Upgrade EMCS Controls Multi Facilities Maxwell AFB - Draft Drawings.pdf
PDF 3 MB Posted
- Attached to
- INTENT TO SOLE SOURCE - PNQS 22-4015, UPGRADE EMCS CONTROLS, MULTIPLE BUILDINGS, MAXWELL AFB
- Solicitation number
- F2X3CE4185A003
About this file
This document appears to be a set of draft drawings for an upgrade to the Energy Management Control System (EMCS) controls at multiple facilities on Maxwell Air Force Base. The drawings provide general control and electrical notes for the upgrade, including details on control cabling, conduit requirements, and electrical installation specifications. A related federal contract opportunity is also referenced, which consists of furnishing all labor, equipment, and materials to upgrade the EMCS controls across multiple buildings at Maxwell AFB per the drawings and contract requirements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
� 8
.... "" u i I u � -t') :::, i1: ,n
� ij I" I g � gj 6 � 0 z g 1 6 � g 1 � C l 1
A I B I
GENERAL CONTROL NOTES
1. NEW BAS/DDC CONTROLS ARE AN EXTENSION OF THE EXISTING SCHNEIDER ELICTRIC SERIES.
C
2. CONTROL CABLE INSIDE MECHANICAL ROOMS TO BE INSTALLED IN CONDUIT (EXCEPT FOR FINAL ACTUATOR AND DEVICE CONNECTIONS). EXISTING CONDUIT CAN BE REUSED. WHERE NEW CONDUIT IS USED, PROVIDE EMT-TYPE
WITH APPROPRIATE JUNCTION BOXES.
3. CONTROL CABLE EXTERIOR TO BUILDING TO BE INSTALLED IN LIQUID TIGHT FLEXIBLE CONDUIT OR GRC-TYPE
CONDUIT.
4. PROVIDE APPROPRIATE NEMA RATED JUNCTION BOXES. PROVIDE ALL CONTROL WIRING, LOW VOLTAGE OR 120-VOLT, REQUIRED FOR A COMPLETE AND OPERABLE SYSTEM.
I D I E F I
GENERAL ELECTRICAL NOTES:
1. THE SERVICE VOLTAGE TO THE FACILITY IS EXISTING.
Q I H I
2. INSTALLATION SHALL COMPLY WITH THE NATIONAL ELECTRICAL CODE, STATE AND LOCAL CODES, AND t.lANUFACTURERS RECOMMENDATIONS.
3. MAINTAAIN ALL CLEARANCES FOR ELECTRICAL EQUIPMENT PER THE NEC.
4. ALL CONDUIT SIZE SHALL BE A MINUMUM )" UNLESS NOTED OTHERWISE IN THE DRAWINGS OR SPECIFICATIONS.
5. ALL EMPTY WALL MOUNTED JUNCTION BOXES SHALL BE PROVIDE WITH A WALL BLANK AND ALL EMPTY RACEWAYS SHALL BE PROVIDED
WITH A PULL WIRES.
6. PROVIDE A CONDUIT EXPANSION JOINTS WITH BONDING JUMPER IN ALL CONDUITS CROSSING AN EXPANSION JOINT.
7. ALL FLEXIBLE CONDUITS ON THE EXTERIOR, IN WET CONDITIONS OR ANY MECHANICAL ROOM SHALL BE LIQUID TIGHT WITH SUITABLE
FITTINGS.
8. PLANNED INTERRUPTIONS OF UTILITY SERVICE TO ANY EXISTING FACILITY OR AREAS WITHIN THE FACILITY AFFECTED BY THIS CONTRACT, SHALL BE CAREFULLY PLANNED AND COORDINATED IN ADVANCE OF THE REQUESTED INTERRUPTION. THE CONTRACTOR SHALL NOT INTERRUPT SERVICES UNTIL SPECIFIED APPROVAL HAS BEEN GRANTED. THE REQUEST SHALL INDICATE SERVICES AND AREAS TO BE AFFECTED, DATE AND TIME OF INTERRUPTION AND DURATION OF OUTAGE. REQUEST FOR INTERRUPTION OF SERVICE WILL NOT BE APPROVED UNTIL ALL EQUIPMENT AND MATERIAL REQUIRED FOR THE COMPLETION OF THAT PARTICULAR PHASE OF WORK ARE ON THE JOB SITE.
CONTRACTOR IS RESPONSIBLE FOR ALL OVERTIME, HOLIDAY, AND WEEKEND PAY TO THEIR Et.lPLOYEES TO DO THIS WORK DURING SCHEDULED NON-NORt.lAL WORK HOURS.
9. BUILDING OWNER MUST RECEIVE RECORD DRAWINGS AND MANUALS THAT PROVIDE INSTRUCTIONS ABOUT THE OPERATION AND t.lAINTENANE
OF THE BUILDING'S ELECTRICAL DISTRIBUTION SYSTEM.
10. HVAC EQUIPMENT POWER WIRING SHALL BE FURNISHED AND INSTALLED BY THIS CONTRACTOR. CONTROL EQUIPMENT AND CONTROL WIRING SHALL BE FURNISHED UNDER DIVISION 23 UNLESS OTHERWISE NOTED. PROVIDE i" CONDUITS WITH PULL WIRE BETWEEN INSIDE AND OUTSIDE UNITS AND/OR MECHANICAL CONTROL PANEL AS APPLICABLE. COORDINATE WITH THE HVAC CONTROLS CONTRACTOR FOR EXACT
LOCATIONS OF ALL EQUIPMENT.
11. ALL JUNCTION BOX COVERS ABOVE THE CEILING SHALL BE CLEARLY t.lARKED WITH WHICH CIRCUITS OR ELECTRICAL SYSTEM THEY CONTAIN.
LAN
SEE PANEL BOX
DETAILS
B
I
_J�\r--4-f/ . /
I
0 0
0 EXISTING CONTROLERS
® LONBUS
© SCHNEIDER JACE 8000 IN PANEL BOX
BAS ARCHITECTURE
I I
L_ __ __y/
Sheet Reference Number:
M-4 i
5 � IIEETS��
LJ L_ A"!__ 1 __.e..__ _1_1 ____,.c..__ _l_l __.D..__ _,_I __.E--__ _,__ _:F _,_l ______cQ=---- _,_l -----'H _,_I I ____,
File details come from the government source that posted it. Updated .