These are engineering drawings for the Town of Oxford Water System Improvement SCADA Rehabilitation project located in Talbot County, Maryland. The project encompasses the installation of new sensors in existing water storage tanks at two locations (Tilghman Street and JL Thompson Drive), the integration of new SCADA software, and the connection of signals into the Town's existing SCADA system. The drawings detail electrical system modifications including the removal and replacement of existing load centers with new Square D QO load centers, installation of new tank level pressure transducers with 3-conductor shielded cabling, new SCADA antennas mounted to tank antenna corrals, and the coordination of signal transmission to existing remote terminal units (RTUs). The project involves upgrades to the control room electrical infrastructure at both the water tank site and the wastewater treatment plant facility, with work including conduit installation, wiring modifications, and equipment replacement to accept new input signals from the upgraded sensors.
The technical specifications indicate that all workstation equipment shall be replaced with current manufacturer model equipment, with detailed coordination required with equipment manufacturers and suppliers for signal re-transmission capabilities. The drawings reference specification section 16900 for scope details and Division 13, sections 13900, 13950, and 13990 for specific implementation details. Construction details are included for erosion and sediment control measures, including stabilized construction entrance, silt fence, and super silt fence installations. The project documentation was prepared by an engineering firm with offices in Baltimore and Easton, Maryland, with drawing dates of April 10, 2026, and revision dates of June 23, 2026.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Oxford Water System SCADA Specifications Signed 06-26.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CO
TALBOT COUNTY, MARYLAND
LOCATION MAP
OXFORD WATER SYSTEM IMPROVEMENTS
SCADA REHABILITATION
TOWN OF OXFORD
ENGINEER'S CERTIFICATION
OWNER'S CERTIFICATE
SCALE: 1" = 800 FT
VICINITY MAP
SCALE: 1" = 8 MILES
6/23/20266/23/26
EX. WIREWAY
EX
PCP
RX. QO LOAD CENTER
100A MAIN, 16 POLE
RX. SIEMENS BOX
EX. TB-S23 (911 COMMUNICATIONS
PANEL)
EX. SERVICE (240/120V,
1Ø, 3 WIRE SERVICE)
EX. CUTLER-HAMMER
DISCONNECT (240V,
2P., 100A.)
RX. BLUE ALARM LIGHT
CHLORINE
ROOM
RTU-TST
RX.
CONTROL
ROOM
LC-5
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
E
S D
S D
SD
SD
SD
RX. ELECTRIC BOX
WATER TOWER
CHAINLINK FENCE
WOOD POST WITH
ELECTRIC BOX
TELEPHONE JUNCTION
BOX
ELECTRICAL EQUIPMENT
TRANSFORMER
TILG
HMAN ST
30665-05219
CONCRETE PEDESTAL
LIGHT POLE
324 TILGHMAN ST.
OXFORD, MARYLAND
SIGN
EX. WELL HOUSE - REFER
TO 1/2" SCALE PLAN,
THIS SHEET
BREAKERS
"LC" 240/120V., 1 Ø, 3 WIRE
FOR
CONTROL RM. HTR.
PANEL SCHEDULE :
RTU-TST
VERIZON NETWORK
SPARE
NO.
FRM. P
INTERIOR LIGHTS
SPARE
FIRE DEPT. SIREN
TOWER SUMP PUMP
TRIP NO.
FOR
A. BUS CAPACITY
A. MAIN BREAKER
BREAKERS
FRM.
P TRIP
1100 20
1100 20
1100 20
1100 20
2100 60
1100 20
1100 20
2100 20
1100 20
2100 20
1100 20
1100 20
1100 20 EXT. HOSE BIB HT. TRACE
SPACE W/ BUS17 18 1- -1- -
19 20 - -1- -
SPARE
SPACE W/ BUS
SPARE
SPACE W/ BUS
CHLORINE ROOM
1SPACE W/ BUS
SPARE
Baltimore, Maryland Easton, Maryland
(410)832-2420
(410)822-8688
1220 East Joppa Road, Suite 223 Towson, MD 21286
NO. DATE REVISIONS
SHEET NO.
TOWN OF OXFORD
TALBOT COUNTY, MARYLAND
P
Jo b s\
\2
O xf o rd
W a te r Im p ro v -D e s\
D w g s\
E le c\ E
-1 .d w g A p r
:0 p m
P A T H
OXFORD WATER SYSTEM IMPROVEMENT
SCADA REHABILITATION
SHEET NOTES:
INCLUDING ASSOCIATED CONDUIT/WIRING BACK TO ORIGIN.
SAME CIRCUIT NUMBER/EQUIPMENT AS EX. LC PANEL.
REMOVE & REPLACE IN KIND W/A NEW SQUARE D QO LOAD
CENTER AS SCHEDULED ON THIS SHEET.
RX. PCP. RETAIN EX. TANK LEVEL PRESSURE LINE FOR
CONNECTION TO NEW TANK LEVEL PRESSURE TRANSDUCER.
NEW SCADA ANTENNA. SECURELY MOUNT TO NEW TANK
ANTENNA CORRAL.
ANTENNA CABLE IN 1 1/4" C. TO RTU-TST.
NEW TANK LEVEL PRESSURE TRANSDUCER.
3/C #18 SHIELDED CABLE IN 3/4" C. TO RTU-TST FOR TANK
LEVEL SIGNAL.
TILGHMAN ST. TANK SITE PLAN,
EX. WELL HOUSE PLAN LEGEND &
PANEL SCHEDULE
J , J.B. JUNCTION BOX
SPECIAL DEVICE OR EQUIPMENT AS NOTED.
WEATHERPROOF
VOLT OR VOLTS
POLE OR POLES
TO BE REMOVED
MOTOR CONTROL CENTER
WP.
V.
P.
T.B.R.
MCC
PCP
CONDUIT-IN OR ON
CEILING OR WALLS
CONDUIT-IN OR
UNDER FLOOR SLAB OR
UNDERGROUND.
HOMERUN TO PANEL - NO. OF ARROWS
INDICATES NO. OF CIRCUITS AND NO. OF
CROSSLINES INDICATES NO. OF #12
CONDUCTORS.
DENOTES REFERENCE TO SHEET NOTE.
PANELBOARD
2#12 & 1
#12GND.-3/4"C.
UNLESS
OTHERWISE
NOTED
EX. CONDUIT/WIRING TO BE REMOVED
EX. CONDUIT/WIRING TO REMAINEX
X
SURGE SUPPRESSER
PUMP CONTROL PANEL
AMP OR AMPERES
CONDUIT
PHASE
A.
C.
Ø
EXISTINGEX.
MCB MAIN CIRCUIT BREAKER
TYPICALTYP.
REMOVE EXISTINGRX.
KILOVOLT AMPERESKVA
GROUNDGND.
S /S
PT PRESSURE TRANSDUCER
REMOTE TERMINAL UNITRTU
PROGRAMMABLE LOGIC CONTROLLERPLC
OPERATOR INTERFACE TERMINALOIT
EX.
OFFICE
EX. PUBLIC
WORKS BLDG.
EX. ELEVATED WATER
STORAGE TANK
EX. MANAGER'S
WORK STATION
OITPLC RADIO S
S/
ETHER-
NET
SWITCH
PT
TANK LEVEL
PRESSURE
TRANSDUCER
PRESSURE TUBING
EX. EX.
120V. POWER
SUPPLY, LC-5
RTU-TST
ANTENNA CABLE IN 1 1/4" C.
ANTENNA SURGE
SUPPRESSOR
EX. PRESSURE LINE
FROM WATER TANK
ANTENNA SECURED TO
TANK CORRAL STRUCTURE
SIGNAL TO WWTP
CONTROL BLDG. &
RTU1
CONNECT TO
EXISTING
FUTURE 120V., 20A. CIRC.
FROM EX. PNL "LC".
FUTURE
TANK MIXER
CONTROLLER
FUTURE 4-20MA ANALOG SIGNAL
PLC
EX.
SIEMENS (WHEL-TECH INC.)
OIT
ETHERNET
SWITCH
EX. RTU3
RE-TRANSMITTED WATER
TANK LEVEL (3/C #18
SHIELDED CABLE IN 3/4" C.)
EX.
FIBER
BREAKOUT
BOX
EX.
EX.
EX. WELL
PUMP
CONTROL
PANEL
FUTURE
TANK MIXER
CONTROLLER
FUTURE 4-20MA ANALOG SIGNAL
FUTURE 120V., 20A. CIRC.
FROM EX. PNL "D".
PRINTER
MONITOR
UPS
INTERNET
ROUTER
KEYBOARD
CPU
ETHERNET TO RTU: MANAGER'S TO RTU3,
SCADA TO RTU1.
MANAGER'S WORK STATION
ONLY
MOUSE
Baltimore, Maryland Easton, Maryland
(410)832-2420
(410)822-8688
1220 East Joppa Road, Suite 223 Towson, MD 21286
NO. DATE REVISIONS
SHEET NO.
TOWN OF OXFORD
TALBOT COUNTY, MARYLAND
P
Jo b s\
\2
O xf o rd
W a te r Im p ro v -D e s\
D w g s\
E le c\ E
-2 .d w g A p r
:0 p m
P A T H
OXFORD WATER SYSTEM IMPROVEMENT
SCADA REHABILITATION
SHEET NOTES:
EX. MTD (MICRO-TECH DESIGNS, INC.) RTU3. COORDINATE
WITH THE MANUFACTURER/SUPPLIER TO UPGRADE THE EX.
RTU AS NEEDED TO ACCEPT THE NEW INPUT SIGNALS
DESCRIBED BELOW.
EX. SIEMENS (WHEL-TECH, INC.) WELL PUMP CONTROL PANEL.
COORDINATE WITH PANEL MANUFACTURER/SUPPLIER TO
PROVIDE RE-TRANSMISSION OF THE WATER TANK LEVEL
SIGNAL TO RTU3.
EX. PANEL "D", 240/120V., 1Ø, 3 WIRE.
REFER TO WORK STATION LAYOUT DETAIL, THIS SHEET.
EX. CONTROL BLDG.
EX. SCADA WORK
STATION
EX. RTU1
PARTIAL WWTP SITE PLAN &
CONNECTION/COMMUNICATION
DIAGRAMS
ALL WORK STATION EQUIPMENT SHALL BE REPLACED W/THE MANUFACTURER
CURRENT MODEL EQUIPMENT. REFER TO SPECIFICATION SECTION 16900 FOR
SCOPE & DIVISION 13, SECTIONS 13900, 13950 & 13990 FOR SPECIFIC DETAILS.
NOTE:
DETAIL B-1 STABILIZED CONSTRUCTION
ENTRANCE
DETAIL E-1 SILT
FENCE
DETAIL E-1 SILT
FENCE
DETAIL E-3 SUPER SILT
FENCE
| G-1 TITLE SHEET.pdf |
| Sheets and Views |
| G-1 TITLE SHEET |
| ESC-1-ESC DETAILS.pdf |
| Sheets and Views |
| ESC DETAILS |
| ESC-2-ESC NOTES.pdf |
| Sheets and Views |
| ESC NOTES |
File details come from the government source that posted it. Updated .