This document is a detailed technical specification (Volume 2) for a Sugarcane Greenhouse Design project for the USDA Agricultural Research Service in Houma, Louisiana. The specification, prepared by Merrick & Company and dated September 2024, provides comprehensive technical requirements for mechanical systems, thermal insulation, plumbing, and related construction elements. The document includes extensive technical details across multiple divisions, covering everything from general requirements and earthwork to specific mechanical, electrical, and plumbing systems for the greenhouse facility.
The specification outlines precise technical standards for materials and installation methods, including requirements for pipe insulation, thermal protection, mechanical systems, and greenhouse-specific infrastructure. Key technical sections address thermal insulation materials, pipe and duct insulation systems, installation procedures, and performance specifications for various mechanical components. The document is meticulously organized, with each section providing detailed technical guidance for contractors, including material specifications, installation methods, quality control requirements, and compliance standards for the greenhouse construction project.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPECIFICATIONS – VOLUME 2 OF 2
SUGARCANE GREENHOUSE DESIGN
HOUMA, LA
September 2024
Submitted to:
U.S. DEPARTMENT OF AGRICULTURE
AGRICULTURAL RESEARCH SERVICE
Submitted by:
Merrick & Company
USDA Sugar cane Gr eenhouse Desi gn 100098. 00 17 Sept ember 2024 Fi nal Tur nover Document s
PROJECT TABLE OF CONTENTS
DI VI SI ON 01 - GENERAL REQUI REMENTS
01 11 00 08/ 15, CHG 2: 08/ 21 SUMMARY OF WORK
01 14 00 11/ 22, CHG 1: 02/ 23 WORK RESTRI CTI ONS
01 20 00 11/ 20, CHG 3: 02/ 23 PRI CE AND PAYMENT PROCEDURES
01 30 00 11/ 20, CHG 3: 08/ 23 ADMI NI STRATI VE REQUI REMENTS
01 32 01. 00 10 08/ 23 PROJECT SCHEDULE
01 32 17. 00 20 11/ 23 COST- LOADED NETWORK ANALYSI S SCHEDULES
( NAS)
01 33 00 08/ 18, CHG 4: 02/ 21 SUBMI TTAL PROCEDURES
01 33 29 02/ 21 SUSTAI NABI LI TY REQUI REMENTS AND
REPORTI NG
01 35 26 11/ 20, CHG 4: 08/ 23 GOVERNMENTAL SAFETY REQUI REMENTS
01 42 00 02/ 19, CHG 1: 08/ 23 SOURCES FOR REFERENCE PUBLI CATI ONS
01 45 00 08/ 23 QUALI TY CONTROL
01 45 00. 15 10 11/ 23 RESI DENT MANAGEMENT SYSTEM CONTRACTOR
MODE ( RMS CM)
01 45 35 11/ 20 SPECI AL I NSPECTI ONS
01 50 00 11/ 20, CHG 2: 08/ 22 TEMPORARY CONSTRUCTI ON FACI LI TI ES AND
CONTROLS
01 57 19 08/ 22 TEMPORARY ENVI RONMENTAL CONTROLS
01 58 00 08/ 19, CHG 5: 08/ 22 PROJECT I DENTI FI CATI ON
01 74 19 02/ 19, CHG 3: 11/ 21 CONSTRUCTI ON WASTE MANAGEMENT AND
DI SPOSAL
01 78 00 05/ 19, CHG 1: 08/ 21 CLOSEOUT SUBMI TTALS
01 78 23 05/ 23 OPERATI ON AND MAI NTENANCE DATA
01 78 24. 00 10 05/ 23 FACI LI TY DATA REQUI REMENTS
01 91 00. 15 05/ 23, CHG 2: 11/ 23 BUI LDI NG COMMI SSI ONI NG
DI VI SI ON 02 - EXI STI NG CONDI TI ONS
02 41 00 08/ 22 DEMOLI TI ON
DI VI SI ON 03 - CONCRETE
03 30 00 02/ 19, CHG 5: 08/ 23 CAST- I N- PLACE CONCRETE
DI VI SI ON 04 - MASONRY
04 20 00 11/ 15, CHG 2: 05/ 19 UNI T MASONRY
DI VI SI ON 05 - METALS
05 05 20 05/ 22 POST- I NSTALLED CONCRETE AND MASONRY
ANCHORS
05 50 13 05/ 17, CHG 1: 08/ 18 MI SCELLANEOUS METAL FABRI CATI ONS
DI VI SI ON 06 - WOOD, PLASTI CS, AND COMPOSI TES
06 73 01 08/ 23 FI BERGLASS REI NFORCED PLASTI C ( FRP)
GRATI NG
DI VI SI ON 07 - THERMAL AND MOI STURE PROTECTI ON
07 21 16 08/ 23 MI NERAL FI BER BLANKET I NSULATI ON
07 41 13 05/ 11, CHG 4: 02/ 21 METAL ROOF PANELS
07 60 00 08/ 23 FLASHI NG AND SHEET METAL
PROJECT TABLE OF CONTENTS Page 1
07 84 00 05/ 10, CHG 1: 08/ 13 FI RESTOPPI NG
07 92 00 08/ 23 JOI NT SEALANTS
DI VI SI ON 08 - OPENI NGS
08 11 13 08/ 20 STEEL DOORS AND FRAMES
08 71 00 02/ 16, CHG 4: 02/ 22 DOOR HARDWARE
08 81 00 05/ 19 GLAZI NG
DI VI SI ON 09 - FI NI SHES
09 90 00 02/ 21 PAI NTS AND COATI NGS
DI VI SI ON 10 - SPECI ALTI ES
10 14 00. 20 08/ 20 I NTERI OR SI GNAGE
10 44 16 11/ 19 FI RE EXTI NGUI SHERS
DI VI SI ON 13 - SPECI AL CONSTRUCTI ON
13 34 13 09/ 24 GREENHOUSE STRUCTURE AND SYSTEMS
13 34 14 02/ 24 GREENHOUSE CONTROL SYSTEMS
DI VI SI ON 22 - PLUMBI NG
22 00 00 11/ 15, CHG 4: 05/ 21 PLUMBI NG, GENERAL PURPOSE
22 13 01 02/ 24 GREENHOUSE PLUMBI NG
DI VI SI ON 23 - HEATI NG, VENTI LATI NG, AND AI R CONDI TI ONI NG ( HVAC)
23 03 00. 00 20 08/ 10, CHG 3: 08/ 18 BASI C MECHANI CAL MATERI ALS AND METHODS
23 05 93 11/ 15 TESTI NG, ADJUSTI NG, AND BALANCI NG FOR
HVAC
23 07 00 02/ 13, CHG 7: 05/ 20 THERMAL I NSULATI ON FOR MECHANI CAL
SYSTEMS
23 08 00 05/ 23 COMMI SSI ONI NG OF MECHANI CAL AND
PLUMBI NG SYSTEMS
23 11 20 05/ 20 FACI LI TY GAS PI PI NG
23 13 01 02/ 24 GREENHOUSE MECHANI CAL
23 21 13. 00 20 04/ 06, CHG 2: 11/ 19 LOW TEMPERATURE WATER ( LTW) HEATI NG
SYSTEM
23 82 00. 00 20 02/ 16, CHG 1: 08/ 18 TERMI NAL HEATI NG UNI TS
DI VI SI ON 26 - ELECTRI CAL
26 05 73 08/ 23 POWER SYSTEM STUDI ES
26 08 00 11/ 22 APPARATUS I NSPECTI ON AND TESTI NG
26 13 50 03/ 24 GREENHOUSE ELECTRI CAL
26 20 00 08/ 23 I NTERI OR DI STRI BUTI ON SYSTEM
DI VI SI ON 27 - COMMUNI CATI ONS
27 10 00 08/ 11 BUI LDI NG TELECOMMUNI CATI ONS CABLI NG
SYSTEM
DI VI SI ON 28 - ELECTRONI C SAFETY AND SECURI TY
28 10 05 05/ 16 ELECTRONI C SECURI TY SYSTEMS ( ESS)
28 31 70 08/ 20 I NTERI OR FI RE ALARM SYSTEM, ADDRESSABLE
PROJECT TABLE OF CONTENTS Page 2
DI VI SI ON 31 - EARTHWORK
31 00 00 08/ 23 EARTHWORK
31 11 00 11/ 18 CLEARI NG AND GRUBBI NG
31 62 19 11/ 20, CHG 2: 02/ 24 TI MBER PI LES
DI VI SI ON 32 - EXTERI OR I MPROVEMENTS
32 12 16. 16 11/ 20 ROAD- MI X ASPHALT PAVI NG
32 14 13. 13 11/ 19 PRECAST CONCRETE UNI T PAVI NG
32 16 19 05/ 18 CONCRETE CURBS, GUTTERS AND SI DEWALKS
DI VI SI ON 33 - UTI LI TI ES
33 11 00 02/ 18, CHG 1: 02/ 22 WATER UTI LI TY DI STRI BUTI ON PI PI NG
33 30 00 05/ 18 SANI TARY SEWERAGE
33 40 00 11/ 21 STORMWATER UTI LI TI ES
- - End of Pr oj ect Tabl e of Cont ent s - -
PROJECT TABLE OF CONTENTS Page 3
THI S PAGE I NTENTI ONALLY LEFT BLANK
PROJECT TABLE OF CONTENTS Page 4
USDA- SUGARCANE GREENHOUSE DESIGN 100098.00
17 SEPTEMBER 2024 FINAL TURNOVER
SECTION 000020 Page 1
PROFESSIONAL SEALS
The construction work for the Project at USDA Houma SCRL in Schriver, LA is issued under a single contract with a single Project Specification in two (2) Volumes. The following pages document the
Designer of Record responsible for each Section.
CIVIL ENGINEER
Steve Buckler, RMF
The seal above is the Designer of Record responsible for the following Sections:
All Sections in Divisions 31-33, except for those noted by other disciplines.
STRUCTURAL ENGINEER
Steve Buckler, RMF responsible for the Sections:
03 30 00, 05 05 20 & 31 62 19.
ARCHITECT
Stephen Helgren, Merrick & Company
All Sections in Divisions 01-10, except for those noted by other disciplines.
GREENHOUSE DESIGN
Gregg D. Short, P.E.
The Seal above is the Designer of Record
All Sections in Divisions 13 and Sections
22 13 01, 23 13 01 & 26 13 50.
S T A T E O F L O U I S I A N A
PROFESSIONAL
ENGINEER
GREGG D. SHORT
License No. 0047601
09/16/2024
ST
EPHEN HELGREN
REG. NO. 10101
09/16/2024
USDA- SUGARCANE GREENHOUSE DESIGN 100098.00
17 SEPTEMBER 2024 FINAL TURNOVER
SECTION 000020 Page 2
PLUMBING ENGINEER
Yang Lu, Merrick & Company
All Sections in Division 22, except 22 13 01.
ELECTRICAL ENGINEER
Jake Gleusner, Merrick & Company
The Seal above is the Designer of Record
All Sections in Divisions 26-28, except 26 13 01.
MECHANICAL ENGINEER
Yang Lu, Merrick & Company
All Sections in Division 23, except 23 13 01.
9/16/2024 9/16/2024 jake.gleusner G:\PE Stamps\Orders\2024\140869 Gleusner LA-Eng\140869 Gleusner LA-Eng Final Model (1) jake.gleusner Text Box 09/16/2024
SECTI ON 22 00 00
PLUMBI NG, GENERAL PURPOSE
11/ 15, CHG 4: 05/ 21
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.
AMERI CAN NATI ONAL STANDARDS I NSTI TUTE ( ANSI )
ANSI Z21. 22/ CSA 4. 4 ( 2015; R 2020) Rel i ef Val ves f or Hot Wat er Suppl y Syst ems
AMERI CAN SOCI ETY OF MECHANI CAL ENGI NEERS ( ASME)
ASME A112. 6. 1M ( 1997; R 2017) Fl oor Af f i xed Suppor t s f or Of f - t he- Fl oor Pl umbi ng Fi xt ur es f or Publ i c Use
ASME A112. 6. 3 ( 2019) St andar d f or Fl oor and Tr ench Dr ai ns
ASME A112. 14. 1 ( 2003; R 2017; R 2022) Backwat er Val ves
ASME A112. 36. 2M ( 1991; R 2017) Cl eanout s
ASME B1. 20. 1 ( 2013; R 2018) Pi pe Thr eads, Gener al Pur pose ( I nch)
ASME B16. 5 ( 2020) Pi pe Fl anges and Fl anged Fi t t i ngs NPS 1/ 2 Thr ough NPS 24 Met r i c/ I nch St andar d
ASME B16. 15 ( 2018) Cast Copper Al l oy Thr eaded Fi t t i ngs Cl asses 125 and 250
ASME B16. 18 ( 2021) Cast Copper Al l oy Sol der Joi nt Pr essur e Fi t t i ngs
ASME B16. 21 ( 2021) Nonmet al l i c Fl at Gasket s f or Pi pe Fl anges
ASME B16. 23 ( 2021) Cast Copper Al l oy Sol der Joi nt Dr ai nage Fi t t i ngs - DWV
ASME B16. 24 ( 2022) Cast Copper Al l oy Pi pe Fl anges, Fl anged Fi t t i ngs, and Val ves Cl asses 150, 300, 600, 900, 1500, and 2500
ASME B16. 29 ( 2022) Wr ought Copper and Wr ought Copper Al l oy Sol der - Joi nt Dr ai nage Fi t t i ngs - DWV
ASME B16. 34 ( 2021) Val ves - Fl anged, Thr eaded and Wel di ng End
SECTI ON 22 00 00 Page 1
ASME B16. 50 ( 2021) Wr ought Copper and Copper Al l oy Br aze- Joi nt Pr essur e Fi t t i ngs
ASME B16. 51 ( 2013) Copper and Copper Al l oy Pr ess- Connect Pr essur e Fi t t i ngs
ASME B31. 5 ( 2022) Ref r i ger at i on Pi pi ng and Heat Tr ansf er Component s
ASME B40. 100 ( 2022) Pr essur e Gauges and Gauge At t achment s
ASME BPVC SEC I V ( 2017) BPVC Sect i on I V- Rul es f or Const r uct i on of Heat i ng Boi l er s
ASME CSD- 1 ( 2021) Cont r ol and Saf et y Devi ces f or Aut omat i cal l y Fi r ed Boi l er s
AMERI CAN SOCI ETY OF SANI TARY ENGI NEERI NG ( ASSE)
ASSE 1003 ( 2020) Per f or mance Requi r ement s f or Wat er Pr essur e Reduci ng Val ves f or Domest i c Wat er Di st r i but i on Syst ems - ( ANSI appr oved 2010)
ASSE 1018 ( 2023) Per f or mance Requi r ement s f or Tr ap Seal Pr i mer Val ves - Pot abl e Wat er Suppl i ed ( ANSI Appr oved 2002
AMERI CAN WATER WORKS ASSOCI ATI ON ( AWWA)
AWWA B300 ( 2018) Hypochl or i t es
AWWA C203 ( 2020) Coal - Tar Pr ot ect i ve Coat i ngs and Li ni ngs f or St eel Wat er Pi pel i nes - Enamel and Tape - Hot - Appl i ed
AWWA C606 ( 2022) Gr ooved and Shoul der ed Joi nt s
AWWA C651 ( 2014) St andar d f or Di s i nf ect i ng Wat er Mai ns
AWWA C652 ( 2019) Di s i nf ect i on of Wat er - St or age Faci l i t i es
AMERI CAN WELDI NG SOCI ETY ( AWS)
AWS A5. 8/ A5. 8M ( 2019) Speci f i cat i on f or Fi l l er Met al s f or Br azi ng and Br aze Wel di ng
AWS B2. 2/ B2. 2M ( 2016) Speci f i cat i on f or Br azi ng Pr ocedur e and Per f or mance Qual i f i cat i on
ASTM I NTERNATI ONAL ( ASTM)
ASTM A74 ( 2021) St andar d Speci f i cat i on f or Cast I r on Soi l Pi pe and Fi t t i ngs
ASTM A105/ A105M ( 2021) St andar d Speci f i cat i on f or Car bon
SECTI ON 22 00 00 Page 2
St eel For gi ngs f or Pi pi ng Appl i cat i ons
ASTM A183 ( 2014; R 2020) St andar d Speci f i cat i on f or Car bon St eel Tr ack Bol t s and Nut s
ASTM A193/ A193M ( 2023) St andar d Speci f i cat i on f or Al l oy- St eel and St ai nl ess St eel Bol t i ng Mat er i al s f or Hi gh- Temper at ur e Ser vi ce and Ot her Speci al Pur pose Appl i cat i ons
ASTM A515/ A515M ( 2017; R2022) St andar d Speci f i cat i on f or Pr essur e Vessel Pl at es, Car bon St eel , f or I nt er medi at e- and Hi gher - Temper at ur e Ser vi ce
ASTM A516/ A516M ( 2017) St andar d Speci f i cat i on f or Pr essur e Vessel Pl at es, Car bon St eel , f or Moder at e-and Lower - Temper at ur e Ser vi ce
ASTM A888 ( 2021a) St andar d Speci f i cat i on f or Hubl ess Cast I r on Soi l Pi pe and Fi t t i ngs f or Sani t ar y and St or m Dr ai n, Wast e, and Vent Pi pi ng Appl i cat i ons
ASTM B32 ( 2020) St andar d Speci f i cat i on f or Sol der Met al
ASTM B42 ( 2020) St andar d Speci f i cat i on f or Seaml ess Copper Pi pe, St andar d Si zes
ASTM B88 ( 2022) St andar d Speci f i cat i on f or Seaml ess Copper Wat er Tube
ASTM B117 ( 2019) St andar d Pr act i ce f or Oper at i ng Sal t Spr ay ( Fog) Appar at us
ASTM B306 ( 2020) St andar d Speci f i cat i on f or Copper Dr ai nage Tube ( DWV)
ASTM B370 ( 2022) St andar d Speci f i cat i on f or Copper Sheet and St r i p f or Bui l di ng Const r uct i on
ASTM B813 ( 2016) St andar d Speci f i cat i on f or Li qui d and Past e Fl uxes f or Sol der i ng of Copper and Copper Al l oy Tube
ASTM C564 ( 2020a) St andar d Speci f i cat i on f or Rubber Gasket s f or Cast I r on Soi l Pi pe and Fi t t i ngs
ASTM C920 ( 2018) St andar d Speci f i cat i on f or El ast omer i c Joi nt Seal ant s
ASTM D2000 ( 2018) St andar d Cl assi f i cat i on Syst em f or Rubber Pr oduct s i n Aut omot i ve Appl i cat i ons
ASTM D2235 ( 2004; R 2016) St andar d Speci f i cat i on f or Sol vent Cement f or Acr yl oni t r i l e- But adi ene- St yr ene ( ABS)
SECTI ON 22 00 00 Page 3
Pl ast i c Pi pe and Fi t t i ngs
ASTM D2564 ( 2020) St andar d Speci f i cat i on f or Sol vent Cement s f or Pol y( Vi nyl Chl or i de) ( PVC) Pl ast i c Pi pi ng Syst ems
ASTM D2665 ( 2014) St andar d Speci f i cat i on f or Pol y( Vi nyl Chl or i de) ( PVC) Pl ast i c Dr ai n, Wast e, and Vent Pi pe and Fi t t i ngs
ASTM D2855 ( 2015) St andar d Pr act i ce f or Maki ng Sol vent - Cement ed Joi nt s wi t h Pol y( Vi nyl Chl or i de) ( PVC) Pi pe and Fi t t i ngs
ASTM D3122 ( 1995; R 2009) Sol vent Cement s f or St yr ene- Rubber ( SR) Pl ast i c Pi pe and Fi t t i ngs
ASTM D3138 ( 2004; R 2016) St andar d Speci f i cat i on f or Sol vent Cement s f or Tr ansi t i on Joi nt s Bet ween Acr yl oni t r i l e- But adi ene- St yr ene ( ABS) and Pol y( Vi nyl Chl or i de) ( PVC) Non- Pr essur e Pi pi ng Component s
ASTM D3139 ( 2019) Joi nt s f or Pl ast i c Pr essur e Pi pes Usi ng Fl exi bl e El ast omer i c Seal s
ASTM D3212 ( 2020) St andar d Speci f i cat i on f or Joi nt s f or Dr ai n and Sewer Pl ast i c Pi pes Usi ng Fl exi bl e El ast omer i c Seal s
ASTM D3311 ( 2017) St andar d Speci f i cat i on f or Dr ai n, Wast e, and Vent ( DWV) Pl ast i c Fi t t i ngs Pat t er ns
ASTM E1 ( 2014) St andar d Speci f i cat i on f or ASTM Li qui d- i n- Gl ass Ther momet er s
ASTM F409 ( 2022) St andar d Speci f i cat i on f or Ther mopl ast i c Accessi bl e and Repl aceabl e Pl ast i c Tube and Tubul ar Fi t t i ngs
ASTM F477 ( 2014; R 2021) St andar d Speci f i cat i on f or El ast omer i c Seal s ( Gasket s) f or Joi ni ng Pl ast i c Pi pe
ASTM F493 ( 2022) St andar d Speci f i cat i on f or Sol vent Cement s f or Chl or i nat ed Pol y ( Vi nyl Chl or i de) ( CPVC) Pl ast i c Pi pe and Fi t t i ngs
ASTM F891 ( 2016) St andar d Speci f i cat i on f or Coext r uded Pol y ( Vi nyl Chl or i de) ( PVC) Pl ast i c Pi pe wi t h a Cel l ul ar Cor e
ASTM F2389 ( 2023) St andar d Speci f i cat i on f or Pr essur e- r at ed Pol ypr opyl ene ( PP) Pi pi ng Syst ems
SECTI ON 22 00 00 Page 4
CAST I RON SOI L PI PE I NSTI TUTE ( CI SPI )
CI SPI 301 ( 2018) Hubl ess Cast I r on Soi l Pi pe and Fi t t i ngs f or Sani t ar y and St or m Dr ai n, Wast e, and Vent Pi pi ng Appl i cat i ons
CI SPI 310 ( 2012) Coupl i ng f or Use i n Connect i on wi t h Hubl ess Cast I r on Soi l Pi pe and Fi t t i ngs f or Sani t ar y and St or m Dr ai n, Wast e, and Vent Pi pi ng Appl i cat i ons
COPPER DEVELOPMENT ASSOCI ATI ON ( CDA)
CDA A4015 ( 2016; 14/ 17) Copper Tube Handbook
I NTERNATI ONAL ASSOCI ATI ON OF PLUMBI NG AND MECHANI CAL OFFI CI ALS
( I APMO)
I APMO PS 117 ( 2005b) Pr ess Type Or Pl ai n End Rub Gasket ed W/ Nai l CU & CU Al l oy Fi t t i ngs 4 I nst al l On CU Tubi ng
I NTERNATI ONAL CODE COUNCI L ( I CC)
I CC A117. 1 ( 2017) St andar d And Comment ar y Accessi bl e and Usabl e Bui l di ngs and Faci l i t i es
I CC I PC ( 2021) I nt er nat i onal Pl umbi ng Code
MANUFACTURERS STANDARDI ZATI ON SOCI ETY OF THE VALVE AND FI TTI NGS
I NDUSTRY ( MSS)
MSS SP- 25 ( 2018) St andar d Mar ki ng Syst em f or Val ves, Fi t t i ngs, Fl anges and Uni ons
MSS SP- 58 ( 2018) Pi pe Hanger s and Suppor t s - Mat er i al s, Desi gn and Manuf act ur e, Sel ect i on, Appl i cat i on, and I nst al l at i on
MSS SP- 67 ( 2022) But t er f l y Val ves
MSS SP- 70 ( 2011) Gr ay I r on Gat e Val ves, Fl anged and Thr eaded Ends
MSS SP- 71 ( 2018) Gr ay I r on Swi ng Check Val ves, Fl anged and Thr eaded Ends
MSS SP- 72 ( 2010a) Bal l Val ves wi t h Fl anged or But t - Wel di ng Ends f or Gener al Ser vi ce
MSS SP- 78 ( 2011) Cast I r on Pl ug Val ves, Fl anged and Thr eaded Ends
MSS SP- 80 ( 2019) Br onze Gat e, Gl obe, Angl e and Check Val ves
MSS SP- 85 ( 2011) Gr ay I r on Gl obe & Angl e Val ves Fl anged and Thr eaded Ends
SECTI ON 22 00 00 Page 5
MSS SP- 110 ( 2010) Bal l Val ves Thr eaded, Socket - Wel di ng, Sol der Joi nt , Gr ooved and Fl ar ed Ends
NACE I NTERNATI ONAL ( NACE)
NACE SP0169 ( 2013) Cont r ol of Ext er nal Cor r osi on on Under gr ound or Submer ged Met al l i c Pi pi ng Syst ems
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 90A ( 2024) St andar d f or t he I nst al l at i on of Ai r Condi t i oni ng and Vent i l at i ng Syst ems
NSF I NTERNATI ONAL ( NSF)
NSF/ ANSI 61 ( 2022) Dr i nki ng Wat er Syst em Component s - Heal t h Ef f ect s
PLASTI C PI PE AND FI TTI NGS ASSOCI ATI ON ( PPFA)
PPFA Fi r e Man ( 2016) Fi r est oppi ng: Pl ast i c Pi pe i n Fi r e Resi st i ve Const r uct i on
SOCI ETY OF AUTOMOTI VE ENGI NEERS I NTERNATI ONAL ( SAE)
SAE J1508 ( 2023) Hose Cl amp Speci f i cat i ons
U. S. ENVI RONMENTAL PROTECTI ON AGENCY ( EPA)
EPA SM 9223 ( 2004) Enzyme Subst r at e Col i f or m Test
U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)
40 CFR 141. 80 Nat i onal Pr i mar y Dr i nki ng Wat er Regul at i ons; Cont r ol of Lead and Copper ;
Gener al Requi r ement s
1. 2 SUBMI TTALS
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" or " S" c l assi f i cat i on. Submi t t al s not havi ng a " G" or " S" c l assi f i cat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval . Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:
SD- 02 Shop Dr awi ngs
Pl umbi ng Syst em; G
Det ai l dr awi ngs consi st i ng of schedul es, per f or mance char t s, i nst r uct i ons, di agr ams, and ot her i nf or mat i on t o i l l ust r at e t he r equi r ement s and oper at i ons of syst ems t hat ar e not cover ed by t he Pl umbi ng Code. Det ai l dr awi ngs f or t he compl et e pl umbi ng syst em i ncl udi ng pi pi ng l ayout s and l ocat i ons of connect i ons; di mensi ons f or r oughi ng- i n, f oundat i on, and suppor t poi nt s; schemat i c di agr ams and wi r i ng di agr ams or connect i on and i nt er connect i on di agr ams. Det ai l dr awi ngs shal l i ndi cat e c l ear ances r equi r ed f or mai nt enance and oper at i on. Wher e pi pi ng and equi pment ar e t o be
SECTI ON 22 00 00 Page 6 suppor t ed ot her t han as i ndi cat ed, det ai l s shal l i ncl ude l oadi ngs and pr oposed suppor t met hods. Mechani cal dr awi ng pl ans, el evat i ons, v i ews, and det ai l s, shal l be dr awn t o scal e.
SD- 03 Pr oduct Dat a
Recycl ed Cont ent f or St eel Pi pe; S
Recycl ed Cont ent f or Cast I r on Pi pe; S
Fi xt ur es
Li st of i nst al l ed f i x t ur es wi t h manuf act ur er , model , and f l ow r at e.
Pl umbi ng Syst em
Di agr ams, i nst r uct i ons, and ot her sheet s pr oposed f or post i ng.
Manuf act ur er ' s r ecommendat i ons f or t he i nst al l at i on of bel l and spi got and hubl ess j oi nt s f or cast i r on soi l pi pe.
SD- 06 Test Repor t s
Test s, Fl ushi ng and Di si nf ect i on
Test r epor t s i n bookl et f or m showi ng al l f i el d t est s per f or med t o adj ust each component and al l f i el d t est s per f or med t o pr ove compl i ance wi t h t he speci f i ed per f or mance cr i t er i a, compl et i on and t est i ng of t he i nst al l ed syst em. Each t est r epor t shal l i ndi cat e t he f i nal posi t i on of cont r ol s.
SD- 10 Oper at i on and Mai nt enance Dat a
Pl umbi ng Syst em; G
Submi t i n accor dance wi t h Sect i on 01 78 23 OPERATI ON AND
MAI NTENANCE DATA.
1. 3 STANDARD PRODUCTS
Speci f i ed mat er i al s and equi pment shal l be st andar d pr oduct s of a manuf act ur er r egul ar l y engaged i n t he manuf act ur e of such pr oduct s.
Speci f i ed equi pment shal l essent i al l y dupl i cat e equi pment t hat has per f or med sat i sf act or i l y at l east t wo year s pr i or t o bi d openi ng.
St andar d pr oduct s shal l have been i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s pr i or t o bi d openi ng. The 2- year use shal l i ncl ude appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze. The pr oduct shal l have been f or sal e on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 2 year per i od.
1. 3. 1 Al t er nat i ve Qual i f i cat i ons
Pr oduct s havi ng l ess t han a t wo- year f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er ' s f act or y or l abor at or y t est s, can be shown.
SECTI ON 22 00 00 Page 7
1. 3. 2 Ser vi ce Suppor t
The equi pment i t ems shal l be suppor t ed by ser vi ce or gani zat i ons. Submi t a cer t i f i ed l i s t of qual i f i ed per manent ser vi ce or gani zat i ons f or suppor t of t he equi pment whi ch i ncl udes t hei r addr esses and qual i f i cat i ons. These ser vi ce or gani zat i ons shal l be r easonabl y conveni ent t o t he equi pment i nst al l at i on and abl e t o r ender sat i sf act or y ser vi ce t o t he equi pment on a r egul ar and emer gency basi s dur i ng t he war r ant y per i od of t he cont r act .
1. 3. 3 Manuf act ur er ' s Namepl at e
Each i t em of equi pment shal l have a namepl at e bear i ng t he manuf act ur er ' s name, addr ess, model number , and ser i al number secur el y af f i xed i n a conspi cuous pl ace; t he namepl at e of t he di st r i but i ng agent wi l l not be accept abl e.
1. 3. 4 Modi f i cat i on of Ref er ences
I n each of t he publ i cat i ons r ef er r ed t o her ei n, consi der t he advi sor y pr ovi s i ons t o be mandat or y, as t hough t he wor d, " shal l " had been subst i t ut ed f or " shoul d" wher ever i t appear s. I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on" , or wor ds of s i mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer .
1. 3. 4. 1 Def i ni t i ons
For t he I nt er nat i onal Code Counci l ( I CC) Codes and t he Loui s i ana St at e Pl umbi ng Coder ef er enced i n t he cont r act document s, advi sor y pr ovi s i ons shal l be consi der ed mandat or y, t he wor d " shoul d" shal l be i nt er pr et ed as " shal l . " Ref er ence t o t he " code of f i c i al " shal l be i nt er pr et ed t o mean t he " Cont r act i ng Of f i cer . " Ref er ences t o t he " per mi t hol der " shal l be i nt er pr et ed t o mean t he " Cont r act or . "
1. 3. 4. 2 Admi ni st r at i ve I nt er pr et at i ons
For I CC Codes r ef er enced i n t he cont r act document s, t he pr ovi s i ons of Chapt er 1, " Admi ni st r at or , " do not appl y. These admi ni st r at i ve r equi r ement s ar e cover ed by t he appl i cabl e Feder al Acqui s i t i on Regul at i ons ( FAR) i ncl uded i n t hi s cont r act and by t he aut hor i t y gr ant ed t o t he Of f i cer i n Char ge of Const r uct i on t o admi ni st er t he const r uct i on of t hi s pr oj ect . Ref er ences i n t he I CC Codes t o sect i ons of Chapt er 1, shal l be appl i ed appr opr i at el y by t he Cont r act i ng Of f i cer as aut hor i zed by hi s admi ni st r at i ve cogni zance and t he FAR.
1. 4 DELI VERY, STORAGE, AND HANDLI NG
Handl e, st or e, and pr ot ect equi pment and mat er i al s t o pr event damage bef or e and dur i ng i nst al l at i on i n accor dance wi t h t he manuf act ur er ' s r ecommendat i ons, and as appr oved by t he Cont r act i ng Of f i cer . Repl ace damaged or def ect i ve i t ems.
1. 5 REGULATORY REQUI REMENTS
Unl ess ot her wi se r equi r ed her ei n, pl umbi ng wor k shal l be i n accor dance wi t h t he Loui s i ana St at e Pl umbi ng Code.
1. 6 PROJECT/ SI TE CONDI TI ONS
The Cont r act or shal l become f ami l i ar wi t h det ai l s of t he wor k, ver i f y
SECTI ON 22 00 00 Page 8 di mensi ons i n t he f i el d, and advi se t he Cont r act i ng Of f i cer of any di scr epancy bef or e per f or mi ng any wor k.
1. 7 I NSTRUCTI ON TO GOVERNMENT PERSONNEL
When speci f i ed i n ot her sect i ons, f ur ni sh t he ser vi ces of compet ent i nst r uct or s t o gi ve f ul l i nst r uct i on t o t he desi gnat ed Gover nment per sonnel i n t he adj ust ment , oper at i on, and mai nt enance, i ncl udi ng per t i nent saf et y r equi r ement s, of t he speci f i ed equi pment or syst em.
I nst r uct or s shal l be t hor oughl y f ami l i ar wi t h al l par t s of t he i nst al l at i on and shal l be t r ai ned i n oper at i ng t heor y as wel l as pr act i cal oper at i on and mai nt enance wor k.
I nst r uct i on shal l be gi ven dur i ng t he f i r st r egul ar wor k week af t er t he equi pment or syst em has been accept ed and t ur ned over t o t he Gover nment f or r egul ar oper at i on. The number of man- days ( 8 hour s per day) of i nst r uct i on f ur ni shed shal l be as speci f i ed i n t he i ndi v i dual sect i on.
When mor e t han 4 man- days of i nst r uct i on ar e speci f i ed, use appr oxi mat el y hal f of t he t i me f or c l assr oom i nst r uct i on. Use ot her t i me f or i nst r uct i on wi t h t he equi pment or syst em.
When si gni f i cant changes or modi f i cat i ons i n t he equi pment or syst em ar e made under t he t er ms of t he cont r act , pr ovi de addi t i onal i nst r uct i on t o acquai nt t he oper at i ng per sonnel wi t h t he changes or modi f i cat i ons.
1. 8 ACCESSI BI LI TY OF EQUI PMENT
I nst al l al l wor k so t hat par t s r equi r i ng per i odi c i nspect i on, oper at i on, mai nt enance, and r epai r ar e r eadi l y accessi bl e. I nst al l conceal ed val ves, expansi on j oi nt s, cont r ol s, damper s, and equi pment r equi r i ng access, i n l ocat i ons f r eel y accessi bl e t hr ough access door s.
PART 2 PRODUCTS
2. 1 MATERI ALS
2. 1. 1 Pi pe Joi nt Mat er i al s
Gr ooved pi pe and hubl ess cast - i r on soi l pi pe shal l not be used under gr ound. Sol der cont ai ni ng l ead shal l not be used wi t h copper pi pe.
Cast i r on soi l pi pe and f i t t i ngs shal l be mar ked wi t h t he col l ect i ve t r ademar k of t he Cast I r on Soi l I nst i t ut e. Joi nt s and gasket mat er i al s shal l conf or m t o t he f ol l owi ng:
a. Coupl i ng f or Cast - I r on Pi pe: f or hub and spi got t ype ASTM A74, AWWA C606. For hubl ess t ype: CI SPI 310
b. Coupl i ng f or St eel Pi pe: AWWA C606.
c. Fl ange Gasket s: Gasket s shal l be made of non- asbest os mat er i al i n accor dance wi t h ASME B16. 21. Gasket s shal l be f l at , 1/ 16 i nch t hi ck, and cont ai n Ar ami d f i ber s bonded wi t h St yr ene But adi ene Rubber ( SBR) or Ni t r o But adi ene Rubber ( NBR) . Gasket s shal l be t he f ul l f ace or sel f cent er i ng f l at r i ng t ype. Gasket s used f or hydr ocar bon ser vi ce shal l be bonded wi t h NBR.
d. Br azi ng Mat er i al : Br azi ng mat er i al shal l conf or m t o AWS A5. 8/ A5. 8M, BCuP- 5.
SECTI ON 22 00 00 Page 9
e. Br azi ng Fl ux: Fl ux shal l be i n past e or l i qui d f or m appr opr i at e f or use wi t h br azi ng mat er i al . Fl ux shal l be as f ol l ows: l ead- f r ee; have a 100 per cent f l ushabl e r esi due; cont ai n s l i ght l y aci di c r eagent s;
cont ai n pot assi um bor i des; and cont ai n f l uor i des.
f . Sol der Mat er i al : Sol der met al shal l conf or m t o ASTM B32.
g. Sol der Fl ux: Fl ux shal l be l i qui d f or m, non- cor r osi ve, and conf or m t o ASTM B813, St andar d Test 1.
h. PTFE Tape: PTFE Tape, f or use wi t h Thr eaded Met al or Pl ast i c Pi pe.
i . Rubber Gasket s f or Cast - I r on Soi l - Pi pe and Fi t t i ngs ( hub and spi got t ype and hubl ess t ype) : ASTM C564.
j . Rubber Gasket s f or Gr ooved Pi pe: ASTM D2000, maxi mum t emper at ur e 230 degr ees F.
j . Fl exi bl e El ast omer i c Seal s: ASTM D3139, ASTM D3212 or ASTM F477.
l . Bol t s and Nut s f or Gr ooved Pi pe Coupl i ngs: Heat - t r eat ed car bon st eel , ASTM A183.
m. Sol vent Cement f or Tr ansi t i on Joi nt s bet ween ABS and PVC Nonpr essur e Pi pi ng Component s: ASTM D3138.
n. Pl ast i c Sol vent Cement f or ABS Pl ast i c Pi pe: ASTM D2235.
o. Pl ast i c Sol vent Cement f or PVC Pl ast i c Pi pe: ASTM D2564 and ASTM D2855.
p. Pl ast i c Sol vent Cement f or CPVC Pl ast i c Pi pe: ASTM F493.
q. Fl anged f i t t i ngs i ncl udi ng, but not l i mi t ed t o, f l anges, bol t s, nut s and bol t pat t er ns shal l be i n accor dance wi t h ASME B16. 5 c l ass 150 and shal l have t he manuf act ur er ' s t r ademar k af f i xed i n accor dance wi t h MSS SP- 25. Fl ange mat er i al shal l conf or m t o ASTM A105/ A105M. Bl i nd f l ange mat er i al shal l conf or m t o ASTM A516/ A516M col d ser vi ce and ASTM A515/ A515M f or hot ser vi ce. Bol t s shal l be hi gh st r engt h or i nt er medi at e st r engt h wi t h mat er i al conf or mi ng t o ASTM A193/ A193M.
r . Pl ast i c Sol vent Cement f or St yr ene Rubber Pl ast i c Pi pe: ASTM D3122.
s. Pr ess f i t t i ngs f or Copper Pi pe and Tube: Copper pr ess f i t t i ngs shal l conf or m t o t he mat er i al and si z i ng r equi r ement s of ASME B16. 51 and per f or mance cr i t er i a of I APMO PS 117. Seal i ng el ement s f or copper pr ess f i t t i ngs shal l be EPDM, FKM or HNBR. Seal i ng el ement s shal l be f act or y i nst al l ed or an al t er nat i ve suppl i ed f i t t i ng manuf act ur er .
Seal i ng el ement shal l be sel ect ed based on manuf act ur er ' s appr oved appl i cat i on gui del i nes.
t . Copper t ubi ng shal l conf or m t o ASTM B88, Type K, L or M.
u. Heat - f usi on j oi nt s f or pol ypr opyl ene pi pi ng: ASTM F2389.
2. 1. 2 Mi scel l aneous Mat er i al s
Mi scel l aneous mat er i al s shal l conf or m t o t he f ol l owi ng:
SECTI ON 22 00 00 Page 10
a. Copper , Sheet and St r i p f or Bui l di ng Const r uct i on: ASTM B370.
b. Hose Cl amps: SAE J1508.
c. Suppor t s f or Of f - The- Fl oor Pl umbi ng Fi xt ur es: ASME A112. 6. 1M.
d. Met al l i c Cl eanout s: ASME A112. 36. 2M.
e. Coal - Tar Pr ot ect i ve Coat i ngs and Li ni ngs f or St eel Wat er Pi pel i nes:
AWWA C203.
f . Hypochl or i t es: AWWA B300.
g. Gauges - Pr essur e and Vacuum I ndi cat i ng Di al Type - El ast i c El ement :
ASME B40. 100.
h. Ther momet er s: ASTM E1. Mer cur y shal l not be used i n t her momet er s.
2. 1. 3 Pi pe I nsul at i on Mat er i al
I nsul at i on shal l be as speci f i ed i n Sect i on 23 07 00 THERMAL I NSULATI ON
FOR MECHANI CAL SYSTEMS.
2. 2 PI PE HANGERS, I NSERTS, AND SUPPORTS
Pi pe hanger s, i nser t s, and suppor t s shal l conf or m t o MSS SP- 58.
2. 3 VALVES
Val ves shal l be pr ovi ded on suppl i es t o equi pment and f i xt ur es. Val ves 2- 1/ 2 i nches and smal l er shal l be br onze wi t h t hr eaded bodi es f or pi pe and sol der - t ype connect i ons f or t ubi ng. Val ves 3 i nches and l ar ger shal l have f l anged i r on bodi es and br onze t r i m. Pr essur e r at i ngs shal l be based upon t he appl i cat i on. Gr ooved end val ves may be pr ovi ded i f t he manuf act ur er cer t i f i es t hat t he val ves meet t he per f or mance r equi r ement s of appl i cabl e MSS st andar d. Val ves shal l conf or m t o t he f ol l owi ng st andar ds:
Descr i pt i on St andar d
But t er f l y Val ves MSS SP- 67
Cast - I r on Gat e Val ves, Fl anged and Thr eaded Ends
MSS SP- 70
Cast - I r on Swi ng Check Val ves, Fl anged and Thr eaded Ends
MSS SP- 71
Bal l Val ves wi t h Fl anged But t - Wel di ng Ends f or Gener al Ser vi ce
MSS SP- 72
Bal l Val ves Thr eaded, Socket - Wel di ng, Sol der Joi nt , Gr ooved and Fl ar ed Ends
MSS SP- 110
Cast - I r on Pl ug Val ves, Fl anged and Thr eaded Ends
MSS SP- 78
SECTI ON 22 00 00 Page 11
Br onze Gat e, Gl obe, Angl e, and Check Val ves
MSS SP- 80
St eel Val ves, Socket Wel di ng and Thr eaded Ends
ASME B16. 34
Cast - I r on Gl obe and Angl e Val ves, Fl anged and Thr eaded Ends
MSS SP- 85
Backwat er Val ves ASME A112. 14. 1
Vacuum Rel i ef Val ves ANSI Z21. 22/ CSA 4. 4
Wat er Pr essur e Reduci ng Val ves ASSE 1003
Wat er Heat er Dr ai n Val ves ASME BPVC SEC I V, Par t HLW- 810:
Requi r ement s f or Pot abl e- Wat er Heat er s Bot t om Dr ai n Val ve
Tr ap Seal Pr i mer Val ves ASSE 1018
Temper at ur e and Pr essur e Rel i ef Val ves f or Hot Wat er Suppl y Syst ems
ANSI Z21. 22/ CSA 4. 4
Temper at ur e and Pr essur e Rel i ef Val ves f or Aut omat i cal l y Fi r ed Hot Wat er Boi l er s
ASME CSD- 1
Saf et y Code No. , Par t CW, Ar t i c l e 5
2. 4 FI XTURES
2. 4. 1 Gr eenhouse Si nks ( S- 1)
ASME A112. 19. 3/ CSA B45. 4 NSF 2, equal doubl e bowl s i nk. 70" x 25- 13/ 16" x 43- 3/ 4" , 16 gauge wi t h 18" l ef t and r i ght dr ai nboar ds and st ai nl ess st eel l egs. Pr ovi de separ at e 1. 5 i nch P- t r ap and dr ai n pi pi ng t o ver t i cal vent pi pi ng f r om each compar t ment .
2. 4. 2 Emer gency Eyewash and Shower
ANSI / I SEA Z358. 1, f l oor suppor t ed f r ee st andi ng uni t . Pr ovi de del uge shower head, st ay- open bal l val ve oper at ed by pul l r od and r i ng or t r i angul ar handl e. Pr ovi de eyewash and st ay- open bal l val ve oper at ed by f oot t r eadl e or push handl e. Pr ovi de a pr essur e- compensat ed t emper i ng val ve, wi t h l eavi ng wat er t emper at ur e set poi nt adj ust abl e t hr oughout t he r ange 60 t o 95 degr ees F.
SECTI ON 22 00 00 Page 12
2. 5 DRAI NS
2. 5. 1 Fl oor and Shower Dr ai ns
2. 5. 1. 1 Dr ai ns and Backwat er Val ves
Dr ai ns and backwat er val ves i nst al l ed i n connect i on wi t h wat er pr oof ed f l oor s or shower pans shal l be equi pped wi t h bol t ed- t ype devi ce t o secur el y c l amp f l ashi ng.
2. 5. 2 Fl oor Dr ai ns FD- 1
Fl oor dr ai ns shal l be pl ai n pat t er n wi t h pol i shed st ai nl ess st eel or hi gh st r engt h PVC per f or at ed or s l ot t ed gr at e wi t h sedi ment bucket and bot t om out l et . The dr ai n shal l be c i r cul ar or squar e wi t h a 12 i nch nomi nal over al l wi dt h or di amet er and 6 i nch nomi nal over al l dept h. Dr ai ns shal l be hi gh st r engt h PVC. Gr at e shal l be easi l y l i f t ed out f or c l eani ng.
Out l et shal l be sui t abl e f or connect i on t o dr ai n pi pe. Dr ai ns shal l conf or m t o ASME A112. 6. 3.
2. 5. 3 Tr ench Dr ai ns
Tr ench dr ai ns shal l be a 6 i nch wi de pr esl oped dr ai nage syst em wi t h 100 per cent pol ypr opyl ene i nt er l ocki ng channel s wi t h r adi used bot t om. Cat ch basi n wi t h t r ash basket f or easy r emoval of debr i s. 3/ 16" x 1/ 2" l ongi t udi nal st ai nl ess st eel s l ot bar gr at e.
2. 6 TRAPS
Unl ess ot her wi se speci f i ed, t r aps shal l be pl ast i c per ASTM F409 or copper - al l oy adj ust abl e t ube t ype wi t h s l i p j oi nt i nl et and swi vel . Tr aps shal l be wi t hout a c l eanout . Pr ovi de t r aps wi t h r emovabl e access panel s f or easy c l ean- out at s i nks and l avat or i es. Tubes shal l be copper al l oy wi t h wal l s not l ess t han 0. 032 i nch t hi ck wi t hi n commer ci al t ol er ances, except on t he out si de of bends wher e t he t hi ckness may be r educed sl i ght l y i n manuf act ur e by usual commer ci al met hods. I nl et s shal l have r ubber washer and copper al l oy nut s f or s l i p j oi nt s above t he di schar ge l evel .
Swi vel j oi nt s shal l be bel ow t he di schar ge l evel and shal l be of met al - t o- met al or met al - t o- pl ast i c t ype as r equi r ed f or t he appl i cat i on.
Nut s shal l have f l at s f or wr ench gr i p. Out l et s shal l have i nt er nal pi pe t hr ead, except t hat when r equi r ed f or t he appl i cat i on, t he out l et s shal l have socket s f or sol der - j oi nt connect i ons. The dept h of t he wat er seal shal l be not l ess t han 2 i nches. The i nt er i or di amet er shal l be not mor e t han 1/ 8 i nch over or under t he nomi nal s i ze, and i nt er i or sur f aces shal l be r easonabl y smoot h t hr oughout . A copper al l oy " P" t r ap assembl y consi st i ng of an adj ust abl e " P" t r ap and t hr eaded t r ap wal l ni ppl e wi t h cast br ass wal l f l ange shal l be pr ovi ded f or l avat or i es. The assembl y shal l be a st andar d manuf act ur ed uni t and may have a r ubber - gasket ed swi vel j oi nt .
2. 7 FLEXI BLE EXPANI ON JOI NTS
Fl exi bl e j oi nt s at t he l ocat i on wher e sani t ar y pi pi ng l eaves t he bui l di ng and subj ect t o soi l subsi dence shal l consi st of a PVC expansi on j oi nt desi gned f or use i n DWV syst ems and mol ded as an i nt egr al par t of a bal l and socket t ype f l exi bl e j oi nt , havi ng a mi ni mum per bal l def l ect i on of 15º .
SECTI ON 22 00 00 Page 13
2. 8 MI SCELLANEOUS PI PI NG I TEMS
2. 8. 1 Escut cheon Pl at es
Pr ovi de one pi ece or spl i t hi nge met al pl at es f or pi pi ng ent er i ng f l oor s, wal l s, and cei l i ngs i n exposed spaces. Pr ovi de chr omi um- pl at ed on copper al l oy pl at es or pol i shed st ai nl ess st eel f i ni sh i n f i ni shed spaces.
Pr ovi de pai nt f i ni sh on pl at es i n unf i ni shed spaces.
2. 8. 2 Pi pe Sl eeves
Pr ovi de wher e pi pi ng passes ent i r el y t hr ough wal l s, cei l i ngs, r oof s, and f l oor s. Sl eeves ar e not r equi r ed wher e suppl y dr ai n, wast e, and vent ( DWV) pi pi ng passes t hr ough concr et e f l oor s l abs l ocat ed on gr ade, except wher e penet r at i ng a membr ane wat er pr oof f l oor .
2. 8. 2. 1 Sl eeves i n Masonr y and Concr et e
Pr ovi de st eel pi pe s l eeves or schedul e 40 PVC pl ast i c pi pe sl eeves.
Sl eeves ar e not r equi r ed wher e dr ai n, wast e, and vent ( DWV) pi pi ng passes t hr ough concr et e f l oor s l abs l ocat ed on gr ade. Cor e dr i l l i ng of masonr y and concr et e may be pr ovi ded i n l i eu of pi pe s l eeves when cavi t i es i n t he cor e- dr i l l ed hol e ar e compl et el y gr out ed smoot h.
2. 8. 2. 2 Sl eeves Not i n Masonr y and Concr et e
Pr ovi de 26 gage gal vani zed st eel sheet or PVC pl ast i c pi pe sl eeves.
2. 8. 3 Pi pe Hanger s ( Suppor t s)
Pr ovi de MSS SP- 58 Type 1 wi t h adj ust abl e t ype st eel suppor t r ods, except as speci f i ed or i ndi cat ed ot her wi se. At t ach t o st eel j oi st s wi t h Type 19 or 23 cl amps and r et ai ni ng st r aps. At t ach t o St eel W or S beams wi t h Type 21, 28, 29, or 30 cl amps. At t ach t o st eel angl es and ver t i cal web st eel channel s wi t h Type 20 cl amp wi t h beam cl amp channel adapt er . At t ach t o hor i zont al web st eel channel and wood wi t h dr i l l ed hol e on cent er l i ne and doubl e nut and washer . At t ach t o concr et e wi t h Type 18 i nser t or dr i l l ed expansi on anchor . Pr ovi de Type 40 i nsul at i on pr ot ect i on shi el d f or i nsul at ed pi pi ng.
2. 8. 4 Namepl at es
Pr ovi de 0. 125 i nch t hi ck mel ami ne l ami nat ed pl ast i c namepl at es, bl ack mat t e f i ni sh wi t h whi t e cent er cor e, f or equi pment , gages, t her momet er s, and val ves; val ves i n suppl i es t o f aucet s wi l l not r equi r e namepl at es.
Accur at el y al i gn l et t er i ng and engr ave mi ni mum of 0. 25 i nch hi gh nor mal bl ock l et t er i ng i nt o t he whi t e cor e. Mi ni mum si ze of namepl at es shal l be
1. 0 by 2. 5 i nches. Key namepl at es t o a char t and schedul e f or each syst em. Fr ame char t s and schedul es under gl ass and pl ace wher e di r ect ed near each syst em. Fur ni sh t wo copi es of each char t and schedul e.
2. 8. 5 Label s
Pr ovi de l abel s f or sensor oper at or s at f l ush val ves and f aucet s. I ncl ude t he f ol l owi ng i nf or mat i on on each l abel :
a. I dent i f i cat i on of t he sensor and i t s oper at i on wi t h gr aphi c descr i pt i on.
SECTI ON 22 00 00 Page 14
b. Range of t he sensor .
c. Bat t er y r epl acement schedul e.
PART 3 EXECUTI ON
3. 1 GENERAL I NSTALLATI ON REQUI REMENTS
Pi pi ng l ocat ed i n ai r pl enums shal l conf or m t o NFPA 90A r equi r ement s.
Pi pi ng l ocat ed i n shaf t s t hat const i t ut e ai r duct s or t hat encl ose ai r duct s shal l be noncombust i bl e i n accor dance wi t h NFPA 90A. I nst al l at i on of pl ast i c pi pe wher e i n compl i ance wi t h NFPA may be i nst al l ed i n accor dance wi t h PPFA Fi r e Man. The pl umbi ng syst em shal l be i nst al l ed compl et e wi t h necessar y f i x t ur es, f i t t i ngs, t r aps, val ves, and accessor i es. Wat er and dr ai nage pi pi ng shal l be ext ended 5 f eet out si de t he bui l di ng, unl ess ot her wi se i ndi cat ed. A bal l val ve and dr ai n shal l be i nst al l ed on t he wat er ser vi ce l i ne i nsi de t he bui l di ng appr oxi mat el y 6 i nches above t he f l oor f r om poi nt of ent r y. Pi pi ng shal l be connect ed t o t he ext er i or ser vi ce l i nes or capped or pl ugged i f t he ext er i or ser vi ce i s not i n pl ace. Sewer and wat er pi pes shal l be l ai d i n separ at e t r enches, except when ot her wi se shown. Ext er i or under gr ound ut i l i t i es shal l be at l east 12 i nches bel ow t he f i ni sh gr ade or as i ndi cat ed on t he dr awi ngs.
I f t r enches ar e c l osed or t he pi pes ar e ot her wi se cover ed bef or e bei ng connect ed t o t he ser vi ce l i nes, t he l ocat i on of t he end of each pl umbi ng ut i l i t y shal l be mar ked wi t h a st ake or ot her accept abl e means. Val ves shal l be i nst al l ed wi t h cont r ol no l ower t han t he val ve body.
3. 1. 1 Wat er Pi pe, Fi t t i ngs, and Connect i ons
3. 1. 1. 1 Ut i l i t i es
The pi pi ng shal l be ext ended t o f i x t ur es, out l et s, and equi pment . The hot - wat er and col d- wat er pi pi ng syst em shal l be ar r anged and i nst al l ed t o per mi t dr ai ni ng. The suppl y l i ne t o each i t em of equi pment or f i x t ur e, except f aucet s, f l ush val ves, or ot her cont r ol val ves whi ch ar e suppl i ed wi t h i nt egr al st ops, shal l be equi pped wi t h a shut of f val ve t o enabl e i sol at i on of t he i t em f or r epai r and mai nt enance wi t hout i nt er f er i ng wi t h oper at i on of ot her equi pment or f i x t ur es. Suppl y pi pi ng t o f i x t ur es, f aucet s, hydr ant s, shower heads, and f l ushi ng devi ces shal l be anchor ed t o pr event movement .
3. 1. 1. 2 Cut t i ng and Repai r i ng
The wor k shal l be car ef ul l y l ai d out i n advance, and unnecessar y cut t i ng of const r uct i on shal l be avoi ded. Damage t o bui l di ng, pi pi ng, wi r i ng, or equi pment as a r esul t of cut t i ng shal l be r epai r ed by mechani cs ski l l ed i n t he t r ade i nvol ved.
3. 1. 1. 3 Pr ot ect i on of Fi xt ur es, Mat er i al s, and Equi pment
Pi pe openi ngs shal l be c l osed wi t h caps or pl ugs dur i ng i nst al l at i on.
Fi xt ur es and equi pment shal l be t i ght l y cover ed and pr ot ect ed agai nst di r t , wat er , chemi cal s, and mechani cal i nj ur y. Upon compl et i on of t he wor k, t he f i x t ur es, mat er i al s, and equi pment shal l be t hor oughl y c l eaned, adj ust ed, and oper at ed. Saf et y guar ds shal l be pr ovi ded f or exposed r ot at i ng equi pment .
SECTI ON 22 00 00 Page 15
3. 1. 1. 4 Mai ns, Br anches, and Runout s
Pi pi ng shal l be i nst al l ed as i ndi cat ed. Pi pe shal l be accur at el y cut and wor ked i nt o pl ace wi t hout spr i ngi ng or f or c i ng. St r uct ur al por t i ons of t he bui l di ng shal l not be weakened. Abovegr ound pi pi ng shal l r un par al l el wi t h t he l i nes of t he bui l di ng, unl ess ot her wi se i ndi cat ed. Br anch pi pes f r om ser vi ce l i nes may be t aken f r om t op, bot t om, or s i de of mai n, usi ng cr ossover f i t t i ngs r equi r ed by st r uct ur al or i nst al l at i on condi t i ons.
Suppl y pi pes, val ves, and f i t t i ngs shal l be kept a suf f i c i ent di st ance f r om ot her wor k and ot her ser vi ces t o per mi t not l ess t han 1/ 2 i nch bet ween f i ni shed cover i ng on t he di f f er ent ser vi ces. Bar e and i nsul at ed wat er l i nes shal l not bear di r ect l y agai nst bui l di ng st r uct ur al el ement s so as t o t r ansmi t sound t o t he st r uct ur e or t o pr event f l exi bl e movement of t he l i nes. Wat er pi pe shal l not be bur i ed i n or under f l oor s unl ess speci f i cal l y i ndi cat ed or appr oved. Changes i n pi pe si zes shal l be made wi t h r educi ng f i t t i ngs. Use of bushi ngs wi l l not be per mi t t ed except f or use i n s i t uat i ons i n whi ch st andar d f act or y f abr i cat ed component s ar e f ur ni shed t o accommodat e speci f i c accept ed i nst al l at i on pr act i ce. Change i n di r ect i on shal l be made wi t h f i t t i ngs, except t hat bendi ng of pi pe 4 i nches and smal l er wi l l be per mi t t ed, pr ovi ded a pi pe bender i s used and wi de sweep bends ar e f or med. The cent er - l i ne r adi us of bends shal l be not l ess t han si x di amet er s of t he pi pe. Bent pi pe showi ng ki nks, wr i nkl es, f l at t eni ng, or ot her mal f or mat i ons wi l l not be accept abl e.
3. 1. 1. 5 Pi pe Dr ai ns
Pi pe dr ai ns i ndi cat ed shal l consi st of 3/ 4 i nch hose bi bb wi t h r enewabl e seat and gat e val ve ahead of hose bi bb. At ot her l ow poi nt s, 3/ 4 i nch br ass pl ugs or caps shal l be pr ovi ded. Di sconnect i on of t he suppl y pi pi ng at t he f i x t ur e i s an accept abl e dr ai n.
3. 1. 1. 6 Expansi on and Cont r act i on of Pi pi ng
Al l owance shal l be made t hr oughout f or expansi on and cont r act i on of wat er pi pe. Each hot - wat er and hot - wat er c i r cul at i on r i ser shal l have expansi on l oops or ot her pr ovi s i ons such as of f set s and changes i n di r ect i on wher e i ndi cat ed and r equi r ed. Ri ser s shal l be secur el y anchor ed as r equi r ed or wher e i ndi cat ed t o f or ce expansi on t o l oops. Br anch connect i ons f r om r i ser s shal l be made wi t h ampl e swi ng or of f set t o avoi d undue st r ai n on f i t t i ngs or shor t pi pe l engt hs. Hor i zont al r uns of pi pe over 50 f eet i n l engt h shal l be anchor ed t o t he wal l or t he suppor t i ng const r uct i on about mi dway on t he r un t o f or ce expansi on, evenl y di v i ded, t owar d t he ends.
Suf f i c i ent f l exi bi l i t y shal l be pr ovi ded on br anch r unout s f r om mai ns and r i ser s t o pr ovi de f or expansi on and cont r act i on of pi pi ng. Fl exi bi l i t y shal l be pr ovi ded by i nst al l i ng one or mor e t ur ns i n t he l i ne so t hat pi pi ng wi l l spr i ng enough t o al l ow f or expansi on wi t hout st r ai ni ng. I f mechani cal gr ooved pi pe coupl i ng syst ems ar e pr ovi ded, t he devi at i on f r om desi gn r equi r ement s f or expansi on and cont r act i on may be al l owed pendi ng appr oval of Cont r act i ng Of f i cer .
3. 1. 1. 7 Thr ust Rest r ai nt
Pl ugs, caps, t ees, val ves and bends def l ect i ng 11. 25 degr ees or mor e, ei t her ver t i cal l y or hor i zont al l y, i n wat er l i nes 4 i nches i n di amet er or l ar ger shal l be pr ovi ded wi t h t hr ust bl ocks, wher e i ndi cat ed, t o pr event movement . Thr ust bl ocki ng shal l be concr et e of a mi x not l eaner t han: 1 cement , 2- 1/ 2 sand, 5 gr avel ; and havi ng a compr essi ve st r engt h of not l ess t han 2000 psi af t er 28 days. Bl ocki ng shal l be pl aced bet ween sol i d gr ound and t he f i t t i ng t o be anchor ed. Unl ess ot her wi se i ndi cat ed or
SECTI ON 22 00 00 Page 16 di r ect ed, t he base and t hr ust bear i ng s i des of t he t hr ust bl ock shal l be pour ed agai nst undi st ur bed ear t h. The si de of t he t hr ust bl ock not subj ect t o t hr ust shal l be pour ed agai nst f or ms. The ar ea of bear i ng wi l l be as shown. Bl ocki ng shal l be pl aced so t hat t he j oi nt s of t he f i t t i ng ar e accessi bl e f or r epai r . St eel r ods and cl amps, pr ot ect ed by gal vani z i ng or by coat i ng wi t h bi t umi nous pai nt , shal l be used t o anchor ver t i cal down bends i nt o gr avi t y t hr ust bl ocks.
3. 1. 2 Joi nt s
I nst al l at i on of pi pe and f i t t i ngs shal l be made i n accor dance wi t h t he manuf act ur er ' s r ecommendat i ons. Mi t er i ng of j oi nt s f or el bows and not chi ng of st r ai ght r uns of pi pe f or t ees wi l l not be per mi t t ed. Joi nt s shal l be made up wi t h f i t t i ngs of compat i bl e mat er i al and made f or t he speci f i c pur pose i nt ended.
3. 1. 2. 1 Thr eaded
Thr eaded j oi nt s shal l have Amer i can St andar d t aper pi pe t hr eads conf or mi ng t o ASME B1. 20. 1. Onl y mal e pi pe t hr eads shal l be coat ed wi t h gr aphi t e or wi t h an appr oved gr aphi t e compound, or wi t h an i ner t f i l l er and oi l , or shal l have a pol yt et r af l uor oet hyl ene t ape appl i ed.
3. 1. 2. 2 Mechani cal Coupl i ngs
Mechani cal coupl i ngs may be used i n conj unct i on wi t h gr ooved pi pe f or abovegr ound, f er r ous or non- f er r ous, domest i c hot and col d wat er syst ems, i n l i eu of uni ons, br azed, sol der ed, wel ded, f l anged, or t hr eaded j oi nt s.
Mechani cal coupl i ngs ar e per mi t t ed i n accessi bl e l ocat i ons i ncl udi ng behi nd access pl at es. Fl exi bl e gr ooved j oi nt s wi l l not be per mi t t ed, except as v i br at i on i sol at or s adj acent t o mechani cal equi pment . Ri gi d gr ooved j oi nt s shal l i ncor por at e an angl e bol t pad desi gn whi ch mai nt ai ns met al - t o- met al cont act wi t h equal amount of pad of f set of housi ngs upon i nst al l at i on t o ensur e posi t i ve r i gi d c l ampi ng of t he pi pe.
Desi gns whi ch can onl y c l amp on t he bot t om of t he gr oove or whi ch ut i l i ze gr i ppi ng t eet h or j aws, or whi ch use mi sal i gned housi ng bol t hol es, or whi ch r equi r e a t or que wr ench or t or que speci f i cat i ons wi l l not be per mi t t ed.
Gr ooved f i t t i ngs and coupl i ngs, and gr oovi ng t ool s shal l be pr ovi ded f r om t he same manuf act ur er . Segment al l y wel ded el bows shal l not be used.
Gr ooves shal l be pr epar ed i n accor dance wi t h t he coupl i ng manuf act ur er ' s l at est publ i shed st andar ds. Gr oovi ng shal l be per f or med by qual i f i ed gr oovi ng oper at or s havi ng demonst r at ed pr oper gr oovi ng pr ocedur es i n accor dance wi t h t he t ool manuf act ur er ' s r ecommendat i ons.
The Cont r act i ng Of f i cer shal l be not i f i ed 24 hour s i n advance of t est t o demonst r at e oper at or ' s capabi l i t y , and t he t est shal l be per f or med at t he wor k s i t e, i f pr act i cal , or at a s i t e agr eed upon. The oper at or shal l demonst r at e t he abi l i t y t o pr oper l y adj ust t he gr oovi ng t ool , gr oove t he pi pe, and t o ver i f y t he gr oove di mensi ons i n accor dance wi t h t he coupl i ng manuf act ur er ' s speci f i cat i ons.
3. 1. 2. 3 Uni ons and Fl anges
Uni ons, f l anges and mechani cal coupl i ngs shal l not be conceal ed i n wal l s, cei l i ngs, or par t i t i ons. Uni ons shal l be used on pi pe si zes 2- 1/ 2 i nches
SECTI ON 22 00 00 Page 17 and smal l er ; f l anges shal l be used on pi pe si zes 3 i nches and l ar ger .
3. 1. 2. 4 Gr ooved Mechani cal Joi nt s
Gr ooves shal l be pr epar ed accor di ng t o t he…