)
10-24" 25" MAX.
48"
MAX.
(FOR 20")
(NOTE #2)
OBSTRUCTED HIGH
SIDE REACH
OBSTRUCTED HIGH
FORWARD REACH
SCALE = NOT TO SCALE
48"
MAX.
(NOTE #2)
10"
MAX.
15"
MIN.
48"
MAX.
(NOTE #2)
15"
MIN.
OBSTRUCTED
SIDE REACH
OBSTRUCTED
FORWARD REACH
NOTES:
1. THESE GUIDLINES SHALL BE USED FOR THE INSTALLATION OF THE FOLLOWING DEVICES:
- WALL SWITCHES
-CONTROL SWITCHES
-RECEPTACLES
-VISUAL DISPLAY TOUCH PANELS
2. NOTE THAT THIS HEIGHT IS TO THE TOP-MOST PART OF THE DEVICE THAT AN OCCUPANT
REQUIRES ACCESS TO.
THE FOLLOWING GENERAL NOTES AS LISTED BELOW SHALL APPLY TO ALL ELECTRICAL REQUIREMENTS AS
INDICATED ON ALL E SERIES CONTRACT DRAWINGS.
DRAWINGS FOR THIS WORK ARE DIAGRAMMATIC AND INTENDED TO CONVEY THE EXTENT, GENERAL ARRANGEMENT AND LOCATIONS OF THE WORK. BECAUSE OF THE SCALE OF THE DRAWINGS, CERTAIN BASIC ITEMS SUCH AS ACCESS PANELS, CONDUITS, CABINET SIZES, PENETRATION SLEEVES, PULL BOXES, BACKBOXES AND JUNCTION BOXES MAY NOT BE SHOWN. INCLUDE ALL ITEMS WHERE REQUIRED BY CODE, MANUFACTURER AND RELATED SPECIFICATION SECTIONS FOR THE PROPER INSTALLATION OF ALL WORK.
DUE TO SCALE OF THE DRAWINGS, ALL ELECTRICAL DEVICE SYMBOLS ARE SHOWN ON DRAWINGS AS CLOSE AS POSSIBLE TO THEIR INTENDED LOCATION. CONTRACTOR SHALL COORDINATE IN THE FIELD THE PROPER INSTALLATION OF ALL EQUIPMENT, DEVICES, CONTROLS AND CONDUITS. REFER TO RELATED SPECIFICATION
SECTIONS FOR ADDITIONAL REQUIREMENTS.
COORDINATE WITH ALL TRADES AND SYSTEM INTEGRATORS ANY CONDITIONS RELATED TO THE INSTALLATION OF ALL SYSTEMS. THE CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE TRADE ALL INSTALLATION REQUIREMENTS IMPACTING THE PLACEMENT OF ALL SYSTEM COMPONENTS TO THE SATISFACTION OF ALL
CONCERNED TRADES.
COORDINATE EXACT LOCATION(S) OF ALL DATA AND TELEPHONE OUTLETS, ELECTRICAL RECEPTACLES WITH THE ARCHITECTURAL PLANS, FURNITURE PLANS AND ALL AFFECTED TRADES PRIOR TO INSTALLATION.
ALL CONDUITS SHALL BE SIZED AND INSTALLED IN ACCORDANCE WITH NFPA 70 AND PROJECT SPECIFICATIONS.
ALL CONDUITS SHALL BE A MINIMUM OF 3/4" UNLESS OTHERWISE NOTED.
PROVIDE ALL EQUIPMENT CLEARANCES IN ACCORDANCE WITH NEC REQUIREMENTS. ARRANGE EQUIPMENT TO
FACILITATE UNRESTRICTED ACCESS FOR MAINTENANCE AND SERVICE AROUND ALL EQUIPMENT,
COMPONENTS AND/OR CABLE TERMINATIONS.
WHERE EQUIPMENT AND/OR JUNCTION BOXES ARE INSTALLED ABOVE FINISHED CEILINGS, THE CONTRACTOR SHALL PROVIDE ACCESS HATCHES LISTED FOR THE INTENDED APPLICATION. ACCESS HATCHES SHALL BE LOCATED SO THAT SERVICE ACCESS TO THE EQUIPMENT AND/OR JUNCTION BOXES IS UNIMPEDED.
ALL PENETRATIONS OF WALLS AND/OR FLOORS SHALL BE FIRE STOPPED IN ACCORDANCE WITH THE ASTM AND NFPA REQUIREMENTS. REFER TO RELATED SPECIFICATION SECTIONS FOR ADDITIONAL INFORMATION.
INSTALLATION OF FIRE-STOPS SHALL BE PERFORMED BY AN APPLICATOR/INSTALLER QUALIFIED AND TRAINED
BY THE MANUFACTURER. INSTALLATION SHALL BE PERFORMED IN STRICT ACCORDANCE WITH
MANUFACTURER'S DETAILED INSTALLATION PROCEDURES.
ALL EQUIPMENT ENCLOSURES LOCATED OUTSIDE OR IN ALL AREAS WITH HIGH MOISTURE OR A RELATIVE
HUMIDITY OF 75% OR GREATER SHALL BE NEMA 4X STAINLESS STEEL AND RATED FOR THAT
APPLICATION.
ALL DEVICES, COMPONENTS OR EQUIPMENT INSTALLED ON THE EXTERIOR OF THE FACILITY SHALL BE
PROVIDED IN ACCORDANCE WITH ALL MANUFACTURERS' REQUIREMENTS TO ENSURE THE PROPER
OPERATION WHEN EXPOSED TO THE ENVIRONMENTAL CONDITIONS AND/OR AVERAGE ANNUAL LOWEST
TEMPERATURE THAT CAN BE ANTICIPATED FOR THE GEOGRAPHIC REGION OF THE FACILITY.
ALL INTERIOR AND/OR EXTERIOR COMPONENTS, DEVICES OR SYSTEMS EQUIPMENT EXPOSED TO THE GENERAL POPULATION SHALL BE INSTALLED IN SECURED EQUIPMENT ENCLOSURES WITH TAMPER SWITCHES AND INSTALLED IN SUCH A MANNER THAT RESISTS TAMPERING AND/OR REMOVAL WITHOUT THE USE OF
SPECIALIZED TOOLS.
FOR EQUIPMENT INSTALLATIONS REQUIRING COORDINATION WITH OTHER TRADES THE CONTRACTOR SHALL PROVIDE ALL TEMPLATES, BACKBOXES AND EQUIPMENT ANCHOR BOLTS FOR MOUNTING OR FLUSH MOUNTING PREPARATION, (E.G. PEDESTALS OR OTHER DEVICES REQUIRING MOUNTING ON WALLS, CONCRETE PADS OR OTHER MATERIALS). COORDINATE DELIVERY OF TEMPLATES AND EQUIPMENT WITH ALL AFFECTED
CONTRACTORS.
THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR THE ENTIRE DOCUMENT SET, I.E. IF WORK IS SHOWN ON OTHER TRADE DRAWINGS AS "BY ELECTRICAL CONTRACTOR", THE ELECTRICAL CONTRACTOR IS RESPONSIBLE
FOR THAT WORK.
ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (LATEST VERSION BEING ENFORCED), AND ALL OTHER APPLICABLE CODES AND STANDARDS BEING ENFORCED BY THE
AUTHORITY HAVING JURISDICTION.
THESE DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS OR INSTRUCTIONS FOR CONSTRUCTION SAFETY. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR ANY WORKMAN'S OR TRANSIENT'S SAFETY, OR FOR THE ADEQUACY OF EQUIPMENT, BUILDING COMPONENTS, WORK AIDS, OR ANY NECESSITY TO WORK ON
ENERGIZED ELECTRICAL COMPONENTS. FURTHER, NO
SUPERINTENDENCE IS INCLUDED OR IMPLIED.
ALL SYSTEMS AND EQUIPMENT SHALL BE INSTALLED AND WIRED ACCORDING TO THE MANUFACTURER'S
RECOMMENDATIONS.
ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE TESTED AND LISTED BY A
NATIONALLY RECOGNIZED TESTING LABORATORY.
THE VERBIAGE ON THE DRAWINGS INDICATING TYPES OF MATERIALS TO BE ENCOUNTERED IS INTENDED TO AID THE ELECTRICAL CONTRACTOR IN UNDERSTANDING THE VARIOUS CONDITIONS LIKELY TO BE ENCOUNTERED.
THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING QUANTITIES OF MATERIALS
REQUIRED TO COMPLETE THE PROJECT.
THE LOCATIONS OF EXISTING UTILITIES, STRUCTURE AND OTHER CONDITIONS SHOWN ON THE PLANS ARE APPROXIMATE. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO VERIFY AND REPORT
ANY DISCREPANCIES TO THE ENGINEER PRIOR TO BEGINNING ANY WORK.
THE ELECTRICAL CONTRACTOR SHALL COORDINATE CONDUIT ROUTING (PLAN AND ELEVATION) WITH THE LIGHTING (NEW AND EXISTING), CEILING ELEVATION, STRUCTURE, DUCTWORK, PIPING, ETC. REQUIRED FOR THE
COMPLETION OF THE PROJECT, PRIOR TO INSTALLATION.
THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NEW OPENINGS IN EXISTING PARTITIONS, EXTERIOR WALLS, FLOORS, AND ROOFS FOR THE INSTALLATION OF ANY NEW ELECTRICAL WORK. FURNISH AND INSTALL ALL REQUIRED LINTELS AND SLEEVES FOR THIS NEW WORK. ALL CONDUITS SHALL HAVE SLEEVES INSTALLED. ALL SLEEVES INSTALLED THROUGH EXTERIOR WALLS SHALL HAVE LINK SEALS INSTALLED.
THE ELECTRICAL CONTRACTOR SHALL PROTECT ALL EXISTING MATERIALS THAT ARE TO REMAIN IN PLACE FROM DAMAGE. ANY DAMAGE TO EXISTING FINISHES, MATERIALS, ETC., SHALL BE REPLACED BY THE
ELECTRICAL CONTRACTOR TO MATCH THE ADJACENT FINISH.
THE ELECTRICAL CONTRACTOR SHALL MAINTAIN THE BUILDING IN WEATHERTIGHT AND WATERPROOF CONDITION THROUGHOUT THE DURATION OF THEIR WORK. DO NOT LEAVE HOLES THROUGH WALLS
AND/OR ROOFS OPEN TO THE ELEMENTS WHEN NO WORK IS OCCURRING IN THOSE AREAS.
THE ELECTRICAL CONTRACTOR SHALL SECURE AND PROTECT THE BUILDING AND/OR WORK AREA WITH FIRE
RETARDANT TEMPORARY PLYWOOD PARTITIONS (WITH LOCKING DOORS), ETC. CLOSE ALL
EXISTING OPENINGS AS REQUIRED. COORDINATE THIS WORK WITH THE OWNERS REPRESENTATIVE PRIOR TO STARTING. IF TEMPORARY PARTITIONS IMPEDE THE FLOW OF EGRESS TO REQUIRED EGRESS DOORS AND STAIRS, THE ELECTRICAL CONTRACTOR SHALL PROVIDE EXIT SIGNS, AND SIGNAGE INDICATING SUCH.
THE ELECTRICAL CONTRACTOR SHALL CAULK ALL JOINTS BETWEEN METAL FRAMES AND EXISTING
CONDITIONS. THIS APPLIES TO BOTH INTERIOR AND EXTERIOR INSTALLATIONS.
THE DIMENSIONS SHOWN ON THE DRAWINGS ARE FOR THE CONVENIENCE OF THE ELECTRICAL CONTRACTOR
ONLY. VERIFY ALL DIMENSIONS IN THE FIELD PRIOR TO PERFORMING ANY WORK.
THE ELECTRICAL CONTRACTOR SHALL INSTALL ALL CONDUITS CONCEALED UNLESS NOTED OTHERWISE.
EXPOSED CONDUIT SHALL ONLY BE INSTALLED IN CHASES, EXPOSED CEILING AREAS, JANITOR CLOSETS, AND
MECHANCIAL/ELECTRICAL ROOMS.
ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED AND/OR BONDED PER THE REQUIREMENTS OF THE
NATIONAL ELECTRIC CODE. PROVIDE ALL GROUNDING AND/OR BONDING COMPONENTS NOT
EXPLICITLY SHOWN ON THE DOCUMENTS.
THE ELECTRICAL CONTRACTOR SHALL PROVIDE TYPEWRITTEN PANELBOARD DIRECTORIES, INDICATING THE LOADS SERVED BY THE RESPECTIVE PANELS. AMEND AS REQUIRED FOR AS-BUILT CONDITIONS. PROVIDE
ELECTRONIC VERSIONS OF THE PANELBOARD SCHEDULES FOR FUTURE USE BY THE OWNER.
THE ELECTRICAL CONTRACTOR SHALL COORDINATE ALL WORK WITH THE OWNER PRIOR TO STARTING ALL PHASES OF THE PROJECT. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE OWNER WHAT
WORK, IF ANY, HAS TO BE COMPLETED DURING SECOND OR THIRD SHIFT.
THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL TEMPORARY POWER CONNECTIONS TO KEEP AREAS UP AND OPERATIONAL DURING THE CONSTRUCTION. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THESE
REQUIREMENTS WITH THE OWNER.
THE ELECTRICAL CONTRACTOR SHALL GENERATE A DETAILED METHOD OF PROCEDURE (MOP) DOCUMENT INDICATING HOW HE/SHE INTENDS TO PERFORM EACH STEP IN THE PROJECT. THIS MOP SHALL BE PRESENTED
TO THE OWNER AND ENGINEER PRIOR TO STARTING THE PROJECT, FOR SIGN OFF.
THE MOP MAY BE REVISED BASED ON CHANGES IN THE PROJECT CONSTRUCTION, ETC. AT ALL POINTS IN THE PROJECT THE OWNER SHALL BE MADE AWARE OF CHANGES TO THE MOP, AND A REVISED MOP SHALL BE
PRESENTED TO THE OWNER AND ENGINEER FOR SIGN OFF.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
37.
LIGHTING SYMBOLS
RECESSED DOWNLIGHT, SURFACE MOUNTED, OR DECORATIVE PENDANT MOUNT
FX = FIXTURE TYPE (REFER TO LIGHTING FIXTURE SCHEDULE FOR DETAILS)
DENOTES FIXTURE IS CONNECTED TO EMERGENCY POWER
DENOTES AIMING DIRECTION OF LIGHT FIXTURE
PENDANT MOUNTED LINEAR DIRECT/INDIRECT
FX = FIXTURE TYPE, Y = FIXTURE LENGTH (REFER TO LIGHTING FIXTURE SCHEDULE
FOR DETAILS)
DENOTES WALL MOUNT ARM OF LIGHT FIXTURE
LED EXIT SIGN, WITH EMERGENCY HEADS, AND BATTERY BACKUP.
LIGHTING CONTROL SYMBOLS
UL924 EMERGENCY TRANSFER DEVICEGTD
POLE MOUNTED LIGHT FIXTURE
POWER SYMBOLS
DUPLEX RECEPTACLE IN A 4" SQUARE BOX
XX: WP=WEATHERPROOF, SS=SURGE SUPPRESSOR, GFI= GROUND FAULT
INTERRUPTER, TR=TAMPER RESISTANT
MULTI-SERVICE FLOOR BOX W/ (2) DUPLEX RECEPTACLES
(REFER TO ET SERIES DRAWINGS FOR # OF DATA OUTLETS)
FUSED DISCONNECT SWITCH
COMBINATION MOTOR STARTER
THREE PHASE MOTOR CONNECTION
XX=HORSE POWER
WALL MOUNTED GROUND BUS BAR (COPPER)
ANNOTATION SYMBOLS
S CEILING MOUNTED SPEAKER
WAP
MISC SYMBOLS
WIRELESS ACCESS POINT
NURSE CALL PATIENT STATION
NURSE CALL EMERGENCY STATIONN
P
J
JUNCTION BOX
POWER ASSIST DOOR PUSHBUTTON
ELECTRIC STRIKEES
FIRE ALARM SYMBOLS
FS
WALL MOUNTED STROBE LIGHT
CEILING MOUNTED SPEAKER/STROBE LIGHT
CONSULTANTS:
Drawing Title
Approved: Project Director
Project Title:
Location:
Date: Checked: Drawn:
Drawing Number
Dwg. of
Building Number
Project Number
Office of Construction and Facilities Management
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
NORTH
FULLY SPRINKLERED
A
B
C
D
E
F
Revisions: Date0
6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
6587 Hamilton Avenue Pittsburgh, Pennsylvania 15206 Ph: 412.287.7333 Fax: 412.287.7334 www.ae-works.com
AE Works Project Number:
ARCHITECTS/ENGINEERS:
AE works
SEAL
K ey plan
AB
C D
Upgrade Public and Staff Restrooms 512-12-118
JJD JMZ
10 NORTH GREENE STREET BALTIMORE,
MD 21201
E001
ELECTRICAL SYMBOLS, ABBREVIATIONS,
NOTES AND SCHEDULES
04 / 30 / 14 158126 12040
100% CONSTRUCTION DOCUMENTS
SHLVS
BENCH
B E
N C
H
S H
L V
S
CABINETS
EXAM
TABLE
SS
Z12
H12B2-72
DRIVING RAMP
AIR SUPPLY
95'
R O
W
IN
G M
A C
H
IN
E
R O
W
IN
G M
A C
H
IN
E
W
EIG
HTS
BENCHES
BENCHES
DESK
T R
E A
D
M
IL
L
UP
UP
DN
UP
DOWN
DOWN
ETO
TANK
STORAGE
BD125
DECONTAMINATION FEMALE LOCKER
BD124
CORRIDOR
CB-15
VESTIBULE
BA118A
ELEVATOR
T-16
ELEVATOR
T-13
ELEVATOR
T-12
SECURITY STORAGE
BD101
SECURITY
STAFF
LOCKER/TOILET
BD102A
ENGG FEMALE
LOCKER/TOILET
BD109A
MANUAL
CART
WASH
BA105B
GENERAL
ENGG STORAGE
BD115
CORRIDOR
CB-30
SUPPLY CHIEF OFFICE
BD105B
SECURITY WAITING
BD105
AFGE OFFICE
BD103
SUPPLY ASST CHIEF OFFICE
BD105A
SECURITY STAFF LOCKER
BD102
POLICE/SECURITY LOUNGE
BD100
STORAGE
BC-125A
STAIR-4
BC-100
MALE
STAFF
TOILET
BB100A
CORRIDOR
CB-2
SOILED
TERMINAL
CB-3
CORRIDOR
CB-1
SOILED
VESTIBULE
CB-4
SOILED
RECEIVING
DECONTAMINATION
BD123AEQUIP
STORAGE
TESTING
BD127D EQUIP ACESS
BD123B
EQUIP WASH
BD123C
HAC
BD123D
HAC
BD127C
DISPATCH
BD127E
CLEAN
RECEIVING
BD127
STERILIZE/NONSTERILE STORAGE
BD127A
BULK
STORAGE
BD127D
ELECTRICAL CLOSET
BD126
ELEVATOR
S-10
STAIR-2
MALE
TOILET/LOCKER
BD104A
STAFF
LOUNGE
BD104
FEMALE
LOCKER/TOILET
BD104B
PREPARATION
ASSEMBLY AND
STERILIZATION
BD124E
CORRIDOR
CB-31
ELECTRICAL SWITCHGEAR
BD107
KEY
SHOP
BD107A
ENGG MALE
STAFF LOCKER
BD109C
ENGG
MALE
TOILET
BD109B
ENGG
STAFF
LOUNGE
BD109
MECH SHOP
FOREMAN
BD108
CARPENTRY SHOP
BD114
PAINT SHOP
BD113STORAGE
BD112
CORRIDOR
CB-34
WORK
ORDER
CLERK
BD110
ARCHITECTURAL FOREMAN OFFICE
BD111
CORRIDOR
CB-35
CARPENTRY
SHOP STORAGE
BD114A
STAIR-3
SVC BAY
BD116
ELECTRICAL CLOSET
BD116A
SIGNAL CLOSET
BD116B
TELEPHONE CLOSET
BD116C
PLUMBING SHOP
BD117
AC/REFR SHOP
BD118
ELECTRICAL SHOP
BD119
ELECTRICAL
SHOP STORAGE
BD119A
AC/REFR
SHOP STORAGE
BD118A
PLUMBING
SHOP…