UPS_Power_Module_with_Battery_Technical_Specifications.docx

DOCX document 24 KB Posted

Attached to
Eaton Powerware 9315 100k UPS EX056ZBA01 Maintenance and Repair for Water Production
Solicitation number
26-P-00520
Issued by
Hillsborough County, Florida

About this file

This is a technical specifications document for preventive maintenance services related to UPS power systems for the State of Florida, specifically for an Eaton Powerware 9315 100K UPS unit (model EX056ZBA01) used in water production operations. The scope of work encompasses comprehensive maintenance and repair services for power conditioning equipment, including visual inspections, internal and external parameter testing, environmental assessments, battery cabinet evaluations, and monitoring parameter reviews. Services cover UPS power modules, DC systems, PDUs, and flywheel equipment, with detailed procedures for inspecting printed circuit boards, power connections, capacitors, subassemblies, and all associated components. The preventive maintenance program includes firmware updates, Field Service Bulletin evaluations, battery testing, charger current verification, generator interface verification where applicable, and air filter replacement as necessary.

The preventive maintenance scope requires technicians to deliver verbal reports to the customer before departing the site, with comprehensive written reports detailing inspection results and specific recommendations for remedial actions, upgrades, and spare parts requirements to be submitted within five business days of each service visit. For sealed battery systems, maintenance includes individual cell voltage measurements, charger output monitoring, AC ripple current and voltage assessment, connection resistance testing, internal ohmic value verification, and ambient temperature monitoring. Parts required under full service agreements with parts coverage are provided at no charge, while parts outside such coverage are billable to the customer. The document does not specify contract term, renewal options, pricing structure, response deadlines, or award dates.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UPS Power Module, DC, PDU, Flywheel Preventive Maintenance Scope of Work Note the applicable features vary by type of equipment being contracted and additional scopes of work may be required.

Visual Inspection

1. Inspect all printed circuit board connections for cleanliness, swab contacts if necessary.

2. Inspect all power connections for signs of overheating

3. Inspect all subassemblies, bridges and legs for signs of component defects or stress

4. Inspect all DC capacitors for signs of leakage

5. Inspect all AC capacitors for signs of leakage

6. Inspect and inventory all customer-owned spare parts 7. Inspect for, and perform as required, any open engineering changes

Internal Parameters

1. DC Ground Detection Offset (if applicable)

2. Inverter leg current average balance (if applicable)

3. Output filter current average phase balance

4. Rectifier bridge current average leg balance

5. AC Protection settings are checked

6. DC Protection settings are checked

7. Input and Output Frequency and Voltage Bandwidth settings are checked

8. Verify DC filter capacitance

9. Verify AC tank and trap filter capacitance

10. Power Supply voltages and waveforms

11. Update firmware as necessary

12. Evaluate Field Service Bulletins (FSBs) for potential updates (parts if required are included at no charge under service agreements with full parts coverage, otherwise billable)

External Parameters

1. System Input Voltages (all phases)

2. System Input Currents (all phases)

3. DC Charging Voltages (float and equalize), record settings, adjust to nominal

4. Rectifier phase on and walk up

5. Inverter phase on and walk up

6. Adjust all panel meters to measured values

7. System Bypass Voltages (all phases)

8. Manual and UV Transfer Testing, verify uninterrupted transfer waveform (if applicable)

9. Outage simulation, and battery capability testing, and verify charger current limit

10. Generator operation and interface verification (if applicable)

Environmental Parameters

1. UPS area ambient temperature and condition of ventilating equipment

2. General Cleanliness of UPS Power Module

3. General Cleanliness of UPS area

4. Replace air filters as applicable and necessary (parts if required are included at no charge under service agreements with full parts coverage, otherwise billable)

5. Clean outside of UPS including control panel/CRT screen

6. Flywheel only: Drain oil and change oil and filters if required.

Battery Cabinet Checks

1. General appearance of Battery System (all types)

2. General cleanliness of Battery System area (all types)

3. Inspect cells for physical abnormalities

4. Inspect all DC connections for abnormalities

5. Battery System area ambient temperature and condition of ventilating equipment

Monitoring Parameters

1. Alarm archive review and printing

2. Alarm lamp test-local and remote (if applicable)

3. Replace all open monitor bulbs

4. Review Battery Test in history (if applicable)

Following the Preventive Maintenance inspection, a written report will be provided detailing the results of the inspection, and making specific recommendations toward future remedial action, upgrades, or sparing.

Sealed Battery System Preventive Maintenance Scope of Work Battery Maintenance of Battery Equipment includes, and is expressly limited to, those tasks set forth below. Due to the size and type of battery, testing and work procedures vary between battery jars above and below 100 watts per battery; work procedures may vary by UPS and battery type and may be limited by safety requirements Performed During Each Visit:

Visually inspect conditions and appearance of the following:

1. Connection terminals inter cell/battery connectors, cables and associated hardware

2. Cell/battery covers, containers, and post seals

3. Battery racks or cabinets and associated components and hardware for structural integrity

4. Inspect cleanliness / corrosion of batteries, cabinet, rack and area

5. Battery monitoring equipment (if present)

6. Cell/battery jar or cover, noting any excessive distortion

Measure and Record the following:

1. Individual cell/battery float voltages or overall float voltage

2. Charger output current and voltage

3. AC ripple current and voltage imposed on the battery

4. Internal ohmic values of each cell/battery or perform a continuity test of each cell/battery

5. Connection Resistance of 100% of the inter cell/battery connection

6. Ambient temperature and ventilation status

7. Negative terminal temperature of all cells/batteries

Perform cleaning of all accessible surfaces as required Reporting Each Preventive Maintenance Visit:

1. The technician(s) will issue the customer a verbal report summarizing the condition of the battery and identifying any critical issues before leaving the customer’s site.

2. A detailed report containing all readings and observations will be sent to the customer within five business days.