TFD_FSSSS_4-29-26.pdf
PDF 211 KB Posted
- Solicitation number
- RFP #27024
- Issued by
- Greenville County, South Carolina
About this file
This is a Fire Sprinkler System Specification Sheet prepared for the Tigerville Fire Department in Travelers Rest, South Carolina (Greenville County) in accordance with state regulation 40-10-250. The project involves the installation of underground piping to the building and a complete wet pipe sprinkler system. The facility contains approximately 3,000 square feet across two hazard areas: a Light Hazard area of 1,500 square feet (offices, restrooms, corridors, training room, break room, daycare, game room, and bunk rooms) and an Ordinary Hazard (Group 1) area of 1,500 square feet (truck bays, storage, mechanical spaces, yard equipment, fluid room, and gear room). The design utilizes NFPA 13 (2019), IBC (2021), and IFC (2021) standards and incorporates seismic design parameters with Site Classification D and Seismic Design Category C. Water supply is provided through municipal dead-end service with flow test data from December 1, 2020, showing static pressure of 150 psi, residual pressure of 82 psi, and flow capacity of 1,384 gpm from a 6-inch pipe connection tested by Mason Fraize of BRRWC.
The specification sheet indicates design parameters for Area 1 (Light Hazard) with 0.10 gpm/ft² density and inside hose flow of 0 gpm with outside hose flow of 100 gpm, and for Area 2 (Ordinary Hazard) with 0.15 gpm/ft² density and inside hose flow of 0 gpm with outside hose flow of 250 gpm. The project does not include a new fire pump or on-site water storage. Engineering services were provided by Warren E. Maddox, P.E., through Maddox Engineering, Inc., located in Greenville, South Carolina. The specification sheet was signed and dated April 29, 2026, and serves as the technical basis for contractor proposals submitted to Greenville County for the Fire Protection & Water Line contract opportunity, which permits bidding on fire sprinkler, fire alarm, and underground fire-service line services individually or in combination.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Sprinkler System Specification Sheet (Per §40-10-250)
Project Data
Project name: Tigerville Fire Department
Location in South Carolina:
Address (street # & name): 2605 SC Hwy 414 State Project: Yes No
City: Travelers Rest, 29690 County: Greenville State Project #:
Water Supply Information (Flow test data must be less than 1 year old per §40-10-250(A)(1))
Date test conducted: 12/1/20 Static pressure (psi): 150 Residual pressure (psi): 82 Flow (gpm): 1384
Distances of test gauges relative to the base of the riser: Horizontal (ft): 20 Vertical (elevation difference in ft): 0
Source of water supply: Municipal dead-end Municipal circulation existing fire pump Other: Pipe Size (in.): 6
Test data by/from: Name: Mason Fraize Title: Tester
Organization: BRRWC Phone: 864-895-1719
Fire pump: New Existing
No Pump
Rated Capacity (gpm): Churn Pressure (psi):
Rated Pressure (psi): Pressure @ 150% flow (psi):
On-site water storage: Yes No New Existing Tank Other: Capacity (gal):
NFPA Hazard Classification (Attach continuation page when necessary)
Area #
Hazard Class or Code Reference
Description of Hazard Protected (including occupancy use group, and details of storage arrangement as applicable (including commodity class, rack arrangement/type, ceiling and storage height.))
1 Light Offices, restrooms, corridors, Training room, break room, dayroom, game room, bunk rooms, etc.
2 OH1 Truck Bays, Storage, Mechanical, Yard EQ., Fluid Rm., Gear Rm., etc.
Design Parameters
(Attach additional continuation pages when necessary)
Area # System Type Density(gpm/ft2)/Area(ft2), or Other (Reference code sections) Inside Hose (gpm) Outside Hose (gpm)
1 Wet 0.10 / 1500 0 100
2 Wet 0.15 / 1500 0 250
Seismic Design Data: SS= 0.306 Site Classification= D Seismic Design Category= C Codes and Standards (Attach continuation page when necessary)
Applicable Codes, Standards, & Editions (i.e. 2018 IBC, 2016 NFPA 13, etc.) for the Scope of Work on the Fire Sprinkler System
NFPA 13 – 2019, IBC – 2021, IFC - 2021
Scope of work (i.e. sprinkler system A.G. from 1'-0" A.F.F., U.G. from tap to 5'-0" outside, etc.) and notes (attach continuation page when necessary):
Contractor to install underground piping to the building and a wet pipe sprinkler system for the building.
Specifier's Information
Name: Warren E. Maddox P.E.
Certificate of Authorization
Professional Engineer’s Seal
Engineering services provided through a firm: Yes No
Firm name: Maddox Engineering, Inc.
Address: PO Box 26266
City: Greenville
State: SC Zip: 29616
Phone: 864-334-1875 Fax: NA
E-mail: warren@maddoxeng.pro
Revision No.: 0
Form Version: July 1, 2021
Page1of 1 Signature:
Date: 4/29/26