Updated Full Set Drawings 5-29-26.pdf

PDF 1 MB Posted

Attached to
Department of Juvenile Justice- 300 KW Standby Generator Replacement
Solicitation number
IFB-122468
Issued by
Chesterfield County, Virginia

About this file

This file consists of updated full set construction drawings for the Department of Juvenile Justice in Richmond, Virginia, specifically for the Bon Air Juvenile Correctional Center Standby Generator Replacement project. The project involves the replacement of an existing 300 KW generator with a new 230 KW Kohler diesel generator system serving Cottages A-3, A-4, and B. The scope of work includes demolition of the existing generator, three automatic transfer switches (ATS), and associated electrical infrastructure, along with installation of new equipment on an expanded concrete pad. New work encompasses furnishing and installing the 230 KW generator with an oversized alternator, new ATS units for each cottage, an 800-ampere generator tap box for load bank testing, a two-section generator switchboard, extension of electrical feeders and control conductors, installation of a remote annunciation system with wireless capability, emergency stop switches, chain link fencing with a double swing gate, and associated signage. The project location is 1900 Chatsworth Avenue, Chesapeake, Virginia, and is designated as DEB Project No. 777-B3777-005.

The electrical system design is based on 208/120-volt, three-phase, four-wire service for all three cottages, with utility power as the primary source and the generator as optional standby power. The drawings include detailed power riser diagrams, electrical site plans, elevation views of service racks and ATS installations, and specifications for grounding systems, conduit sizing, and equipment placement. All work must comply with the 2018 International Fire Code, Virginia Construction Code, Virginia Electrical Code, NFPA 241-2013, and National Electrical Code 702 for optional standby systems. The contractor is responsible for securing all necessary permits from the fire marshal, coordinating with Virginia 811 for subsurface utility identification at least 72 hours prior to excavation, and maintaining temporary power during construction to minimize facility disruption. The drawings specify that the contractor must remove and dispose of the existing generator with the owner retaining first right of refusal on all demolished materials, preserve and reuse the existing diesel fuel after filtering and cleaning, and leave the new generator fuel tank full upon completion of testing.

View the file

Other files

File Type Posted
Map- Bon Air JCC.jpg JPG image
300KW Specifications 777-B3777-005.pdf PDF
IFB 300KW Generator Replacement.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

P

LO

T D

A

TE

D A

TE

C O

N

TR

A C

T N

O

SHEET

IDENTIFICATION

SHEET OF

D E

P A

R

TM

E N

T O

F

R

IC

H M

O N

D , V

IR

G

IN

IA

JU

V

E N

IL

E

J U

S

TI

C E

B O

N A

IR

J

U V

E N

IL

E

C O

R R

E C

TI

O

N A

L C

E N

TE

R

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P

LA

C E

M E

N T

A -3

, A -4

, B , C

O

TT

A G

E

K

W

N O

TE

D

FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

T- 1.

dw g

P

LO

TT

E

D : M on da y, M ay

8, M A

Y

9, FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

T- 1.

dw g

P

LO

TT

E

D : M on da y, M ay

8, A N

S I D

Chesapeake, VA. 23320 Telephone: 757.348.9588

SCG

Say Consulting Group

R

IC

H M

O N

D , V

IR

G

IN

IA

D E

B P

R O

JE

C

T N

O

7-

B

-0

5/29/26

C H

A

TS

W O

R

TH

A V

E N

U E

JC

S

JC

S

D

LS

JC

S

TI

TL

E S

H E

E T

T101

INDEX OF DRAWINGS

SHEET NO. SHEET TITLE

TITLE SHEETT101

DATE: MAY 29, 2026

RICHMOND, VIRGINIA

DEB PROJECT NO: 777-B3777-005

LOCATION MAP

Chesapeake, VA. 23320 Telephone: 757.348.9588

SCG

Say Consulting Group

POINTS OF CONTACT:

REFERENCED CODES

R. JENNINGS JAMES - DJJ PROGRAM MANAGER, VCCA

JOHN WALDROP - DJJ MAINTENANCE SUPERVISOR

ES101

NOTES, ABBREVIATIONS AND LEGENDE001

ELECTRICAL SITE PLAN EXISTING

1900 CHATSWORTH AVENUE

E101 POWER RISER DIAGRAM - DEMOLITION

E102 POWER RISER ELEVATION DRAWING - NEW WORK

E104 ELECTRICAL PLANS NEW WORK

E105 COTTAGE A-3 AND A-4 ATS SERVICE RACK ELEVATION - DEMOLITION AND NEW WORK

E106 COTTAGE B ATS SERVICE RACK ELEVATION - DEMOLITION AND NEW WORK

E107 DETAILS

E108 DETAILS

LEAD MATERIALS

DISCLOSURE STATEMENT

ASBESTOS

DISCLOSURE STATEMENT

AN ASBESTOS INSPECTION WAS NOT PERFORMED BECAUSE ALL PORTIONS OF THE EXISTING

BUILDING THAT MAY BE AFFECTED BY THE WORK WERE ORIGINALLY CONSTRUCTED AFTER

JANUARY 1, 1985.

AN INSPECTION TO IDENTIFY LEAD CONTAINING OR COATED BUILDING COMPONENTS HAS NOT

BEEN CONDUCTED BECAUSE THE BUILDING WAS CONSTRUCTED AFTER JANUARY 1, 1985, AND

THE OWNER HAS NO KNOWLEDGE OF LEAD CONTAINING OR COATED BUILDING COMPONENTS IN

THE BUILDING. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COMPLY WITH ALL VIRGINIA

OCCUPATIONAL SAFETY AND HEALTH (VOSH) REGULATIONS AS THEY PERTAIN TO EMPLOYEE

EXPOSURES TO LEAD. ALL LEAD AND LEAD-COATED BUILDING COMPONENTS SHALL BE

RECYCLED TO THE EXTENT POSSIBLE.

DISCLOSURE STATEMENT

FOR ALL PROJECTS THE CONTRACTOR IS PROHIBITED FROM USING ANY ASBESTOS CONTAINING

MATERIALS. NO ASBESTOS CONTAINING MATERIAL SHALL BE USED ON THE PROJECT.

DELEGATED DESIGN LIST

BY SPECIFICATION

NO DELEGATED DESIGN FOR THIS PROJECT.

DIG NOTICE PER CPSM

CONTACT VIRGINIA 811 AT 811, 1-800-552-7001, OR HTTPS.//WWW.VA811.COM NO LESS THAN 72

HOURS PRIOR TO EXCAVATION AND DO NOT DISTURB SOIL UNTIL DIG TICKET HAS BEEN

PROCESSED.

E103 ELECTRICAL PLANS DEMOLITION

JC

S

JC

S

D

LS

JC

S

A N

D L

E G

E N

D N

O

TE

S , A

B B

R E

V

IA

TI

O

N S

E001

NEW TO EXISTING CONNECTION

INDICATES EXISTING ITEMS TO BE

REMOVED, UNLESS OTHERWISE NOTED

POINT OF DISCONNECTION

1 DEMOLITION NOTE

LEGEND AND ABBREVIATIONS

(E) EXISTING

AFF ABOVE FINISHED FLOOR

1 NEW WORK NOTE

J JUNCTION BOX

E EQUIPMENT CONNECTION

PANELBOARD

E

E

EXISTING CONDUIT RUN

NEW CONDUIT RUN

GENERAL NOTES

MINIMUM RACEWAY SIZE SHALL BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO

LIMIT RACEWAY FILL RATIO TO LESS THAN 40% FULL.

CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER TRADES THROUGH

THE GENERAL CONTRACTOR AND SHALL BE RESPONSIBLE FOR SECURING SPACE

REQUIREMENTS FOR ELECTRICAL EQUIPMENT.

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING CATALOG NUMBERS ON THESE

DRAWINGS TO MATCH WITH MATERIAL DESCRIPTIONS INDICATED.

ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED GROUND

CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO

EACH DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND

BUS. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT.

MULTIPLE BRANCH CIRCUITS IN ONE RACEWAY REQUIRE ONLY ONE GROUND

CONDUCTOR.

VERIFY EXACT LOCATIONS OF BEFORE ROUGHING-IN.

EXISTING ELECTRICAL WORK (NOT SHOWN) SHALL REMAIN, UNLESS INDICATED

OTHERWISE. SHOULD ANY EXISTING ELECTRICAL POWER, LIGHTING OR AUXILIARY

CIRCUIT, FEEDER OR EQUIPMENT BE SEVERED, DISCONNECTED OR DELETED IN THE

PROCESS OF CONSTRUCTION OR REMODELING WHICH IS DONE AS A RESULT OF

CONTRACT PLANS AND SPECIFICATIONS, AND UNLESS SPECIFICALLY DESIGNATED BY

THE DRAWINGS TO BE DELETED, THEN SAID CIRCUIT OR FEEDER SHALL BE RESTORED

TO WORKING CONDITION. THE RESTORATION SHALL INCLUDE RE-ROUTING,

RELOCATION, RECONNECTION OR REPLACEMENT AS MAY BE REQUIRED BY THE NEW

WORK. ANY SUCH WORK REQUIRED SHALL BE INCLUDED IN THE CONTRACT AND NO

EXTRA COMPENSATION WILL BE GRANTED.

NEW WORK SHALL BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER, SIMILAR

ITEMS OF NEW WORK SHALL BE CHECKED AGAINST EXISTING WORK FOR TYPE

MOUNTING, MOUNTING HEIGHTS, ETC. ITEMS SHOWN IN NEW WORK AT VARIANCE FROM

THE EXISTING SHALL BE REFERRED TO THE ENGINEER FOR DECISION BEFORE

ROUGH-IN.

PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE

ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL,

MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL

APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED

WITHIN THESE DRAWINGS AND SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.

DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE

ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT

EQUIPMENT FROM ALL CONNECTIONS, REMOVE FROM THE OWNER'S SITE, AND DISPOSE

OF IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES.

OWNER HAS FIRST RIGHT OF REFUSAL ON DEMOLISHED MATERIAL. SHOULD OWNER

NOT EXERCISE HIS RIGHT, THE CONTRACTOR MUST REMOVE COMPLETE OFF SITE ALL

DEMOLISHED MATERIAL.

CONTRACTOR TO PROVIDE A 3RD PARTY SUB SURFACE INVESTIGATION OF AREA.

PROVIDE MARKING OF ALL SUB SURFACE UTILITIES AND DELIVER REPORT TO OWNER.

CONTRACTOR IS REQUIRED TO ADHERE TO THE PROVISIONS OF THE 2018

INTERNATIONAL FIRE CODE (CHAPTER 33), VCC SECTION 3302.3, AND VEBC SECTION

1201.5 AND 1210.7.

CONTRACTOR SHALL COMPLY WITH NFPA 241-2013 FOR CONDITIONS NOT COVERED BY

THE IFC SECTION 3301.1.

CONTRACTOR SHALL ADHERE TO THE VEBC AND THE INTERNATIONAL FIR CODE (IFC)

AND STRICTLY OBSERVE SAFE GUARDS AGAINST ALL FIRE HAZARDS ATTENDED UPON

CONSTRUCTION OPERATIONS. VEBC SECTION 1204.2 AND SECTION 3309.2.

FOR FIRE HAZARD DURING DEMOLITION AND CONSTRUCTION THE CONTRACTOR SHALL

STRICTLY OBSERVE THE PROVISIONS OF THE 2018 INTERNATIONAL FIRE CODE

(CHAPTER 33).

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

EQUIPMENT

M MOTOR CONNECTION

EPO

EMERGENCY POWER OFF

11.

COMBINATION ACROSS THE

LINE MOTOR STARTER

SWITCH SINGLE POLE 120V

DISCONNECT SWITCH

S O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

P

LO

T D

A

TE

D A

TE

C O

N

TR

A C

T N

O

SHEET

IDENTIFICATION

SHEET OF

D E

P A

R

TM

E N

T O

F

R

IC

H M

O N

D , V

IR

G

IN

IA

JU

V

E N

IL

E

J U

S

TI

C E

B O

N A

IR

J

U V

E N

IL

E

C O

R R

E C

TI

O

N A

L C

E N

TE

R

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P

LA

C E

M E

N T

A -3

, A -4

, B , C

O

TT

A G

E

K

W

N O

TE

D

FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E -0

.d w g

P

LO

TT

E

D : S at ur da y, M ay

6, M A

Y

9, FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E -0

.d w g

P

LO

TT

E

D : S at ur da y, M ay

6, A N

S I D

Chesapeake, VA. 23320 Telephone: 757.348.9588

SCG

Say Consulting Group

R

IC

H M

O N

D , V

IR

G

IN

IA

D E

B P

R O

JE

C

T N

O

7-

B

-0

5/29/26

C H

A

TS

W O

R

TH

A V

E N

U E

SIGNAGE CHART

MARK MOUNTING LOCATION

COTTAGE B

ELECTRICAL

ROOM DOOR

SIGNAGE COLORS

RED FACED WITH

WHITE LETTERS

SIGNAGE TEXT

4 COTTAGE B

SERVICE

DISCONNECT

RED FACED WITH

WHITE LETTERS

COTTAGE B SERVICE DISCONNECT

5 COTTAGE A-3

SERVICE

DISCONNECT

RED FACED WITH

WHITE LETTERS

COTTAGE A-3 SERVICE DISCONNECT

6 COTTAGE A-4

SERVICE

DISCONNECT

RED FACED WITH

WHITE LETTERS

COTTAGE A-4 SERVICE DISCONNECT

7 COTTAGE B

AUTOMATIC

TRANSFER

SWITCH

RED FACED WITH

WHITE LETTERS

COTTAGE B AUTOMATIC TRANSFER SWITCH

8 RED FACED WITH

WHITE LETTERS

9 RED FACED WITH

WHITE LETTERS

10 GENERATOR

SWITCHBOARD

RED FACED WITH

WHITE LETTERS

GENERATOR SWITCHBOARD

11 DOCKING STATION RED FACED WITH

WHITE LETTERS

DOCKING STATION

TEMPORARY GENERATOR CONNECTION POINT

12 GENERATOR TAP

BOX

RED FACED WITH

WHITE LETTERS

13 230 KW GENERATOR

BREAKER DOOR

RED FACED WITH

WHITE LETTERS

COTTAGE A-3

AUTOMATIC

TRANSFER

SWITCH

COTTAGE A-4

AUTOMATIC

TRANSFER

SWITCH

14 230 KW GENERATOR

BREAKER DOOR

RED FACED WITH

WHITE LETTERS

COTTAGE A-3 AUTOMATIC TRANSFER SWITCH

COTTAGE A-4 AUTOMATIC TRANSFER SWITCH

GENERATOR TAP BOX

LOAD BANK CONNECTION POINT

800 AMP BREAKER BEHIND THIS DOOR SERVES AS

DISCONNECT FOR EMERGENCY SWITCHBOARD

800 AMP BREAKER BEHIND THIS DOOR SERVES

AS DISCONNECT FOR GENERATOR TAP BOX

2 COTTAGE A-3

ELECTRICAL

ROOM DOOR

RED FACED WITH

WHITE LETTERS

3 COTTAGE A-4

ELECTRICAL

ROOM DOOR

RED FACED WITH

WHITE LETTERS

OMNI DIRECTIONAL ANTENNA

TRANSMITTER ANTENNA

GROUNDING

DIRECTIONAL TRANSMITTER

ANTENNA

12.

13.

14.

COTTAGE A-4 ELECTRICAL SERVICE IS A 208/120 VOLT, 3 PHASE SERVICE

SERVED BY A SINGLE FEEDER WITH MULTIPLE POWER SOURCES. POWER

SOURCE 1 IS UTILITY POWER AND SOURCE 2 IS BY GENERATOR USED AS

OPTIONAL STANDBY POWER. SERVICE DISCONNECT AND TRANSFER SWITCH IS

LOCATED AT GENERATOR YARD IN THE FIELD BEHIND COTTAGE A-3. UTILITY

DISCONNECT IS A FUSED 3 POLE, 400 AMP SWITCH. GENERATOR SOURCE

DISCONNECT LOCATED IN THE GENERATOR SWITCHBOARD ADJACENT TO THE

GENERATOR.

WARNING

COTTAGE A-3 ELECTRICAL SERVICE IS A 208/120 VOLT, 3 PHASE SERVICE

SERVED BY A SINGLE FEEDER WITH MULTIPLE POWER SOURCES. POWER

SOURCE 1 IS UTILITY POWER AND SOURCE 2 IS BY GENERATOR USED AS

OPTIONAL STANDBY POWER. SERVICE DISCONNECT AND TRANSFER SWITCH IS

LOCATED AT GENERATOR YARD IN THE FIELD BEHIND COTTAGE A-3. UTILITY

DISCONNECT IS A FUSED 3 POLE, 400 AMP SWITCH. GENERATOR SOURCE

DISCONNECT LOCATED IN THE GENERATOR SWITCHBOARD ADJACENT TO THE

GENERATOR.

WARNING

COTTAGE B ELECTRICAL SERVICE IS A 208/120 VOLT, 3 PHASE SERVICE SERVED

BY A SINGLE FEEDER WITH MULTIPLE POWER SOURCES. POWER SOURCE 1 IS

UTILITY POWER AND SOURCE 2 IS BY GENERATOR USED AS OPTIONAL

STANDBY POWER. SERVICE DISCONNECT AND TRANSFER SWITCH IS LOCATED

AT GENERATOR YARD IN THE FIELD BEHIND COTTAGE A-3. UTILITY

DISCONNECT IS A FUSED 3 POLE, 400 AMP SWITCH. GENERATOR SOURCE

DISCONNECT LOCATED IN THE GENERATOR SWITCHBOARD ADJACENT TO THE

GENERATOR.

WARNING

DISCONNECT SERVICE SWITCH IS A 208/120 VOLT, 3 PHASE SYSTEM.

DISCONNECT LOAD CONDUCTORS TO THE COTTAGE B AUTOMATIC

TRANSFER.

DISCONNECT SERVICE SWITCH IS A 208/120 VOLT, 3 PHASE SYSTEM.

DISCONNECT LOAD CONDUCTORS TO THE COTTAGE A-3 AUTOMATIC

TRANSFER.

DISCONNECT SERVICE SWITCH IS A 208/120 VOLT, 3 PHASE SYSTEM.

DISCONNECT LOAD CONDUCTORS TO THE COTTAGE A-4 AUTOMATIC

TRANSFER.

AUTOMATIC TRANSFER AND GENERATOR IS A 208/120 VOLT, 3 PHASE SYSTEM.

UTILITY POWER TERMINATION FROM COTTAGE B SERVICE DISCONNECT.

EMERGENCY POWER TERMINATION FROM EMERGENCY SWITCHBOARD CIRCUIT

BREAKER. TRANSFER SWITCH LOAD TERMINATION IS A SINGLE FEEDER TO THE

COTTAGE ELECTRICAL ROOM MAIN PANEL BOARD.

AUTOMATIC TRANSFER AND GENERATOR IS A 208/120 VOLT, 3 PHASE SYSTEM.

UTILITY POWER TERMINATION FROM COTTAGE A-3 SERVICE DISCONNECT.

EMERGENCY POWER TERMINATION FROM EMERGENCY SWITCHBOARD CIRCUIT

BREAKER. TRANSFER SWITCH LOAD TERMINATION IS A SINGLE FEEDER TO THE

COTTAGE ELECTRICAL ROOM MAIN PANEL BOARD.

AUTOMATIC TRANSFER AND GENERATOR IS A 208/120 VOLT, 3 PHASE SYSTEM.

UTILITY POWER TERMINATION FROM COTTAGE A-4 SERVICE DISCONNECT.

EMERGENCY POWER TERMINATION FROM EMERGENCY SWITCHBOARD CIRCUIT

BREAKER. TRANSFER SWITCH LOAD TERMINATION IS A SINGLE FEEDER TO THE

COTTAGE ELECTRICAL ROOM MAIN PANEL BOARD.

15.

S

JC

S

D

LS

JC

S

D E

M O

LI

TI

O N

P O

W E

R R

IS

E

R D

IA

G

R A

M

E101

S O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

P

LO

T D

A

TE

D A

TE

C O

N

TR

A C

T N

O

SHEET

IDENTIFICATION

SHEET OF

D E

P A

R

TM

E N

T O

F

R

IC

H M

O N

D , V

IR

G

IN

IA

JU

V

E N

IL

E

J U

S

TI

C E

B O

N A

IR

J

U V

E N

IL

E

C O

R R

E C

TI

O

N A

L C

E N

TE

R

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P

LA

C E

M E

N T

A -3

, A -4

, B , C

O

TT

A G

E

K

W

N O

TE

D

FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E

1.

dw g P

LO

TT

E D

: S at ur da y, M ay

6, M A

Y

9, FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E

1.

dw g P

LO

TT

E D

: S at ur da y, M ay

6, A N

S I D

Chesapeake, VA. 23320 Telephone: 757.348.9588

SCG

Say Consulting Group

R

IC

H M

O N

D , V

IR

G

IN

IA

D E

B P

R O

JE

C

T N

O

7-

B

-0

5/29/26

C H

A

TS

W O

R

TH

A V

E N

U E

DISCONNECT SWITCH

EQUIPMENT SHOWN IN DASH

LINE TO BE REMOVED

LEGEND

NEW WORK NOTE

DEMOLITION WORK NOTE

ELECTRICAL PANEL

SURFACE ELECTRICAL WIREWAY

GROUND

ELECTRICAL CONDUIT RACEWAY

POWER RISER DIAGRAM DEMOLITION NOTES

DISCONNECT AND REMOVE COMPLETE THE A-3 COTTAGE ATS. PRESERVE AND PROTECT

ALL CONDUCTORS AND RACEWAYS FOR CONNECTION TO THE NEW ATS UNDER NEW

WORK.

DISCONNECT AND REMOVE COMPLETE THE A-4 COTTAGE ATS. PRESERVE AND PROTECT

ALL CONDUCTORS AND RACEWAYS FOR CONNECTION TO THE NEW ATS UNDER NEW

WORK.

DISCONNECT AND REMOVE COMPLETE THE B COTTAGE ATS. PRESERVE AND PROTECT ALL

CONDUCTORS AND RACEWAYS FOR CONNECTION TO THE NEW ATS UNDER NEW WORK

DISCONNECT AND REMOVE COMPLETE THE EXISTING 300 KW GENERATOR. REMOVE ALL

FLUIDS AND PROTECT THE AREA AGAINST SPILLAGE. CONTRACTOR TO REMOVE AND

DISPOSE OF THE EXISTING 300 KW GENERATOR. OWNER HAS FIRST RIGHT OF REFUSAL

FOR ALL PARTS AND COMPONENTS. REMOVE THE DIESEL FUEL, FILTER CLEAN AND

PRESERVE THE FUEL FOR INSTALLATION UNDER NEW WORK. CONTRACTOR TO SECURE

THE VSFPC REQUIRED PERMIT FROM THE FIRE MARSHAL PRIOR TO COMMENCEMENT OF

WORK.

DISCONNECT THE EXISTING 300 KW GENERATOR BRANCH CIRCUITS. PRESERVE AND

PROTECT ALL CONDUCTORS AND RACEWAYS FOR CONNECTION TO THE NEW GENERATOR

SWITCH BOARD UNDER NEW WORK.

REMOVE THE CONTROL AND UTILITY BRANCH CIRCUITS JUNCTION BOXES IN THE

GENERATOR WIRING COMPARTMENT. PRESERVE AND PROTECT ALL CONDUCTORS AND

RACEWAYS FOR CONNECTION TO THE NEW GENERATOR SWITCHBOARD UNDER NEW

WORK.

REMOVE THE EXTERNAL WEATHERPROOF RECEPTACLE FROM THE EXTERIOR OF THE

GENERATOR HOUSING. PRESERVE AND PROTECT THE RECEPTACLE AND BRANCH CIRCUIT

FOR INSTALLATION UNDER NEW WORK.

REMOVE COMPLETE THE REMOTE ANNUNCIATION TRANSMITTER AND RECEIVER FROM THE

GENERATOR AND ADMINISTRATION BUILDING.

EXISTING

PANEL

B 300A

EXISTING

PANEL

A-3 225A

COTTAGE

B

COTTAGE

A-3

225A 3P

225A 3P

300A 3P

225A 3P

J

EXISTING

PANEL

A-4 225A

COTTAGE

A-4

EXISTING

300KW

GENERATOR

EXISTING

SERVICE

LATERALS

EXISTING (2)

GROUND

RODS AT

10'-0" O.C.

(2) GROUND

RODS AT

10'-0" O.C.

EXISTING

GROUND ROD

EXISTING

GROUND

ROD

EXISTING 1" CONDUITS FOR

GENERATOR CONTROL WIRING

EXISTING CONDUIT 2-1/2" FOR CONNECTION

OF A3 AND A4 DISCONNECT SWITCHES TO

VA. POWER SERVICE LATERAL

NEMA 3R WIRE TROUGH

ATS

A-3

ATS

A-4A-3

DISC

SW

A-4

DISC

SW

EXISTING (1) #3/0 BARE CU

GROUNDING ELECTRODE

CONDUCTOR

FLOOD LIGHT

WP

RF TRANSMITTER

ANTENNA FOR

TRANSMITTER FOR

REMOTE ANNUNCIATION

AT ADMINISTRATION BLDG.

FINISH

FLOOR/GRADE

EXISTING 3#10-3/4"C FOR

CONNECTION TO

GENERATOR BLOCK

HEATER.20A/2P CIRCUIT

BREAKER N A SPACE IN

COTTAGE A-3, 120/208

VOLT PANEL BOARD FOR

THIS BRANCH CIRCUIT.

EXISTING 3#10-3/4"C FOR CONNECTION TO BATTERY

CHARGER, FLOODLIGHT AND RECEPTACLE. 20A/1P

CIRCUIT BREAKER N A SPACE IN COTTAGE A-3,

120/208 VOLT PANEL BOARD FOR THIS BRANCH

CIRCUIT.

EXISTING 2-1/2" CONDUIT

CONNECTION OF COTTAGE A-4

4#4/0, 1#4G, 2-1/2"C

EXISTING CU GROUNDING

ELECTRODE CONDUCTOR

EXISTING

SERVICE

LATERALS

ATS

BB

DISC

SW

EXISTING

4#350KCM,

3"C

POWER RISER DIAGRAM - DEMOLITION

NO SCALE

COTTAGE B COTTAGE A-4

EXISTING 2-1/2" CONDUIT FOR

CONNECTION OF COTTAGE A-3

EXISTING

4#350KCM,

1#4G, 3"C

COTTAGE A-3

REFER TO SHEET E105 FOR

ADDITIONAL INFORMATION

REFER TO SHEET E103 FOR

ADDITIONAL INFORMATION

REFER TO SHEET

E106 FOR ADDITIONAL

INFORMATION

1 2

4 5 6 7 8

EXISTING SERVICE

LATERAL

TOP OF EXISTING

GENERATOR PAD

S

JC

S

D

LS

JC

S

N E

W W

O R

K P

O W

E R

R

IS

E R

E

LE

V A

TI

O

N D

R A

W

IN

G

E102

S O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

P

LO

T D

A

TE

D A

TE

C O

N

TR

A C

T N

O

SHEET

IDENTIFICATION

SHEET OF

D E

P A

R

TM

E N

T O

F

R

IC

H M

O N

D , V

IR

G

IN

IA

JU

V

E N

IL

E

J U

S

TI

C E

B O

N A

IR

J

U V

E N

IL

E

C O

R R

E C

TI

O

N A

L C

E N

TE

R

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P

LA

C E

M E

N T

A -3

, A -4

, B , C

O

TT

A G

E

K

W

N O

TE

D

FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E

2.

dw g P

LO

TT

E D

: S at ur da y, M ay

6, M A

Y

9, FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E

2.

dw g P

LO

TT

E D

: S at ur da y, M ay

6, A N

S I D

Chesapeake, VA. 23320 Telephone: 757.348.9588

SCG

Say Consulting Group

R

IC

H M

O N

D , V

IR

G

IN

IA

D E

B P

R O

JE

C

T N

O

7-

B

-0

5/29/26

C H

A

TS

W O

R

TH

A V

E N

U E

RISER NOTES

FURNISH AND INSTALL COMPLETE THE A-3 COTTAGE NEW ATS. CONNECT ALL PRESERVED

AND PROTECT CONDUCTORS AND RACEWAYS TO THE NEW ATS. MODIFY THE EXISTING RACK

AND STURT SUPPORT SYSTEM FOR THE NEW ATS. COORDINATE THE GENERATOR START

SIGINAL AS RECOMMENDED BY GENERATOR MANUFACTURE.

FURNISH AND INSTALL COMPLETE THE A-4 COTTAGE NEW ATS. CONNECT ALL PRESERVED

AND PROTECT CONDUCTORS AND RACEWAYS TO THE NEW ATS. MODIFY THE EXISTING RACK

AND STURT SUPPORT SYSTEM FOR THE NEW ATS. COORDINATE THE GENERATOR START

SIGINAL AS RECOMMENDED BY GENERATOR MANUFACTURE.

FURNISH AND INSTALL COMPLETE THE B COTTAGE NEW ATS. CONNECT ALL PRESERVED AND

PROTECT CONDUCTORS AND RACEWAYS TO THE NEW ATS. MODIFY THE EXISTING RACK AND

STURT SUPPORT SYSTEM FOR THE NEW ATS. COORDINATE THE GENERATOR START SIGINAL

AS RECOMMENDED BY GENERATOR MANUFACTURE.

APPLY TO THE EXISTING COTTAGE SERVICES DISCONNECT SWITCHES, APPLY TWO COATS,

BRUSHED ON RUSTOLEUM PROFESSIONAL PROTECTIVE ENAMEL PAINT, COLOR SMOKE GRAY.

ALLOW 24 HOURS OF DRY TIME BEFORE SECOND COAT. FOLLOW MANUFACTURE

RECOMMENDED APPLICATION PROCEDURES.

ATTACH INFORMATION/WARNING SIGNAGE TO THE FRONT COVERS OF COTTAGE A-3 NEW ATS.

REFER TO THE SIGNAGE CHART ON SHEET E001 FOR THE PROPER SIGNAGE.

ATTACH INFORMATION/WARNING SIGNAGE TO THE FRONT COVERS OF COTTAGE A-4 NEW ATS.

REFER TO THE SIGNAGE CHART ON SHEET E001 FOR THE PROPER SIGNAGE.

EXISTING

PANEL

B 300A

EXISTING

PANEL

A-3 225A

COTTAGE

B

COTTAGE

A-3

800A 3P

800A 3P

EXISTING

PANEL

A-4 225A

COTTAGE

A-4

230KW

GENERATOR

EXISTING

SERVICE

LATERALS

(2) GROUND

RODS AT

10'-0" O.C.

EXISTING

GROUND ROD

EXISTING

GROUND

ROD

EXISTING 2" CONDUIT FOR CONNECTION OF

A3 AND A4 DISCONNECT SWITCHES TO VA.

POWER SERVICE LATERAL

NEMA 3R WIRE TROUGH

ATS

A-3

ATS

A-4A-3

DISC

SW

A-4

DISC

SW

RF TRANSMITTER

ANTENNA FOR TRANSMITTER

FOR REMOTE ANNUNCIATION

AT EXPANSION BLDG.

FINISH

FLOOR/GRADE

2-1/2" CONDUIT CONNECTION

OF COTTAGE A-4

4#4/0, 1#4G, 2-1/2"C

EXISTING (1) #3/0 BARE CU GROUNDING

ELECTRODE CONDUCTOR

EXISTING

SERVICE

LATERALS

ATS

BB

DISC

SW

EXISTING

4#350KCM,

3"C

#1/OCU TO

MAIN CW

SERVICE

POWER RISER ELEVATION DRAWING - NEW WORK

NO SCALE

COTTAGE B COTTAGE A-4

EXISTING 2-1/2" CONDUIT FOR

CONNECTION OF COTTAGE A-3

EXISTING

4#350KCM,

1#4G, 3"C

COTTAGE A-3

REFER TO SHEET E105 FOR

ADDITIONAL INFORMATION

FOR VOLTAGE, PHASE, AMPS,

AIC RATING

REFER TO SHEET E103 FOR

ADDITIONAL INFORMATION

REFER TO SHEET

E106 FOR ADDITIONAL

INFORMATION FOR

VOLTAGE, PHASE,

AMPS, AIC RATING

J J

WP

EXTEND #10 THWN CU CONDUCTOR IN A 1"

CONDUIT TO NEW GENERATOR LOCATION

EXISTING 3#10-3/4"C FOR BATTERY CHARGER,

FLOODLIGHT AND RECEPTACLE. 20A/1P CIRCUIT

BREAKER N A SPACE IN COTTAGE A-3, 120/208 VOLT

PANEL BOARD FOR THIS BRANCH CIRCUIT.

J

J800A

225A

225A

300A

60A

TVSS

800A

800 AMP

TAP BOX

GENERATOR

SWITCHBOARD

EXISTING 1" CONDUITS WITH

GENERATOR CONTROL WIRING

ATTACH INFORMATION/WARNING SIGNAGE TO THE FRONT COVERS OF COTTAGE B NEW ATS.

REFER TO THE SIGNAGE CHART ON SHEET E001 FOR THE PROPER SIGNAGE.

ATTACH INFORMATION/WARNING SIGNAGE TO THE FRONT COVERS OF COTTAGE A-3

EXISTING SERVICE DISCONNECT SWITCH. REFER TO THE SIGNAGE CHART ON SHEET E001

FOR THE PROPER SIGNAGE.

ATTACH INFORMATION/WARNING SIGNAGE TO THE FRONT COVERS OF COTTAGE A-4

EXISTING SERVICE DISCONNECT SWITCH. REFER TO THE SIGNAGE CHART ON SHEET E001

FOR THE PROPER SIGNAGE.

ATTACH INFORMATION/WARNING SIGNAGE TO THE FRONT COVERS OF COTTAGE B EXISTING

SERVICE DISCONNECT SWITCH. REFER TO THE SIGNAGE CHART ON SHEET E001 FOR THE

PROPER SIGNAGE.

ATTACH THE WEATHERPROOF RECEPTACLE TO THE EXTERIOR OF THE GENERATOR

SWITCHBOARD HOUSING. EXTEND THE PRESERVE BRANCH CIRCUIT AS NECESSARY.

INSTALL COMPLETE A REMOTE ANNUNCIATION TRANSMITTER AND RECEIVER FROM THE

GENERATOR AND EXPANSION BUILDING.

FURNISH AND INSTALL COMPLETE A NEW 230 KW DIESEL GENERATOR WITH OVER SIZED

ALTERNATOR ON NEW CONCRETE PAD. INSTALL THE SAVED FILTERED AND CLEANED DIESEL FUEL

FROM THE REMOVED GENERATOR. CONTRACTOR TO LEAVE THE GENERATOR FUEL TANK FULL

AFTER ALL TESTING THE IS COMPLETE. GENERATOR DESIGN IS BASED ON A KOHLER 230 KW

208/120V, 3 PHASE, 4 WIRE UNIT, MODEL 230 REOZJE WITH A 4UA13 ALTERNATOR. FUEL

TANK CAPACITY 1074 GALLON.

K

K

13 14

1 5 2 6 3 7

J18

FURNISH AND INSTALL AN 800-AMP GENERATOR TAP BOX WITH MOUNTING RACK FOR

CONNECTION OF LOAD BANK TEST EQUIPMENT.

FURNISH AND INSTALL A TWO-SECTION GENERATOR SWITCHBOARD. SECTION #1 IS A SWITCH

BOARD AND SECTION #2 IS A GENERATOR DOCKING STATION. EXTEND AS NECESSARY, THE

EXISTING BARE GROUNDING CONDUCTOR TO CONNECTION TO THE SWITCHBOARD GROUNDING

BAR. EXTEND AS NECESSARY THE EXISTING GENERATOR BRANCH CIRCUIT CONDUCTORS TO THE

SWITCHBOARD BRANCH CIRCUIT BREAKERS. PROVIDE AND INSTALL COMPRESSION BUTT SPLICE

CONNECTION FOR EACH CONDUCTOR. EXTEND THE EXISTING ATS / GENERATOR START CIRCUIT

CONDUCTORS TO THE NEW GENERATOR LOCATION. EXTEND THE EXISTING 120 VOLT BATTERY

CHARGER AND GENERATOR HEATER CIRCUIT AS NECESSARY TO THE NEW GENERATOR LOCATION.

FURNISH AND INSTALL THE GENERATOR EMERGENCY STOP PUSH BUTTON SWITCH. MOUNT THE

SWITCH TO THE EXISTING FENCE. PROVIDE A MOUNTING AND BACKING PLATE TO SUPPORT THE EPO SWITCH. REFER TO THE SIGNAGE CHART FOR THE PROPER SIGNAGE. EXTEND 2 #12 AND 1 #12

GROUND IN A 1” CONDUIT UNDERGROUND TO THE NEW GENERATOR. CONNECT THE EMERGENCY

STOP SWITCH AS RECOMMENDED BY THE MANUFACTURE. ALL CONDUIT RISERS TO BE

GALVANIZED RIGID STEEL CONDUIT.

2-SETS OF (4) 500 MCM THWN AND (1)-1/0 IN A 3 ½” CONDUIT. CONDUIT RISER ABOVE THE SLAB

MUST BE GALVANIZED RIGID STEEL CONDUIT. PROVIDE INSULATED BONUDING GROUNDING

BUSHINGS.

PROVIDE A GROUND ROD AND 1/0 BARE GROUNDING CONDUCTOR FROM EACH OPPOSITE

CORNER ON THE NEW GENERATOR TO 1 FOOT BEYOND THE NEW CONCRETE GENERATOR PAD.

CONNECT TO THE 1/0 BARE CU GROUNDING RING.

EPO

(2) ETS 4-500 MCM THWN CU

+ 1 1/O CU GND IN 3-1/2"C

(2) SETS 4-500 MCM THWN

CU + 1 1/O CU GND IN 2-1/2"C

K K

OPTIONAL STANDBY SYSTEM

NATIONAL ELECTRICAL CODE 702

1 4 5 6 7

COTTAGE B SERVICE

RACK AND ATS

COTTAGE A-3 AND A-4

EXISTING SERVICE

RACK AND ATS

APPROX. 33'-0"

A P

P R

O X

. 1 7'

-0

APPROX. 6'-4"

EXISTING SLAB TO REMAIN

±18'-2"

X X X X X X

X X XX X X

X X

±1 4'

-8

GRASS

AREA

EXISTING

ASPHALT CART

AND WALKING

PATH

CUT AND REMOVE EXISTING

ASPHALT TO INSTALL NEW

GENERATOR PAD

REMOVE SOIL AND

GRASS IN THIS AREA

GRASS

AREA

GRASS

AREA

EXISTING

ASPHALT CART

AND WALKING

PATH

EXISTING

ASPHALT CART

AND WALKING

PATHGRASS

AREA

ELECTRICAL PLAN - DEMOLITION

SCALE: 1/4" = 1'-0"

JC

S

JC

S

D

LS

JC

S

D E

M O

LI

TI

O N

E

LE

C

TR

IC

A

L P

LA

N

S

E1031/4"=1'-0"

0 2' 4' 8' 16'

DEMOLITION NOTES

COORDINATE WITH THE FACILITY MAINTENANCE FOR THE

INSTALLATION OF A TEMPORARY GENERATOR TO ALLOW FOR THE

CONSTRUCTION OF THE NEW GENERATOR. PROVIDE TEMPORARY

POWER FOR THE COTTAGES REQUIRING POWER TO MAINTAIN

FACILITY USE. POWER OUTAGES TO BE KEPT TO A MINIMUM TO

MINIMIZE DISRUPTION OF THE FACILITY OPERATIONS.

REFER TO THE COTTAGE A-3, A-4 SERVICE AND ATS ELEVATION

DETAIL ON SHEET E105 FOR ADDITIONAL INFORMATION.

REMOVE THE CHAIN LINK FENCING AND SUPPORT POLES ALONG

THE REAR OF THE EXISTING GENERATOR PAD.

DISCONNECT AND REMOVE COMPLETE THE EXISTING 300 KW

GENERATOR. REMOVE ALL FLUIDS AND PROTECT THE AREA

AGAINST SPILLAGE. CONTRACTOR TO REMOVE AND DISPOSE OF

THE EXISTING 300 KW GENERATOR. OWNER HAS FIRST RIGHT OF

REFUSAL FOR ALL PARTS AND COMPONENTS. REMOVE THE DIESEL

FUEL, FILTER CLEAN AND PRESERVE THE FUEL FOR INSTALLATION

UNDER NEW WORK. CONTRACTOR TO SECURE THE VSFPC

REQUIRED PERMIT FROM THE FIRE MARSHALL PRIOR TO

COMMENCEMENT OF WORK.

DISCONNECT THE EXISTING 300 KW GENERATOR BRANCH

CIRCUITS. PRESERVE AND PROTECT ALL CONDUCTORS AND

RACEWAYS FOR CONNECTION TO THE NEW EMERGENCY SWITCH

BOARD UNDER NEW WORK.

REMOVE THE CONTROL AND UTILITY BRANCH CIRCUITS JUNCTION

BOXES IN THE GENERATOR WIRING COMPARTMENT. PRESERVE

AND PROTECT ALL CONDUCTORS AND RACEWAYS FOR

CONNECTION TO THE NEW EMERGENCY SWITCHBOARD UNDER

NEW WORK.

REMOVE THE EXTERNAL WEATHERPROOF RECEPTACLE FROM THE

EXTERIOR OF THE GENERATOR HOUSING. PRESERVE AND

PROTECT THE RECEPTACLE AND BRANCH CIRCUIT FOR

INSTALLATION UNDER NEW WORK.

SAW CUT AND REMOVE COMPLETE AN AREA OF THE EXISTING

CONCRETE GENERATOR PAD TO ALLOW FOR THE INSTALLATION OF

THE NEW GENERATOR FEEDERS AND CONTROL CONDUCTORS AND

RACEWAYS.

REMOVE THE REMOTE ANNUNCIATOR ANTENNA AND TRANSMITTER.

REMOVE COMPLETE THE ADEMCO ANNUNCIATOR RECEIVER

MOUNTED IN THE ADMINISTRATION BUILDING. REFER TO SHEET

E107.

S O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

P

LO

T D

A

TE

D A

TE

C O

N

TR

A C

T N

O

SHEET

IDENTIFICATION

SHEET OF

D E

P A

R

TM

E N

T O

F

R

IC

H M

O N

D , V

IR

G

IN

IA

JU

V

E N

IL

E

J U

S

TI

C E

B O

N A

IR

J

U V

E N

IL

E

C O

R R

E C

TI

O

N A

L C

E N

TE

R

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P

LA

C E

M E

N T

A -3

, A -4

, B , C

O

TT

A G

E

K

W

N O

TE

D

FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E

3.

dw g P

LO

TT

E D

: S at ur da y, M ay

6, M A

Y

9, FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E

3.

dw g P

LO

TT

E D

: S at ur da y, M ay

6, A N

S I D

Chesapeake, VA. 23320 Telephone: 757.348.9588

SCG

Say Consulting Group

R

IC

H M

O N

D , V

IR

G

IN

IA

D E

B P

R O

JE

C

T N

O

7-

B

-0

5/29/26

C H

A

TS

W O

R

TH

A V

E N

U E

X X X X X X

X X XX X X

X X

X

X X X X X X

X X

X X

X X

X X

X

X

X X

COTTAGE A-3 AND A-4

SERVICE RACK AND

ATS

APPROX. 33'-0"

A P

P R

O X

. 1 7'

-0

APPROX. 6'-4"

EPO

COTTAGE B SERVICE

RACK AND ATS

EXISTING

GENERATOR

PAD

NEW GENERATOR PAD

GENERATOR

AND FUEL TANK

±2 3'

-6

±22'-4"

GENERATOR SERVICE

AND WORK PLATFORM

AND STAIRS. SEE

DETAIL ON SHEET

E108 (TYPICAL FOR

BOTH SIDES)

G E

N E

R A

TO

R

S E

R V

IC

E

A N

D W

O R

K P

LA

TF

O R

M A

N D

S

TA

IR

S

±48"

±48"

DOUBLE 5'-0"

SWING GATE

GRASS

AREA

EXISTING

ASPHALT CART

AND WALKING

PATH

GRASS

AREA

GRASS

AREA

EXISTING

ASPHALT CART

AND WALKING

PATH

EXISTING

ASPHALT CART

AND WALKING

PATHGRASS

AREA

EDGE OF

EXISTING

ASPHALT

CART AND

WALKING

PATH

±14'-0" R

NEW ASPHALT

CART AND

WALKING

PATH

JC

S

JC

S

D

LS

JC

S

N E

W W

O R

K E

LE

C

TR

IC

A L

P

LA

N S

E1041/4"=1'-0"

0 2' 4' 8' 16'

NEW WORK NOTES

COORDINATE WITH THE FACILITY MAINTENANCE FOR THE

INSTALLATION OF A TEMPORARY GENERATOR TO ALLOW FOR

THE CONSTRUCTION OF THE NEW GENERATOR. PROVIDE

TEMPORARY POWER FOR THE COTTAGES REQUIRING POWER

TO MAINTAIN FACILITY USE. POWER OUTAGES TO BE KEPT TO A

MINIMUM TO MINIMIZE DISRUPTION OF THE FACILITY

OPERATIONS.

FURNISH AND INSTALL COMPLETE A NEW 230 KW DIESEL

GENERATOR WITH OVER SIZED ALTERNATOR ON NEW

CONCRETE PAD. GENERATOR DESIGN IS BASED ON A KOHLER

230 KW, 208/120V, 3 PHASE, 4W UNIT. INSTALL THE SAVED

FILTERED AND CLEANED DIESEL FUEL FROM THE REMOVED

GENERATOR. CONTRACTOR TO LEAVE THE GENERATOR FUEL

TANK FULL AFTER ALL TESTING THE IS COMPLETE.

EXTEND, FURNISH, AND INSTALL THE CHAIN LINK FENCING AND

SUPPORT POLES ALONG THE EDGE OF THE EXTENDED

GENERATOR PAD. PROVIDE A 10 FT. DOUBLE SWING GATE ON

THE END OF THE FENCE. PROVIDE THREE STRAND BARBED

WIRE ALONG THE TOP OF THE FENCE. REFER TO DETAILS ON

SHEET E108.

FURNISH AND INSTALL AN 800-AMP GENERATOR TAP BOX WITH

MOUNTING RACK FOR CONNECTION OF LOAD BANK TEST

EQUIPMENT. SEE SHEET E107 FOR ADDITIONAL INFORMATION.

FURNISH AND INSTALL A TWO-SECTION GENERATOR

SWITCHBOARD. SECTION #1 IS A SWITCHBOARD AND SECTION

#2 IS A GENERATOR DOCKING STATION. EXTEND AS

NECESSARY, THE EXISTING BARE GROUNDING CONDUCTOR TO

CONNECTION TO THE SWITCHBOARD GROUNDING BAR. EXTEND

AS NECESSARY THE EXISTING GENERATOR BRANCH CIRCUIT

CONDUCTORS TO THE GENERATOR SWITCHBOARD BRANCH

CIRCUIT BREAKERS. PROVIDE AND INSTALL COMPRESSION BUTT

SPLICE CONNECTION FOR EACH CONDUCTOR.

EMERGENCY SHUT DOWN SWITCH. MOUNT TO EXISTING FENCE.

ROUTE CONDUIT UNDER GROUND TO NEW GENERATOR. SEE

SIGNAGE CHART ON SHEET E001 FOR THE PROPER SIGNAGE.

REMOTE ANNUNCIATOR TRANSMITTER.

REMOTE ANNUNCIATOR ANTENNA. ANTENNA INSTALLED ON

GEN SET ENCLOSURE FOR WIRELESS REMOTE TRANSMISSION

TO REMOTE ANNUNCIATOR LOCATED IN EXPANSION BUILDING

M-P ROOM SP101. REFER TO DIVISION 26 SPECIFICATIONS -

ENGINE GENERATORS, FOR ADDITIONAL REQUIREMENTS FOR

THE WIRELESS ANNUNCIATOR SYSTEM. PROVIDE NEW

WIRELESS RADIO MODEM, OMMNI DIRECTIONAL ANTENNA

(ANTENNA SHALL USE SAME MAST AS THE ANTENNA FOR THE

CENTRAL INFIRMARY WIRELESS ANNUNCIATOR SYSTEM). COAX

CABLE AND CONNECTORS, INSTALL ON EXTERIOR OF EXISTING

EXPANSION BUILDING NEXT TO THE EXISTING ANTENNAS FOR

WIRELESS ANNUNCIATORS. MATCH EXISTING ANTENNA

SUPPORT METHOD TO MAST , WIRE WAY, CONDUIT AND COAX

CABLING CONNECTIONS. SEAL ALL PENETRATIONS THRU

EXTERIOR WALL INTO ROOM C-100. FOR ADDITIONAL

INFORMATION CONTACT TED GROVE IN SALES OR ADREIN IN

TECHNICAL SUPPORT. BENTECK SYSTEMS, PHONE (403)

243-5135. SEE DETAIL ON SHEET E107.

BOND FENCE POST TO GENERATOR GROUND ROD WITH A #6 CU

BONDING STRAP. PROVIDE U SHAPE FENCE CLAMPS.

ACTUAL SIZE IS DEPENDENT ON GENERATOR AND FUEL TANK

SELECTED.

ALIGN NEW SLAB TOP ELEVATION WITH EXISTING SLAB TOP.

INSTALL EXPANSION JOINT AS NEEDED.

TIE IN NEW ASPHALT CART AND WALKING PATH TO EDGE OF

EXISTING ASPHALT CART AND WALKING PATH.

ELECTRICAL PLAN - NEW WORK

SCALE: 1/4" = 1'-0"

S O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

P

LO

T D

A

TE

D A

TE

C O

N

TR

A C

T N

O

SHEET

IDENTIFICATION

SHEET OF

D E

P A

R

TM

E N

T O

F

R

IC

H M

O N

D , V

IR

G

IN

IA

JU

V

E N

IL

E

J U

S

TI

C E

B O

N A

IR

J

U V

E N

IL

E

C O

R R

E C

TI

O

N A

L C

E N

TE

R

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P

LA

C E

M E

N T

A -3

, A -4

, B , C

O

TT

A G

E

K

W

N O

TE

D

FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E

4.

dw g P

LO

TT

E D

: S at ur da y, M ay

6, M A

Y

9, FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E

4.

dw g P

LO

TT

E D

: S at ur da y, M ay

6, A N

S I D

Chesapeake, VA. 23320 Telephone: 757.348.9588

SCG

Say Consulting Group

R

IC

H M

O N

D , V

IR

G

IN

IA

D E

B P

R O

JE

C

T N

O

7-

B

-0

5/29/26

C H

A

TS

W O

R

TH

A V

E N

U E

COTTAGE A-4 ATS

COTTAGE A-4 SERVICE

DISCONNECT

COTTAGE A-3 ATS

COTTAGE A-3 SERVICE

DISCONNECT

1 2

AND ATS ELEVATION DEMOLITION

SCALE: NONE

E105E103

COTTAGE A-3 AND A-4 SERVICE RACK

EXISTING

GENERATOR

PAD

GRADE

COTTAGE A-4, 4 POLE,

ATS, 400A, 208/120V,

3PH, 4W, 42 KAIC (MIN.)

COTTAGE A-4, SERVICE

DISCONNECT, 400A,

225AF, 208/120V, 3PH, 4W

COTTAGE A-3, 4 POLE,

ATS, 400A, 208/120V,

3PH, 4W, 42 KAIC (MIN)

COTTAGE A-3, SERVICE

DISCONNECT, 400A,

225AF, 208/120V, 3PH, 4W

1 4

AND ATS ELEVATION NEW WORK

SCALE: NONE

E105E103

COTTAGE A-3 AND A-4 SERVICE RACK

EXISTING

GENERATOR

PAD

GRADE

JC

S

JC

S

E M

O

LI

TI

O

N A

N D

N E

W W

O R

K

JC

S

D E

M O

LI

TI

O N

A N

D N

E W

W O

R K

A

TS

S E

R V

IC

E

R A

C K

E

LE

V A

TI

O

N S

C

O

TT

A G

E A

-3 A

N D

A -4

E105

S O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

P

LO

T D

A

TE

D A

TE

C O

N

TR

A C

T N

O

SHEET

IDENTIFICATION

SHEET OF

D E

P A

R

TM

E N

T O

F

R

IC

H M

O N

D , V

IR

G

IN

IA

JU

V

E N

IL

E

J U

S

TI

C E

B O

N A

IR

J

U V

E N

IL

E

C O

R R

E C

TI

O

N A

L C

E N

TE

R

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P

LA

C E

M E

N T

A -3

, A -4

, B , C

O

TT

A G

E

K

W

N O

TE

D

FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E

5.

dw g P

LO

TT

E D

: S at ur da y, M ay

6, M A

Y

9, FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E

5.

dw g P

LO

TT

E D

: S at ur da y, M ay

6, A N

S I D

Chesapeake, VA. 23320 Telephone: 757.348.9588

SCG

Say Consulting Group

R

IC

H M

O N

D , V

IR

G

IN

IA

D E

B P

R O

JE

C

T N

O

7-

B

-0

5/29/26

C H

A

TS

W O

R

TH

A V

E N

U E

NEW WORK NOTES

FURNISH AND INSTALL COMPLETE THE A-3 COTTAGE NEW ATS. CONNECT ALL

PRESERVED AND PROTECT CONDUCTORS AND RACEWAYS TO THE NEW ATS. MODIFY

THE EXISTING RACK AND STRUT SUPPORT SYSTEM FOR THE NEW ATS. COORODINATE

THE GENERATOR START SIGNAL AS RECOMMENDATED BY GENERATOR MANUFACTURE.

FURNISH AND INSTALL COMPLETE THE A-4 COTTAGE NEW ATS. CONNECT ALL

PRESERVED AND PROTECT CONDUCTORS AND RACEWAYS TO THE NEW ATS. MODIFY

THE EXISTING RACK AND STRUT SUPPORT SYSTEM FOR THE NEW ATS. CORRODINATE

THE GENERATOR START SIGNAL AS RECOMMENDATED BY GENERATOR MANUFACTURE.

APPLY TO THE EXISTING COTTAGE SERVICES DISCONNECT SWITCHES, APPLY TWO

COATS, BRUSHED ON RUST OLEUM PROFESSIONAL PROTECTIVE ENAMEL PAINT,

COLOR SMOKE GRAY. ALLOW 24 HOURS OF DRY TIME BEFORE SECOND COAT. FOLLOW

MANUFACTURE RECOMMENDED APPLICATION PROCEDURES.

ATTACH INFORMATION/WARNING SIGNAGE TO THE FRONT COVERS OF COTTAGE A-3

NEW ATS. REFER TO THE SIGNAGE CHART ON SHEET E001 FOR THE PROPER SIGNAGE.

ATTACH INFORMATION/WARNING SIGNAGE TO THE FRONT COVERS OF COTTAGE A-4

NEW ATS. REFER TO THE SIGNAGE CHART ON SHEET E001 FOR THE PROPER SIGNAGE.

ATTACH INFORMATION/WARNING SIGNAGE TO THE FRONT COVERS OF COTTAGE A-3

EXISTING SERVICE DISCONNECT SWITCH. REFER TO THE SIGNAGE CHART ON SHEET

E001 FOR THE PROPER SIGNAGE.

ATTACH INFORMATION/WARNING SIGNAGE TO THE FRONT COVERS OF COTTAGE A-4

EXISTING SERVICE DISCONNECT SWITCH. REFER TO THE SIGNAGE CHART ON SHEET

E001 FOR THE PROPER SIGNAGE.

DEMOLITION NOTES

DISCONNECT AND REMOVE COMPLETE THE A-3 COTTAGE ATS. PRESERVE

AND PROTECT ALL CONDUCTORS AND RACEWAYS FOR CONNECTION TO

THE NEW ATS UNDER NEW WORK.

DISCONNECT AND REMOVE COMPLETE THE A-4 COTTAGE ATS. PRESERVE

AND PROTECT ALL CONDUCTORS AND RACEWAYS FOR CONNECTION TO

THE NEW ATS UNDER NEW WORK.

COTTAGE B 400A, ATS, 4

POLE, 208/120V, 3PH, 4W

COTTAGE B SERVICE

DISCONNECT, 400A,

300AF, 208/120V, 3PH,

4W

AND ATS ELEVATION DEMOLITION

SCALE: NONE

E106E104

COTTAGE B SERVICE RACK

COTTAGE B SERVICE

DISCONNECT, 400A,

300AF, 208/120V, 3PH,

4W

COTTAGE B 400A, ATS, 4

POLE, 208/120V, 3PH, 4W,

42 KAIC (MIN)

AND ATS ELEVATION NEW WORK

SCALE: NONE

E106E104

COTTAGE B SERVICE RACK

JC

S

JC

S

D

LS

JC

S

D E

M O

LI

TI

O N

A N

D N

E W

W O

R K

S E

R V

IC

E

R A

C K

E

LE

V A

TI

O

N

C O

TT

A

G E

B A

TS

E106

S O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

P

LO

T D

A

TE

D A

TE

C O

N

TR

A C

T N

O

SHEET

IDENTIFICATION

SHEET OF

D E

P A

R

TM

E N

T O

F

R

IC

H M

O N

D , V

IR

G

IN

IA

JU

V

E N

IL

E

J U

S

TI

C E

B O

N A

IR

J

U V

E N

IL

E

C O

R R

E C

TI

O

N A

L C

E N

TE

R

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P

LA

C E

M E

N T

A -3

, A -4

, B , C

O

TT

A G

E

K

W

N O

TE

D

FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E

6.

dw g P

LO

TT

E D

: S at ur da y, M ay

6, M A

Y

9, FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E

6.

dw g P

LO

TT

E D

: S at ur da y, M ay

6, A N

S I D

Chesapeake, VA. 23320 Telephone: 757.348.9588

SCG

Say Consulting Group

R

IC

H M

O N

D , V

IR

G

IN

IA

D E

B P

R O

JE

C

T N

O

7-

B

-0

5/29/26

C H

A

TS

W O

R

TH

A V

E N

U E

NEW WORK NOTES

FURNISH AND INSTALL COMPLETE THE B COTTAGE NEW ATS. CONNECT ALL

PRESERVED AND PROTECT CONDUCTORS AND RACEWAYS TO THE NEW ATS. MODIFY

THE EXISTING RACK AND STURT SUPPORT SYSTEM FOR THE NEW ATS. CORRODINATE

THE GENERATOR START SIGINAL AS RECOMMENDATED BY GENERATOR

MANUFACTURE.

APPLY TO THE EXISTING B COTTAGE SERVICES DISCONNECT SWITCHE, APPLY TWO

COATS, BRUSHED ON, RUST OLEUM PROFESSIONAL PROTECTIVE ENAMEL PAINT,

COLOR SMOKE GRAY. ALLOW 24 HOURS OF DRY TIME BEFORE SECOND COAT. FOLLOW

MANUFACTURE RECOMMENDED APPLICATION PROCEDURES.

ATTACH INFORMATION/WARNING SIGNAGE TO THE FRONT COVERS OF COTTAGE B NEW

ATS. REFER TO THE SIGNAGE CHART ON SHEET E001FOR THE PROPER SIGNAGE.

ATTACH INFORMATION/WARNING SIGNAGE TO THE FRONT COVERS OF COTTAGE B

EXISTING SERVICE DISCONNECT SWITCH. REFER TO THE SIGNAGE CHART ON SHEET

E001 FOR THE PROPER SIGNAGE.

DEMOLITION NOTES

DISCONNECT AND REMOVE COMPLETE THE B COTTAGE ATS. PRESERVE

AND PROTECT ALL CONDUCTORS AND RACEWAYS FOR CONNECTION TO

THE NEW ATS UNDER NEW WORK.

3"X3"X3/16" HOT ROLLED

GALVANIZED STEEL ANGLE

POST CONCRETE ENCASED.

GENERATOR PAD.

800 AMP GENERATOR TAP BOX.

1-1/2" GALVANIZED STRUT.

GENERATOR CIRCUITS.

GROUND CONDUCTOR IN 1"

PVC.

GROUND ROD.

24"

8"

GRADE

NOTES:

24"

8"

GENERATOR TAP BOX DETAIL

SCALE: NONE

E107E103

4'-0"

5' -0

JC

S

JC

S

D

LS

JC

S

D E

TA

IL

S

E107

S O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

P

LO

T D

A

TE

D A

TE

C O

N

TR

A C

T N

O

SHEET

IDENTIFICATION

SHEET OF

D E

P A

R

TM

E N

T O

F

R

IC

H M

O N

D , V

IR

G

IN

IA

JU

V

E N

IL

E

J U

S

TI

C E

B O

N A

IR

J

U V

E N

IL

E

C O

R R

E C

TI

O

N A

L C

E N

TE

R

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P

LA

C E

M E

N T

A -3

, A -4

, B , C

O

TT

A G

E

K

W

N O

TE

D

FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E

7.

dw g P

LO

TT

E D

: S at ur da y, M ay

6, M A

Y

9, FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E

7.

dw g P

LO

TT

E D

: S at ur da y, M ay

6, A N

S I D

Chesapeake, VA. 23320 Telephone: 757.348.9588

SCG

Say Consulting Group

R

IC

H M

O N

D , V

IR

G

IN

IA

D E

B P

R O

JE

C

T N

O

7-

B

-0

5/29/26

C H

A

TS

W O

R

TH

A V

E N

U E

EXISTING REMOTE ANNUNCIATOR SYSTEM RISER DIAGRAM

NO SCALE

3-FOOT QUARTER WAVE ANTENNA

W/18'-0" OF COAXIAL CABLE, LINEAR

SECURITY MODEL #ANT-2

LINEAR SECURITY MODEL #XT-1 RF

TRANSMITTER LOCATED IN WEATHER

PROTECTED GENERATOR ENCLOSURE,

AT EACH GENERATOR LOCATION.

(LOCATE AS DIRECTED BY GENERATOR

MANUFACTURER.

3-FOOT QUARTER WAVE ANTENNA

W/18'-0" OF COAXIAL CABLE, LINEAR

SECURITY MODEL #ANT-2

LINEAR SECURITY MODEL #XR-16 RECIEVER,

LOCATED AT MAINTENANCE SHOP PER

OWNERS INSTRUCTIONS. (REFER TO ADEMCO

VISTA-40 PANEL BELOW)

ADEMCO MODEL #4208 REMOTE POINT

MODULE, LOCATED ABOVE ADEMCO

VISTA-40 PANEL ON WALL AT

MAINTENANCE BLDG.

ADEMCO VISTA-40 SECURITY PANEL FOR

ALPHA-NUMERICAL LCD DISPLAY OF

GENERATOR COMMON ANNUNCIATOR.

(LOCATE IN MAINTENANCE SHOP AT BON

AIR JUVENILE DETENTION AS DIRECTED BY

ONWNER.

ADEMCO MODEL #6139 LCD, MOUNT ON

FACE OF SECURITY PANEL FOR ALARM

DISPLAY

UTILIZE 12DC POWER SUPPLY IN

ADEMCO VISTA-40 PANEL FOR POWER

TO RECEIVER AND REMOTE POINT

MODULE

(8) 2/C #18 (ALARM INPUTS)

2/C #18 (12DC POWER FROM ADEMCO VISTA-40)

2/C #18 SHELDED (DATA) RS232 CONNECTION

2/C #18 NON SHELDED (POWER)

2/C #18 SHELDED (DATA)

2/C #18 NON SHELDED (POWER)

CONNECT TO NEAREST AVAILABLE 120V

POWER CKT. AT MAINTENANCE BLDG.

LOCAL AUDIBLE ALARM AT PANEL

NO SCALE

GROUNDING DETAIL

A B C N

GROUND ROD

1/0 BARE CU

NOTE:

GROUND GENERATOR NEUTRAL TERMINATION AND

GENERATOR FRAME. INSTALL GROUND RODS AT EACH

OF THE CORNERS OUT SIDE NEW PAD. THERMO WELD

GROUND CONDUCTOR TO GROUND ROD.

REMOVE COMPLETE EXISTING REMOTE ANNUNCIATION

SYSTEM AT ADMINISTRATION OFFICE.

TYPICAL GENERATOR

GENERATOR SWITCHBOARD

TRIP WIRE

SIZE

LOAD SERVEDCKT

NO. POLE

1 60 6 3 TVSS

800A MCB 208Y/120V 3PH 4W FREE STANDING 42K AIC MIN

2 300 350 3 COTTAGE B ATS

3 225 4/0 3

4 225 4/0 3

COTTAGE A-3 ATS

COTTAGE A-4 ATS

GENERATOR EQUIPMENT PAD

NO SCALE

3" MIN.

NOTES:

4" MIN.

M

IN

SELECT FILL BASE

UNDISTURBED SOIL

6" MINIMUM COMPACTED

8"

12"

CONCRETE PAD

2" MINIMUM COVER

6"

1" CHAMFER (TYP

ALL AROUND)

8" (TYP ALL AROUND). MIN CLEAR

DISTANCE FROM EQUIPMENT

ANCHORAGE TO EDGE OF SLAB OR

EQUIP. SUPPLIER RECOMMENDATIONS

WHICH EVER IS LARGER

6" 8"

FINISHED

GRADE TO

DRAIN AWAY

GENERATORDIMENSION AS REQUIRED

(1) - #4 CONT. BAR

#4 BAR @ 12" O.C. (MAX. EACH WAY)

TOP AND BOTTOM

SAW CUT JOINTS @ 8'-0" O.C. MAX

VERIFY LOCATION OF ALL UNDERGROUND UTILITIES PRIOR TO BEGINNING CONSTRUCTION OF EQUIPMENT FOUNDATION.

PROVIDE LARGER OF 8" OR EQUIPMENT MANUFACTURER REQUIRED AS MINIMUM OR ARCH/SITE DETERMINED DIMENSION.

MAINTAIN MANUFACTURERS RECOMMENDED DISTANCE FROM GRADE.

ALIGN TOP OF SLAB WITH EXISTING CONCRETE PAD.

GENERAL CONTRACTOR TO COORDINATE ALL UTILITY SUB UPS WITH EQUIPMENT SUPPLIER PRIOR TO PLACEMENT OF CONCRETE.

SLOPE PAD TOWARD EXISTING DRAINAGE PATTERN.

CONCRETE TO BE AIR ENTRAINED 4,500 PSI PER SPECS, WITH A BROOM FINISH.

COMPACT SUB GRADE AND BASE TO 95% OF ASTM D-1557.

GENERATOR PAD AND SUB BASE IS TO BE PLACED ON UNDISTURBED SOIL WITH ALLOWABLE BEARING PRESSURE OF 2000 PSF PER GEOTECHNICAL REPORT.

1.

2.

3.

4.

5.

6.

7.

8.

9.

BENTECK

900 MHZ

TRANSMITTER

GENERATOR

CONTROLLER

BENTECK

900 MHZ

RECEIVER

X

ANTENNA

CABLE

RS 485 CABLE

BENTECK ANTENNA MOUNTED ON

GENERATOR HOUSING

BENTECK 24V

POWER

TRANSFORMER

GENERATOR

HOUSING

EXPANSION

BUILDING

BENTECK 24V

POWER

TRANSFORMER

BENTECK ANTENNA MOUNTED

AT EXPANSION BUILDING

RS 485 CABLE

REMOTE

ANNUNCIATOR

POWER SUPPLY

KOHLOR REMOTE

ANNUNCIATOR

MOUNTED IN

EXPANSION

BUILDING SECURITY

OFFICE

ANTENNA DETAIL REMOTE ANNUNCIATOR

NO SCALE

VARIES FROM 168" TO 214"

DEPENDING ON THE GENERATOR

FUEL TANK MANUFACTURER

±3 7"

±4 1"

42"

GUARDRAILS

21"-26" FULLY

ADJUSTABLE

GUARDRAILS

36"

HANDRAIL

7" MAX

11" TREAD

WORK PLATFORM DETAIL

SCALE: NONE

E108E104

GENERATOR SERVICE AND

PLAN VIEW

ELEVATION VIEW

SUPPORT PLANKS

1' -7

1'

-7

JC

S

JC

S

D

LS

JC

S

D E

TA

IL

S

E108

FASTENING DETAILS

NO SCALE

CONCRETE BASE

5% MIN.

TENSION BAND

LINE POST ATTACHMENTS

END OR GATE POST DETAIL

TENSION BAND DETAIL

FABRIC

TIE WIRE

TENSION BAR

CARRIAGE BOLT

FABRIC

TENSION BAR TO

ENGAGE EACH FABRIC LINK

TENSION BAND

WITHIN 4" FROM

(12" O.C. MAX.)

BRACE RAIL ATTACHMENT

FROM BOTTOM OF FABRIC)

(15" O.C. MAX. AND WITHIN 4"

BOTTOM OF FABRIC)

TENSION WIRE

(15" O.C. MAX. AND

WIRE TIES

H-BEAM ROUND POST

TOP OR BRACE RAIL ATTACHMENT

FABRIC

WITHIN 4" FROM WITHIN 4" FROM

OF FABRIC) OF FABRIC)

(2'-0" O.C. MAX.)

(15" O.C. MAX. AND

TOP AND BOTTOM

(15" O.C. MAX. AND

TOP AND BOTTOM

WIRE TIE WIRE TIE

WIRE TIES

CORNER POST

6" (T

YP.)

3/8" PLAIN PIN

RIVETED FLUSH (TYP.)

45°

LINE POST

1'-

6" BARBED WIRE (TYP.)

1' -0

" LOCK PIN (TYP.)

1'-0"

7.5" (T

YP.)

3/8 " PLAIN PIN

RIVETED FLUSH (TYP.)

35°

1'-10"

1' -0

LINE POST ATTCHMENTS

NO SCALE

EXTENSION ARM DETAILS

NO SCALE

BRACE RAIL CLAMP DETAIL

NO SCALE

TRUSS ROD AND BAND

NO SCALENOT TO SCALE

SECURITY FENCE DETAIL - EQUIPMENT AREA ONLY

DOUBLE RAIL END

LINE POST

W/PEEN THREADS

(12" O.C. MAX.)

FABRIC

BOTTOM RAIL

2" MAX.

SECURE SIDE

3/8" CARRIAGE BOLT

GRADE

WIRE TIES

FABRIC

BOTTOM RAIL DETAILS

NOT TO SCALE

GROUNDING ROD

10' x 3/4"

"C""B" 40"46"

"A" DIA.

18"

TYPE POST

36"42"12"

EXTENSION ARM

WITH 3 STRANDS

OF BARBED WIRE

8'

TOP RAIL

OR BRACE

GROUND CLAMP

CENTER OF POST (MAX.)

10' CENTER OF POST TO

2" (T

Y P

NOTES:

1.

"B ""C

1"

(T Y

P

"A"

2.

GRADE

CONCRETE

FOOTING

GROUND ROD BY

ATTACHMENT CLAMP

CONNECTED TO

#6 AWG CU WIRE

MORE THAN 50' APART ALONG FENCE.

CORNER, EACH SIDE OF GATES AND SPACED NO

GROUNDING SHALL BE PROVIDED AT EACH END,

TERMINAL POSTS INCLUDE END, CORNER, AND

BRACE POSTS.

LINE POSTS

GATE POSTS

TERMINAL POSTS

CENTER RAIL

CONTINUOUS

RAIL

BOTTOM

16" 42" 36"

GROUNDING ROD SHALL BE CU-CLAD STEEL.3.

S O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

P

LO

T D

A

TE

D A

TE

C O

N

TR

A C

T N

O

SHEET

IDENTIFICATION

SHEET OF

D E

P A

R

TM

E N

T O

F

R

IC

H M

O N

D , V

IR

G

IN

IA

JU

V

E N

IL

E

J U

S

TI

C E

B O

N A

IR

J

U V

E N

IL

E

C O

R R

E C

TI

O

N A

L C

E N

TE

R

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P

LA

C E

M E

N T

A -3

, A -4

, B , C

O

TT

A G

E

K

W

N O

TE

D

FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E

8.

dw g P

LO

TT

E D

: S at ur da y, M ay

6, M A

Y

9, FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E

8.

dw g P

LO

TT

E D

: S at ur da y, M ay

6, A N

S I D

Chesapeake, VA. 23320 Telephone: 757.348.9588

SCG

Say Consulting Group

R

IC

H M

O N

D , V

IR

G

IN

IA

D E

B P

R O

JE

C

T N

O

7-

B

-0

5/29/26

C H

A

TS

W O

R

TH

A V

E N

U E

NOTES:

1. 21"-26" GRIP STRUT OMNI STEP AND PLATFORMS.

QUANTITY: 1 LEFT, 1 RIGHT (LEFT SHOWN).

PLATFORM CAN BE SET FROM 21" TO 26". EACH LEG IS

INDEPENDENTLY ADJUSTABLE TO MATCH GRADE.

ALL ALUMINUM WELDED CONSTRUCTION WITH STAINLESS STEEL

HARDWARE.

APPROXIMATE WEIGHT: 264 LBS.

2.

3.

4.

5.

TRUSS ROD (3/8" MIN. DIA.)

4. CONCRETE POST FOOTING TO BE 4500 PSI.

EXISTING

OVERHEAD

TRANSFORMER

BANK

PARKING

AREA

PARKING

AREA

SERVICE ROAD

SERVICE

ROAD

EXISTING UTILITY

POWER POLE

OHE

OHE

OHE

EXISTING

GENERATOR

EXISTING UTILITY

POWER POLE

OHE

B

ELECTRICAL

ROOM

A-4

ELECTRICAL

ROOM

A-3

ELECTRICAL

ROOM

EXISTING UTILITY

POWER POLE

EXISTING UTILITY

POWER POLE

GRASS

AREA

EXISTING

ROAD

EXISTING

ROAD

ELECTRICAL SITE PLAN - EXISTING

SCALE: 1" = 30'-0"

S O

LI

C

IT

A

TI

O

N N

O

FI

LE

N A

M E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

TE

FI

LE

N U

M B

E R

S

IZ

E

S U

B M

IT

TE

D B

Y

P

LO

T S

C A

LE

P

LO

T D

A

TE

D A

TE

C O

N

TR

A C

T N

O

SHEET

IDENTIFICATION

SHEET OF

D E

P A

R

TM

E N

T O

F

R

IC

H M

O N

D , V

IR

G

IN

IA

JU

V

E N

IL

E

J U

S

TI

C E

B O

N A

IR

J

U V

E N

IL

E

C O

R R

E C

TI

O

N A

L C

E N

TE

R

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P

LA

C E

M E

N T

A -3

, A -4

, B , C

O

TT

A G

E

K

W

N O

TE

D

FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E S

-1 .d w g

P

LO

TT

E

D : S at ur da y, M ay

6, M A

Y

9, FI

LE

N A

M E

: C :\D oc um en ts a nd

S et tin gs

\S m ile yD

\D es kt op

\S ay

C on su lti ng G ro up

\D

JJ

S

TA

N D

B Y

G E

N E

R A

TO

R

R E

P A

C E

M E

N T\

E S

-1 .d w g

P

LO

TT

E

D : S at ur da y, M ay

6, A N

S I D

Chesapeake, VA. 23320 Telephone: 757.348.9588

SCG

Say Consulting Group

R

IC

H M

O N

D , V

IR

G

IN

IA

D E

B P

R O

JE

C

T N

O

7-

B

-0

5/29/26

C H

A

TS

W O

R

TH

A V

E N

U E

JC

S

JC

S

D

LS

K L

E X

IS

TI

N G

E

LE

C

TR

IC

A

L S

IT

E

P

LA

N

ES101

WORK NOTES

REFER TO SIGNAGE CHART ON SHEET E001 FOR

ELECTRICAL ROOM SIGNAGE. ATTACH INFORMATION

SIGNAGE TO EXTERIOR OF ELECTRICAL ROOM DOOR.

1"=30'-0"

0 30' 60' 90'

DISCLAIMER NOTE:

THE DRAWING DEPICTS A

VISUAL REPRESENTATION

OF THE DJJ BON AIR SITE.

A-4 COTTAGE

B COTTAGE

A-3 COTTAGE

A-2 COTTAGE

EXPANSION

BUILDING

A-1 COTTAGE

KEYPLAN

SCALE: NONE

AREA

OF WORK

A-3 COTTAGEA-4 COTTAGE

B COTTAGE

GENERATOR