This document is a technical exhibit for a federal cooling tower at Building 12400. It provides detailed specifications and engineering data for a Marley AV6202A1 cooling tower, including equipment description, technical data, schematic drawings, and fan assembly instructions. The cooling tower has a 213-ton nominal capacity, is factory-assembled with galvanized steel construction, and includes features such as a drift eliminator, basin heater, and vibration cutoff switch. The document covers topics like fill, louvers, drift eliminators, the Marley X7 fan design, and maintenance procedures. This appears to be supporting documentation for a federal contract opportunity to overhaul chillers and cooling towers for the Department of the Army at USAG Humphreys.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P-12400 Cooling Tower Fill
Fill
Fan Assembly
Gap between wall and Fill
Accumulated Dust
Building 12400 Deteriorated
Alignment
1) COOLING TOWER (CT1~4)
A. EQUIPMENT DESCRIPTION (& TECHNICAL DATA)
a. Item No : 23 65 00 - 1
b. MFR & Model : U .S Marley AV6202A1
c. Address : P.O. BOX 7322
Baltimore, Maryland 21227 Tele : (410)799-6920 Fax : (410)799-6416
d. POU : Item #CT 1- 4 Cooling Tower
e. Actual Data : 5 YEARS WARRANTY FOR FANS, FAN DRIVES, ELECTRIC MOTORS, COLD WATER BASIN
BASIN HEATER, 7.5KW X 1SET
INDUCED DRAFT CROSS-FLOW, FAN 4/8 POLE CHANGE
CONTROL
BASIN HEATER, ELECTRIC WATER LEVEL CONTROL
EXTERNAL SERVICE PLATFORM, INTERNAL SERVICE
PLATFORM
AIR INLET SCREEN, SUMP DEBRIS SCREENS,
VIBRATION CUTOFF SWITCH
VIBRATION I SOLATION , EXTENDED LUBRICATION
LINES, CORRISION PROTECTION SYSTEM
GALVANIZED STEEL COLD DECK BASIN, GALVANIZED
STEEL CONSTRUCTION
FILLER TYPE PVC (ASTM STD E84-77A),ELIMINATOR
DRIFT LOSS 0.001 %
CONSTRUCTION G235 GALVANIZED STEEL. COLD
WATER BASIN G235 GALVANIZED
HOT WATER BASIN G235 GALVANIZED STEEL, CASING
G235 GALVANIZED STEEL
MOTOR PREMIUM EFFICIENCY WEG ELECTRIC CORP.
60HZ X 4/8P X 460V
PIPING INLET DIA 8", SIDE SUCTION OUTLET DIA 8",
OVER FLOW 4", DRAIN 3"
VIBRATION SWITCH M-5, VIBRATION ISOLATION
RSM-1-1000 UNISON
M7-5
1407833674.LN
Highlight
1407833674.LN
Highlight
1407833674.LN
Highlight
FAN MARLEY X7, ELECTRIC WATER LEVEL CONTROL :
LOW-LEVEL ALARM & CUTOFF
DETAIL DESCRIPTION OF EQUIPMENT SHALL BE AS
FOLLOWS ; SPX DATA SHEET
COOLING TOWER DEFINITION : MODEL AV6202A1 , CTI
CERTIFIED YES,
FAN MOTOR OUTPUT PER CELL 7.457 BKW , AIR FLOW
PER CELL 28.39 ㎥/S
ASHRAE 90.1 PERFORMANCE 23.9 ㎥/H.KW
CONDITIONS : 214 T. HOT WATER TEMP. 350℃, COLD
WATER TEMP. 29.4℃
WET BULB TEMP. 25SC. WATER FLOW 134.2 M3/H,
CAPACITY 107.6 %
WEIGHTS & DIMENSIONS : OPERATING WEIGHT 4916
KGF, 50% OPEN WALL 1.246M
WIDTH 3.569M, LENGTH 3.607M, HEIGHT 3.739M,
HEATER KW/CELL 7.5KW
M7-6
Marley AV
COOLI NG TOWE R
E NG I N E E R I NG DATA
AN D S PECI FICATION S
M7-10
AV towers are galvanized steel, factory-assembled, general purpose crossflow cooling towers, designed to serve normal air conditioning and refrigeration systems as well as light industrial loads. They evolve from a singleflow concept of towers pioneered by Marley in the 1950s, and incorporate all of the design advancements that our customers have found valuable. They represent the current state of the art in this cooling tower category.
This booklet not only relates the language to use in describing an appropriate AV cooling tower—but also defines why certain items and features are important enough to specify with the intention of insisting upon compliance by all bidders. The left hand column of pages 18 thru 35 provides appropriate text for the various specification paragraphs, whereas the right hand column comments on the meaning of the subject matter and explains its value.
Pages 18 thru 25 indicate those paragraphs which will result in the purchase of a basic cooling tower—one that accomplishes the specified thermal performance, but which will lack many operation—and maintenance-enhancing accessories and features that are usually desired by those people who are responsible for the continued and continuing operation of the system of which the tower is part.
It will also incorporate those standard materials which testing and experience has proven to provide acceptable longevity in normal operating conditions.
Pages 26 thru 35 provide paragraphs intended to add those features, components, and materials that will customize the tower to meet the user's requirements.
AV Cooling Tower 3
M7-12
AV Cooling Tower — Engineering Data: Schematic 4
11'-81/2" 1'-115/16"
31/2"
33/4 "
H
INSTALLED
HEIGHT
S
P
INLET PIPING DETAILS
L
HINGED ACCESS
DOOR
A
TO
W
ER
" I N
LE
T
8" INLET
INLET FACE
INLET FACE INLET
BASE OF
TOWER
BASE OF
TOWER
CL
PI
PI
N G
C L
CLINLETCL
CL
C L
CL
SHORT RADIUS
ELBOW
(BY OTHERS)
8" INLET PIPING
(BY OTHERS)
8" INLET PIPING
(BY OTHERS)
MARLEY HC VALVE
(OPTION)
Use this data for preliminary layouts only. Obtain current drawing from your Marley sales representative.
UPDATE™ web-based selection software, available at spxcooling.com/update provides AV cooling tower model recommendations based on customer's specific design requirements.
M7-13
AV Cooling Tower — Engineering Data: Schematic 5
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current drawings from your Marley sales representative. All table data is per cell.
2 Last numeral of model number indicates number of cells. Change as appropriate for your selection.
3 Nominal tons are based upon 95°F HW, 85°F CW, 78°F WB and 3 GPM/ton.
4 Standard overflow is a 4" dia. connection in the collection basin wall on the air inlet side of the tower. A 3" dia. drain connection is located below the overflow. See page 7 for details
5 Outlet sizes vary according to GPM and arrangement. See pages 6 and 7 for outlet sizes and details.
6 Makeup water connection may be 1" or 2" dia., depending upon tower heat load, water pressure, and desired connections. See page 6 for additional information.
Tower Model note 2
Nominal Tons note 3
Dimensions Motor hp
Design Operating Wt/Cell lb
Shipping Weight lb
L H A S P Weight/Cell Heaviest Section
AV6100A 117
8'-4" 12'-33⁄16" 8'-71⁄2" 11'-611⁄16" 12'-315⁄16"
3 8098 4248 —
AV6101A 138 5 8135 4285 —
AV6102A 157 71⁄2 8165 4315 —
AV6103A 167 10 8356 4506 —
AV6104A 195 15 8454 4604 —
AV6200A 172
11'-10" 12'-33⁄16" 12'-11⁄2" 11'-611⁄16" 12'-315⁄16"
5 10779 5316 —
AV6201A 193 71⁄2 10809 5346 —
AV6202A 213 10 10837 5374 —
AV6203A 229 15 11192 5729 —
AV6204A 259 20 11235 5772 —
AV6205A 275 25 11335 5872 —
AV6300A 190
8'-4" 15'-211⁄16" 8'-71⁄2" 14'-63⁄16" 15'-37⁄16"
71⁄2 9939 5467 3112
AV6301A 204 10 9969 5497 3142
AV6302A 232 15 10248 5776 3335
AV6303A 248 20 10344 5872 3431
AV6304A 264 25 10442 5970 3529
AV6400A 201
8'-4" 16'-715⁄16" 8'-71⁄2" 15'-117⁄16" 16'-811⁄16"
71⁄2 10573 5735 3112
AV6401A 217 10 10583 5765 3142
AV6402A 246 15 10836 6057 3335
AV6403A 263 20 10932 6153 3431
AV6404A 285 25 11029 6250 3528
AV6405A 302 30 11069 6290 3568
AV6500A 242
9'-10" 16'-715⁄16" 10'-11⁄2" 15'-117⁄16" 16'-811⁄16"
10 12019 6428 3513
AV6501A 270 15 12120 6529 3614
AV6502A 288 20 12468 6877 3836
AV6503A 311 25 12572 6981 3940
AV6504A 329 30 12615 7019 3978
AV6505A 345 40 12780 7189 4148
AV6600A 279
11'-10" 15'-211⁄16" 12'-11⁄2" 14'-65⁄16" 15'-37⁄16"
15 13247 6943 3990
AV6601A 305 20 13400 7036 4083
AV6602A 322 25 13774 7410 4326
AV6603A 343 30 13812 7448 4364
AV6604A 355 40 13982 7618 4534
AV6700A 293
11'-10" 16'715⁄16" 12'-11⁄2" 15'-117⁄16" 16'-811⁄16"
15 14052 7267 3990
AV6701A 320 20 14145 7360 4083
AV6702A 344 25 14249 7464 4187
AV6703A 365 30 14578 7641 4364
AV6704A 390 40 14748 7811 4534
M7-14
Specifications Specification Value
AV Cooling Tower — Specifications: Base 22
7.0 Fill, Louvers, and Drift Eliminators:
7.1 Fill shall be film-type, thermoformed of
PVC, with louvers and eliminators formed as part of each fill sheet. Fill shall be suspended from hot-dip galvanized struc-tural tubing supported from the tower structure, and shall be elevated above the floor of the cold water basin to facilitate cleaning. The air inlet face of the tower shall be free of water splash-out.
7.2 Drift eliminators shall be PVC, triple-pass, and shall limit drift losses to no more than 0.005% of the design GPM flow rate.
Louvers integral with the fill keep the flowing water within the confines of the fill. The separate external louvers used by others permit water to escape the fill and form ice or produce an unsightly situation adjacent to the tower. If you plan to use your tower in the wintertime, particularly for free cooling, integral louvers will put your operating concerns to rest.
Drift rate varies with design water loading and air rate, as well as drift eliminator depth and number of directional changes. A drift rate of 0.001% is readily available on many stan-dard models. If a lower rate is required, please discuss with your Marley sales representa-tive.
Drift Eliminators
Fill Sheets
Louvers
M7-31
1407833674.LN
Highlight
1407833674.LN
Highlight
1407833674.LN
Highlight
1407833674.LN
Highlight
1407833674.LN
Highlight
1407833674.LN
Highlight
M7-77
M7-78
M7-79
M7-80
The Marley X7™ fan is designed for induced-draft cooling tower and fluid cooler applications offering distinct advantages over other fan designs. The Marley FlareTip™ blade enhancement provides increased performance overcoming tip clearance losses—aiding the movement of air next to the fan cylinder.
The wide chord blade design is well suited for low noise operation as well, delivering superior air flow and pressure capability at reduced speed. The high performance X7 airfoil is one of the most efficient in the industry today.
The hollow 6063-T6 aluminum alloy extruded blade is designed with a deep section airfoil making the X7 robust, yet light and easy to handle. It also withstands the extreme heat and humidity imposed by the rigorous cooling tower environment.
The blade end-caps are injection molded impact-resistant, polypropylene with a section on the upper surface to allow for consistent fan pitch setting.
Additionally, all X7 fan assemblies are statically balanced at the factory to minimize vibration.
Each blade is secured to the hub with two stainless steel U-bolts that allow blades to be easily rotated to adjust desired pitch angle, delivering precise utilization of fan horsepower.
Superior strength, excellent quality, light weight and outstanding performance makes the X7 fan an outstanding choice for cooling tower applications—and best of all it’s made by Marley.
Marley X7 Fan
AXIAL FLOW FAN S
M7-83
High Efficiency The aerodynamic design optimizes the performance characteristics of the X7 blade.
The FlareTip design, adapted from the well-proven and highly successful Marley HP7i and HP7000 fiberglass fans, is a characteristic unique among extruded aluminum fan designs.
The blade taper and flared tip reduce blade tip losses and distributes airflow evenly across the entire blade length, improving overall fan efficiency.
Lightweight The single-piece X7 hub design was chosen specifically to work in an evaporative cooling environment at the common fan diameter range of factory-assembled package products.
This optimization allowed for a significantly smaller overall hub compared to other manufacturer’s offerings, yielding significant weight savings. Additionally, the simple and proven U-bolt method of blade to hub connection results in a minimum quantity of hardware.
Corrosion Resistance Marley X7 fans are designed for continuous duty in all cooling operating environments. Available in diameters from 66" through 168", the X7 utilizes a single-piece galvanized ductile iron hub with series 300 U-bolts. Blade shanks are galvanized carbon steel, and all blade hardware is series 300 stainless steel. 316 stainless hardware and triple-epoxy hub coating is available as an option for more corrosive environments.
In the interest of technological progress, all products are subject to design and/or material change without notice ISSUED 2/2012 SP-X7-A
COPYRIGHT © 2012 SPX Corporation
SPX COOLING TECHNOLOGIES, INC. | OVERLAND PARK, KS 66213
P: 913 664 7400 F: 913 664 7439 spxcooling@spx.com spxcooling.com
M7-84
Marley X7 Fan
D E S IG N E D FOR I N D UCE D-D RAFT COOLI NG TOWE R APPLICATION S
M2010-1234A ISSUED 3/2012 R EAD AN D U N D E R STAN D TH I S MAN UAL PR IOR TO OPE RATI NG OR S E RVICI NG TH I S PROD UCT.
US E R MAN UAL
M7-85
Order No. _______________________________________
Trial Pitch Angle __________________________________
Final Pitch Angle _________________________________
Speed-rpm ______________________________________
Contract hp _____________________________________
Fan Components
Figure 1—Typical Fan Assembly
1 2
M7-86
Fan Assembly Instructions
The following instructions apply to installations having straight bores or tapered output shafts without split taper bushings.
It is convenient to preassemble the fan prior to installation on the driving shaft.
Marley X7 fans are statically balanced as a complete assembly. If fan is shipped unassembled, blades and hubs are match-marked to insure proper re-assembly.
1—Select a large open area corresponding to the fan diameter.
2—Position the fan hub 1 in the center of the work area with the blade sockets up.
3—Place a blade 2 in a blade socket on the hub. On fans where the blades overlap at the hub be sure to have the leading edge under the trailing edge of the forward blade. Refer to Figure 2.
4—Ensure the blade shank safety collar is inboard of the inner hub rim.
Refer to Figure 3.
5—Lubricate U-bolt threads and bearing surface of self-locking nuts.
Install U-bolt through inner row of holes in the hub. Finger tighten the self-locking nut with flat washer onto U-bolt threads. Progressively tighten each leg of the U-bolt until blade is held in place.
6—Pull blade radially outward to be certain the shank safety collar is in contact with hub inner ring. Refer to Figure 3.
7—Repeat steps 5 and 6 as required with the outer U-bolt 4.
8—Repeat steps 3 through 7 for all blades.
Figure 2
Note
LEADING
EDGE
TRAILING
EDGE
M7-87
Figure 3
9—Progressively tighten each side of the U-bolt until the blades are barely able to move when twisting the blade.
Fan Installation Instructions
1—Be sure motor is locked out.
2—Clean the hub bore and driving shaft extension for the full length of the key.
3—Insert the key in the keyway. The top of the key must be below the top of the shaft by not more than 1/8″ (3 mm) . The key is a tight fit across the width and must never be altered.
4—After cleaning, apply a coat of anti-seize compound to the engage-ment portion of the shaft.
5—Raise the fan assembly above the shaft and slowly lower the hub onto the shaft with the keyways aligned. Make certain the key does not slide down during installation.
6—Install the Hub Retention Cap Screw with Lock Washer. Torque hub retention cap screw to 40 ft·lbƒ (54 N·m).
BLADE
SAFETY COLLAR
INNER HUB
RIM
M7-88
Adjusting Fan Blade Pitch
The trial pitch is the calculated setting for design conditions (water rate , heat load, air density, and brake horsepower). The trial pitch is provided by SPX (see page 2).
1–Select a position on the fan circumference and rotate each blade to this common location when setting or checking blade pitch. Support the blade tip to maintain a common rotation plane while setting the fan pitch. The pitch is set by placing a protractor on top of a straight edge or with a digital level that extends across blade near the tip. For flare-tip blades, the pitch is measured across the end cap as shown in Figure 4.
For full chord blades, the pitch is measured across the aluminum airfoil about 1” inboard of the end cap as shown in Figure 5.
2–Be sure all blades are positioned correctly on hub, then set the pitch.
Blades should be within ± 1/4° of the desired pitch angle. After the de-sired setting is obtained, progressively tighten the U-bolt nuts according to Table 6. Recheck the pitch angle. If required, loosen the hex nuts and reset the pitch as necessary until the proper pitch angle is obtained.
Note
Figure 4
Figure 5
SETTING PITCH ON
FLARE-TIP BLADE
(LEVEL PLACED ACROSS END CAP)
SETTING PITCH ON
FULL CHORD BLADE
(LEVEL PLACED ACROSS AIR FOIL)
M7-89
Fan Maintenance
Preventative maintenance will prolong useful life and assure continued trouble-free operation. After the first week and subsequently at six month intervals:
cylinder segments, and corrosive attack. Correct any situations deter-mined detrimental to fan operation.
Service
Proper identification of your fan is necessary to insure you receive cor-rect replacement parts. The Marley cooling tower serial number can be used to determine the fan and any components installed and maintained as original equipment on a Marley cooling tower. Please provide the Marley sales representative the necessary information when ordering replacement fans or components.
Replacement of individual fan blades may require rebalancing the entire fan.
If rebalancing is desired, contact the Marley sales representative in your area.
Table 6
Fan Model
Bolt Diameter mm
Torque Wrench Setting ft·lbƒ N·m
X71 12 40 54
X72 16 70 95
M7-90 seongeun 선
Motor Load
The corrected horsepower should be close to but not exceed the con-tract horsepower specified by SPX. Determine corrected horsepower using the following equation.
Actual volts and amperage must be obtained with the fan running and the specified rate of water flowing over the tower after the motor and Geareducer have reached operating temperature (approximately 30 minutes of operation).
Note Measurements taken on motors operating with Variable Fre-quency Drive controls may read up to 15% high from errors in measuring the approximated sine wave. Instruments capable of measuring a squared off wave form accurately should be used for measuring power in this situation.
Do not start the motor more than four to five times per hour (each low speed start and each high speed start count as one start).
N
AMPSN = Nameplate Amperage
HPN = Nameplate Horsepower
DENSITYD = Design Air Density
HPC = Corrected Horsepower
A
AMPSA = Actual Amperage
DENSITYA = Actual Air Density
A × AMPSA × DENSITYD
N × AMPSN × DENSITYA
HPC = × HPN
M7-91