TP09 Final Drawings.pdf

PDF 11 MB Posted

Attached to
Z2DA--657-19-113JC, FCA-REPLACE OBSOLETE AND FAILING AIR CONDITIONING UNITS
Solicitation number
36C25520R0096
Issued by

View the file

Other files

File Type Posted
TP09 Final Specifications - (658 Pages).pdf PDF
36C25520R0096_1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DRAWING LIST

1i

GRID / COLUMN

LINE

DESIGNATOR

EQUIPMENT NUMBER

DOOR NUMBER

Ga5xFB1

WALL TYPE

WINDOW TYPE

ROOM NAME/NUMBER

REVISION TAG

NORTH ARROW w/

TRUE NORTH

INDICATION

ROOM NAME

ELEVATION NUMBER

SECTION

INTERIOR ELEVATION

ENLARGEMENT,

DETAIL

SPOT ELEVATION

Name

Elevation

FLOOR LEVEL & NAME

PLATE NUMBER WHERE

SECTION/DETAIL IS

DRAWN

PLATE NUMBER WHERE

SECTION/DETAIL IS

DRAWN

PLATE NUMBER WHERE

SECTION/DETAIL IS

DRAWN

SHEET KEYNOTE

A101

SIM

EXTERIOR ELEVATION

A101

PLATE NUMBER WHERE

SECTION/DETAIL IS

DRAWN

INDEX OF DRAWINGS

202-A101

DISCIPLINE:

G - GENERAL

C - CIVIL

L - LANDSCAPE

S - STRUCTURAL

A - ARCHITECTURE

P - PLUMBING

M - MECHANICAL

E - ELECTRICAL

T - TELECOM

Q - FOOD SERVICE

SHEET TYPE

DESIGNATOR

VICINITY MAP

PROJECT TEAMBUILDING SUMMARY

PROJECT INFORMATION

GENERAL:

ALL WORK COORDINATED THROUGH BRAD PETROVIC AT VAMC - JOHN COCHRAN (ST. LOUIS) ENGINEERING DEPARTMENT. A FULL PHASING PLAN WILL BE COORDINATED WITH REGARDS TO NIGHTTIME AND WEEKEND WORK SCHEDULES AND SHUTDOWNS. EACH OF THE FOLLOWING TASKS SHOULD BE COMPLETED INDEPENDENTLY OF OTHERS - START-TO-FINISH

WITHOUT DELAY TO WORK ON ANOTHER TASK.

BUILDING 1 - 01-AC-03 REPLACEMENT:

ALL DUCT AND PIPING TO BE SHOP-FABRICATED PRIOR TO DELIVERY TO SITE. PREPARE FOR CONTINGENCY PIPE SECTIONS AND CONNECTIONS IN FIELD OF 12 INCHES IN LENGTH OR LESS. INTERSTITIAL SPACE ALLOWS FOR UNIT TO BE TRANSPORTED TO MECHANICAL ROOM IN COMPONENTS THAT FIT THROUGH A STANDARD 3'-0" X 7'-0" DOORWAY. VERIFY AND COORDINATE

EQUIPMENT COMPONENT PATHWAYS THROUGH LEVEL 3 INTERSTITIAL SPACE.

BUILDING 1 - 01-AC-17 AND CHILLER REPLACEMENT:

WORK TO BE ACCOMPLISHED IN MONTHS OF APRIL-MAY OR SEPT-OCT. INSTALL AS MUCH OF THE NEW STEAM & CHILLED WATER SYSTEM (PUMPS, PIPING, ACCESSORIES) AS POSSIBLE PRIOR TO DEMOLITION OF EXISTING CHILLER AND AIR HANDLER TO MINIMIZE EQUIPMENT DOWN-TIME. NEW CHILLER SUPPORTS TO BE PRE-FABRICATED AND MANUFACTURER PROVIDED WITH SEISMIC PRE-APPROVAL RATINGS. DELIVER NEW CHILLER AND REMOVE EXISTING ROOFTOP CONDENSER ON SAME DAY AND CRANE USE. PROVIDE AIR HANDLER THAT CAN BE TRANSPORTED TO MECHANICAL ROOM IN COMPONENTS THAT FIT THROUGH A STANDARD 3'-0" X 7'-0" DOORWAY. VERIFY AND COORDINATE EQUIPMENT COMPONENT PATHWAYS THROUGH LEVEL 3

INTERSTITIAL SPACE.

BUILDING 1 - 01-ITAC-03&06 & 01-ITCU-03&06 NETWORK RACK COOLING UNITS REPLACEMENT:

REMOVE NETWORK RACK COOLING SYSTEM #6 FIRST (NOT IN OPERATION) WITHOUT INTERRUPTING NETWORK CONNECTIVITY TO UNIT #3 (IN OPERATION). COORDINATE SWITCH-OVER OF NETWORK CONNECTION TO NEW UNIT BEFORE REPLACEMENT OF OF REDUNDANT RACKS TO MAINTAIN CONSTANT NETWORK OPERATION THROUGHOUT CONSTRUCTION PROCESS. PROVIDE CONTROL CONDUIT AND WIRING SCOPE OF WORK PRIOR TO DEMOLITION OF EXISTING SYSTEMS TO MINIMIZE TIME TO GET

FULLY REDUNDANT RACK SYSTEMS WITH BAS SYSTEM INTEGRATION AS SHOWN IN DRAWINGS.

BUILDING 1 - 01-RAH-1A&B HEAT WHEEL REPLACEMENT:

PRE-FABRICATE AS MANY DUCTWORK COMPONENTS AS POSSIBLE PRIOR TO EXISITING SYSTEM DEMOLITION TO MINIMIZE AC-1 DOWN-TIME. PRIOR TO REMOVAL OF OUTDOOR AIR DUCT FROM E-WHEEL, COVER LOUVER OPENING WITH FILTER FABRIC.

COMPONENTS CAN BE TRANSPORTED TO MECHANICAL ROOM IN PARTS THAT FIT THROUGH A STANDARD 3'-0" X 7'-0" DOORWAY.

VERIFY AND COORDINATE EQUIPMENT COMPONENT PATHWAYS THROUGH LEVEL 3 INTERSTITIAL SPACE.

BLDG 3 03-AC-01 REPLACEMENT:

PRE-FABRICATE NEW AHU TO BE READY TO RECEIVE CHILLED WATER AND STEAM PIPING CONNECTIONS PRIOR TO DELIVERY TO SITE. DELIVER NEW AHU AND REMOVE (DECOMMISSION) EXISTING ROOFTOP AHU ON SAME DAY AND CRANE USE.

BLDG 8 08-VAU-B1 REPLACEMENT:

PROVIDE UNIT THAT CAN BE TRANSPORTED TO THE BASEMENT THROUGH THE BOILER BUILDING. BASEMENT STAIR OPENING IS

LIMITED TO A 3'-0" OPENING.

BLDG 8 08-AC-M3 REPLACEMENT:

EQUIPMENT AND SYSTEM COMPONENTS TO BE CRANE LIFTED TO THE CHILLER PLANT ROOF AND TRANSPORTED THROUGH POP-OUT WINDOW ADJACENT TO EXISTING UNIT. PROVIDE UNIT WITH COMPONENTS THAT CAN BE TRANSPORTED THROUGH A

4'-0" X 4'-0" WINDOW OPENING.

ANNOTATION DRAWING SYMBOLSGENERAL NOTES

PROJECT NAME: REPLACE OBSOLETE AND FAILING AIR CONDITIONING UNITS VA ST. LOUIS HEALTH CARE SYSTEM

PROJECT NUMBER: 657-19-113JC

PROJECT LOCATION: JOHN COCHRAN DIVISION - VA ST. LOUIS HEALTH CARE SYSTEM

PROJECT PURPOSE/USE: REPLACE OBSOLETE AND FAILING AIR CONDITIONING UNITS

BUILDING NUMBER

1. THESE DRAWINGS SHALL BE USED ONLY FOR THIS SPECIFIC PROJECT/SITE LOCATION. THESE DRAWINGS ARE A COMPOSITE SET OF CONTRACT DOCUMENTS AND SHALL NOT BE SEPARATED FOR DISTRIBUTION. THE GC SHALL REVIEW

ALL DRAWINGS AND PROVIDE/DISTRIBUTE THE ENTIRE SET TO EACH SUBCONTRACTOR.

2. THE GC SHALL VISIT THE SITE TO INSPECT EXISTING CONDITIONS AND VERIFY WORK BEING PERFORMED BEFORE

SUBMITTING COST QUOTATIONS FOR WORK.

3. NOTIFY THE ARCHITECT PROMPTLY OF ANY ERRORS, OMISSIONS, INCONSISTENCIES, DISCREPANCIES AND CONFLICTS WITHIN THE CONTRACT DOCUMENTS AND ITS ASSOCIATED FIELD/PROJECT CONDITIONS SO THAT A RESOLUTION CAN BE

PROVIDED PRIOR TO CONTINUING WITH WORK.

4. DO NOT SCALE THE DRAWINGS. REQUEST ANY MISSING DIMENSIONS FROM THE ARCHITECT

5. ALL WORK PERFORMED SHALL BE IN STRICT COMPLIANCE WITH GOVERNING FEDERAL, STATE AND LOCAL BUILDING CODE REQUIREMENTS, SHALL BE EXECUTED IN ACCORDANCE WITH ACCEPTED INDUSTRY STANDARDS, AND SHALL CONFORM TO SPECIFIC REGULATIONS AS MANDATED BY THE OWNER, THE ARCHITECT, AND THE AUTHORITIES HAVING JURISDICTION.

THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ANY FEES ASSOCIATED WITH PROCURING SUCH PERMITS AND CERTIFICATES AND SHALL FURNISH COPIES OF PERMITS, INSPECTIONS, AND CERTIFICATES TO THE OWNER.

6. THE GENERAL CONTRACTOR SHALL COORDINATE ALL WORK TO MINIMIZE DISRUPTION OF ANY EXISTING TENANTS OR BUILDING OPERATIONS. THE GENERAL CONTRACTOR SHALL TAKE ADEQUATE PRECAUTIONS TO PROTECT BUILDING OCCUPANTS, MATERIALS, AND EXISTING CONSTRUCTION THROUGHOUT ALL PHASES OF CONSTRUCTION. DAMAGE TO EXISTING-TO-REMAIN CONSTRUCTION OR EQUIPMENT SHALL BE RESTORED TO ORIGINAL CONDITION AT THE

CONTRACTOR'S EXPENSE.

7. THE GENERAL CONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM THE JOB SITE ON A DAILY BASIS.

8. ANY REQUESTS FOR SUBSTITUTIONS OF ANY SPECIFIED ITEM ARE TO BE SUBMITTED TO THE ARCHITECT IN WRITING AND WILL BE CONSIDERED ONLY IF THE ALTERNATE PROPOSED IS PROVEN TO BE ADVANTAGEOUS TO THE OWNER WITH

RESPECT TO DELIVERY DATE, QUALITY, OR COST.

9. THE MEANS AND METHODS OF CONSTRUCTION, AND TEMPORARY STRUCTURES AND FACILITIES, ARE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE ARCHITECT DOES NOT ASSUME ANY RESPONSIBILITY FOR THE CONTRACTOR'S

MEANS AND METHODS OR FOR TEMPORARY STRUCTURES.

10. DEMOLITION OF EXISTING STRUCTURES IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE CONTRACTOR SHALL

EMPLOY ENGINEERING EXPERTISE AS NEEDED TO ASSIST IN DEMOLITION.

11. JOB SITE SAFETY AND SECURITY ARE THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE GENERAL CONTRACTOR SHALL CONSULT WITH LOCAL FIRE AUTHORITIES TO ASCERTAIN REQUIREMENTS FOR FIRE SUPPRESSION AND SAFETY DURING CONSTRUCTION. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR MEETING OSHA

REGULATIONS DURING CONSTRUCTION.

12. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR STORAGE AND PROTECTION OF BUILDING MATERIALS, AND INSTALLED CONSTRUCTION, FROM INCLEMENT WEATHER, THEFT, AND OTHER HAZARDS. THE GC SHALL FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS FOR STORAGE OF MATERIALS. PARTIALLY COMPLETED WALLS SHALL BE COVERED TO PROTECT FROM WATER INTRUSION. DAMAGE, INCLUDING BUT NOT LIMITED TO MOLD, RESULTING FROM WATER INTRUSION DURING CONSTRUCTION SHALL BE REPAIRED AT THE GENERAL CONTRACTOR'S EXPENSE.

A101

A101

PLAN NORTH

SHEET NUMBER

WITHIN SERIES

ARCHITECT:

Romanyk Consulting Corp.

3308 Preston Road, Suite 350-164 Plano, Texas 75093

Rebecca Olson, AIA ACHA rebecca.olsen@romanykconsulting.com

855.424.3838 x302

602.430.1265 cell

MECHANICAL ENGINEER:

Romanyk Consulting Corp.

3308 Preston Road, Suite 350-164 Plano, Texas 75093

Scott Thraen, PE Scott.Thraen@RomanykConsulting.com

855.424.3838 x312

402.981.8882 cell

ELECTRICAL ENGINEER:

IMEG Corp.

15 Sunnen Drive, Suite 104 St. Louis, Missouri 63143

Zachary W. Carter, P.E., LEED BD+C Zachary.W.Carter@imegcorp.com

314.951.2529

OWNER:

St. Louis John Cochran VAHCS 915 N Grand Blvd.

St. Louis, MO 63016

Contact Name: Brad Petrovic, COR bradley.petrovic@va.gov

314.652.4100 x58724 Contracting Officer: Cedric Graham

PHASING NOTES:

DEDUCT BID ALTERNATES:

1. BUILDING 1 AC-3 REPLACEMENTS NOT INCLUDED IN SCOPE OF PROJECT.

2. NO REPLACEMENT OF ELECTRICAL PLANELS OR CONDUCTORS.

3. NO REMOVAL OF AC-17 SURGE TANK.

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

NOT FOR

PERMITTING OR

CONSTRUCTION

A/E:Consultant:

U.S. Department of Veterans Affairs

Spinklered

B

IM

/V

IS

N

A E

S e rv ic e s

A ir H a n d lin g U n it s /A

E S e rv ic e s

A H

U M

E P

.r v t

/2

/2

:5 :2

P

M

COVER SHEET

ST DW

SPRINKLERED

ST. LOUIS, MO

APRIL 29, 2020

ST. LOUIS,

MO

GI100

657-19-113JC

PROJECT NUMBER - 657-19-113JC

OBLIGATION NUMBER - RCC #657C90258

TASK ORDER NUMBER - RCC 36C25519N0287

REPLACE OBSOLETE AND FAILING AIR CONDITIONING UNITS

CONSTRUCTION DOCUMENTS REPLACE OBSOLETE AND FAILING

AIR CONDITIONING UNITS

CONSTRUCTION DOCUMENTS

APRIL 29, 2020

GENERAL

GI100 COVER SHEET

CIVIL - SITE

CS100 SITE PLAN

ARCHITECTURAL

AE100 ARCHITECTURAL ENLARGED PLANS - BLDG. 03, ROOF

AE101 ARCHITECTURAL ENLARGED PLANS - BLDG. 01, LEVEL 03 & ROOF

AE102 ARCHITECTURAL REFLECTED CELING PLANS - BLDG. 03,08, LEVELS 01 & 02

AE200 ARCHITECTURAL DETAILS

MECHANICAL

M-001 MECHANICAL SYMBOLS, NOTES, AND ABBREVIATIONS

MD100 MECHANICAL DEMOLITION ENLARGED PLANS - BLDG. 01, LEVEL 00

MD101 MECHANICAL DEMOLITION ENLARGED PLANS - BLDG. 01, LEVEL 03 AND BLDG. 03, LEVEL 02

MD102 MECHANICAL DEMOLITION ENLARGED PLANS - BLDG. 01, LEVEL 03 & ROOF

MD103 MECHANICAL DEMOLITION ENLARGED PLANS - BLDG. 08

MH100 MECHANICAL HVAC ENLARGED PLANS - BLDG. 01, LEVEL 03 AND BLDG. 03, LEVEL 02

MH101 MECHANICAL HVAC ENLARGED PLANS - BLDG. 01, LEVEL 03 & ROOF

MH102 MECHANICAL HVAC ENLARGED PLANS - BLDG. 08

MH200 MECHANICAL HVAC SECTIONS AND 3D VIEWS - BLDG. 01, AC-1

MH201 MECHANICAL HVAC SECTIONS AND 3D VIEWS - BLDG. 01, AC-3

MH202 MECHANICAL HVAC SECTIONS AND 3D VIEWS - BLDG. 01, AC-1 HEAT WHEEL

MH203 MECHANICAL HVAC SECTIONS AND 3D VIEWS - BLDG. 08, AC-1, VAU-1

MH300 MECHANICAL HVAC DETAILS

MH301 MECHANICAL HVAC DETAILS

MH400 MECHANICAL HVAC SCHEDULES

MI100 MECHANICAL EQUIPMENT CONTROL DIAGRAMS

MI101 MECHANICAL EQUIPMENT CONTROL DIAGRAMS

MP100 MECHANICAL PIPING ENLARGED PLANS - BLDG. 01, LEVEL 00

MP101 MECHANICAL PIPING ENLARGED PLANS - BLDG. 01, LEVEL 03 AND BLDG. 03, LEVEL 02

MP102 MECHANICAL PIPING ENLARGED PLANS - BLDG. 01, LEVEL 03 & ROOF

MP103 MECHANICAL PIPING ENLARGED PLANS - BLDG. 08

MP200 MECHANICAL PIPING DETAILS

MP201 MECHANICAL PIPING DETAILS

MP202 MECHANICAL PIPING DETAILS

MP203 MECHANICAL PIPING DETAILS

MP300 MECHANICAL PIPING SCHEDULES

ELECTRICAL

E-001 ELECTRICAL SYMBOLS, NOTES, AND ABBREVIATIONS

ED100 ELECTRICAL DEMOLITION ENLARGED PLANS - BLDG. 01, LEVEL 00

ED101 ELECTRICAL DEMOLITION ENLARGED PLANS - BLDG. 01, LEVEL 03 AND BLDG. 03, LEVEL 02

ED102 ELECTRICAL DEMOLITION ENLARGED PLANS - BLDG. 01, LEVEL 03 & ROOF

ED103 ELECTRICAL DEMOLITION ENLARGED PLANS - BLDG. 03

ED104 ELECTRICAL DEMOLITION ENLARGED PLANS - BLDG. 08

EP100 ELECTRICAL ENLARGED PLANS - BLDG. 01, LEVEL 00

EP101 ELECTRICAL ENLARGED PLANS - BLDG. 01, LEVEL 03

EP102 ELECTRICAL ENLARGED PLANS - BLDG. 01, LEVEL 03 & ROOF

EP103 ELECTRICAL ENLARGED PLANS - BLDG. 03, LEVEL 02 & ROOF

EP104 ELECTRICAL ENLARGED PLANS - BLDG. 08

EP200 ELECTRICAL SCHEDULES

EP201 ELECTRICAL DETAILS

Grand total: 45

VA ST. LOUIS HEALTH CARE SYSTEM, JOHN COCHRAN DIVISION

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.02Revisions: Date: 04/29/2020

Phase

CONTRACT DOCUMENTS FOR

BIDDING

NOT FOR

PERMITTING OR

CONSTRUCTION

T

BUILDING SCHEDULE

1 MAIN HOSPITAL & CLINICAL ADDITION

1A EMERGENCY GENERATOR VAULT

1B EMERGENCY GENERATOR VAULT

EDUCATION, MEDICAL MEDIA,

CHAPEL & RESEARCH

2T METHADONE CLINIC

2T2 OATP CLINIC

3 IRM & RESEARCH

4 NON-VA CARE / AFGE

5T OEF/OIF

6 RESEARCH

6A RESEARCH

7 RESEARCH

7A RESEARCH

8 BOILER PLANT

8A CHILLER PLANT

8B EMERGENCY GENERATOR

10 FLAG POLE

11 GAS METER HOUSE

12 WET SALT STORAGE

14 GARAGE

16 ENGINEERING / TRANSITION CARE TEAM

24 WASTE STORAGE FACILITY

DEC DECON TRAILER

1T MODULAR BUILDING

RESTAURANT VACANT

BLDG.

14 3

DELMAR AVE.

ENRIGHT AVE.

S P

R

IN

G S

T

AMEREN MISSOURI

SUBSTATION

8A 7

8B

7A

6A

BELL AVE.

1A

G R

A N

D B

L V

D

2T

5T

2T2

1T

DEC

1B

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Spinklered

PLAN NORTH

B

IM

/V

IS

N

A E

S e rv ic e s

A ir H a n d lin g U n it s /A

E S e rv ic e s

A H

U M

E P

.r v t

/2

/2

:5 :2

P

M

SITE PLAN

ST DW

CONSTRUCTION DOCUMENTS 657-19-113JC

CS100

REPLACE OBSOLETE AND FAILING

AIR CONDITIONING UNITS

ST. LOUIS, MO

APRIL 29, 2020

ST. LOUIS,

MO

SPRINKLERED

1" = 50'-0"1

SITE PLAN

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.02

0' 50' 100'25'

Graphic Scale : 1" = 50'-0"

Revisions: Date: 04/29/2020

Phase

CONTRACT DOCUMENTS FOR

BIDDING

Phase

CONTRACT DOCUMENTS FOR

BIDDING

NOT FOR

ROOF(EX)

AREA OF ROOFING

TO BE REMOVED.

DEMO EXISTING HVAC

EQUIPMENT AND CURB

180"

15' - 0"

ROOF(EX)

AE200

Typ.

EXISTING MOBILE GUARDRAIL TO

REMAIN. MAINTAIN IN CURRENT

LOCATION FOR FALL PROTECTION

TO MEET OSHA REQUIREMENTS

180"

15' - 0"

PATCH AND REPAIR ROOF IN

THE WORK AREA INDICATED

DASHED LINES INDICATE NEW

CURB UNDER HVAC EQUIPMENT

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Spinklered

KEY PLAN

B

IM

/V

IS

N

A E

S e rv ic e s

A ir H a n d lin g U n it s /A

E S e rv ic e s

A H

U .r v t

/2

/2

:1

:3

A

M

ARCHITECTURAL ENLARGED PLANS - BLDG. 03,

ROOF

GC EM

CONSTRUCTION DOCUMENTS 657-19-113JC

AE100

REPLACE OBSOLETE AND FAILING

AIR CONDITIONING UNITS

ST. LOUIS, MO

APRIL 29, 2020

ST. LOUIS,

MO

SPRINKLERED

1/4" = 1'-0"

ENLARGED ARCHITECTURAL DEMOLITION PLAN - BUILDING 03 AC-1 ROOF

1/4" = 1'-0"

ENLARGED ARCHITECTURAL PLAN - BUILDING 03 AC-1 ROOF

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.02Revisions: Date: 04/29/2020

Phase

CONTRACT DOCUMENTS FOR

BIDDING

NOT FOR

ROOF(EX)

AREA OF ROOF TO BE REMOVED

AND PATCHED

REMOVE EXISTING RAIL SUPPORTS

REMOVE EXISTING HVAC UNIT, CURB AND ALL

ASSOCIATED CONNECTIONS AND EQUIPMENT.

EXISTING STEAM RELIEF PIPE

PENETRATION TO BE RELOCATED. PATCH

EXISTING ROOF PENETRATION.

AREA OF ROOF TO BE

REMOVED AND PATCHED.

36"

3' - 0" REMOVE PORTION OF ROOF

TO PREP FOR NEW PIPE PENTRATION

AND HOOD.

DEMO ROOF AREA FOR LOCATION OF

NEW STEAM PIPE. VERFIY LOCATION WITH

MECHANICAL SHEET INFORMATION.

36"

3' - 0"

36"

3' - 0"

" 240"

20' - 0"

ROOF(EX)

AE200

Typ.

AE200

Typ.

36"

3' - 0"

AREA OF NEW ROOF INSTALLATION

TO MATCH EXISTING.

NEW CURB UNDER NEW

HVAC EQUIPMENT

NEW SEISMICALLY RATED RAIL

SYSTEM FOR HVAC EQUIPMENT

PROVIDED BY MANUFACTURER

NEW PIPE PENETRATION

HOOD. PROVIDE FLASHING

PER MANUFACTURER'S

RECOMMENDATIONS.

NEW STEAM PIPE LOCATION.

VERIFY LOCATION WITH

MECHANICAL SHEETS.

PATCH ROOF WHERE OLD

STEAM PIPE WAS REMOVED

36"

3' - 0"

36"

3' - 0"

AE200

Typ.

AE200

Typ.

240"

20' - 0"

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Spinklered

KEY PLAN

B

IM

/V

IS

N

A E

S e rv ic e s

A ir H a n d lin g U n it s /A

E S e rv ic e s

A H

U .r v t

/2

/2

:1

:3

A

M

ARCHITECTURAL ENLARGED PLANS - BLDG. 01,

LEVEL 03 & ROOF

GC EM

CONSTRUCTION DOCUMENTS 657-19-113JC

AE101

REPLACE OBSOLETE AND FAILING

AIR CONDITIONING UNITS

ST. LOUIS, MO

APRIL 29, 2020

ST. LOUIS,

MO

SPRINKLERED

1/4" = 1'-0"

ENLARGED ARCHITECTURAL DEMOLITION PLAN - BUILDING 01 - AC-17 ROOF

1/4" = 1'-0"

ENLARGED ARCHITECTURAL PLAN - BUILDING 01 - AC-17 ROOF

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.02Revisions: Date: 04/29/2020

Phase

CONTRACT DOCUMENTS FOR

BIDDING

NOT FOR

OFFICE

REMOVE EXISTING 2X4 CEILING AND GRID

DURING HVAC WORK. REPLACE EXISTING

2X4 CEILING WHEN HVAC WORK IS

COMPLETE WITH NEW 2X4 LAY-IN

CEILING AND GRID AT THE SAME HEIGHT

AS THE ORIGINAL CEILING.

AREA OF WORK

SALVAGE AND

REUSE LIGHT

FIXTURES,TYP.

OFFICE

REMOVE EXISTING 2X4 CEILING AND

GRID DURING HVAC WORK. REPLACE

2X4 CEILING AND GRID WHEN HVAC

WORK IS COMPLETE WITH NEW LAY-IN

2X4 CEILING TILES AT THE SAME HEIGHT

AS ORIGINAL CEILING. REPLACE GRID IF

NECESSARY.

AREA OF WORK

SALVAGE AND REUSE

LIGHT FIXTURES (TYP.)

COMPUTER TRAINING

CLOSET

115A

REMOVE EXISTING 2X4 CEILING AND

GRID DURING HVAC WORK. REPLACE

EXISTING 2X4 CEILING AND GRID WHEN

HVAC WORK IS COMPLETE WITH NEW

2X4 LAY-IN CEILING TILES AT THE SAME

HEIGHT AS ORIGINAL CEILING. REPLACE

GRID IF NECESSARY.

AREA OF WORK

SALVAGE AND REUSE

LIGHT FIXTURES, TYP.

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Spinklered

KEY PLAN

3PLAN NORTH

B

IM

/V

IS

N

A E

S e rv ic e s

A ir H a n d lin g U n it s /A

E S e rv ic e s

A H

U .r v t

/2

/2

:1

:3

A

M

ARCHITECTURAL REFLECTED CELING PLANS -

BLDG. 03,08, LEVELS 01 & 02

GC EM

CONSTRUCTION DOCUMENTS 657-19-113JC

AE102

REPLACE OBSOLETE AND FAILING

AIR CONDITIONING UNITS

ST. LOUIS, MO

APRIL 29, 2020

ST. LOUIS,

MO

SPRINKLERED

1/8" = 1'-0"

ENLARGED RCP - BUILDING 08 - LEVEL 01

1/8" = 1'-0"

ENLARGED RCP - BUILDING 08 - LEVEL 02

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.02

1/8" = 1'-0"

ENLARGED REFLECTED CEILING PLAN BUILDING 03 - LEVEL 01

Revisions: Date: 04/29/2020

Phase

CONTRACT DOCUMENTS FOR

BIDDING

NOT FOR

CLOSED - BEST FOR NEW

CONSTRUCTION WITH CONSISTENT

SIZED CURB

1 PIECE - BEST FOR CONSISTENT

SIZED CURBS WITH EXISTING

EQUIPMENT

2 PIECES - BEST FOR

CONSISTENT SIZED CURBS WITH

EXISTING EQUIPMENT

4 PIECES - BEST FOR VARIABLE

SIZED CURBS FOR MAXIMUM

ADJUSTMENT

CUSTOM CURB FLASHING CONFIGURATIONS

T-JOINT COVER

(SEE NOTE 7 AND 8)

NOTES:

1. REFER TO FIRESTONE OR VA APPROVED EQUAL WEBSITE FOR

MOST CURRENT INFORMATION.

2. ULTRAPLY TPO CUSTOM CURB FLASHING COMES IN CUSTOM

SIZES TO FIT SPECIFIC CURB SIZES (SEE CHART TO LEFT).

3. REFER TO UT-LS-1 AND UT-LS-2 FOR WELD WIDTH.

4. BONDING ADHESIVE REQUIRED BETWEEN CURB AND CUSTOM

CURB FLASHING.

5. WHEN REINFORCEMENT OF TPO MEMBRANE IS EXPOSED, REFER

TO UT-LS-14 FOR CUT EDGE SEALANT APPLICATION.

6. T-JOINT COVERS REQUIRED AT ALL VERTICAL TRANSITIONS ON

NON-FACTORY WELDS FOR ALL MEMBRANE THICKNESSES.

7. T-JOINT COVERS REQUIRED AT ALL 60 MIL REINFORCED

MEMBRANE OVERLAPS.

8. ULTRAPLY TPO FLASHING (UNSUPPORTED) (4" x 4" MIN. WITH

ROUNDED CORNERS) MAY BE USED IN LIEU OF T-JOINT COVER.

ULTRAPLY TPO CUSTOM

CURB FLASHING

(SEE NOTES 3, 4, AND 5)

CURB

T-JOINT COVER

(SEE NOTES 6 AND 8)

ULTRAPLY TPO FIELD MEMBRANE

TREATED 2x4 NAILER

SS GASKETED FAST, 12" OC MAX

INSUL MET CURB - SIZE

HEIGHT FOR 8" MIN ABOVE

ROOF W/2" TOP RETURN

FLASHING & METAL GAUGE

TO SUPPORT RTU

(RE:MECH)

1-1/2" RIGID INSUL

1-1/4" SS ROOF NAILS, 12" OC MAX

ALUM COUNTERFLASHING WITH

MIN 4" FACE & DRIP RETURN

TPO CURB FLASHING (RE:D3/A124)

TPO BONDING ADHESIVE

ROOF MANUF FAST & SEAM PLATE, 12" OC

2" MIN WELDED SPLICE

NEW TPO ROOF MEMBRANE AROUND THE

NEW CURB AND HVAC UNIT.

R-30 RIGID INSULATION, OR MATCH EXISTING

THICKNESS AT THIS LOCATION.

REPAIR/REPLACE SECTIONS OF METAL DECK AS NEEDED

TO INSTALL NEW HVAC CURB

ROOF OPENING, RE:MECH

SEALING MATERIAL -

MUST BE CONTINUOUS

ON TOP OF THE CURB

1/2"

MIN1"

BASE OF UNIT EXTENDS 1/2" MIN BEYOND TOP OF CURB

RTU - FLANGE EXTENDS 1" MIN BELOW TOP OF CURB

8" MIN

VERIFY

NEW PERIMETER BENT STEEL PLATE AROUND OPENING

INTERPLY REQUIRED FOR

15 & 20 YEAR SYSTEMS

MODIFIED BITUMEN GRANULE

SURFACED CAP SHEET

SUBSTRATE

FIRESTONE OR VA APPROVED EQUAL

INSULATION

FIRESTONE OR VA APPROVED EQUAL

INSULATION

COVERBOARD (AS REQUIRED) BASE AND INTERPLY

SHEETS AS REQUIRED FOR

DESIRED WARRANTY

[2 m m

M

IN

[76 mm]

3" MIN

[76 mm]

3" MIN

METAL COUNTERFLASHING BY

OTHERS; 3" [76mm] MIN FACE

GASKETED FASTENERS BY OTHERS

12" [304mm] O.C. MAX

R.T.U.

FASTEN 8" [203mm] O.C.

MODIFIED BITUMEN GRANULE

SURFACED CAP SHEET

NOTES:

1. REFER TO FIRESTONE OR VA APPROVED EQUAL

WEBSITE FOR MOST CURRENT INFORMATION.

2. WOOD NAILERS MUST BE INSTALLED WITH SUITABLE

FASTENERS TO MEET APPLICABLE BUILDING CODES

(200 LBS PER LINEAR FOOT MIN IN ANY GIVEN

DIRECTION).

3. ALL SHEET METAL IS TO BE INSTALLED PER SMACNA

GUIDELINES.

4. GRANULES MUST BE EMBEDDED WHEN THERMALLY

FUSING GRANULE SURFACED CAP SHEET.

5. FLASHING LAPS MUST BE OFFSET FROM FIELD LAPS

BY A MINIMUM OF 12" [305mm].

6. WHEN POSSIBLE, MECHANICAL UNITS SHOULD NOT

BE SET UNTIL THE ROOF MEMBRANE AND FLASHING

HAVE BEEN INSTALLED.

INTERPLY REQUIRED FOR

15 & 20 YEAR SYSTEMS

BASE AND INTERPLY SHEETS

AS REQUIRED FOR DESIRED

WARRANTY

MODIFIED BITUMEN

GRANULE SURFACED

CAP SHEET

MODIFIED BITUMEN GRANULE

SURFACED CAP SHEET

HIGH-DOMED, CAPPED,

GASKETED FASTENERS

AS REQUIRED

FIRESTONE OR VA APPROVED EQUAL INSULATION

COVERBOARD (AS REQUIRED)

FIRESTONE OR VA APPROVED EQUAL INSULATION

FIRESTONE OR VA APPROVED EQUAL INSULATION

COVERBOARD (AS REQUIRED)

FIRESTONE OR VA APPROVED EQUAL INSULATION

GASKET

SET BOLT IN SEALANT

SHEET METAL COVER

SUBSTRATE

FASTEN 8" [203 mm] O.C.

3" [76 mm] MIN

3" [76 mm] MIN

[2 m m

M

IN

NOTES:

1. REFER TO FIRESTONE OR VA APPROVED EQUAL WEBSITE FOR MOST CURRENT

INFORMATION.

2. WOOD NAILERS MUST BE INSTALLED WITH SUITABLE FASTENERS TO MEET APPLICABLE

BUILDING CODES (200 LBS PER LINEAR FOOT MIN IN ANY GIVEN DIRECTION).

3. ALL SHEET METAL IS TO BE INSTALLED PER SMACNA GUIDELINES.

4. GRANULES MUST BE EMBEDDED WHEN THERMALLY FUSING GRANULE SURFACED CAP

SHEET.

5. FLASHING LAPS MUST BE OFFSET FROM FIELD LAPS BY A MINIMUM OF 12" [305 mm]

SHEET-METAL SLEEVE

APPROPRIATE HIGH TEMPERATURE

SEALANT (SEE NOTE 2)

SHEET-METAL RAIN COLLAR

OVERLAPPING FLASHING

COLLAR BY 3" TO 4"

STAINLESS STEEL CLAMPING RING

TREATED WOOD BLOCKING

ROOF DECK

SPECIFIED COVER BOARD

SPECIFIED INSULATION

SPECIFIED BUR MEMBRANE

TWO-PLY STRIPPING

4" MIN. FLANGE SET IN ASPHALT

CEMENT AND MECHANICALLY

FASTENED 3" OC

BATTEN INSULATION

MASTIC SEAL AT PERIMETER

EXISTING INSULATED

METAL LINER (SEE NOTE 3 )

HOT STACK

NOTES:

1. PRIME ALL METAL SURFACES THAT WILL COME INTO CONTACT WITH THE SPECIFIED ADHESIVE.

2. WHEN HOT STACK SERVICE TEMPERATURE EXCEEDS 400 DEGREES, WELD OR SOLDER RAIN COLLAR TO PIPE IN LIEU OF

INSTALLING SEALANT.

3. THE CLEARANCE REQUIRED BETWEEN THE HOT PIPE AND INSULATED METAL LINER WILL DEPEND ON THE TEMPERATURE

OF THE MATERIAL HANDLED BY THE STACK.

8" MIN

[200mm]

WOOD NAILER SECURED TO DECK WITH

APPROPRIATE FASTENERS, 2 ROWS

STAGGERED EACH ROW 24'' OC SPECIFIED BUR MEMBRANE

INSULATION

ROOF DECK AS SPECIFIED

GRAVEL SURFACING

TWO-PLY STRIPPING

FLANGE SET IN SPECIFIED ASPHALT

CEMENT, MECHANICALLY FASTENED 3''

OC, PRIME METALFLANGE BEFORE

STRIPPING

SLOPE PIPES DOWN AND

AWAY FROM HOOD

FASTENERS 8'' OC

SHEET METAL COLLAR

SEAL

INSULATE INSIDE OF

METAL WORK

SHEET METAL HOOD

CROSS BREAK OR

SLOPE FOR DRAINAGE

METAL

SCREW

SEAL

ENCLOSURE DETAIL

ASPHALT CEMENT SEAL

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Spinklered

NOT TO SCALE

B

IM

/V

IS

N

A E

S e rv ic e s

A ir H a n d lin g U n it s /A

E S e rv ic e s

A H

U .r v t

/2

/2

:1

:3

A

M

ARCHITECTURAL DETAILS

GC EM

CONSTRUCTION DOCUMENTS 657-19-113JC

AE200

REPLACE OBSOLETE AND FAILING

AIR CONDITIONING UNITS

ST. LOUIS, MO

APRIL 29, 2020

ST. LOUIS,

MO

SPRINKLERED

NTS

CURB FLASHING WITH TPO ROOF

NTS

ROOF TYPICAL EQUIP CURB WITH TPO ROOF

NTS

EQUIPMENT CURB W/MODIFIED BITUMEN ROOF

NTS

EQUIPMENT SUPPORT CURB W/MODIFIED BITUMEN ROOF

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.02

NTS

PIPE PENETRATION DETAIL

NTS

PIPE HOOD PENETRATION DETAIL

Revisions: Date: 04/29/2020

Phase

CONTRACT DOCUMENTS FOR

BIDDING

NOT FOR

MECHANICAL NOTES

WEATHER DESIGN DATA

38.8 N

LATITUDE

95.5° F Db SUMMER 76.8° F Wb SUMMER 6.6° F Db WINTER

EXTREME OUTDOOR DESIGN CONDITIONS

(FOR EQUIPMENT PERFORMANCE

RATINGS AND FREEZE PROTECTION)

90.4 W

LONGITUDE

564 FEET

ABOVE SEA LEVEL

OUTDOOR DESIGN

TEMPERATURES

99.9° F Db SUMMER

0.7° F Db WINTER

SITE GEOGRAPHIC LOCATION DATA:

VAMC ST. LOUIS JOHN COCHRAN

SEISMIC DESIGN REQUIREMENTS

OCCUPANCY:

SDS =

SD1 =

SEISMICITY:

RISK CATEGORY:

SEISMIC DESIGN CAT., SDS:

SEISMIC DESIGN CAT., SD1:

SEISMIC IMPORTANCE FACTOR:

HOSPITAL WITH SURGERY - IBC 1604

CRITICAL FACILITY VA H-18-8, TABLE 5

0.423 VA H-18-8

0.164 VA H-18-8

MOD. HIGH VA H-18-8

IV IBC TABLE 1604.5

D IBC TABLE 1613.3.5

D IBC TABLE 1613.3.5

1.5 ASCE 7-10, TABLE 1.5-2

PRESCRIBED REQUIREMENTS:

H-18-8, 4.2:

H-18-8 MECHANICAL:

SMACNA SEISMIC RESTRAINTS GUIDELINES:

EQUIPMENT REQUIRED TO HAVE "SPECIAL

SEISMIC CERTIFICATION"

SPECIAL SEISMIC CERTIFICATION (ASCE 7, 13.2.2)

FOR AHU, CHILLER, COOLING TOWER, CTRL

PANEL.

(COMPLIANCE REQUIRED BY VA HVAC DESIGN

MANUAL)

DATA SOURCE: VA HVAC DESIGN GUIDE

*SEE SPECIFICATIONS SECTION 13 05 41 FOR ADDITIONAL SEISMIC DESIGN REQUIREMENTS.

MH100

MH100

DRAWING SYMBOLS

01-SF-3

08-TU-1-1

DETAIL NUMBER (VIEW # ON SHEET SHOWN)

TYPICAL UNIT NO.

BUILDING NO. WHERE EQUIPMENT IS LOCATED

EQUIPMENT ABBREVIATION (SUPPLY FAN)

ITEM NUMBER (TERMINAL UNIT NO. 1)

EQUIPMENT ABBREVIATION (TERMINAL UNIT)

SERVED BY (AIR HANDLER UNIT NO. 1)

DRAWING NUMBER ON SHEET SHOWN

BUILDING NO. WHERE EQUIPMENT IS LOCATED

SECTION NUMBER (VIEW # ON SHEET SHOWN)

DRAWING NUMBER ON SHEET SHOWN

ITEM NUMBER (SUPPLY FAN NO. 1)

LIMIT OF DEMOLITION

SUPPLY DUCT UP

EXHAUST DUCT UP

CEILING SUPPLY DIFFUSER/GRILLE (SQUARE 4-WAY):

DIFFUSER/GRILLE TYPE

BALANCED FLOW RATE

• REFER TO AIR DEVICE SCHEDULE (SUPPLY)

SUPPLY TOP REGISTER OR GRILLE (WALL MOUNT)

EXHAUST OR RETURN CEILING REGISTER OR GRILLE

EXHAUST OR RETURN BOTTOM

REGISTER OR GRILLE (WALL MOUNT)

EXHAUST OR RETURN REGISTER OR

TOP GRILLE (WALL MOUNT)

CONNECT NEW DUCT TO EXISTING DUCT

D

INCLINED RISE, IN DIRECTION OF AIR FLOW

INCLINED DROP, IN DIRECTION OF AIR FLOW

R

RETURN DUCT UP

SUPPLY DUCT DOWN

EXHAUST DUCT DOWN

RETURN DUCT DOWN

FC

10"x8" <OR> 10"x8"SA

FLEXIBLE CONNECTION (FC) - EQUIPMENT,

VIBRATION, OR SEISMIC

VANED ELBOW (PROVIDE ALL SQUARE OR

RECTANGULAR ELBOWS. VANE SYMBOL ARE NOT

SHOWN ON PLANS)

VANED ELBOW (SHORT RADIUS)

STANDARD RADIUS ELBOW (LONG RADIUS)

DUCT LABELING NOTE:

• INSIDE DIMENSIONS: WIDTH x DEPTH

• SA = SUPPLY AIR

• RA = RETURN AIR

• OA = OUTSIDE AIR SUPPLY

• EA = EXHAUST AIR

EXISTING DUCT TO REMAIN

VD

MANUAL VOLUME DAMPER

EXISTING DUCT TO BE REMOVED

10"x8"(EX) <OR> 10"x8"SA(EX)

10"x8"

HVAC SYMBOLS

NEW DUCT

CEILING RETURN/EXHAUST GRILLE:

DIFFUSER/GRILLE TYPE

BALANCED FLOW RATE

• REFER TO AIR DEVICE SCHEDULE (RETURN)

SD-14

470 CFM

REDUCER OR INCREASER

DIRECTION OF FLOW

SIDE CONNECTION

BOTTOM CONNECTION, 45° OR 90°

TOP CONNECTION, 45° OR 90°

DIRECTION OF PIPE PITCH (DOWN)

UNION

RISE OR DROP IN PIPE

CAPPED OUTLET

PRESSURE GAGE

THERMOMETER

PIPE UP

PIPE DOWN

CONDENSATE PUMP DISCHARGE

LOW PRESSURE STEAM CONDENSATE RETURN

LOW PRESSURE STEAM (15 PSIG AND BELOW)

MEDIUM PRESSURE STEAM CONDENSATE RETURN

MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)

SANITARY WASTE

REFRIGERANT PIPING

DRAIN LINE

MPS

MPR

LPS

LPR

PC

SAN

REF

D

NEW PIPE

EXISTING PIPE TO BE REMOVED

EXISTING PIPE TO REMAIN (?=SIZE/TYPE, EX=EXISTING)

PIPING SYMBOLS

CHILLED WATER SUPPLYCHS

CHILLED WATER RETURNCHR

?" (EX)

FIRE PROTECTION (WET)FP

HIGH PRESSURE STEAM CONDENSATE RETURN

HIGH PRESSURE STEAM (60 PSIG AND GREATER)HPS

HPR

BALL VALVE

GATE VALVE WITH 3/4" HOSE ADAPTER

CHECK VALVE

ANGLE GLOBE VALVE

BUTTERFLY VALVE

MODULATING CONTROL VALVE

TWO POSITION CONTROL VALVE

THREE-WAY MODULATING CONTROL VALVE

AUTOMATIC BALANCING CONTROL VALVE

PRESSURE SAFETY VALVE

GATE VALVE - THREADED/FLANGED

GLOBE VALVE - THREADED/FLANGED

PRESSURE REGULATING VALVE

THREE-WAY TWO POSITION CONTROL VALVE

WYE STRAINER (WITH BALL VALVE &

HOSE CONNECTION)

FLEXIBLE CONNECTION

CIRCUIT SETTER VALVE

PRESSURE REDUCING VALVE (PRV)

WYE STRAINER WITH VALVED DRAIN AND

QUICK-COUPLE HOSE CONNECTOR

PIPING (VALVE) SYMBOLS

1. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A COMPLETE HEATING, VENTILATING, PLUMBING AND COOLING

SYSTEM WHICH MEETS ALL GOVERNING CODES AND IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.

2. ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF: THE INTERNATIONAL MECHANICAL CODE (IMC), THE NATIONAL FIRE

PROTECTION ASSOCIATION (NFPA), AND UNDERWRITER'S LABORATORIES (U.L.).

3. WORK SHALL CONFORM TO THE STANDARDS OF THE ASSOCIATION OF HEATING, REFRIGERATING, AND AIR CONDITIONING ENGINEERS (ASHRAE), SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION (SMACNA), AND THE

ASSOCIATED AIR BALANCE COUNCIL (AABC).

4. THE CONTRACTOR SHALL PAY FOR ALL FEES, PERMITS, AND CHARGES AS REQUIRED TO FURNISH AN APPROVED

INSTALLATION.

5. MECHANICAL WORK SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE.

6. CONTRACTOR SHALL ELECTRONICALLY SUBMIT FOR REVIEW OF ALL EQUIPMENT, DEVICES, AND MATERIALS USED FOR THE JOB. ALLOW A MINIMUM OF 14 DAYS REVIEW TIME FOR SCHEDULING PURPOSES. WHEN REQUESTED, SUBMIT ANY PRODUCT

SAMPLES TO ARCHITECT FOR REVIEW.

7. PROPOSED "OR EQUAL" PRODUCT SUBSTITUTIONS MUST BE SUBMITTED IN WRITING FOR APPROVAL AND MUST BE APPROVED

IN WRITING BY THE CONTRACTING OFFICER'S REPRESENTATIVE (COR).

8. PROVIDE ACCESS PANELS IN DUCTS, WALLS, AND CEILINGS AS REQUIRED TO ACCESS AND MAINTAIN DAMPERS, VALVES, AND OTHER ENCLOSED ITEMS. COORDINATE LOCATION OF ALL ACCESS PANELS WITH ENGINEER THROUGH SHOP DRAWING

PROCESS.

9. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM, TERMINAL UNITS, FILTERS, COILS, ETC. LOSS

FOR FILTERS SHALL BE FOR FILTERS AT 50% LOADING.

10. SEISMIC PROVISIONS - REFER TO SEISMIC DESIGN REQUIREMENTS TABLE.

11. ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS OTHERWISE NOTED.

COORDINATION REQUIREMENTS:

12. THE CONTRACTOR IS REQUIRED TO VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING CONDITIONS PRIOR TO SUBMITTING

A BID.

13. THE DRAWINGS MAY NOT SHOW ALL EXISTING ITEMS OR CONDITIONS. CONTRACTOR SHALL NOT RECEIVE EXTRA PAYMENT FOR REQUIREMENTS WHICH CAN BE INFERRED THROUGH OBSERVATION OF EXISTING CONDITIONS. WHERE EXISTING CONDITIONS ARE ENCOUNTERED WHICH MAY VARY SIGNIFICANTLY FROM THOSE INDICATED IN THE DRAWINGS, NOTIFY THE

DESIGNER BEFORE PROCEEDING WITH WORK.

14. CONTRACTOR SHALL FIELD VERIFY BY MEASUREMENTS THE EXACT LOCATION OF EQUIPMENT, DUCTWORK, PIPING, STRUCTURE, AND OTHER CONDITIONS WHICH WILL AFFECT INSTALLATION. CONTRACTOR SHALL LOCATE EQUIPMENT AND ROUTE DUCTWORK AND PIPING TO AVOID CONFLICTS AND IN REFERENCES WITH EXISTING FIELD CONDITIONS.

15. PRIOR TO ANY INSTALLATION, CLOSELY COORDINATE ALL MECHANICAL WORK WITH PLUMBING, ELECTRICAL, FIRE PROTECTION, ARCHITECTURAL AND STRUCTURAL WORK. CONTRACTOR TO ENSURE ALL EQUIPMENT AND SERVICES WILL FIT IN AVAILABLE SPACES ALLOWING CEILING HEIGHTS INDICATED ON ARCHITECTURAL PLANS. INSTALL EQUIPMENT SO AS TO PROVIDE CLEARANCES SHOWN ON DRAWINGS AND AS RECOMMENDED BY MANUFACTURER FOR AIRFLOW, SERVICE, MAINTENANCE, AND FILTER REMOVAL AS APPLICABLE.

16. COORDINATE DUCT, PIPING, AND EQUIPMENT LOCATIONS WITH ELECTRICAL PANEL LOCATIONS. DO NOT PASS ANY MECHANICAL OR PLUMBING ITEMS DIRECTLY OVER ELECTRICAL PANELS. SEE ELECTRICAL DRAWINGS FOR EXACT PANEL

LOCATIONS.

17. CEILING DIFFUSER AND REGISTER LOCATIONS ARE APPROXIMATE ONLY. EXACT LOCATIONS TO BE DETERMINED BY EXISTING CONDITIONS. COORDINATE EXHAUST BRICK VENT MOUNTING HEIGHTS AND LOCATIONS WITH ARCHITECTURAL CEILING

HEIGHTS.

18. ALL CUTTING AND PATCHING SHALL BE COORDINATED WITH THE GENERAL CONTRACTOR. ALL PATCHING SHALL RESTORE

EACH DAMAGED SURFACE TO ITS ORIGINAL FINISH.

DUCTWORK:

19. ALL AIR DISTRIBUTION SYSTEMS SHALL BE TESTED AND BALANCED IN ACCORDANCE WITH AABC REQUIREMENTS TO WITHIN FIVE PERCENT (5%) OF THE VALUES SHOWN ON THE DRAWINGS. A COMPLETED ELECTRONIC VERSION OF CERTIFIED TEST AND BALANCE (TAB) REPORT SHALL BE GIVEN TO THE ENGINEER FOR REVIEW PRIOR TO PROJECT CLOSE OUT.

20. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED. DUCT SIZES ARE NET INSIDE

DIMENSIONS.

21. LOW-PRESSURE DUCT RUNOUTS TO DIFFUSERS AND REGISTERS TO BE AS NOTED UNLESS OTHERWISE INDICATED ON PLANS.

CONTRACTOR TO PROVIDE A TRANSITION AT NECK OF EACH TERMINAL DEVICE.

22. WHERE BRANCH TAPS OCCUR, PROVIDE INDIVIDUAL SPIN-IN FITTINGS WITH MANUAL VOLUME DAMPERS FOR BALANCING. DO NOT USE E-TYPE WITH AIR SCOOP/EXTRACTOR. ADDITIONALLY, PROVIDE OPPOSED-BLADE VOLUME DAMPERS AT EACH AIR

TERMINAL DEVICE.

23. SUPPLY DUCT LOCATED IN UNCONDITIONED SPACE IS TO BE EXTERNALLY INSULATED WITH 1-1/2" THICK, 1LB. DENSITY, FLEXIBLE, FACTORY-REINFORCED GLASS FIBER BLANKET WITH FOIL-FACED VAPOR BARRIER JACKET. SEAL ALL SEAMS, RIPS, TEARS, STAPLES, ETC. IN VAPOR BARRIER WITH VAPOR BARRIER MASTIC EMBEDDED WITH FIBERGLASS MESH CLOTH.

PRESSURE-SENSITIVE ADHESIVE NOT ALLOWED. REFER TO SPECIFICATION FOR CONDITIONED SPACE INSULATION.

24. ALL DUCT DIMENSIONS SHOWN ON DRAWINGS ARE INSIDE CLEAR. ALLOWANCE MUST BE MADE IN SHEET METAL SIZE WHERE

DUCT LINER IS SPECIFIED.

25. PROVIDE STANDARD METAL-EDGED FLEXIBLE DUCT CONNECTORS BETWEEN AIR HANDLERS AND FANS AND CONNECTING DUCTWORK. CONNECTORS SHALL BE CONSTRUCTED AS FOLLOWS: FLEXIBLE CONNECTOR OF FLAME-RETARDANT OR NONCOMBUSTIBLE FABRICS, COATINGS AND ADHESIVES COMPLYING WITH UL 181, CLASS 1. FACTORY-FABRICATED STRIP OF FABRIC 3-1/2 INCHES WIDE ATTACHED TO 2 STRIPS OF 3-3/4 INCH WIDE, 24-GAUGE GALVANIZED SHEET STEEL OR 0.032 INCH ALUMINUM SHEETS. SELECT METAL COMPATIBLE WITH CONNECTED DUCT SYSTEM, FOLD AND CRIMP METAL EDGE SHEETS ONTO FABRIC AS ILLUSTRATED IN LATEST EDITION OF SMACNA HVAC DUCT CONSTRUCTION STANDARDS. PROVIDE FLAT- BRAIDED GROUNDING STRAP 3/4 INCH WIDE OF SUFFICIENT LENGTH TO ALLOW FREE MOVEMENT OF THE CONNECTOR FABRIC, BRAIDED STRAP SHALL BE COPPER OR STAINLESS STEEL, SECURELY BONDED ELECTRICALLY TO DUCT AND TO

EQUIPMENT TO MAINTAIN CONTINUOUS GROUND ACROSS THE CONNECTOR.

26. SUPPORT ALL DUCTWORK WITH SUITABLE SHEARED GALVANIZED METAL OF 1” X 1/8” STEEL BAND IRON HANGERS ON EACH SIDE OF DUCT. SPACE HANGER MAXIMUM 8 FEET ALONG DUCT AND SECURE HANGER TO STRUCTURE AS REQUIRED.

PIPING:

27. PROVIDE REFRIGERANT PIPING INSTALLED PER THE MANUFACTURER’S INSTRUCTIONS. COORDINATE WITH SPECIFICATIONS.

28. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO EQUIPMENT, SEE STANDARD EQUIPMENT DETAILS.

29. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO PROVIDE COUNTER FLOW BETWEEN

WATER AND AIR.

30. PROVIDE PIPING LABELS AND TAGS PER SPECIFICATION SECTIONS.

TERMINAL UNIT WITHOUT REHEAT COIL

MECHANICAL EQUIPMENT

HEATING COIL (STEAM)

MECHANICAL EQUIPMENT (IN GENERAL) - DEMOLITION

MECHANICAL EQUIPMENT (IN GENERAL) - NEW

COIL (HEATING OR COOLING, IF APPLICABLE)

MANUFACTURER'S RECOMMENDED

MAINTENANCE/OPERATIONAL CLEARANCE

KEYNOTE SYMBOL ON SHEET

KEYNOTE DESIGNATIONS

KEYNOTES

THIS IS AN EXAMPLE OF WHAT KEYNOTE 3 COULD BE. IT

MIGHT BE THE FIRST KEYNOTE ON A SHEET. IT MIGHT ALSO

SHOW ON MULTIPLE SHEETS.

THIS IS AN EXAMPLE OF WHAT KEYNOTE 7 COULD BE. IT

MIGHT ALSO SHOW ON MULTIPLE SHEETS.

THIS IS AN EXAMPLE OF WHAT KEYNOTE 22 COULD BE. IT

MIGHT ALSO SHOW ON MULTIPLE SHEETS.

KEYNOTE NUMBER (ON SHEET)

KEYNOTE DESCRIPTION

NOTE:

KEYNOTES RESIDE ON A 'MASTER' SCHEDULE FOR DEMOLITION AND NEW WORK.

THIS IS FURTHER BROKEN DOWN BY SHEET. ALL KEYNOTES MAY NOT PERTAIN

TO EACH SHEET, THEREFORE:

• ONLY KEYNOTES ON THE SHEET WILL BE LISTED IN THE KEYNOTE LEGEND.

• KEYNOTE MAY NOT BEGIN AT "1" FOR A SHEET.

• KEYNOTES MAY SKIP NUMBERS, BUT WILL LIST IN NUMERICAL ORDER FOR

THAT SHEET.

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Spinklered

B

IM

/V

IS

N

A E

S e rv ic e s

A ir H a n d lin g U n it s /A

E S e rv ic e s

A H

U M

E P

.r v t

/2

/2

:5 :2

P

M

MECHANICAL SYMBOLS, NOTES, AND

ABBREVIATIONS

ST DW

CONSTRUCTION DOCUMENTS 657-19-113JC

M-001

REPLACE OBSOLETE AND FAILING

AIR CONDITIONING UNITS

ST. LOUIS, MO

APRIL 29, 2020

ST. LOUIS,

MO

SPRINKLERED

ABBREVIATIONS

K - - - - - - - - - - - - - - - - - - - - - - - - - -

KG KILOGRAM

KPa KILOPASCAL

KW KILOWATT

L - - - - - - - - - - - - - - - - - - - - - - - - - -

LAT LEAVING AIR TEMPERATURE

LF LINEAR FOOT (FEET)

LPR LOW PRESSURE RETURN (STEAM CONDENSATE)

LPS LOW PRESSURE STEAM

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

M - - - - - - - - - - - - - - - - - - - - - - - - - -

MAX MAXIMUM

MBH 1,000 BTUH

MHP MOTOR HORSEPOWER

MIN MINIMUM

MM MILLIMETER

MPR MEDIUM PRESSURE RETURN (STEAM CONDENSATE)

MPS MEDIUM PRESSURE STEAM

MVD MANUAL VOLUME DAMPER

N - - - - - - - - - - - - - - - - - - - - - - - - - -

N/A NOT APPLICABLE

NC NORMALLY CLOSED

NO NORMALLY OPEN

NPSH NET POSITIVE SUCTION HEAD

NTS NOT TO SCALE

O - - - - - - - - - - - - - - - - - - - - - - - - - -

OA OUTSIDE AIR

OAD OUTDOOR AIR DAMPER

P - - - - - - - - - - - - - - - - - - - - - - - - - -

P PUMP

PC PUMPED CONDENSATE

PD PRESSURE DROP

PF PRE-FILTER

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH – GAGE

R - - - - - - - - - - - - - - - - - - - - - - - - - -

RA RETURN AIR

RAD RETURN AIR DAMPER

RC REHEAT COIL

RF RETURN FAN

RG RETURN GRILLE

RPM REVOLUTIONS PER MINUTE

RTU ROOF TOP UNIT

S - - - - - - - - - - - - - - - - - - - - - - - - - -

SA SUPPLY AIR

SAD SUPPLY AIR DIFFUSER

SF SUPPLY FAN

SHC STEAM HEATING COIL

SI SQUARE INCHES

SP STATIC PRESSURE

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT (FEET)

ST STEAM TRAP

SV STEAM PRESSURE REDUCING VALVE

T - - - - - - - - - - - - - - - - - - - - - - - - - -

TAB TESTING, ADJUSTING, BALANCE

V - - - - - - - - - - - - - - - - - - - - - - - - - -

V VALVE

VD VOLUME DAMPER (MANUAL OPPOSED BLADE)

VFD VARIABLE FREQUENCY DRIVE

VI VIBRATION ISOLATOR

VSD VARIABLE SPEED DRIVE

W - - - - - - - - - - - - - - - - - - - - - - - - - -

Wb WET-BULB (TEMPERATURE)

WG WATER GAGE

WPD WATER SIDE PRESSURE DROP

ABBREVIATIONS

A - - - - - - - - - - - - - - - - - - - - - - - - - -

ACCH AIR COOLED CHILLER

AFF ABOVE FINISHED FLOOR

AFMS AIR FLOW MEASURING STATION

AHU AIR-HANDLING UNIT

AMP AMPERE

AP ACCESS PANEL

ASHRAE AMERICAN SOCIETY OF HEATING REFRIGERATION

AIR CONDITIONING ENGINEERS

B - - - - - - - - - - - - - - - - - - - - - - - - - -

BHP BRAKE HORSEPOWER

BOB BOTTOM OF BEAM

BOD BOTTOM OF DUCT

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C - - - - - - - - - - - - - - - - - - - - - - - - - -

C CENTIGRADE (CELSIUS)

CC COOLING COIL

CCCD COOLING COIL CONDENSATE DRAIN

CD CEILING DIFFUSER

CFM CUBIC FEET PER MINUTE

CG CEILING GRILLE

CHP CHILLED WATER PUMP

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CP CONDENSATE PUMP

CU CONDENSING UNIT

DB DECIBELS

Db DRY-BULB TEMPERATURE

DDC DIRECT DIGITAL CONTROLS

DEG DEGREE

DEMO DEMOLISH

DIA DIAMETER

DPS DIFFERENTIAL PRESSURE SENSOR

DPT DEW POINT TEMPERATURE

E - - - - - - - - - - - - - - - - - - - - - - - - - -

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EWT ENTERING WATER TEMPERATURE

EX EXISTING

F - - - - - - - - - - - - - - - - - - - - - - - - - -

F FAHRENHEIT

FPM FEET PER MINUTE

FT FEET

FT-WC FEET OF WATER COLUMN

FV FACE VELOCITY

G - - - - - - - - - - - - - - - - - - - - - - - - - -

GPM GALLONS PER MINUTE

H - - - - - - - - - - - - - - - - - - - - - - - - - -

HC HEATING COIL

HP HORSEPOWER

HPR HIGH PRESSURE RETURN (STEAM CONDENSATE)

HPS HIGH PRESSURE SUPPLY (STEAM)

HR HOUR

HRW HEAT RECOVERY WHEEL

HSTAT HUMIDISTAT

HZ HERTZ

I - - - - - - - - - - - - - - - - - - - - - - - - - -

IN INCHES

IN-HG INCHES OF MERCURY

IN-LB INCH-POUND

IN-WC INCH WATER COLUMN

IN-WG INCH WATER GAUGE

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.02Revisions: Date: 04/29/2020

Phase

CONTRACT DOCUMENTS FOR

BIDDING

NOT FOR

LEGEND

KEYNOTES

GENERAL NOTES

OUTSIDE SPACE ABOVE

TELEPHONE SWITCHGEAR

A001

SERVER ROOM

A001A

PHONE ROOM

A001L

MECHANICAL ROOM

A002A

SERVER ROOM

A001A

1 1

01-ITCU-6(EX)01-ITCU-3(EX)

01-ITAC-3(EX)

01-ITAC-6(EX)

A R

E A

W E

LL

AREA WELL

(TYP.)

(TYP.)

NO SCOPE OF WORK ASSOCIATED

WITH THIS AREA

SCOPE OF WORK AREA AS

DESIGNATED/NOTED

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Spinklered

KEY PLAN

3PLAN NORTH

B

IM

/V

IS

N

A E

S e rv ic e s

A ir H a n d lin g U n it s /A

E S e rv ic e s

A H

U M

E P

.r v t

/2

/2

:5 :2

P

M

MECHANICAL DEMOLITION ENLARGED PLANS -

BLDG. 01, LEVEL 00

ST DW

CONSTRUCTION DOCUMENTS 657-19-113JC

MD100

REPLACE OBSOLETE AND FAILING

AIR CONDITIONING UNITS

ST. LOUIS, MO

APRIL 29, 2020

ST. LOUIS,

MO

SPRINKLERED

1/4" = 1'-0"1

ENLARGED MECHANICAL DEMOLITION PLAN -

BUILDING 01 - LEVEL 00 (TELEPHONE AREA)

1 EXISTING IT RACK AIR CONDITIONERS, CONDENSING UNITS AND

ALL ASSOCIATED REFRIGERANT PIPING TO BE REMOVED.

2 EXISTING RACK AIR CONDITIONERS AND ALL REFRIGERANT

PIPING TO BE REMOVED.

3 CUT CONDENSATE PIPING SERVING IT RACK UNITS AT CEILING

AND CAP FOR REUSE.

33 EXISTING EXTERIOR WALL PIPE PENETRATION SLEEVES TO

REMAIN FOR REUSE.

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.02

1. SEQUENCE REMOVAL AND REPLACEMENT OF IT RACK

COOLING SYSTEMS TO KEEP ESSENTIAL TELEPHONE

SERVICES IN SERVICE THROUGHOUT CONSTRUCTION.

COORDINATE SEQUENCING AND SCHEDULING WITH

PROJECT MANAGER AND GENERAL CONTRACTOR.

COORDINATE ELECTRICAL LOADS AND SOURCES WITH

NEAREST AVAILABLE PLUGS/PANELS. SEE COVER SHEET

FOR ADDITIONAL PHASING NOTES.

Revisions: Date: 04/29/2020

Phase

CONTRACT DOCUMENTS FOR

BIDDING

NOT FOR

GENERAL NOTES

01-ERW-1(EX)

96"x78"

"x

"x

40"x40"

40"x38"

"x

MECHANICAL ROOM

D302C

MECHANICAL ROOM

D302B

STAIR 06

S306

18"x14"(EX)

L P

S

C H

S

C H

R

L P

S

C H

S

C H

R

V(EX)

SAN(EX)

"x

E X

"x

E X

12"x12"(EX)12"x12"(EX)

"x

E X

"x

E X

01-AC-3(EX)

01-EF-19(EX)

S A

N (E

X

V (E

X

-R

F- 3(

E X

"x

"x

"x

"x

"x

-A

C -3

(E X

REF(EX)

REF(EX)

R E

F (E

X

R E

F (E

X

MD101

MD101

EXISTING 1 1/4" CWS

EXISTING 1 1/4" CWR

V(EX)

EXISTING 2" MPS

EXISTING 2" MPR

REMOVE

EXISTING OA

PRE-FILTER BANK 47

MECHANICAL ROOM

D303

REMOVE

EXISTING RA

PRE-FILTER BANK

03-AC-1(EX)

37 38

NO SCOPE OF WORK ASSOCIATED

WITH THIS AREA

SCOPE OF WORK AREA AS

DESIGNATED/NOTED

LEVEL 03 LEVEL 03LEVEL 03 LEVEL 03

12"x12"(EX)

12"x12" RA(EX)

01-EF-19(EX)

"x

"(E

X)

12"x12" RA(EX)

01-AC-3(EX)16"x12"

"x

18"x14"

12"x12"

12"x12"

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Spinklered

KEY PLAN

3PLAN NORTH

B

IM

/V

IS

N

A E

S e rv ic e s

A ir H a n d lin g U n it s /A

E S e rv ic e s

A H

U M

E P

.r v t

/2

/2

:5 :2

P

M

MECHANICAL DEMOLITION ENLARGED PLANS -

BLDG. 01, LEVEL 03 AND BLDG. 03, LEVEL 02

ST DW

CONSTRUCTION DOCUMENTS 657-19-113JC

MD101

REPLACE OBSOLETE AND FAILING

AIR CONDITIONING UNITS

ST. LOUIS, MO

APRIL 29, 2020

ST. LOUIS,

MO

SPRINKLERED

1/4" = 1'-0"1

ENLARGED MECHANICAL DEMOLITION PLAN -

BUILDING 01 - AC-3 AND AC-1 ENERGY RECOVERY WHEEL LEVEL 03 INTERSTITIAL

1/4" = 1'-0"2

ENLARGED MECHANICAL DEMOLITION PLAN -

BUILDING 03 - AC-1 ROOF

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.02

1. PROVIDE TEMPORARY COOLING FOR OFFICES SERVED BY

01-AC-3(EX). COORDINATE ELECTRICAL PLUG LOCATIONS

AND LOADS WITH PROJECT MANAGER AND GENERAL

CONTRACTOR. SEE COVER SHEET FOR PHASING NOTES.

2. PROVIDE TEMPORARY COOLING FOR OFFICES AND

CRITICAL SPACES SERVED BY 03-AC-1(EX). COORDINATE

COOLING REQUIREMENTS, ESSENTIAL COMMUNICATION

SYSTEM REQUIREMENTS AND ELECTRICAL PLUG

LOCATIONS/LOADS WITH PROJECT MANAGER AND

GENERAL CONTRACTOR. SEE COVER SHEET FOR PHASING

NOTES.

3. COORDINATE SHUT-DOWN OF 01-AC-1 WITH PROJECT

MANAGER AND GENERAL CONTRACTOR TO REPLACE

EXISTING ENERGY WHEEL AND DUCTWORK. SEE COVER

SHEET FOR PHASING NOTES.

4. COORDINATE 01-AC-3(EX) SHUT-DOWN SCHEDULE WITH

PROJECT MANAGER AND GENERAL CONTRACTOR. SEE

COVER SHEET FOR PHASING NOTES.

1/2" = 1'-0"

MECHANICAL SECTION - BUILDING 01 - AC-3 LOOKING SOUTH - DEMOLITION

10 DEMO EXISTING DUCTWORK TO POINT SHOWN. PREPARE

REMAINING DUCTWORK FOR NEW CONNECTION.

11 EXISTING PIPING NOT IN SCOPE OF WORK SHOWN FOR

REFERENCE ONLY.

12 APPROXIMATE LOCATION OF EXISTING CONTROL AND

ELECTRICAL PANELS TO BE REMOVED. COORDINATE WORK

WITH ELECTRICAL CONTRACTOR.

13 DEMOLISH EXISTING MPS/MPR AND CWS/CWR SERVING

01-AC-3 TO POINT SHOWN. PREPARE REMAINING PIPING FOR

NEW CONNECTION. EXISTING ISOLTION VALVES ARE LOCATED

IN 3RD FLOOR INTERSTITIAL SPACE. COORDINATE SHUT-DOWN

OF EXISTING SYSTEMS SERVED BY ISOLATION VALVES.

14 EXISTING TCP-AC-03 CONTROL PANEL AND ASSOCIATED

WIRING TO BE REMOVED AND DISCARDED.

15 REMOVE AND DISPOSE OF 01-AC-03 AND ALL ASSOCIATED

ACCESSORIES AND CONTROLS, INCLUDING: FAN, COILS, DUCT,

PIPING, TO LIMITS OF ROOM. AFTER REMOVAL OF

DUCT/PIPING, PROTECT OPENINGS UNTIL REPLACEMENT

PRODUCTS ARE READY TO BE CONNECTED TO EXISTING

SYSTEMS. REMOVE (3) EXISTING HOUSEKEEPTING PADS

ASSOCIATED WITH EXISTING 01-AC-03.

34 REMOVE AND DISPOSE OF INLINE RETURN AIR FAN, RF-3.

35 REMOVE EXISTING RF-3.

37 REMOVE AND DISPOSE OF ROOFTOP UNIT WHEN NEW UNIT IS

READY TO BE SET IN PLACE. CAP AND SEAL CWS/CHR, STEAM

PIPING AND DUCTWORK WHILE UNIT IS BEING SET IN PLACE.

SEE ARCHITECTURAL PLANS FOR ROOF WORK AND CEILING

WORK BELOW.

38 REMOVE ASSOCIATED PNEUMATIC CONTROL BOX AND

COMPONENTS SERVING 03-AC-1(EX). EXISTING CONTROL

PANEL LOCATED IN BASEMENT TECHNOLOGY ROOM B06.

39 EXISTING ENERGY WHEEL, CONTROLS, DUCTWORK AND

ASSOCIATED COMPONENTS TO BE REMOVED TO POINTS

INDICATED.

47 EXISTING HOUSEKEEPING PAD TO REMAIN.

49 EXISTING REFRIGERATION LINES TO REMAIN.

50 EXISTING IN-LINE FANS, DUCTWORK, AND ASSOCIATED

CONTROLS TO REMAIN.

67 HAZARDOUS MATERIALS REPORT INDICATES A TAN ASBESTOS

CONTAINING SEALANT TO BE PRESENT ON THE EXISTING

SYSTEM'S DUCTWORK. REFER TO REPORT FOR SPECIAL

DEMOLITION PROCEEDURES.

Revisions: Date: 04/29/2020

Phase

CONTRACT DOCUMENTS FOR

BIDDING

NOT FOR

GENERAL NOTES

01-CU-17(EX)

MH200

MH200

EXISTING OUTDOOR AIR INTAKE

HOOD TO REMAIN AND BE

REUSED.

EXISTING ROOF ACCESS

DOOR TO REMAIN.

45 46

EXISTING ROOF DEMO

AREA

01-AC-17(EX)

MH200

MH200

MH200

MH200

28"ø SA

18"ø

16"ø SA

MECHANICAL ROOM AC-17

D303A

18"ø

01-CH-1(EX)

EXISTING MPS/R PIPING

TO EXISTING UNIT HEATER

IN ADJACENT SPACE. PIPING

TO REMAIN

EXISTING MPS/R PIPING

TO REMAIN

(TYP.)

EF-17(EX)

REMOVE

EXISTING 2"

CONDENSATE

REMOVE EXISTING

3/4" STEAM

CONDENSATE

MP203

DEMOILTION

PIPING

DIAGRAM

NO SCOPE OF WORK ASSOCIATED

WITH THIS AREA

SCOPE OF WORK AREA AS

DESIGNATED/NOTED

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Spinklered

KEY PLAN

3PLAN NORTH

B

IM

/V

IS

N

A E

S e rv ic e s

A ir H a n d…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .