VA_WAC Fire Suppression - Bid Set Drawings.pdf

PDF 46 MB Posted

Attached to
Y1DA--674A4-20-110 Improve Fire Suppression System - Waco Federal contract opportunity
Solicitation number
36C25722B0008
Issued by
Department of Veterans Affairs

About this file

This solicitation is for a construction contract to improve the fire suppression system at the Doris Miller VA Medical Center in Waco, Texas. The Department of Veterans Affairs will award a firm-fixed-price contract with an estimated value between $5-10 million through an invitation for bid process. Contractors will provide all labor, materials and equipment to upgrade the fire suppression system in specified buildings by November 15, 2022 based on provided specifications and drawings. Work includes general construction, fire suppression components, sprinkler heads and associated repair work over a 365-day performance period. This requirement is set aside 100% for Service-Disabled Veteran Owned Small Businesses.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--674A4-20-110 Improve Fire Suppression System - Waco, newest first.
File Type Posted
36C25722B0008 0002.docx DOCX document
Prebid Sign in Sheet.pdf PDF
36C25722B0008 0001.docx DOCX document
36C25722B0008_1.docx DOCX document
VA_WAC Fire Suppression - Bid Set Narrative.pdf PDF
674A4-20-110 Specs.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Above finished floor AFF Acoustic ACST Acoustic Panel Ceiling APC Addendum ADD Alternate ALT Aluminum AL Angle L Approximate APPROX Architecture, architectural ARCH Asbestos ASB Asphalt ASPH Assistant ASST Association ASSN Automatic AUTO Average AVG Base plate BP Basement BSMT Beam BM Bearing BRG Bedroom BR Benchmark BM Board BD Boiler BLR Bottom BOT Brick BRK Building line BL Building BLDG Built-up-roof BUR Cabinet CAB Carpet CPT Catalog CAT Ceiling height CH Ceiling CLG Center CTR Centerline CL Ceramic Tile CT Ceramic CER Chalkboard CB Clear CLR Closet CLO Coated CTD Cold rolled CR Column COL Company CO Composition COMP Concrete Masonry Unit CMU Concrete CONC Construction joint CJ Construction CONSTR "Continue, Continuous" CONT Corridor CORR Countersink CSK Cubic CU Curve(d) CRV Dampproofing DP Degree DEG Department(al) DEPT Detail DET Diagonal DIAG Diameter DIA Dimension DIM Dishwasher DW Dispenser DISP Door DR Double DBL Double-hung DH Down DN Downspout DS Drain DR Drawing DWG Each EA East E Electric Water Cooler EWC "Electric, electrical" ELEC Elevation EL Elevator ELEV Engineer ENGR Entrance ENTR Equal EQ Equipment EQUIP Exhaust EXH Existing EXIST Expansion joint EXP JT Exposed EXP Exterior EXT Fabricate FAB Face of Stud F. OF S.

Fan Coil Unit FCU Fiberglass-reinforced plastics FRP Finish FIN Finished Floor FF Fire Extinguisher FE Fire Extinguisher & Cabinet FEC Fire Retardant Treated FRT Fireproof FPRF Fixture FXTR Flange FLG Flashing FL Floor FL Floor drain FD Flooring FLG Fluorescent FLUOR

Footing FTG Foundation FDN Furnish(ed), furniture FURN Furring FURR Gage (gauge) GA Galvanize(d) GALV Galvanized Iron GALVI Glazed Wall Tile GWT Grab Bar GB Grade GR Gravel GVL Gypsum Wallboard GWB Gypsum GYP Handicapped HC Hardware HDW Heating ventilating and HVAC air conditioning Height HGT High Point HPT High Performance HP High Performance Coating HPC Hollow Metal HM Horizontal HORIZ Include(d), inclusive INCL Incorporated INC Information INFO Inside diameter ID Install(ed), installation INSTL Insulation INSUL Interior INT Janitor JAN Joint JT Joist J, JST Junction box JB Knock down KD Laboratory LAB Lavatory LAV Left Hand LH Left L Length LG Level LVL Light LT Machine MACH Maintenance MAINT Manager MGR Manual MNL Manufacturing MFG Markerboard MB Masonry opening MO Masonry MSNRY Master bedroom MBR Material MATL Maximum MAX Mechanical MECH Membrane MEMB Men M Metal MET, MTL Mezzanine MEZZ Minimum MIN Mirror MIR Miscellaneous MISC Mounted MTD Mounting MTG Necessary NEC Noise-reduction coefficient NRC Nominal NOM Non Combustible NC, NONCOM North N Not in Contract NIC Not to scale NTS Not available NA Number NO Office OFF On center OC Opening OPNG Opposite OPP Outside diameter OD Overall OA Overhead OVHD Page P Painted PTD Pair PR Panel PNL Partition PTN Percent PCT Perforate(d) PERF Permanent PERM Perpendicular PERP Piece PC Plastic Laminate PLAM Plastic Laminate PLAS.LAM Plate PL Plumbing PLMB Plywood PLYWD Point PT Polyvinyl chloride PVC Precast PRCST Prefabricated PREFAB Preliminary PRELIM Preparation, prepare PREP Program PRGM Projection Screen PS

Project PROJ Property PROP Public Address PA Quality control QC Quality QUAL Quantity QTY Quarry Tile QT Radius RAD Rain Leader RL Received RCVD Receptacle RCPT Receptionist RECPT Recess(ed) REC Refer, reference REF Refrigerate, refrigerator REFR Reinforce REINF Reinforced concrete RC Remove RMV Repair RPR Required REQD Revise, revision REV Right hand RH Road RD Roof Drain RD Roof RF Roofing RFG Room RM Rubber tile floor RTF Rubber RBR Schedule SCHED Schematic SCHEM Section SECT Service SVCE "Sheet, sheeting" SHT Shower SH Siding SDG Similar SIM Slope SL Sound-transmission class STC South S Speaker SPKR Specification SPEC Sprinkler SPR Square SQ Stainless steel SS Standard STD Standpipe SP Steel STL Storage STOR Structural Glazed Facing Tile SGFT Structural, structure STRUCT Substitute SUBST Surface SURF Suspend(ed) SUSP Switch SW Symmetrical SYM System SYS Tackboard TB Tackstrip TS Telephone TEL Television TV Temporary TEMP Terrazzo TER Thick THK Through THRU Toilet T Tongue and groove T&G Top and bottom T&B Top chord TC Top of Masonry Parapet TMP Top of Bearing TOFB Top of Steel T.O.S.

Topping TOPG Total TOT Transformer XFMR Transom TR Transparent TRANS Tread TRD Threshold THRESH Typical TYP Underground UG Underwriters Laboratories UL Unfinished UNF Unit Ventilator UV Unless Otherwise Noted UON Urinal UR US Gypsum Company USG Vertical VERT Vestibule VEST, V Vinyl Reducing Strip VRS Vinyl Composite Tile VCT Vinyl asbestos tile VAT Wardrobe WARD Water closet WC Waterproof WP Weight WT Welded WLD Welded Wire Mesh WWM With W/ Without W/O Women W Wood WD Wrought Iron WI

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

06/25/2021

100% BID SET 4800 MEMORIAL DRIVE

WACO, TX 76711

67A4-20-110

EWMDLO

COVER SHEET

GI001

A

-2

-1

G I0

/0

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

SUPPRESSION CAMPUS UPGRADES

Fire Suppression Campus Upgrades

100% BID SET

67A4-20-110

Waco VA Medical Center 4800 Memorial Drive

Waco, TX 76711

219-FX101 BUILDING 219 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL X X

219-FD101 BUILDING 219 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT PLAN X

202-FX101 BUILDING 202 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL X X

202-FD101 BUILDING 202 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL X X

189-FX101 BUILDING 189 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL X X

189-FD101 BUILDING 189 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL X

99-FX101 BUILDING 99 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL AND LEVEL 1 X X

99-FD101 BUILDING 99 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL AND LEVEL 1 X

94-FX103 BUILDING 94 - FIRE SUPPRESSION PLAN - ATTIC X X

94-FX102 BUILDING 94 - FIRE SUPPRESSION PLAN - LEVEL 1 X X

94-FX101 BUILDING 94 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL X X

94-FD103 BUILDING 94 - FIRE SUPPRESSION DEMOLITION PLAN - ATTIC X X

94-FD102 BUILDING 94 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 1 X X

94-FD101 BUILDING 94 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL X X

93-FX104 BUILDING 93 - FIRE SUPPRESSION PLAN - ATTIC X X

93-FX103 BUILDING 93 - FIRE SUPPRESSION PLAN - LEVEL 2 X X

93-FX102 BUILDING 93 - FIRE SUPPRESSION PLAN - LEVEL 1 X X

93-FX101 BUILDING 93 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL X X

93-FD104 BUILDING 93 - FIRE SUPPRESSION DEMOLITION PLAN - ATTIC X X

93-FD103 BUILDING 93 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 2 X X

93-FD102 BUILDING 93 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 1 X X

93-FD101 BUILDING 93 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL X X

92-FX104 BUILDING 92 - FIRE SUPPRESSION PLAN - ATTIC X X

92-FX103 BUILDING 92 - FIRE SUPPRESSION PLAN - LEVEL 2 X X

92-FX102 BUILDING 92 - FIRE SUPPRESSION PLAN - LEVEL 1 X X

92-FX101 BUILDING 92 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL X X

92-FX100 BUILDING 92 - FIRE SUPPRESSION PLAN - SUB-BASEMENT LEVEL X X

92-FD104 BUILDING 92 - FIRE SUPPRESSION DEMOLITION PLAN - ATTIC X X

92-FD103 BUILDING 92 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 2 X X

92-FD102 BUILDING 92 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 1 X X

92-FD101 BUILDING 92 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL X X

92-FD100 BUILDING 92 - FIRE SUPPRESSION DEMOLITION PLAN - SUB-BASEMENT LEVEL X X

91-FX104 BUILDING 91 - FIRE SUPPRESSION PLAN - ATTIC X X

91-FX103 BUILDING 91 - FIRE SUPPRESSION PLAN - LEVEL X X

91-FX102 BUILDING 91 - FIRE SUPPRESSION PLAN - LEVEL X X

91-FX101 BUILDING 91 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL X X

91-FX100 BUILDING 91 - FIRE SUPPRESSION PLAN - SUB-BASEMENT LEVEL X

91-FD104 BUILDING 91 - FIRE SUPPRESSION DEMOLITION PLAN - ATTIC X X

91-FD103 BUILDING 91 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 2 X X

91-FD102 BUILDING 91 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 1 X X

91-FD101 BUILDING 91 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL X X

91-FD100 BUILDING 91 - FIRE SUPPRESSION DEMOLITION PLAN - SUB-BASEMENT LEVEL X

90-FX104 BUILDING 90 - FIRE SUPPRESSION PLAN - ATTIC X X

90-FX103 BUILDING 90 - FIRE SUPPRESSION PLAN - LEVEL 1 X X

90-FX102 BUILDING 90 - FIRE SUPPRESSION PLAN - LEVEL 1 X X

90-FX101 BUILDING 90 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL X X

90-FX100 BUILDING 90 - FIRE SUPPRESSION PLAN - SUB-BASEMENT LEVEL X X

90-FD104 BUILDING 90 - FIRE SUPPRESSION DEMOLITION PLAN - ATTIC X X

90-FD103 BUILDING 90 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 2 X X

90-FD102 BUILDING 90 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 1 X X

90-FD101 BUILDING 90 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL X X

90-FD100 BUILDING 90 - FIRE SUPPRESSION DEMOLITION PLAN - SUB-BASEMENT LEVEL X X

24-FX101 BUILDING 24 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL X X

18-FX100 BUILDING 18 - FIRE SUPPRESSION PLANS X X

18-FD100 BUILDING 18 - FIRE SUPPRESSION DEMOLITION PLANS X X

16-FX101 BUILDING 16 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL X X

16-FD101 BUILDING 16 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL X X

98-FX101 BUILDING 98 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL X X

98-FD101 BUILDING 98 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL X

15-FX101 BUILDING 15 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL X

15-FD101 BUILDING 15 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL X X

12-FX101 BUILDING 12 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL X X

11-FX104 BUILDING 11 - FIRE SUPPRESSION PLAN - ATTIC X X

11-FX103 BUILDING 11 - FIRE SUPPRESSION PLAN - LEVEL 2 X X

11-FX102 BUILDING 11 - FIRE SUPPRESSION PLAN - LEVEL 1 X X

11-FX101 BUILDING 11 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL X X

11-FD104 BUILDING 11 - FIRE SUPPRESSION DEMOLITION PLAN - ATTIC X X

11-FD103 BUILDING 11 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 2 X X

11-FD102 BUILDING 11 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 1 X X

11-FD101 BUILDING 11 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL X X

8-FX104 BUILDING 8 - FIRE SUPPRESSION PLAN - ATTIC X X

7-FX104-C BUILDING 7 - FIRE SUPPRESSION PLAN - ATTIC AREA C X X

7-FX104-A&B BUILDING 7 - FIRE SUPPRESSION PLAN - ATTIC AREAS A&B X X

7-FX103-C BUILDING 7 - FIRE SUPPRESSION PLAN - LEVEL AREA C X X

7-FX103-A&B BUILDING 7 - FIRE SUPPRESSION PLAN - LEVEL AREAS A&B X X

7-FX102-C BUILDING 7 - FIRE SUPPRESSION PLAN - LEVEL AREA C X X

7-FX102-A&B BUILDING 7 - FIRE SUPPRESSION PLAN - LEVEL AREAS A&B X X

7-FX101-C BUILDING 7 - FIRE SUPPRESSION PLAN - BASEMENT AREA C X X

7-FX101-A&B BUILDING 7 - FIRE SUPPRESSION PLAN - BASEMENT AREAS A&B X X

7-FD104-C BUILDING 7 - FIRE SUPPRESSION DEMOLITION PLAN - ATTIC AREA C X X

7-FD104-A&B BUILDING 7 - FIRE SUPPRESSION DEMOLITION PLAN - ATTIC AREAS A&B X X

7-FD103-C BUILDING 7 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 2 AREA C X X

7-FD103-A&B BUILDING 7 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 2 AREAS A&B X X

7-FD102-C BUILDING 7 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 1 AREA C X X

7-FD102-A&B BUILDING 7 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 1 AREAS A&B X X

7-FD101-C BUILDING 7 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT AREA C X X

7-FD101-A&B BUILDING 7 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT AREA A&B X X

6-FX101 BUILDING 6 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL X X

6-FX100 BUILDING 6 - FIRE SUPPRESSION PLAN - SUB-BASEMENT LEVEL X X

6-FD101 BUILDING 6 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL X X

6-FD100 BUILDING 6 - FIRE SUPPRESSION DEMOLITION PLAN - SUB-BASEMENT LEVEL X X

5-FX104 BUILDING 5 - FIRE SUPPRESSION PLAN - ATTIC X X

5-FX103 BUILDING 5 - FIRE SUPPRESSION PLAN - LEVEL 2 X X

5-FX102 BUILDING 5 - FIRE SUPPRESSION PLAN - LEVEL 1 X X

5-FX101 BUILDING 5 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL X X

5-FD104 BUILDING 5 - FIRE SUPPRESSION DEMOLITION PLAN - ATTIC X X

5-FD103 BUILDING 5 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 2 X X

5-FD102 BUILDING 5 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 1 X X

5-FD101 BUILDING 5 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL X X

4-FX103 BUILDING 4 - FIRE SUPPRESSION PLAN - ATTIC X X

4-FX102 BUILDING 4 - FIRE SUPPRESSION PLAN - LEVEL 1 X X

4-FX101 BUILDING 4 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL X X

4-FD103 BUILDING 4 - FIRE SUPPRESSION DEMOLITION PLAN - ATTIC X X

4-FD102 BUILDING 4 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 1 X X

4-FD101 BUILDING 4 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL X X

2-FX102 BUILDING 2 - FIRE SUPPRESSION PLAN - LEVEL 2 & ATTIC X X X

2-FX101 BUILDING 2 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL & LEVEL 1 X X X

2-FD102 BUILDING 2 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 2 & ATTIC X X X

2-FD101 BUILDING 2 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL & LEVEL 1 X X X

FX101 HYDRANT FLOW TEST SITE PLAN X

FIRE PROTECTION:

GI003 PENETRATION DETAILS X

GI002 VA WACO SITE ORIENTATION PLAN X

GI001 COVER SHEET X X X

GENERAL:

SHEET NUMBER SHEET NAME 35% 65% 100% 100% FINAL

Russell Snapshot

G A T E

G A T E

G A T E

M A

IN

G A T E

G A T E

OLD FARM ROAD

OLD FARM ROAD

DORIS MILLER CIRCLE

DORIS MILLER CIRCLE

D

OR

IS

M

IL

LE

R

CI

RC

LE

DOR

IS M

ILLE

R C

IRCL

E

O U T E R

L O O P

R O A D

O U T E R

L O O P

R O A D

O U T E R

L O O P

R O A D

O U T E R

LO

O P

R O

AD

OUTER LOOP ROAD OUTER LOOP ROAD

OU

TE

R

LO

OP

C

IR

CL

E

MEMORIAL BLVD.

MEMORIAL BLVD.

QUARTERS DRIVE

C

IR

C

LE

D

RI

VE

BEVERLY DRIVE

BEVERLY DRIVE

BEVERLY DRIVE

N E W

R O A D

N E W

R O A D

H C

V A

N H

C

COURT

COURT

C O

U R

T

V A

N

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

06/25/2021

100% BID SET 4800 MEMORIAL DRIVE

WACO, TX 76711

67A4-20-110

EWMDLO

SITE ORIENTATION PLAN

GI002

A

-2

-1

G I0

/0

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

SUPPRESSION CAMPUS UPGRADES

N TRUE

NORTH

SCALE: NTS

A12

VA WACO SITE ORIENTATION PLAN

219 PHYSICAL THERAPY

202 DIETETICS

189 TRANSPORTATION

99 FMS SHOPS

98 VBA

94 INPATIENT PSYCH

93 FUTURE CENTER OF EXCELLENCE

92 VA FINANCE CENTER

91 SPECIALTY CLINICS

90 PHARMACY CALL CENTER

24 F.M.S./SHOPS

18 POLICE

16 GARAGE MISC.

15 VBA

12 REG'L COUNCIL/PROSTHETICS/EMS/VACANT

11 NURSING HOME (GP)

8 FUTURE ACUTE MENTAL HEALTH/PARTIAL OCCUPANCY

7 BLIND REHAB UNIT/VACANT

6 AUDITORIUM

5 PHARMACY/EDUCATION

4 OUTPATIENT CLINIC/LAB CLINIC

2 ADMINISTRATIVE

BUILDING # BUILDING NAME

Russell Snapshot

G

T E

G A T E

G A T E

M A

IN

G A T E

G A T E

OLD FARM ROAD

OLD FARM ROAD

DORIS MILLER CIRCLE

DORIS MILLER CIRCLE

D

OR

IS

M

IL

LE

R

CI

RC

LE

DOR

IS M

ILLE

R C

IRCL

E

O U T E R

L O O P

R O A D

O U T E R

L O O P

R O A D

O U T E R

L O O P

R O A D

O U T E R

LO

O P

R O

AD

OUTER LOOP ROAD OUTER LOOP ROAD

OU

TE

R

LO

OP

C

IR

CL

E

MEMORIAL BLVD.

MEMORIAL BLVD.

QUARTERS DRIVE

C

IR

C

LE

D

RI

VE

BEVERLY DRIVE

BEVERLY DRIVE

BEVERLY DRIVE

N E W

R O A D

N E W

R O A D

H C

V A

N H

C

COURT

COURT

C O

U R

T

V A

N

FIRE HYDRANT (FH)

WATER VALVE

FH = FIRE HYDRANT

CM = CONTROL MONUMENT

WATER METER

18 20

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

06/25/2021

100% BID SET 4800 MEMORIAL DRIVE

WACO, TX 76711

67A4-20-110

EWMDLO

HYDRANT FLOW TEST SITE PLAN

FX001

A

-2

-1

F X

/1

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

SUPPRESSION CAMPUS UPGRADES

32 72 65 919 2714

31 73 66 1244 3713

30 At Building 8 68 60 1138 2995

29 At Building 221 70 61 993 2506

28 At Building 226 70 60 1278 3047

27 At Building 219 70 65 1138 3946

26 At Building 99 73 68 1186 4245

25 Parking Lot Between Bldgs 90&91 65 60 1186 3886

24 Parking Lot Between Bldgs 91&92 72 67 1186 4202

23 Parking Lot Between Bldgs 92&93 69 64 1126 3861

22 Parking Lot Between Bldgs 93&94 70 65 1061 3680

21 Inner Loop Behind Bldg 11 65 60 1061 3476

20 Inner Loop Behind Bldg 5 68 60 1061 2793

19 Inner Loop Behind Bldg 9 68 63 1210 4104

18 Inner Loop Behind Bldg 6 67 63 1186 4488

17 At Building 90 69 65 1186 4590

16 At Building 91 68 62 1233 3790

15 At Building 93 70 63 1244 3598

14 At Building 94 70 65 1244 4315

13 At Building 5 69 65 993 3841

12 At Building 202 67 64 1233 5448

11 At Building 1 65 50 1126 3687

10 Front Driveway By Gate Entrance 69 65 1163 4498

9 Front Driveway Between Bldgs... 68 63 1138 3860

8 At Building 18 69 65 1186 4590

7 At Building 21 69 65 1126 4355

6 At Building 11 68 63 1278 4334

5 East Of Building At Gate 2 73 70 1278 6025

4 At Building 4 69 65 1126 4355

3 At Building 12 69 65 1186 4590

2 At Building 15 70 65 1300 4507

1 At Building 14 70 66 993 3442

Hydrant# LOCATION STATIC RESIDUAL FIREFLOW (gpm) FLOW AT 20 psi

SCALE: NTS

A13

HYDRANT FLOW TEST SITE PLAN

N TRUE

NORTH

FIRE RESISTANT RATED WALL CONSTRUCTION

THROUGH PENETRATION FIRESTOPPING SYSTEM

PROVIDE SYSTEM IN ACCORDANCE WITH FIRESTOPPING SCHEDULE

WALL PENETRATION - SEE DRAWINGS

SLAB PENETRATION - SEE DRAWINGS

THROUGH PENETRATION FIRESTOPPING SYSTEM

PROVIDE SYSTEM IN ACCORDANCE WITH

FIRESTOPPING SCHEDULE

FIRE RESISTANCE RATED FLOOR CONSTRUCTION

FLOOR PIPE PENETRATION

UL No: F-L-1020

JOINT SEALANT APPLIED

WITHIN OPENING

METAL PIPE

CONCRETE OVER COMPOSITE

STEEL DECK

MINERAL WOOL INSULATION

JOINT SEALANT

JOINT SEALANT

MINERAL WOOL

INSULATION

METAL PIPE

FLOOR PIPE PENETRATION

UL No: F-L-5014

JOINT SEALANT APPLIED

WITHIN OPENING

METAL PIPE

CONCRETE OVER COMPOSITE

STEEL DECK

MINERAL WOOL INSULATION

JOINT SEALANT

JOINT SEALANT

MINERAL WOOL

INSULATION

GLASS FIBER INSULATION

GLASS FIBER

INSULATION

METAL PIPE

SINGLE CONDUIT/PIPE PENETRATION

UL No: W-L-1063

JOINT SEALANT

PIPE / CONDUIT

JOINT SEALANT

RATED WALL ASSEMBLY - VERIFY

WALL TYPE IN FIELD

48" MAX

V A

R

IE

S

6" M

A X

2" MAX, 1" MIN

1" M

A X

MULTIPLE CONDUIT/PIPE PENETRATIONS

UL No: W-L-1063

MINERAL WOOL INSULATION

WALL TYPE, SEE PLAN

MINERAL WOOD INSULATION

MINERAL WOOL INSULATION

WALL TYPE, SEE PLAN

WALL TYPE, SEE PLAN

SINGLE CONDUIT/PIPE PENETRATION

UL No: W-L-5044

PIPE/CONDUIT

FORMING MATERIAL

JOINT SEALANT

VERIFY WALL TYPE IN FIELD

JOINT SEALANT

PIPE / CONDUIT

WALL TYPE

SMALL PENETRATIONS IN PARTITIONS

RATED UP TO 2 HOURS

NO TREATMENT REQUIRED FOR UP

TO 1/8" GAP

MAXIMUM GAP 1/4"

MAXIMUM GAP 1/2", FILL TO FULL DEPTH

OF DRYWALL AND STRIKE OFF AT FACE

OF DRYWALL, DO NOT SPREAD BEYOND

OPENING

2'-0" (PER UL)

SHALLOW FIVE SIDED BOX

RATED WALL ASSEMBLY-

SEE PARTITION TYPES FOR

NUMBER OF LAYERS OF

GYPSUM BOARD

ELECTRICAL JUNCTION BOX

16 SQ INCH MAX OPENING

MAX 100 SQ INCHES IN 100 SQ FEET

LAMINATE BACK PIECE

TO WALLBOARD

REQUIRED BOX EXCEEDS 16 SQ INCHES

OR AGGREGATE SUM OF BOXES

EXCEEDS 100 SQ INCHES IN 100 SQ

FEET OF WALL AREA

ADJACENT ELECTRICAL BOXES

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

06/25/2021

100% BID SET 4800 MEMORIAL DRIVE

WACO, TX 76711

67A4-20-110

EWMDLO

PENETRATION DETAILS

GI003

A

-2

-1

G I0

/1

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

SUPPRESSION CAMPUS UPGRADES

SCALE: NTS

A5

THROUGH PENETRATION FIRESTOP SYSTEM KEY

SCALE: NTS

F6

PENETRATION DETAIL

SCALE: NTS

F3

PENETRATION DETAIL

SCALE: NTS

A9

PENETRATION DETAIL

SCALE: NTS

D9

PENETRATION DETAIL

SCALE: NTS

D6

PENETRATION DETAIL

SCALE: NTS

D3

PENETRATIONS

SCALE: NTS

F9

ELECTRICAL JUNCTION BOX DETAIL

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12

ELE. EQPT.

B1A100

OFFICE

B1A101

HRMS OFFICE

B1A102

OFFICE

B1A103

OFFICE

B1A104

OFFICE

B1A105

MECHANICAL

B1A106

HRMS

CONFERENCE

STORAGE

B1A107

HRMS OFFICE

B1A108

OFFICE

B1A105A

OFFICE

B1A105B

SERVICE

ROOM

B1B100

WOMEN

B1B101

MEN

B1B102

XEROX/ E-QUIP

B1B104

SWING ROOM

B1B105

HRMS

OFFICE

B1B106

PIV

B1B107

HRMS

CONFERENCE

B1B108

HRMS

OFFICE

B1B109

HRMS

OFFICE

B1B110

ELE. CLO.

B1B111

TEL.

B1B108A

IDF

B1B108B

FX05

FX05

FX02FX01

FX03

B3

FD101

FD08

FD08

CORRIDOR

CB1-2

CORRIDOR

CB1-1

ELEVATOR PUMP

ROOM

B1A100A

STAIR 2

VESTIBULE

B1B102A

VESTIBULE

B1B103A

STAIR 1

1. THE BUILDING IS CURRENTLY PARTIALLY SPRINKLERED. RECOMMENDATION IS TO

REMOVE ALL SPRINKLERS, PIPING AND VALVING BACK TO THE UNDERGROUND

STUB IN AND REPLACE WITH A NEW SYSTEM.

2. STANDPIPES MAY REMAIN, BUT REPLACE FIRE HOSE VALVES WITH NEW.

3. CONTRACTOR TO COORDINATE WITH FIRE DEPARTMENT TO RELOCATE FDC TO A

MORE ACCESSIBLE LOCATION.

SCOPE OF WORK

1. EXISTING SYSTEM TO BE MODIFIED AS INDICATED ON THE PLANS.

2. ATTIC DRY PIPE SYSTEMS CURRENTLY INSTALLED WITH GALVNIZED PIPING SHALL

BE REPLACED WITH BLACK STEEL PIPING. FIRE PROTECTION CONTRACTOR TO

VERIFY EXISTING SYSTEM EQUIPMENT LAYOUT.

3. EQUIPMENT AND PIPING SHOWING EXCESSIVE CORROSION OR DETERIORATION

SHALL BE REPLACED WITH NEW AS INDICATED ON THE PLANS.

4. FIRE PROTECTION CONTRACTOR SHALL FOLLOW NFPA 241 AND THE ILSM WHEN

MODIFYING EXISTING SYSTEMS.

FIRE SUPPRESSION DEMOLITION NOTES

FIRE SUPPRESSION HATCH LEGEND

LIGHT HAZARD

DENSITY: 0.10 GPM/SQFT OVER 1500 SQFT

ORDINARY HAZARD

DENSITY: 0.15 GPM/SQFT OVER 1500 SQFT

HATCH LEGEND

ORDINARY HAZARD

DENSITY: 0.20 GPM/SQFT OVER 2500 SQFT

EXISTING PIPING TO BE DEMOLISHED

EXISTING PIPING TO REMAIN

NEW PIPING

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12

MHBM

1A100

MHBM

1A101

OFFICE

1A102C

MHBM

1A103

BREAK ROOM

1A104

NURSING

1A105

NURSING

1B100

HAC

1B101

WOMENS

1B102

MENS

1B103

DIRECTOR'S

CONFERENCE

ROOM

1B104

NURSING

CONFERENCE

ROOM

1B105

NURSING

1B106

NURSING

1B107

NURSING

1B108

WORK ROOM

1B108A

OFFICE

1A102A

FX05 FX05FX20

FD08

FD08

VESTIBULE

1B102A

CLOSET

1A105A

CORRIDOR

C1-3 CORRIDOR

C1-2

FOYER

1B109

ELEVATOR

VESTIBULE

1B103A

STAIR 1 STAIR 2

TOILET

1A102B

OFFICE

1A102F

OFFICE

1A102

OFFICE

1A102E

CORRIDOR

C1-1

BASEMENT

0"

DEMOLISH EXISTING PIPE

BACK TO 6" UNDERGROUND

STUB IN

DEMOLISH EXISTING CONTROL

VAVLE AND CHECK VALVE

DEMOLISH PIPE ROUTED TO

FDC INCLUDING THE EXISTING

FDCAND CHECK VALVE

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

PARTIALLY

SPRINKLERED Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

06/25/2021

100% BID SET BUILDING 2 - ADMINISTRATIVE

4800 MEMORIAL DRIVE

WACO, TX 76711

024-10124-000

EWMEAG

FIRE SUPPRESSION DEMOLITION

PLAN - BASEMENT LEVEL & LEVEL 1

2-FD101

2 1 4

-1

-0

F D

/2

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

SUPPRESSION CAMPUS UPGRADE

KEYNOTE LEGEND

FD08 DEMOLISH EXISTING HOSE VALVE CONNECTIONS. EXISTING STANDPIPES ARE TO

REMAIN.

FX01 EXISTING LOCATION OF MAIN FIRE WATER ENTRANCE.

FX02 EXISTING LOCATION OF MAIN VALVE ASSEMBLY.

FX03 EXISTING LOCATION OF FDC.

FX05 EXISTING LOCATION OF STANDPIPE.

FX20 EXISTING INSPECTOR'S TEST.

SCALE: 1/8" = 1'-0"

A12

BUILDING 2 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL

N TRUE

NORTH

SCALE: 1/8" = 1'-0"

E12

BUILDING 2 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 1

SCALE: 1/2" = 1'-0"

B3

EXISTING VALVE ASSEMBLY DETAIL

Russell Snapshot

1. EXISTING SYSTEM TO BE MODIFIED AS INDICATED ON THE PLANS.

2. ATTIC DRY PIPE SYSTEMS CURRENTLY INSTALLED WITH GALVNIZED PIPING SHALL

BE REPLACED WITH BLACK STEEL PIPING. FIRE PROTECTION CONTRACTOR TO

VERIFY EXISTING SYSTEM EQUIPMENT LAYOUT.

3. EQUIPMENT AND PIPING SHOWING EXCESSIVE CORROSION OR DETERIORATION

SHALL BE REPLACED WITH NEW AS INDICATED ON THE PLANS.

4. FIRE PROTECTION CONTRACTOR SHALL FOLLOW NFPA 241 AND THE ILSM WHEN

MODIFYING EXISTING SYSTEMS.

FIRE SUPPRESSION DEMOLITION NOTES

FIRE SUPPRESSION HATCH LEGEND

LIGHT HAZARD

DENSITY: 0.10 GPM/SQFT OVER 1500 SQFT

ORDINARY HAZARD

DENSITY: 0.15 GPM/SQFT OVER 1500 SQFT

HATCH LEGEND

ORDINARY HAZARD

DENSITY: 0.20 GPM/SQFT OVER 2500 SQFT

EXISTING PIPING TO BE DEMOLISHED

EXISTING PIPING TO REMAIN

NEW PIPING

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12

EQUIPMENT

2A100

MAS

2A101

MAS

2A102

MAS

2A103

CONFERENCE

ROOM

2A104

MAS

2A105A

BREAK ROOM

2A106

WACO

COMPUTER

TRAINING

2A107

RESTROOM

2B100

QS&V (OFF. OF

DIRECTOR)

2B101

NURSING

EDUCATION

ROOM

2B102

QS&V (OFF OF

DIRECTOR)

2B103

QS&V (OFF. OF

DIRECTOR)

2B104

NURSING

2B105

MAS

2A105

NURSING

2A108

NURSING

2A109

QS&V (OFF. OF

DIRECTOR)

2A110

QS&V (OFF. OF

DIRECTOR)

2A111

FX05

FX05

FX20

FD08

FD08

STAIR 2

CORRIDOR

C2-5

CORRIDOR

C2-2

LOBBY

C2-1

ELEVATOR

STAIR 1

CORRIDOR

C2-3

CORRIDOR

C2-4

HAC

2B101

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12

FD01

FX20

DEMOLISH COMPLETE

EXISTING ATTIC SYSTEM

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

PARTIALLY

SPRINKLERED Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

06/25/2021

100% BID SET BUILDING 2 - ADMINISTRATIVE

4800 MEMORIAL DRIVE

WACO, TX 76711

024-10124-000

EWMEAG

FIRE SUPPRESSION DEMOLITION

PLAN - LEVEL 2 & ATTIC

2-FD102

2 2 4

-1

-0

F D

/2

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

SUPPRESSION CAMPUS UPGRADE

KEYNOTE LEGEND

FD01 REPLACE ALL DRY SYSTEM COMPONENTS IN ATTIC INCLUDING ANY GALVANIZED

PIPING.

FD08 DEMOLISH EXISTING HOSE VALVE CONNECTIONS. EXISTING STANDPIPES ARE TO

REMAIN.

FX05 EXISTING LOCATION OF STANDPIPE.

FX20 EXISTING INSPECTOR'S TEST.

N TRUE

NORTH

SCALE: 1/8" = 1'-0"

A12

BUILDING 2 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 2

SCALE: 1/8" = 1'-0"

E12

BUILDING 2 - FIRE SUPPRESSION DEMOLITION PLAN - ATTIC

Russell Snapshot

ELE. EQPT.

B1A100

OFFICE

B1A101

HRMS OFFICE

B1A102

OFFICE

B1A103

OFFICE

B1A104

OFFICE

B1A105

MECHANICAL

B1A106

HRMS

CONFERENCE

STORAGE

B1A107

HRMS OFFICE

B1A108

OFFICE

B1A105A

OFFICE

B1A105B

SERVICE

ROOM

B1B100

WOMEN

B1B101

MEN

B1B102

XEROX/ E-QUIP

B1B104

SWING ROOM

B1B105

HRMS

OFFICE

B1B106

PIV

B1B107

HRMS

CONFERENCE

B1B108

HRMS

OFFICE

B1B109

HRMS

OFFICE

B1B110

ELE. CLO.

B1B111

TEL.

B1B108A

IDF

B1B108B

FX05

FX05

FX02FX01

FX03

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12

B3

FX101

FX23FX23

ELEVATOR PUMP

ROOM

B1A100A

CORRIDOR

CB1-1

CORRIDOR

CB1-2

STAIR 2

VESTIBULE

B1B102A

VESTIBULE

B1B103A

STAIR 1

1. THIS FACILITY IS TO BE PROTECTED THROUGHOUT WITH AUTOMATIC FIRE

SPRINKLER SYSTEMS PER THE PROJECT REQUIREMENTS. A WET PIPE SYSTEM

SHALL BE INSTALLED IN ALL CONDITIONED SPACES OF THE BUILDING. A DRY PIPE

SYSTEM SHALL BE INSTALLED IN THE ATTIC AND ANY ADDITIONAL SPACES

EXPOSED TO TEMPERATURES BELOW 40 DEG F.

2. THE DESIGN AND INSTALLATION OF THE FIRE SUPPRESSION SYSTEMS SHALL BE

IN ACCORDANCE WITH NFPA 13 (2019 EDITION), NFPA 14 (2019 EDITION), THE VA

DESIGN MANUAL AND THE CONTRACT DOCUMENTS.

3. THESE DRAWINGS ARE SCHEMATIC IN NATURE. ALL PIPE ROUTING AND DETAILS

SHOWN SHALL BE CONFIRMED BY THE FIRE PROTECTION CONTRACTOR AND

FULLY COORDINATED WITH ALL DISCIPLINES. THE FIRE PROTECTION

CONTRACTOR SHALL FURNISH COMPLETE CONSTRUCTION SHOP DRAWINGS

SHOWING ALL SPRINKLERS, PIPE, VALVE AND DRAIN LOCATIONS.

4. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL PHASING

OF THE PROJECT. ALL SPRINKLER SYSTEMS MUST REMAIN IN SERVICE AT ALL

TIMES WHEN BUILDING IS OCCUPIED. FOLLOW ILSM PROTOCOLS FOR

SHUTDOWNS.

5. WIRING OF EQUIPMENT AND DEVICES IS BY DIVISION 26.

6. PAINTING, PATCHING AND REPAIR OF EXISTING FINISHES IS BY OTHERS.

7. EXISTING SPRINKLER SYSTEMS SHALL BE MODIFIED AS INDICATED ON THE

DOCUMENTS.

8. SPRINKLER SYSTEMS SHALL BE HYDRAULICALLY CALCULATED IN ACCORDANCE

WITH NFPA 13.

9. THE MAXIMUM COVERAGE PER SPRINKLER IS 225 SQUARE FEET FOR LIGHT

HAZARD AREAS AND 130 SQUARE FEET FOR ORDINARY HAZARD AREAS.

10. INSPECTOR'S TEST VALVES SHALL BELOCATED NO MORE THAN 7'-0 ABOVE

FINISHED FLOOR.

11. ALL HANGERS SHALL BE PROVIDED AND INSTALLED IN ACCORDANCE WITH NFPA

13.

12. ALL VALVES (DRAIN, INSPECTOR'S TEST, CONTROL) SHALL BE IDENTIFIED AS

REQUIRED BY NFPA 13.

13. PROVISIONS FOR DRAINING OF SPRINKLER PIPING SHALL BE PROVIDED IN

ACCORDANCE WITH NFPA 13.

14. PROVIDE MEANS TO TEST FORWARD FLOW THROUGH THE BACKFLOW

PREVENTER IN ACCORDANCE WITH NFPA 13 16.14.5.

15. ALL MAIN DRAINS AND REMOTE TEST CONNECTIONS SHALL DISCHARGE TO A SAFE

LOCATION OUTSIDE THE BUILDING. IF UNABLE TO PIPE TO THE OUTSIDE, THEY

SHALL BE PIPED TO AN INTERIOR DRAIN CAPABLE OF HANDLING THE FULL FLOW.

16. SPRINKLER TEMPERATURE RATINGS NEAR HEAT SOURCES SHALL BE IN

ACCORDANCE WITH NFPA 13.

17. COMMUNICATION AND MECHANICAL ROOMS OR SIMILAR SHALL BE PROTECTED

USING INTERMEDIATE TEMPERATURE SPRINKLERS.

18. PIPING 2" AND LESS IN DIAMETER SHALL BE BLACK STEEL, SCHEDULE 40. PIPE

GREATER THAN 2" SHALL BE BLACK STEEL, SCHEDULE 10. DRY PIPE SYSTEMS

SHALL BE BLACK STEEL, SCHEDULE 40 PIPING WITH NITROGEN IN LIEU OF

COMPRESSED AIR WHERE NOTED ON THE DRAWINGS.

19. TO AID IN PREVENTION OF INTERNAL PIPE CORROSION, INSTALL AUTOMATIC AIR

VENTING NEAR A HIGH POINT ON EACH SYSTEM AS REQUIRED BY NFPA 13.

20. THE CONTRACTOR SHALL PERFORM A HYDRANT FLOW TEST PRIOR TO SYSTEM

CALCULATION TO DETERMINE AVAILABLE WATER PRESSURE AND FLOW. THE

CONTRACTOR SHALL USE THE FOLLOWING FLOW TEST AND DATA FOUND ON

SHEET FX001 AS THE BASIS OF DESIGN UNLESS THE CONFIRMING FLOW TEST

DATA IS WORSE.

FIRE SUPPRESSION GENERAL NOTES

FIRE SUPPRESSION HATCH LEGEND

LIGHT HAZARD

DENSITY: 0.10 GPM/SQFT OVER 1500 SQFT

ORDINARY HAZARD

DENSITY: 0.15 GPM/SQFT OVER 1500 SQFT

HATCH LEGEND

ORDINARY HAZARD

DENSITY: 0.20 GPM/SQFT OVER 2500 SQFT

EXISTING PIPING TO BE DEMOLISHED

EXISTING PIPING TO REMAIN

NEW PIPING

MHBM

1A100

MHBM

1A101

OFFICE

1A102C

MHBM

1A103

BREAK ROOM

1A104

NURSING

1A105

NURSING

1B100

HAC

1B101

WOMENS

1B102

MENS

1B103

DIRECTOR'S

CONFERENCE

ROOM

1B104

NURSING

CONFERENCE

ROOM

1B105

NURSING

1B106

NURSING

1B107

NURSING

1B108

WORK ROOM

1B108A

OFFICE

1A102A

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12

FX05

FX05

FX20

FX23FX23

STAIR 2

ELEVATOR

FOYER

1B109

CORRIDOR

C1-2

CORRIDOR

C1-3

OFFICE

1A102

OFFICE

1A102E

OFFICE

1A102F

TOILET

1A102B

STAIR 1

CORRIDOR

C1-1

CLOSET

1A105A

VESTIBULE

1B102A

VESTIBULE

1B103A

BASEMENT

0"

TO FDC

PROVIDE NEW 4"

BACKFLOW PREVENTER

PROVIDE NEW 4"

CONTROL VALVE

PROVIDE NEW 4" CHECK

VALVE

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

FULLY

SPRINKLERED Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

06/25/2021

100% BID SET BUILDING 2 - ADMINISTRATIVE

4800 MEMORIAL DRIVE

WACO, TX 76711

024-10124-000

EWMEAG

FIRE SUPPRESSION PLAN -

BASEMENT LEVEL & LEVEL 1

2-FX101

2 3 4

-1

-0

F X

/2

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

SUPPRESSION CAMPUS UPGRADE

SCALE: 1/8" = 1'-0"

A12

BUILDING 2 - FIRE SUPPRESSION PLAN - BASEMENT LEVEL

KEYNOTE LEGEND

FX01 EXISTING LOCATION OF MAIN FIRE WATER ENTRANCE.

FX02 EXISTING LOCATION OF MAIN VALVE ASSEMBLY.

FX03 EXISTING LOCATION OF FDC.

FX05 EXISTING LOCATION OF STANDPIPE.

FX20 EXISTING INSPECTOR'S TEST.

FX23 PROVIDE NEW HOSE VALVE CONNECTION TO EXISTING 4" STANDPIPE.

N TRUE

NORTH

SCALE: 1/8" = 1'-0"

E12

BUILDING 2 - FIRE SUPPRESSION PLAN - LEVEL 1

SCALE: 1/2" = 1'-0"

B3

NEW VALVE ASSEMBLY DETAIL

Russell Snapshot

1. THIS FACILITY IS TO BE PROTECTED THROUGHOUT WITH AUTOMATIC FIRE

SPRINKLER SYSTEMS PER THE PROJECT REQUIREMENTS. A WET PIPE SYSTEM

SHALL BE INSTALLED IN ALL CONDITIONED SPACES OF THE BUILDING. A DRY PIPE

SYSTEM SHALL BE INSTALLED IN THE ATTIC AND ANY ADDITIONAL SPACES

EXPOSED TO TEMPERATURES BELOW 40 DEG F.

2. THE DESIGN AND INSTALLATION OF THE FIRE SUPPRESSION SYSTEMS SHALL BE

IN ACCORDANCE WITH NFPA 13 (2019 EDITION), NFPA 14 (2019 EDITION), THE VA

DESIGN MANUAL AND THE CONTRACT DOCUMENTS.

3. THESE DRAWINGS ARE SCHEMATIC IN NATURE. ALL PIPE ROUTING AND DETAILS

SHOWN SHALL BE CONFIRMED BY THE FIRE PROTECTION CONTRACTOR AND

FULLY COORDINATED WITH ALL DISCIPLINES. THE FIRE PROTECTION

CONTRACTOR SHALL FURNISH COMPLETE CONSTRUCTION SHOP DRAWINGS

SHOWING ALL SPRINKLERS, PIPE, VALVE AND DRAIN LOCATIONS.

4. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL PHASING

OF THE PROJECT. ALL SPRINKLER SYSTEMS MUST REMAIN IN SERVICE AT ALL

TIMES WHEN BUILDING IS OCCUPIED. FOLLOW ILSM PROTOCOLS FOR

SHUTDOWNS.

5. WIRING OF EQUIPMENT AND DEVICES IS BY DIVISION 26.

6. PAINTING, PATCHING AND REPAIR OF EXISTING FINISHES IS BY OTHERS.

7. EXISTING SPRINKLER SYSTEMS SHALL BE MODIFIED AS INDICATED ON THE

DOCUMENTS.

8. SPRINKLER SYSTEMS SHALL BE HYDRAULICALLY CALCULATED IN ACCORDANCE

WITH NFPA 13.

9. THE MAXIMUM COVERAGE PER SPRINKLER IS 225 SQUARE FEET FOR LIGHT

HAZARD AREAS AND 130 SQUARE FEET FOR ORDINARY HAZARD AREAS.

10. INSPECTOR'S TEST VALVES SHALL BELOCATED NO MORE THAN 7'-0 ABOVE

FINISHED FLOOR.

11. ALL HANGERS SHALL BE PROVIDED AND INSTALLED IN ACCORDANCE WITH NFPA

13.

12. ALL VALVES (DRAIN, INSPECTOR'S TEST, CONTROL) SHALL BE IDENTIFIED AS

REQUIRED BY NFPA 13.

13. PROVISIONS FOR DRAINING OF SPRINKLER PIPING SHALL BE PROVIDED IN

ACCORDANCE WITH NFPA 13.

14. PROVIDE MEANS TO TEST FORWARD FLOW THROUGH THE BACKFLOW

PREVENTER IN ACCORDANCE WITH NFPA 13 16.14.5.

15. ALL MAIN DRAINS AND REMOTE TEST CONNECTIONS SHALL DISCHARGE TO A SAFE

LOCATION OUTSIDE THE BUILDING. IF UNABLE TO PIPE TO THE OUTSIDE, THEY

SHALL BE PIPED TO AN INTERIOR DRAIN CAPABLE OF HANDLING THE FULL FLOW.

16. SPRINKLER TEMPERATURE RATINGS NEAR HEAT SOURCES SHALL BE IN

ACCORDANCE WITH NFPA 13.

17. COMMUNICATION AND MECHANICAL ROOMS OR SIMILAR SHALL BE PROTECTED

USING INTERMEDIATE TEMPERATURE SPRINKLERS.

18. PIPING 2" AND LESS IN DIAMETER SHALL BE BLACK STEEL, SCHEDULE 40. PIPE

GREATER THAN 2" SHALL BE BLACK STEEL, SCHEDULE 10. DRY PIPE SYSTEMS

SHALL BE BLACK STEEL, SCHEDULE 40 PIPING WITH NITROGEN IN LIEU OF

COMPRESSED AIR WHERE NOTED ON THE DRAWINGS.

19. TO AID IN PREVENTION OF INTERNAL PIPE CORROSION, INSTALL AUTOMATIC AIR

VENTING NEAR A HIGH POINT ON EACH SYSTEM AS REQUIRED BY NFPA 13.

20. THE CONTRACTOR SHALL PERFORM A HYDRANT FLOW TEST PRIOR TO SYSTEM

CALCULATION TO DETERMINE AVAILABLE WATER PRESSURE AND FLOW. THE

CONTRACTOR SHALL USE THE FOLLOWING FLOW TEST AND DATA FOUND ON

SHEET FX001 AS THE BASIS OF DESIGN UNLESS THE CONFIRMING FLOW TEST

DATA IS WORSE.

FIRE SUPPRESSION GENERAL NOTES

FIRE SUPPRESSION HATCH LEGEND

LIGHT HAZARD

DENSITY: 0.10 GPM/SQFT OVER 1500 SQFT

ORDINARY HAZARD

DENSITY: 0.15 GPM/SQFT OVER 1500 SQFT

HATCH LEGEND

ORDINARY HAZARD

DENSITY: 0.20 GPM/SQFT OVER 2500 SQFT

EXISTING PIPING TO BE DEMOLISHED

EXISTING PIPING TO REMAIN

NEW PIPING

EQUIPMENT

2A100

MAS

2A101

MAS

2A102

MAS

2A103

CONFERENCE

ROOM

2A104

MAS

2A105A

BREAK ROOM

2A106

WACO

COMPUTER

TRAINING

2A107

RESTROOM

2B100

QS&V (OFF. OF

DIRECTOR)

2B101

NURSING

EDUCATION

ROOM

2B102

QS&V (OFF OF

DIRECTOR)

2B103

QS&V (OFF. OF

DIRECTOR)

2B104

NURSING

2B105

MAS

2A105

NURSING

2A108

NURSING

2A109

QS&V (OFF. OF

DIRECTOR)

2A110

QS&V (OFF. OF

DIRECTOR)

2A111

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12

FX05

FX05

FX23

FX23

STAIR 2STAIR 1

HAC

2B101

ELEVATOR

LOBBY

C2-1

CORRIDOR

C2-5

CORRIDOR

C2-2

CORRIDOR

C2-3

CORRIDOR

C2-4

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12

FD01

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

FULLY

SPRINKLERED Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

06/25/2021

100% BID SET BUILDING 2 - ADMINISTRATIVE

4800 MEMORIAL DRIVE

WACO, TX 76711

024-10124-000

EWMEAG

FIRE SUPPRESSION PLAN - LEVEL 2

& ATTIC

2-FX102

2 4 4

-1

-0

F X

/2

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

SUPPRESSION CAMPUS UPGRADE

KEYNOTE LEGEND

FD01 REPLACE ALL DRY SYSTEM COMPONENTS IN ATTIC INCLUDING ANY GALVANIZED

PIPING.

FX05 EXISTING LOCATION OF STANDPIPE.

FX23 PROVIDE NEW HOSE VALVE CONNECTION TO EXISTING 4" STANDPIPE.

N TRUE

NORTH

SCALE: 1/8" = 1'-0"

A12

BUILDING 2 - FIRE SUPPRESSION PLAN - LEVEL 2

SCALE: 1/8" = 1'-0"

E12

BUILDING 2 - FIRE SUPPRESSION PLAN - ATTIC

Russell Snapshot

UP

UP

UP

1 2 3 5

6 7 8 9 10 11 12

13 14 15

A

B

C

D

E

F

G

H

I

J

K

L

M

ELECTRICAL

BA130

WOMEN

RESTROOM

BA125B

NURSING OFFICE

CB15

MENS

RESTROOM

BA125A

WAITING AREA

CB2B

CORRIDOR

CB5

HOUSEKEEPING

BA166

WOMEN

RESTROOM

BA164

CORRIDOR

CB23

STORAGE,

GENERAL

BA139

COFFEE BAR

BA173

CONTROLLED

NARCOTICS

BB104

ELECTRICAL

ROOM

BA172

PHARMACIST

BA169

PHARMACY

BB104A

EXAM ROOM

BA117

DIABETICS/

TELERETINAL

IMAGING

BA112

EXAM ROOM

BA109

HAC

BB102

PHARMACY

BREAK ROOM

BB103

PATIENT REP

BA170

MECHANICAL

ROOM

BA171

EMS STORAGE

BB100

MED SUPPLY

STORAGE

BA115

AMBULANCE

ENTRANCE

CB2C

RESTROOM

BA110

TREATMENT

ROOM

BA106

TREATMENT

ROOM

BA107

EXAM ROOM

BA111

EXAM ROOM

BA113

AMBULATORY

CARE DESK

BA114

EXAM ROOM

BA153

MEANS TEST

BA101B

PROCESSING/REGISTRATION

BA101C

VET ID CARD

BA101A

WAITING AREA

CB2A

MENS

RESTROOM

BA168

PRIMARY CARE

OFFICE

BA163

CAFE

BB101

CLEAN LINEN

CB-18A

SOILED LINEN

CB-18B

PHARMACY HELP

LINE

BB103B

EXAM ROOM

BA161

PHARMACY

BA162

CORRIDOR

CB2

CORRIDOR

CB20

CORRIDOR

CB10

CORRIDOR

CB17

CORRIDOR

CB11

CORRIDOR

CB8

CORRIDOR

CB16

ELEVATOR

LOBBY

CB-18

ELEVATOR

MACHINE ROOM

BA100

STAIR 2

BAS2

STORAGE

NO

LABEL

SUB BSMT

ACCESS

VIDEO ROOM

BA105

CHASE

BB100A

STAIR 6

BAS6

STAIR 5

BAS5

TREATMENT

ROOM

BA157

EXAM ROOM

BA160

EXAM ROOM

BA156

EXAM ROOM

BA159

DISPOSITION

AREA

BA123

SOCIAL WORKER

BA129

OFFICE

BA124

EXAM ROOM

BA121

MAROON TEAM

CHECK-IN DESK

BA122

WAITING AREA

BA149

NURSING

INTERVEIW

ROOM

BA152

UNISEX

RESTROOM

BA145B

CORRIDOR

CB14

IMAGING

RECEPTION

BA146

EXAM ROOM

BA155

WAITING AREA

2 EXAM ROOM

BA154

FORM STORAGE

SUPERVISOR

BA103

OFFICE

BA116

INFORMATION

RECEPTIONIST

BA101

ELECTRICAL

BA119

COMMUNICATIONS

CLOSET

BA120

CLINIC MANAGER

BA118

CLEAN LINEN

ROOM

BA103-3

EXAM ROOM

BA104

SOILED UTILITY

BA103-2

STORAGE,

EQUIPMENT

BA103-1OXYGEN

BA103-4

EXAM ROOM

BA167

HOUSEKEEPING

BA127

NURSE

BA126

STAFF LOUNGE

BA125

VESTIBULE

CB1

MULTI PURPOSE

ROOM

BA165

CORRIDOR

CB3

NURSE LOCKER

ROOM

BA128

WAITING AREA

CORRIDOR

XXX

PROGRAM CLERK

BA132

NURSE MANAGER

BA131

MENS

RESTROOM

BA137

OFFICE

BA133

NUTRITION

CLINIC DIETITION

BA129A

WAITING AREA

B13A

CORRIDOR

CB12

PATIENT FUNDS

BA138

TRAVEL

BA134

WOMENS

RESTROOM

BA136

STAIR 1

BAS1

SUB BASEMENT

ACCESS

AGENT CASHIER

BA135

CORRIDOR

CB13

ULTRASOUND

BA147A

IMAGING

EDUCATION

BA144 STORAGE,

GENERAL

TECH OFFICE

BA143

CT SCAN

BA145

IMAGING

MANAGEMENT

BA148

CT CONTROL

BA145A

IMAGING OFFICE

BA142

X-RAY IMAGING

BA140

VESTIBULE

9 DIGITAL

PROCESSING

BA141A

X-RAY IMAGING

BA141

RESTROOM

BA140A

TOILET

BA163A

BUILDING 4 BUILDING 202

FX07

FD02

DEMOLISH RISER

MOUNTED

COMPRESSOR AND

REPLACE WITH FREE

STANDING TANK

WITH NITROGEN

SYSTEM

FD04

ZONE 1

ZONE BOUNDARY

ZONE 1

ZONE 2

EXISTING BASEMENT LEVEL

ZONE 1 SPRINKLER

CONTROL VALVE.

EXISTING BASEMENT LEVEL

ZONE 2 SPRINKLER

CONTROL VALVE.

DEMOLISH 4" DRY

PIPE MAIN BACK TO

DRY PIPE VALVE

SUPPLYING ATTIC

SYSTEMS.

EXISTING 4" WET MAIN TO

REMAIN

F5

FD101

STORAGE,

GENERAL

BA139

FX20

FX20

1. EXISTING SYSTEM TO BE MODIFIED AS INDICATED ON THE PLANS.

2. ATTIC DRY PIPE SYSTEMS CURRENTLY INSTALLED WITH GALVNIZED PIPING SHALL

BE REPLACED WITH BLACK STEEL PIPING. FIRE PROTECTION CONTRACTOR TO

VERIFY EXISTING SYSTEM EQUIPMENT LAYOUT.

3. EQUIPMENT AND PIPING SHOWING EXCESSIVE CORROSION OR DETERIORATION

SHALL BE REPLACED WITH NEW AS INDICATED ON THE PLANS.

4. FIRE PROTECTION CONTRACTOR SHALL FOLLOW NFPA 241 AND THE ILSM WHEN

MODIFYING EXISTING SYSTEMS.

FIRE SUPPRESSION DEMOLITION NOTES

1. RECOMMEND FULL REPLACEMENT OF VALVE ASSEMBLY FROM THE

UNDERGROUND STUB IN AS INDICATED ON THE PLANS.

2. RECOMMEND NITROGEN SYSTEM FOR DRY SYSTEMS.

3. RECOMMEND FULL ATTIC REPLACEMENT BACK TO THE DRY PIPE VALVE.

4. REPLACE ALL QUICK RESPONSE SPRINKLERS DATED 20 YEARS AND OLDER

MATCHING TYPE AND LOCATION.

SCOPE OF WORK

BASEMENT

0"

L

6" UNDERGROUND STUB IN

FIRE SUPPRESSION HATCH LEGEND

LIGHT HAZARD

DENSITY: 0.10 GPM/SQFT OVER 1500 SQFT

ORDINARY HAZARD

DENSITY: 0.15 GPM/SQFT OVER 1500 SQFT

HATCH LEGEND

ORDINARY HAZARD

DENSITY: 0.20 GPM/SQFT OVER 2500 SQFT

EXISTING PIPING TO BE DEMOLISHED

EXISTING PIPING TO REMAIN

NEW PIPING

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1 /2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

FULLY

SPRINKLERED Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

06/25/2021

100% BID SET BUILDING 4 - OUTPATIENT CLINIC

4800 MEMORIAL DRIVE

WACO, TX 76711

024-10124-000

EWMEAG

FIRE SUPPRESSION DEMOLITION

PLAN - BASEMENT LEVEL

4-FD101

4 1 6

-1

-0

F D

/2

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

SUPPRESSION CAMPUS UPGRADES

KEYNOTE LEGEND

FD02 EXISTING LOCATION OF MAIN VALVE ASSEMBLY. REPLACE THE MAIN VALVE

ASSEMBLY FROM THE UNDERGROUND FLANGE.

FD04 REPLACE ALL SPRINKLER HEADS AGED 20 YEARS AND OLDER PER NFPA 25.

FX07 EXISTING LOCATION OF FREE-STANDING FDC.

FX20 EXISTING INSPECTOR'S TEST.

SCALE: 1/8" = 1'-0"

A13

BUILDING 4 - FIRE SUPPRESSION DEMOLITION PLAN - BASEMENT LEVEL NTRUE

NORTH

SCALE: 1/2" = 1'-0"

F5

EXISTING MAIN VALVE ASSEMBLY DETAIL

Russell Snapshot

DN

DN

DN

DN

DN

DN

DN

UP

UP

1 2 3 5

6 7 8 9 10 11 12

13 14 15

A

B

C

D

E

F

G

H

I

J

K

L

M

MEN'S LOCKER

1A100A

MEN'S

RESTROOM

1A100B

OFFICE

1A107A

OFFICE

1A104

CORRIDOR

1A106C

OFFICE

1A107

OFFICE

1A104A

BIOSAFETY

LOUNGE

1A100

PHLEBOTOMY

SUPPLY ROOM

1A-157A

ELEVATOR MACH.

ROOM

1A156

HEMATOLOGY

1A157F

WOMEN'S

LOCKER

1A100C

WOMEN'S

RESTROOM

1A100D

SERVER ROOM

1A106

HOUSEKEEPING

1A128

EXAM ROOM

1A114

SERVER ROOM

FOYER

OFFICE/EXAM

1A103A

SPD CLOSET

1A129

LIQUID NITROGEN

1A151

SERVER ROOM

1A105

STORAGE

STORAGE

CHEMISTRY

1A157E

URINALYSIS

1A157H

LEVEL 3 LAB

SUITE

1A157

PCR LAB

1A157I

LAB OFFICE

1A157L

DECONTAMINATION

ROOM

1A157K

COPY/STORAGE

1A126A

CLINIC

RECEPTION

1A126

ELECTRICAL

CLOSET

1A109

CORRIDOR

C1-7

STAIR 4

1S4

GLUCOSE METER

CLINIC

1A122

OFFICE/EXAM

1A103

SECRETARY

1A-157C

TOXICOLOGY

1A157G

CORRIDOR

DEIONIZED

WATER

1A-157B

HOUSEKEEPING

1A157R

ANCILLARY

TESTING OFFICE

1A157P

ANCILLARY

TESTING

1A157N STAIR 2

1S2

LIFT

MANAGER'S

OFFICE

1A157D

VIEWING ROOM

1A157J1

STERILE/SOLUTION

PREP

1A157M

MYCOBACTERIOLOGY

ROOM

1A157J2

MYCOLOGY

1A157J3

CORRIDOR

C1 10

CORRIDOR

C1 12

WAITING

C1 1C

WAITING

C1 8A

CORRIDOR

C1 8

STAIR 3

1S3

CORRIDOR

C1 13

WAITING

C1

11D

WORKROOM

1A145C

CORRIDOR

C1 11

COMMUNICATIONS

CLOSET

1A134A

EXAM ROOM

1A135

TELEPHONE

CLOSET

1A110A

EXAM ROOM

1A149

SOILED

UTILITY/LINEN

1A150

CLEAN LINEN

1A130

OFFICE/EXAM

1A146

RESTROOM

1A148

GROUP

CLINIC/EXAM

1A152

LAB COLLECTION

AREA

1A127

CORRIDOR

RESTROOM

1A127A

EXAM ROOM

1A152A

STORAGE

CLOSET

1A145A

HEALTH

TECHNICIAN

1A144

SPEECH/LANGUAGE

PATHOLOGIST

1A143

WAITING ROOM

C1

13A

HEARING AID

REPAIR

1A140

HEARING

AID/EVOKED

RESPONSE

TESTING

1A142

CLINICAL

AUDIOLOGIST

1A141

OFFICE/EXAM

1A147

PULMONARY

FUNCTION

1A145

OFFICE/EQUPT.

STORAGE

1A145B

FIRE SIGNAL

CLOSET

1A133

RECEPTION

CUBICLE

C1

11C

RECEPTION

CUBICLE

C1-151

ELECTRICAL

CLOSET

1A134

EKG ROOM

1A132

STAIR 1

1S1

STAIR 5

1S5

STAIR 6

1S6

ATTIC ACCESS

1A108

WOMEN'S

RESTROOM

1A102

MEN'S

RESTROOM

1A101

RESTROOM

154A

PROCEDURE

ROOM

1A154

EXAM ROOM

1A153

CORRIDOR

C1

CORRIDOR

C1 9

SOUND BOOTH

1A

SOUND BOOTH

SOUND BOOTH

CORRIDOR

ELEVATOR

LOBBY

C1 1A

ELEVATOR

LOBBY

C1 8C

CORRIDOR

C1 14

CORRIDOR

C1 6

CORRIDOR

C1 2

CORRIDOR

C1 1

STORAGE ROOM

1A117

EXAM ROOM

1A116

NURSE

1A119

PHYSICIAN

WORK/CONF

ROOM

1A121

OFFICE/EXAM

1A113

TREATMENT

ROOM

1A136

AUDIOLOGIST

BOOTH 2

1A137

PHYSICIAN EXAM

ROOM

1A118

EXAM ROOM

1A124

NURSE

1A125

EXAM ROOM

1A155

MEN'S

RESTROOM

1A123

EMPLOYEE

BREAK ROOM

1A110

EXAM ROOM

1A115

WOMEN'S

RESTROOM

1A120

OFFICE/EXAM

1A111

NURSES/TREATMENT

ROOM

1A112

ATTIC ACCESS

ATTIC ACCESS

FD04

BUILDING 4 BUILDING 202

ZONE BOUNDARY

ZONE 3

ZONE 4

4" DRY PIPE

SUPPLY TO

ATTIC.

DRY PIPE ROUTED

TO ATTIC ABOVE.

DRY PIPE ROUTED

TO ATTIC ABOVE.

EXISTING LEVEL 1 ZONE

3 SPRINKLER ZONE

CONTROL VALVE.

EXISTING LEVEL 1

ZONE 2 SPRINKLER

ZONE CONTROL

VALVE.

FX20

FX20 FX20

1. EXISTING SYSTEM TO BE MODIFIED AS INDICATED ON THE PLANS.

2. ATTIC DRY PIPE SYSTEMS CURRENTLY INSTALLED WITH GALVNIZED PIPING SHALL

BE REPLACED WITH BLACK STEEL PIPING. FIRE PROTECTION CONTRACTOR TO

VERIFY EXISTING SYSTEM EQUIPMENT LAYOUT.

3. EQUIPMENT AND PIPING SHOWING EXCESSIVE CORROSION OR DETERIORATION

SHALL BE REPLACED WITH NEW AS INDICATED ON THE PLANS.

4. FIRE PROTECTION CONTRACTOR SHALL FOLLOW NFPA 241 AND THE ILSM WHEN

MODIFYING EXISTING SYSTEMS.

FIRE SUPPRESSION DEMOLITION NOTES

FIRE SUPPRESSION HATCH LEGEND

LIGHT HAZARD

DENSITY: 0.10 GPM/SQFT OVER 1500 SQFT

ORDINARY HAZARD

DENSITY: 0.15 GPM/SQFT OVER 1500 SQFT

HATCH LEGEND

ORDINARY HAZARD

DENSITY: 0.20 GPM/SQFT OVER 2500 SQFT

EXISTING PIPING TO BE DEMOLISHED

EXISTING PIPING TO REMAIN

NEW PIPING

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1 /2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

FULLY

SPRINKLERED Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

06/25/2021

100% BID SET BUILDING 4 - OUTPATIENT CLINIC

4800 MEMORIAL DRIVE

WACO, TX 76711

024-10124-000

EWMEAG

FIRE SUPPRESSION DEMOLITION

PLAN - LEVEL 1

4-FD102

4 2 6

-1

-0

F D

/2

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

SUPPRESSION CAMPUS UPGRADES

KEYNOTE LEGEND

FD04 REPLACE ALL SPRINKLER HEADS AGED 20 YEARS AND OLDER PER NFPA 25.

FX20 EXISTING INSPECTOR'S TEST.

SCALE: 1/8" = 1'-0"

A13

BUILDING 4 - FIRE SUPPRESSION DEMOLITION PLAN - LEVEL 1

NTRUE

NORTH

Russell Snapshot

2. ATTIC DRY PIPE SYSTEMS CURRENTLY INSTALLED WITH GALVNIZED PIPING SHALL

BE REPLACED WITH BLACK STEEL PIPING. FIRE PROTECTION CONTRACTOR TO

VERIFY EXISTING SYSTEM EQUIPMENT LAYOUT.

3. EQUIPMENT AND PIPING SHOWING EXCESSIVE CORROSION OR DETERIORATION

SHALL BE REPLACED WITH NEW AS INDICATED ON THE PLANS.

4. FIRE PROTECTION CONTRACTOR SHALL FOLLOW NFPA 241 AND THE ILSM WHEN

MODIFYING EXISTING SYSTEMS.

FIRE SUPPRESSION DEMOLITION NOTES

1 2 3 5

6 7 8 9 10 11 12

13 14 15

A

B

C

D

E

F

G

H

I

J

K

L

M

FD03

FD03

EXISTING PENTHOUSE

ZONE 5 SPRINKLER

CONTROL VALVE.

ZONE 5

PENTHOUSE

FIRE SUPPRESSION HATCH LEGEND

LIGHT HAZARD

DENSITY: 0.10 GPM/SQFT OVER 1500 SQFT

ORDINARY HAZARD

DENSITY: 0.15 GPM/SQFT OVER 1500 SQFT

HATCH LEGEND

ORDINARY HAZARD

DENSITY: 0.20 GPM/SQFT OVER 2500 SQFT

EXISTING PIPING TO BE DEMOLISHED

EXISTING PIPING TO REMAIN

NEW PIPING

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1 /2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

FULLY

SPRINKLERED Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

06/25/2021

100% BID SET BUILDING 4 - OUTPATIENT CLINIC

4800 MEMORIAL DRIVE

WACO, TX 76711

024-10124-000

EWMEAG

FIRE SUPPRESSION DEMOLITION

PLAN - ATTIC

4-FD103

4 3 6

-1

-0

F D

/2

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

SUPPRESSION CAMPUS UPGRADES

KEYNOTE LEGEND

FD03 REPLACE EXISTING SPRINKLERS, BRANCH LINES, MAINS AND FITTINGS.

NTRUE

NORTH

SCALE: 1/8" = 1'-0"

A14

BUILDING 4 - FIRE SUPPRESSION DEMOLITION PLAN - ATTIC

Russell Snapshot

UP

UP

ELECTRICAL

BA130

WOMEN

RESTROOM

BA125B

NURSING OFFICE

CB15

MENS

RESTROOM

BA125A

WAITING AREA

CB2B

CORRIDOR

CB5

HOUSEKEEPING

BA166

WOMEN

RESTROOM

BA164

CORRIDOR

CB23

STORAGE,

GENERAL

BA139

COFFEE BAR

BA173

CONTROLLED

NARCOTICS

BB104

ELECTRICAL

ROOM

BA172

PHARMACIST

BA169

PHARMACY

BB104A

EXAM ROOM

BA117

DIABETICS/

TELERETINAL

IMAGING

BA112

EXAM ROOM

BA109

HAC

BB102

PHARMACY

BREAK ROOM

BB103

PATIENT REP

BA170

MECHANICAL

ROOM

BA171

EMS STORAGE

BB100

MED SUPPLY

STORAGE

BA115

AMBULANCE

ENTRANCE

CB2C

RESTROOM

BA110

TREATMENT

ROOM

BA106

TREATMENT

ROOM

BA107

EXAM ROOM

BA111

EXAM ROOM

BA113

AMBULATORY

CARE DESK

BA114

EXAM ROOM

BA153

MEANS TEST

BA101B

PROCESSING/REGISTRATION

BA101C

VET ID CARD

BA101A

WAITING AREA

CB2A

MENS

RESTROOM

BA168

PRIMARY CARE

OFFICE

BA163

CAFE

BB101

CLEAN LINEN

CB-18A

SOILED LINEN

CB-18B

PHARMACY HELP

LINE

BB103B

EXAM ROOM

BA161

PHARMACY

BA162

CORRIDOR

CB2

CORRIDOR

CB20

CORRIDOR

CB10

CORRIDOR

CB17

CORRIDOR

CB11

CORRIDOR

CB8

CORRIDOR

CB16

ELEVATOR

LOBBY

CB-18

ELEVATOR

MACHINE ROOM

BA100

STAIR 2

BAS2

STORAGE

NO

LABEL

SUB BSMT

ACCESS

VIDEO ROOM

BA105

CHASE

BB100A

STAIR 6

BAS6

STAIR 5

BAS5

TREATMENT

ROOM

BA157

EXAM ROOM

BA160

EXAM ROOM

BA156

EXAM ROOM

BA159

DISPOSITION

AREA

BA123

SOCIAL WORKER

BA129

OFFICE

BA124

EXAM ROOM

BA121

MAROON TEAM

CHECK-IN DESK

BA122

WAITING AREA

BA149

NURSING

INTERVEIW

ROOM

BA152

UNISEX

RESTROOM

BA145B