TFD_FSSSS_4-29-26.pdf

PDF 211 KB Posted

Attached to
Fire Protection & Water Line (Underground Fire-Service Line)
Solicitation number
RFP #27024
Issued by
Greenville County, South Carolina

About this file

This is a Fire Sprinkler System Specification Sheet prepared for the Tigerville Fire Department in Travelers Rest, South Carolina (Greenville County) in accordance with state regulation 40-10-250. The project involves the installation of underground piping to the building and a complete wet pipe sprinkler system. The facility contains approximately 3,000 square feet across two hazard areas: a Light Hazard area of 1,500 square feet (offices, restrooms, corridors, training room, break room, daycare, game room, and bunk rooms) and an Ordinary Hazard (Group 1) area of 1,500 square feet (truck bays, storage, mechanical spaces, yard equipment, fluid room, and gear room). The design utilizes NFPA 13 (2019), IBC (2021), and IFC (2021) standards and incorporates seismic design parameters with Site Classification D and Seismic Design Category C. Water supply is provided through municipal dead-end service with flow test data from December 1, 2020, showing static pressure of 150 psi, residual pressure of 82 psi, and flow capacity of 1,384 gpm from a 6-inch pipe connection tested by Mason Fraize of BRRWC.

The specification sheet indicates design parameters for Area 1 (Light Hazard) with 0.10 gpm/ft² density and inside hose flow of 0 gpm with outside hose flow of 100 gpm, and for Area 2 (Ordinary Hazard) with 0.15 gpm/ft² density and inside hose flow of 0 gpm with outside hose flow of 250 gpm. The project does not include a new fire pump or on-site water storage. Engineering services were provided by Warren E. Maddox, P.E., through Maddox Engineering, Inc., located in Greenville, South Carolina. The specification sheet was signed and dated April 29, 2026, and serves as the technical basis for contractor proposals submitted to Greenville County for the Fire Protection & Water Line contract opportunity, which permits bidding on fire sprinkler, fire alarm, and underground fire-service line services individually or in combination.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire Sprinkler System Specification Sheet (Per §40-10-250)

Project Data

Project name: Tigerville Fire Department

Location in South Carolina:

Address (street # & name): 2605 SC Hwy 414 State Project: Yes No

City: Travelers Rest, 29690 County: Greenville State Project #:

Water Supply Information (Flow test data must be less than 1 year old per §40-10-250(A)(1))

Date test conducted: 12/1/20 Static pressure (psi): 150 Residual pressure (psi): 82 Flow (gpm): 1384

Distances of test gauges relative to the base of the riser: Horizontal (ft): 20 Vertical (elevation difference in ft): 0

Source of water supply: Municipal dead-end Municipal circulation existing fire pump Other: Pipe Size (in.): 6

Test data by/from: Name: Mason Fraize Title: Tester

Organization: BRRWC Phone: 864-895-1719

Fire pump: New Existing

No Pump

Rated Capacity (gpm): Churn Pressure (psi):

Rated Pressure (psi): Pressure @ 150% flow (psi):

On-site water storage: Yes No New Existing Tank Other: Capacity (gal):

NFPA Hazard Classification (Attach continuation page when necessary)

Area #

Hazard Class or Code Reference

Description of Hazard Protected (including occupancy use group, and details of storage arrangement as applicable (including commodity class, rack arrangement/type, ceiling and storage height.))

1 Light Offices, restrooms, corridors, Training room, break room, dayroom, game room, bunk rooms, etc.

2 OH1 Truck Bays, Storage, Mechanical, Yard EQ., Fluid Rm., Gear Rm., etc.

Design Parameters

(Attach additional continuation pages when necessary)

Area # System Type Density(gpm/ft2)/Area(ft2), or Other (Reference code sections) Inside Hose (gpm) Outside Hose (gpm)

1 Wet 0.10 / 1500 0 100

2 Wet 0.15 / 1500 0 250

Seismic Design Data: SS= 0.306 Site Classification= D Seismic Design Category= C Codes and Standards (Attach continuation page when necessary)

Applicable Codes, Standards, & Editions (i.e. 2018 IBC, 2016 NFPA 13, etc.) for the Scope of Work on the Fire Sprinkler System

NFPA 13 – 2019, IBC – 2021, IFC - 2021

Scope of work (i.e. sprinkler system A.G. from 1'-0" A.F.F., U.G. from tap to 5'-0" outside, etc.) and notes (attach continuation page when necessary):

Contractor to install underground piping to the building and a wet pipe sprinkler system for the building.

Specifier's Information

Name: Warren E. Maddox P.E.

Certificate of Authorization

Professional Engineer’s Seal

Engineering services provided through a firm: Yes No