TE A - Tank Testing Types and Frequencies.pdf
PDF 62 KB Posted
- Solicitation number
- PANMCC-26-P-048611
About this file
This is a technical exhibit specifying tank testing requirements and frequencies for underground storage tank systems at two facilities (30512 and 23462). The document establishes a comprehensive testing matrix for ten tanks of varying capacities, ranging from 5,000 gallons to 300,000 gallons, including both pressure and safe suction tank configurations.
The testing requirements apply uniformly across most tanks and include probe function tests, interstitial sensor tests, tank tightness tests, console (ATG) tests, MLD/ALM functions checks, line tightness testing, overfill tests, overfill valve tests, and STP sump testing. Spill bucket testing and under dispenser containment/sensor testing apply selectively based on tank configuration, with notation that tanks equipped with double wall spill buckets or under dispenser cabinets are marked as N/A for certain tests. Triennial testing is scheduled for 2027 and 2030. The document notes that tanks U061–U063, while maintained by DPW Environmental, are tested and repaired through the LRC. Physical tests noted with an asterisk are not connected to the Veeder-Root console system.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Performance Work Statement_ UST Testing 2027_01OCT2026.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Technical Exhibit A
Tank Test Type and Frequency
* Physical test not connected to the Veeder-Root console
** Triennial Testing due 2027 and 2030.
Tanks U061 – U063 permits are maintained by DPW Environmental but are tested and repairs through the LRC.
N/A – Has double wall spill buckets and/or Under Dispenser Cabinet (UDC)
Facility 30512 & 23462
5000gl Pressure
300000gl Pressure
10000gl Pressure
10000gl Pressure
10000gl Pressure
20000gl Safe
Suction
10000gl Safe
Suction
10000gl Safe
Suction
10000gl Safe
Suction
10000gl Safe
Suction U001 U057 U058 U059 U060 U064 U065 U066 U067 U068
Probe Function Test
X X X X X X X X X X
Interstitial Sensor Test
X X X X X X X X X X
Tank Tightness
Test
X X X X X X X X X X
Console (ATG) Test
X X X X X X X X X X
MLD/ALM
Functions
Check
X X X X X X X X X X
Line Tightness
Testing
X X X X X X X X X X
Overfill Test X X X X X X X X X X
Overfill Valve Test*
X X X X X X X X X X
Spill Bucket Test **
X N/A N/A N/A N/A N/A N/A N/A X X
Under Dispenser
Containment/ Sensor Test
X N/A X X X N/A N/A N/A N/A N/A
STP Sump Testing **
X X X X X X X X X X
File details come from the government source that posted it. Updated .