UD-26-342 Fire Hydrants and Fire Hydrant Parts ITB_Addendum 1~1.pdf

PDF 354 KB Posted

Attached to
Fire Hydrants and Fire Hydrant Parts
Solicitation number
UD-26-342
Issued by
Los Angeles County, California

About this file

This is an Addendum No. 1 Notice to Bidders issued by Long Beach Utilities on July 16, 2026, for Invitation to Bid (ITB) UD-26-342 regarding Fire Hydrants and Fire Hydrant Parts. The addendum provides clarifications to the original ITB specifications through a Question and Answer format. Key technical clarifications include confirmation that materials may be either domestic or import; fire hydrant flanges must comply with AWWA C110 (ANSI 125-pound flanges) with six equally spaced 3/4-inch holes on a 9-3/8-inch bolt circle; break-off hydrant risers are required; plastic caps are preferred but ductile caps will not be rejected; and bronze (brass) bushings must feature female national standard hydrant thread by female iron pipe thread connections. The document also distinguishes between two line items: Line 29 specifies the 1-1/8" operating nut, while Line 30 specifies the machine nut used to retain the operating nut to the stem.

Bidders are required to acknowledge receipt of this addendum by signing and submitting it with their bid submission. Failure to submit the signed addendum may result in bidder disqualification. The addendum was prepared by Esme Houtepen, Utilities Procurement Representative, and requires acknowledgment from the bidding company with signature, company name, printed name, title, and date on the form provided.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

July 16, 2026

NOTICE TO BIDDERS

ADDENDUM NO. 1: Q & A

ITB UD-26-342

FIRE HYDRANTS AND FIRE HYDRANT PARTS

This addendum changes and supersedes the language in the original RFQ. Please acknowledge receipt of this addendum by signing and submitting with your bid. Any bidder who fails to submit this addendum may be disqualified.

As of July 16, 2026:

The following are answers to questions submitted:

Question 1. Is there a requirement for the materials listed on the bid to be Domestic or can they be Import, as well? Thank you in advance.

Answer 1. The materials can be either domestic or import.

Question 2. Are you requesting 6 hole or 8 hole hydrants?

Answer 2. Refer to ITB Detailed Specifications Checklist, page 21. Fire Hydrant Flanges: Flanges for fire hydrant extensions shall comply with the provisions of AWWA C110 (ANSI 125‐pound flanges) with six equally spaced 3/4‐inch holes on a 9‐3/8‐inch bolt circle. All flanges shall be plain faced with smooth finish.

Question 3. Solid or break off hydrant risers?

Answer 3. Break off.

Question 4. Plastic or DI caps for their hydrants to start? Or only the plastic caps separately?

Answer 4. Plastic is preferred, but ductile will not be rejected.

Question 5. Clarify threading for 2‐1/2x2 bronze (brass) bushing (FNSHTXFIPT – two female?

Female national standard hydrant thread by female iron pipe thread?)

Answer 5. This is correct. Female national standard hydrant thread by female iron pipe thread.

Question 6. What is the difference between line 29 and line 30?

300 Jones Operating Nut

300 Jones Operating Nut Nut

Answer 6. Line 29 is the 1‐1/8” operating nut. Line 30 is the machine nut to retain the operating nut to the stem.

PREPARED BY:

Esme Houtepen, Utilities Procurement Representative

ACKNOWLEDGED BY: