Tab 2 - SOW - BLDG 97 - VOQ.pdf
PDF 9 MB Posted
- Attached to
- DSCR B97 VOQ Renovation
- Solicitation number
- SP470325R0004
- Issued by
-
Defense Logistics Agency
About this file
This document is a pre-solicitation notice for a Request for Proposal (RFP) to renovate Building 97 Visiting Officers Quarters (VOQ) at the Defense Supply Center Richmond (DSCR) facility. The solicitation number is SP4703-25-R-0004. The resulting contract will be a firm-fixed price award with an expected one-year Period of Performance from the Notice to Proceed.
This acquisition is set-aside for 100% small businesses under NAICS code 236220 (Miscellaneous Building Renovation) with a $45M size standard. Award will be made to the lowest priced, technically acceptable offeror meeting the requirements of the Statement of Work. Past performance will be considered as part of technical acceptability. Contractors must be within a 120-mile radius commutable distance to DSCR. Access to the facility is through the Defense Biometric Identification System (DBIDS) pre-enrollment and credentialing process. No other project-specific details are provided in this pre-solicitation notice.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| DSCR B97 DD100 Specs-Rev1 .pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 2 3 4 5
D
C
B
A
NO. REVISIONS DATE
Defense Supply Center Richmond
DEFENSE LOGISTICS AGENCY
6090 Strathmore Road
RICHMOND VA, 23237
DESIGNED BY:
DRAWN BY:
SCALE:
CHECKED BY:
CIVIL
ELECTRICAL
MECHANICAL
ARCHITECTURAL
STRUCTURAL
PROJECT NO.
DRAWING NO.
DATE
AS NOTED
SHEET NAME.
BUILDING NAME.
613 NW LOOP 410, STE 700
SAN ANTONIO, TX 78216
(210) 841-2800
HDR ENGINEERING, INC
TEXAS P.E. FIRM
REGISTRATION NO. F-754
K. LE
C. HABY
J. JANOTA
J. CORONADO
PROJECT SITE
D
C
B
A
1 2 3 4 5
D. EMANUS
PROJECT SITE
DSCR MAIN GATE #01
6090 Strathmore Road Richmond, VA 23237
DSCR BLDG 97 VOQ RENOVATION
100% DESIGN SUBMITTAL
JW
KH
22 AUG 2024
10356006
G-001
COVER SHEET
DSCR BUILDING 97 VOQ RENOVATION
22 AUG 2024
NTS
SITE MAP
NTS
VICINITY MAP
A2
B4
PLAN NORTH
C
B
A
NO. REVISIONS DATE
Defense Supply Center Richmond
DLA Installation Management Richmond
6090 Strathmore Road
Richmond, VA 23237
DESIGNED BY:
DRAWN BY:
SCALE:
CHECKED BY:
CIVIL
ELECTRICAL
MECHANICAL
ARCHITECTURAL
STRUCTURAL
PROJECT NO.
DRAWING NO.
DATE
AS NOTED
SHEET NAME.
BUILDING NAME.
613 NW LOOP 410, STE 700
SAN ANTONIO, TX 78216
(210) 841-2800
HDR ENGINEERING, INC
TEXAS P.E. FIRM
REGISTRATION NO. F-754
K. LE
C. HABY
J. JANOTA
J. CORONADO
D
C
B
A
1 2 3 4 5
D. EMANUS
JW
KH
22 AUG 2024
10356006
G-002
SHEET INDEX
DSCR BUILDING 97 VOQ RENOVATION
22 AUG 2024
SHEET LIST
SHEET NUMBER SHEET NAME
65%
05/20/2024 95%
07/11/2024 100%
08/15/2024
GENERAL
G-001 COVER SHEET X
G-002 SHEET INDEX X
G-003 GENERAL NOTES, ABBREVIATIONS X
G-100 CODE ANALYSIS X
G-101 LIFE SAFETY PLAN X
STRUCTURAL
S-001 GENERAL STRUCTURAL NOTES X
ARCHITECTURAL
AD101 FIRST FLOOR PLAN DEMOLITION X
AD105 FIRST FLOOR REFLECTED CEILING PLAN DEMOLITION X
A-101 FIRST FLOOR PLAN - BASE DESIGN X
A-102 FIRST FLOOR PLAN - OPTION 1 X
A-105 FIRST FLOOR REFLECTED CEILING PLAN X
A-201 EXTERIOR ELEVATIONS
FIRE PROTECTION
F-001 FIRE PROTECTION GENERAL NOTES X
FD101 FIRE ALARM PLAN - DEMOLITION X
FD102 FIRE SUPPRESSION PLAN - DEMOLITION X
FA101 FIRE ALARM PLAN - NEW WORK X
FA501 FIRE ALARM DETAILS X
FA601 FIRE ALARM MATRIX X
FX101 FIRE SUPPRESSION PLAN - NEW WORK X
FX501 FIRE SUPPRESSION DETAILS X
MECHANICAL
M-001 MECHANICAL GENERAL NOTES, SYMBOLS & ABBREVIATIONS X
PLUMBING
P-101 PLUMBING DEMOLITION PLAN X
P-102 PLUMBING NEW WORK PLAN X
P-501 PLUMBING DETAILS X
P-601 PLUMBING SCHEDULES X
ELECTRICAL
E-001 ELECTRICAL SYMBOLS AND LEGEND X
ED101 ELECTRICAL LIGHTING PLAN DEMOLITION - BID OPTION X
ED102 ELECTRICAL POWER PLAN DEMOLITION X
E-101 ELECTRICAL LIGHTING PLAN - BID OPTION X
E-102 ELECTRICAL POWER PLAN X
E-601 ELECTRICAL ONE-LINE DIAGRAM AND PANEL SCHEDULES X
TELECOMMUNICATIONS
TD101 TELECOMMUNICATIONS DEMOLITION PLAN X
T-101 TELECOMMUNICATIONS PLAN X
DRAWING ABBREVIATIONS
INDEX OF DRAWINGS
BUILDING SUMMARY
NUMBERING SYSTEM:
XX100
DISCIPLINE:
C - CIVIL
L - LANDSCAPE
A - ARCHITECTURE
M - MECHANICAL
E - ELECTRICAL
P - PLUMBING
S - STRUCTURAL
K - FOOD SERVICE
F - FIRE PROTECTION
T - TELECOMMUNICATIONS
DISCIPLINE MODIFIER
ANNOTATION CALLOUTS/DRAWING SYMBOLS
GENERAL NOTES
A ---------------------
A LABEL CLASS A DOOR
A/C AIR CONDITION
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AB ANCHOR BOLT
ACC ACCESSIBLE
ACS AUTOMATIC CONTROL SYSTEM
ACS DR ACCESS DOOR
ACS PNL ACCESS PANEL
ACT ACOUSTICAL CEILING TILE
ADA AMERICANS WITH DISABILITIES
ACT
ADMIN ADMINISTRATION
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AGGR AGGREGATE
AHU AIR HANDLING UNIT
AIB AIR INFILTRATION BARRIER
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZE
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATE
AR AS REQUIRED
ARCH ARCHITECT
ASC ABOVE SUSPENDED CEILING
ASSY ASSEMBLY
ATC ACOUSTICAL TILE CEILING
AVG AVERAGE
AW ARCHITECTURAL WOODWORK
AWT ACOUSTICAL WALL TREATMENT
B ---------------------
B LABEL CLASS B DOOR
BALC BALCONY
BB BASEBOARD
BC BOOKCASE
BD BOARD
BDRY BOUNDARY
BFF BELOW FINISH FLOOR
BHMA BUILDER'S HARDWARE
MANUFACTURER'S ASSOCIATION
BLDG BUILDING
BLKG BLOCKING
BLT IN BUILT-IN
BN BULLNOSE
BOS BOTTOM OF STEEL
BOT BOTTOM
BP BUILDING PAPER
BRKT BRACKET
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT-UP ROOFING
C ---------------------
C CONC CAST CONCRETE
C LABEL CLASS C DOOR
CAB CABINET
CATW CATWALK
CAV CAVITY
CBB CEMENTITIOUS (BACKER) BOARD
CD CONSTRUCTION DOCUMENTS
CDW CHILLED DRINKING WATER
CEM PLAS CEMENT PLASTER
CER CERAMIC
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR
FURNISHED/CONTRACTOR
INSTALLED
CFE CONTRACTOR FURNISHED
EQUIPMENT
CFLG COUNTERFLASHING
CFM CUBIC FEET PER MINUTE
CFMF COLD-FORMED METAL FRAMING
CFS CUBIC FEET PER SECOND
CG CORNER GUARD
CI CAST IRON
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLG DIFF CEILING DIFFUSER
CLG HT CEILING HEIGHT
CLL COLUMN LINE
CLO CLOSET
CLR COLOR
CLRM CLASSROOM
CMU CONCRETE MASONRY UNIT
CNDS CONDENSATE
CDR CARD READER
CO CLEANOUT
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
CONC FLR CONCRETE FLOOR
CONF CONFERENCE
CONT CONTINUE
COORD COORDINATE
CORR CORRIDOR
CP CONCRETE PIPE
CPT CARPET
CR CONTROL ROOM
CS CAST STONE
CSWK CASEWORK
CT CERAMIC TILE
CTB CERAMIC TILE BASE
CTF CERAMIC TILE FLOOR
CTR CENTER
CU FT CUBIC FEET
CW CASEMENT WINDOW
D ---------------------
D DEPTH
D LABEL CLASS D DOOR
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIR DIRECTION
DIST DISTANCE
DOC DOCUMENT
DR DOOR
DS DOWNSPOUT
E ---------------------
E LABEL CLASS E DOOR
EA EACH
EF EACH FACE
EIFS EXTERIOR INSULATION AND
FINISH SYSTEM
EJ EXPANSION JOINT
ES EACH SIDE
EL ELEVATION
ELEV ELEVATOR
ENTR ENTRANCE
EPS EXPANDED POLYSTYRENE
BOARD (INSULATION)
EQ EQUAL
EWC ELECTRIC WATER COOLER
EXP EXPOSED
EXT EXTERIOR
EXT EXTINGUISHER
EXT GR EXTERIOR GRADE
F ---------------------
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR
PANEL
FAS BD FASCIA BOARD
FC BRK FACE BRICK
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FED FEDERAL
FF FINISH FACE
FF EL FINISH FLOOR ELEVATION
FF INSUL FOIL BACKED INSULATION
FGL FIBERGLASS
FH FIRE HOSE
FHP FULL HEIGHT PARTITION
FIN FINISH
FIN BS FINISH BOTH SIDES
FIN FLR FINISH FLOOR
FIN GR FINISH GRADE
FIXT FIXTURE
FLDG FOLDING
FLEX FLEXIBLE
FLG FLOORING
FLMT FLUSH MOUNT
FLR FLOOR
FM FACTORY MUTUAL
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FR FIRE RESISTANT
FRG FIBER REINFORCED GYPSUM
FRMG FRAMING
FRP FIBERGLASS REINFORCED
PLASTIC
FRTW FIRE RETARDANT TREATED
WOOD
FS FEDERAL SPECIFICATION
FSTNR FASTENER
FT FEET
FTG FOOTING
FWC FABRIC WALLCOVERING
G ---------------------
G NATURAL GAS
GALV GALVANIZED
GB GRAB BAR
GFCI GOVERNMENT FURNISHED
CONTRACTOR INSTALLED
GFGI GOVERNMENT INSTALLED
GOVERNMENT INSTALLED
GFRG GLASS-FIBER-REINFORCED
GYPSUM
GLZ GLAZING
GR FL GROUND FLOOR
GUT GUTTER
GYP BD GYPSUM BOARD
GYP PLAS GYPSUM PLASTER
H ---------------------
HB HOSE BIBB
HDPE HIGH DENSITY POLYETHYLENE
HDW HARDWARE
HDWD HARDWOOD
HEPA HIGH EFFICIENCY PARTICULATE
AIR (FILTER)
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HORIZ HORIZONTAL
HT HEIGHT
HYDR HYDRAULIC
I ---------------------
IBC INTERNATIONAL BUILDING CODE
INSUL INSULATION
INT INTERIOR
ILO IN LIEU OF
J ---------------------
JAN JANITOR
K ---------------------
KPD KEYPAD
KIT KITCHEN
KPL KICKPLATE
L ---------------------
LAM LAMINATE
LAV LAVATORY
LBR LUMBER
LBS POUND
LDG LANDING
LF LINEAR FEET (FOOT)
LIB LIBRARY
LIN LINEAR
LKR LOCKER
LOC LOCATION
LT LIGHT
LVDR LOUVER DOOR
LVR LOUVER
M ---------------------
MACH RM MACHINE ROOM
MATL MATERIAL
MAX MAXIMUM
MC MOISTURE CONTENT
MD METAL DECK
MECH MECHANICAL
MECH RM MECHANICAL ROOM
MEMB MEMBRANE
MF MILL FINISH
MFR MANUFACTURER
MID MIDDLE
MIL STD MILITARY STANDARD
MIN MINIMUM, MINUTE
MIRR MIRROR
MISC MISCELLANEOUS
MLDG MOLDING (MOULDING)
MO MASONRY OPENING
MOD MODIFY
MB MOISTURE BARRIER
MTG MOUNTING
MTL METAL
MVBL MOVABLE
MWP MEMBRANE WATERPROOFING
N ---------------------
N NORTH
NA NOT APPLICABLE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NP NO PAINT
NRC NOISE REDUCTI
O -------------------
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OFF OFFICE
OGL OBSCURE GLASS
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPQ OPAQUE
OWSJ OPEN WEB STEEL JOIST
OPR OPERABLE
ORD OVERFLOW ROOF DRAIN
ORIG ORIGINAL
P --------------------
PA PUBLIC ADDRESS
PAR PARAPET
PAT PATTERN
PB PULL BOX
PBD PARTICLEBOARD
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PCT PERCENT
PERF PERFORATED
PERIM PERIMETER
PH PHASE
PIL PILASTER
PL PROPERTY LINE
PL GL PLATE GLASS
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLG PILING
PLYWD PLYWOOD
PNL PANEL
PP PL PUSH/PULL PLATE
PR PAIR
PRCST PRECAST
PRKG PARKING
PS CONC PRESTRESSED CONCRETE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PTDR PAPER TOWEL DISPENSER AND
RECEPTACLE
PTN PARTITION
PWR POWER
Q --------------------
QT QUARRY TILE
QTY QUANTITY
R --------------------
RB RESILIENT BASE
RBM REINFORCED BRICK MASONRY
RBR RUBBER
RC REINFORCED CONCRETE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RDG INS RIGID INSULATION, SOLID
REC RECESSED
REC ROOM RECREATION ROOM
REF REFERENCE
REM REMOVABLE
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RESIL RESILIENT
REST RESTROOM
RF RESILIENT FLOORING
RFG ROOFING
RH ROOF HATCH
RHR RIGHT HAND REVERSE
RL ROOF LEADER
RLG RAILING
RM ROOM
RO ROUGH OPENING
RSD ROLLING STEEL DOOR
RV ROOF VENT
RVL REVEAL
REFER TO A/E/C CAD STANDARD FOR
SHEET NUMBERINGSTANDARDS
REVISION
TAG
NORTH ARROW w/
TRUE NORTH
INDICATION
ROOM TAG
ELEVATION NUMBER
SECTION
EXTERIOR ELEVATION
ENLARGEMENT,
DETAIL
SPOT ELEVATION
LEVEL NAME
SHEET NUMBER
SHEET NUMBER
SHEET NUMBER
SHEET KEYNOTE
INTERIOR ELEVATION
SHEET NUMBER
S --------------------
SB SPLASH BLOCK
SCHED SCHEDULE
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SFTWD SOFTWOOD
SGL SINGLE
SHT MTL SHEET METAL
FLASH (FLASHING)
SHTHG SHEATHING
SHV SHELVING
SIM SIMILAR
SJ SCORED JOINT
SKLT SKYLIGHT
SLNT SEALANT
SMK SMOKE
SMLS SEAMLESS
SP EL SPOT ELEVATION
SPEC SPECIFICATION
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SST STAINLESS STEEL
ST STAIRS
STD STANDARD
STL JST STEEL JOIST
STL RF DK STEEL ROOF DECK
STOR STORAGE
STR STRINGERS
STRB/HRN STROBE/HORN
SUB FL SUBFLOOR
SV SHEET VINYL
SW SIDEWALK
T --------------------
T TREAD
T/S TUB/SHOWER
TC TERRA COTTA
TD TRENCH DRAIN
TEL TELEPHONE
TEMP TEMPORARY
TER TERRAZZO
TFF TOP OF FINISH FLOOR
THK THICKNESS
TK BD TACKBOARD
TMPD GL TEMPERED GLASS
TN TRUE NORTH
TOF TOP OF FOOTING
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOPO TOPOGRAPHY
TOS TOP OF SLAB
TRANS TRANSOM
TRTD TREATED
TV TELEVISION
SHEET NUMBER WITHIN SERIES
A1
A201
A204
A1
A301
A401
ROOM
100'
LEVEL 01
100'
PLAN NORTH
A1
FIRST FL
1/4" = 1'-0"
1 2 3 4 5
D
C
B
A
NO. REVISIONS DATE
Defense Supply Center Richmond
DLA Installation Management Richmond
6090 Strathmore Road
Richmond, VA 23237
DESIGNED BY:
DRAWN BY:
SCALE:
CHECKED BY:
CIVIL
ELECTRICAL
MECHANICAL
ARCHITECTURAL
STRUCTURAL
PROJECT NO.
DRAWING NO.
DATE
AS NOTED
SHEET NAME.
BUILDING NAME.
613 NW LOOP 410, STE 700
SAN ANTONIO, TX 78216
(210) 841-2800
HDR ENGINEERING, INC
TEXAS P.E. FIRM
REGISTRATION NO. F-754
K. LE
C. HABY
J. JANOTA
J. CORONADO
D
C
B
A
1 2 3 4 5
D. EMANUS
MB
VV
22 AUG 2024
10356006
G-003
GENERAL NOTES, ABBREVIATIONS
DSCR BUILDING 97 VOQ RENOVATION
22 AUG 2024
STRUCTURAL ABBREVIATIONS
ABBREVI
ATION ABBREVIATION NAME
# NUMBER
& AND
= EQUAL, EQUALS
@ AT
A/C AIR CONDITIONING
AB ANCHOR BOLT
ACI AMERICAN CONCRETE INSTITUTE
ADDL ADDITIONAL
ADJ ADJACENT
AFF ABOVE FINISEHD FLOOR
AH, AHU AIR HANDLING UNIT
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ALT ALTERNATE
APA AMERICAN PLYWOOD ASSOCIATION
APPROX APPROXIMATELY
ARCH ARCHITECTURAL
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AT/FP ANTI-TERRORISM/ FORCE PROTECTION
AWS AMERICAN WELDING SOCIETY
BET BETWEEN
BLW BELOW
BM BEAM
BN BOUNDARY NAIL
BOF BOTTOM OF FOOTING
BOT BOTTOM
BRG BEARING
C CHANNEL
CE CARBON EQUIVALENT
CENT CENTERED
CFMF COLD-FORMED METAL FRAMING
CFS COLD-FORMED STEEL
CIP CAST IN PLACE
CJ CONTROL JOINT/CEILING JOIST
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
COND CONDITION
CONN CONNECT, CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CORNER
CWB CAPILLARY WATERBARRIER
D DEEP, DEPTH
DEG DEGREE
DEM DEMOLISH, DEMOLITION
DEP DEPRESSED
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DL DEADLOAD
DO DITTO
DT DRAG TRUSS
DWG(S) DRAWINGS
DWL DOWEL
EA EACH
EF EACHFACE
ELEC ELECTRICAL
ELEV ELEVATION
EN EDGE NAIL
EQN EQUATION
EQUIP EQUIPMENT
ES EACH SIDE
EW EACH WAY
EXIST EXISTING
EXT EXTERNAL, EXTERIOR
FF FAR FACE
FFE FINISH FLOOR ELEVATION
FG FINISH GRADE
FJ FLOOR JOIST
FMG FRAMING
FN FIELD NAIL
FND FOUNDATION
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FOS FACE OF STUD
FS FAR SIDE
FT, ' FOOT
FTG FOOTING
Fy YIELD STRESS
GA GAUGE
GLB GLUED LAMINATED BEAM
GT GIRDER TRUSS
GUSS GUSSET
GYP BD GYPSUM BOARD
HD HOLD DOWN
HDR HEADER
HGR HANGER
HK HOOK
HORIZ HORIZONTAL
HP HIGH POINT
HSS HOLLOW STRUCTURAL SECTION
HT HEIGHT
HVAC HEATNG/ VENTILATING/ AIR CONDITIONING
I MOMENT OF INERTIA
IBC INTERNATIONAL BUILDING CODE
ICF INSULATED CONCRETE FORM
ID INSIDE DIAMETER
IN, " INCH
STRUCTURAL ABBREVIATIONS
ABBREVI
ATION ABBREVIATION NAME
INCL INCLUDE
INFO INFORMATION
INS INSULATED, INSULATION
JST JOIST
K, KIPS THOUSAND POUNDS
L LENGTH, ANGLE
LB POUND
LG LONG
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOC LOCATE, LOCATION
LONG LONGITUDINAL
LP LOW POINT
LW LIGHT WEIGHT
MAS MASONRY
MB MACHINE BOLT
MBR MEMBER
MECH MECHANICAL
MED MEDIUM
MEZZ MEZZANINE
MF MOMENT FRAM
MFG MANUFACTURING
MIN MINIMUM
MO MASONRY OPENING
MOD MODIFY, MODIFIED
MRF MANUFACTURER
NF NEAR FACE
NOM NOMINAL
NS NEAR SIDE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OPPOSITE HAND, OVERHEAD
OWSJ OPEN WEB STEEL JOIST
P/C PIN CONNECTED
PAR PARALLEL
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PEN PENETRATION
PFJ PERIMETER FELT JOINT
PL PLATE
PLYWD PLYWOOD
PNL PANEL
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED, POINT, PRETENSIONED
REINF REINFORCING, REINFORCED
REQ REQUIRED
RET RETURN, RETAINING
REV REVISION, REVISED
RF ROOF
RFT RAFTERS
RPM REVOLUTIONS PR MINUTE
RS ROUGH SAWN
RT ROOF TRUSS
S SECTION MODULUS
SC SLIP CRITICAL
SCBRW SEGMENTAL CONCRETE BLOCK RETAINING WALL
SCHED SCHEDULE
SDI STEEL DECK INSTITUTE
SECT SECTION
SEIS SEISMIC
SEP SEPARATION
SHT SHEET
SIM SIMILAR
SJI STEEL JOIST INSTITUTE
SMS SHEET METAL SCREW
SPEC(S) SPECIFICATION(S)
SPRT SUPPORT
SQ SQUARE
SS STAINLESS STEEL
ST SNUG TIGHT
STD STANDARD
STIF/STIFF STIFFENER
STL STEEL
STRUCT STRUCTURAL, STRUCTURE
SUSP SUSPENDED
SYM SYMMETRICAL
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TGB TOP OF GRADE BEAM
THK THICK, THICKNESS
TL TOTAL LOAD
TN TOE NAIL
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOS TOP OF STEEL
TOW TOP OF WALL
TYP TYPICAL
UFC UNITED FACILITES CRITERIA
UNO UNLESS NOTED OTHERWISE
UON UNLESS OTHERWISE NOTED
VB VAPOR BARRIER
VERT VERTICAL
W WIDTH, WEST, WIDE FLANGE
w/ WITH
WF WIDE FLANGE
WPT WORKING POINT
WWF WELDED WIRE FABRIC
WWM WELDED WIRE MESH
x BY, TIMES
C
B
A
NO. REVISIONS DATE
Defense Supply Center Richmond
DLA Installation Management Richmond
6090 Strathmore Road
Richmond, VA 23237
DESIGNED BY:
DRAWN BY:
SCALE:
CHECKED BY:
CIVIL
ELECTRICAL
MECHANICAL
ARCHITECTURAL
STRUCTURAL
PROJECT NO.
DRAWING NO.
DATE
AS NOTED
SHEET NAME.
BUILDING NAME.
613 NW LOOP 410, STE 700
SAN ANTONIO, TX 78216
(210) 841-2800
HDR ENGINEERING, INC
TEXAS P.E. FIRM
REGISTRATION NO. F-754
K. LE
C. HABY
J. JANOTA
J. CORONADO
D
C
B
A
1 2 3 4 5
D. EMANUS
RM
JM
22 AUG 2024
10356006
G-100
CODE ANALYSIS
BLDG 97 VOQ RENOVATION
22 AUG 2024
SPRINKLERED BUILDINGS
• CORRIDORS PROVIDING ACCESS TO AN EXIT: NO RATING REQUIRED IN FULLY 38.3.6.1(3), 42.3.6, & 40.3.6
NFPA 101 EXIT ACCESS CORRIDORS:
• ROOF CONSTRUCTION (INCLUDING SUPPORTING BEAMS AND JOISTS) 0 HOUR
• FLOOR CONSTRUCTION (INCLUDING SUPPORTING BEAMS AND JOISTS) 0 HOUR
• NONBEARING WALLS & PARTITIONS - INTERIOR 0 HOUR
• NONBEARING WALLS - EXTERIOR SEPARATION DISTANCE >30' 0 HOUR
• BEARING WALLS - INTERIOR 0 HOUR
• BEARING WALLS - EXTERIOR SEPARATION DISTANCE >30' 0 HOUR
• STRUCTURAL FRAME (INCLUDING COLUMNS, GIRDERS, AND TRUSSES) 0 HOUR
IBC 601 & TABLE 602 ALL ALLOWABLE
COMBUSTIBLE MATERIALS AS DEFINED
IN SECTION 603
IBC STRUCTURAL ELEMENTS:
FIRE RESISTANCE REQUIREMENTS
• ALLOWABLE HEIGHT: THREE (3) STORIES (S-1 OCCUPANCY) IBC TABLE 506.2
• ALLOWABLE GROSS SQUARE FEET OF BUILDING: 7,000 SQUARE FEET IBC §507.5
ALLOWABLE IBC BUILDING HEIGHT AND FLOOR AREA:
MODERATE-HAZARD STORAGE NFPA CHAPTER 42
EXSTING HOTELS AND DORMITORIES NFPA CHAPTER 29
• NFPA OCCUPANCY CLASSIFICATIONS - MULTIPLE OCCUPANCY, SEPARATED OCCUPANCY NFPA 101 § 6.1.14
GROUP S-1 (MODERATE STORAGE) IBC § 311.2 (MODERATE STORAGE)
GROUP R-2 (RESIDENTIAL WITH TWO OR MORE SLEEPING UNITS) IBC § 310 (RESIDENTIAL)
• IBC OCCUPANCY CLASSIFICATIONS - MIXED USE, SEPARATED OCCUPANCY IBC § 508
BUILDING OCCUPANCY CLASSIFICATION
• BUILDING IS PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM
• BUILDING HEIGHT AND STORIES: 16'-0" AND ONE (1) STORY IBC § 502 BUILDING HEIGHT DEFINITION
• TOTAL BUILDING AREA: 2,844 SQ.FT. IBC § 502 BUILDING AREA DEFINITION
• TYPE VB CONSTRUCTION (IBC) IBC § 602 & TABLE 601
BUILDING DESCRIPTION - PROVIDED
AFM 32-1084, FACILITY REQUIREMENTS
ASME/ANSI A13.1- SCHEME FOR THE IDENTIFICATION OF PIPING SYSTEMS.
INTERNATIONAL EXISTING BUILDING CODE (IEBC), 2021 EDITION. (AS AMENDED BY UFC 1-200-01)
INTERNATIONAL CODE COUNCIL, INTERNATIONAL BUILDING CODE (IBC), 2021 EDITION. (AS AMENDED BY UFC 1-200-01)
OTHER REFERENCES
NFPA 1963, STANDARD FOR FIRE HOSE CONNECTIONS, 2019 EDITION.
NFPA 400, HAZARDOUS MATERIALS CODE, 2022 EDITION.
NFPA 291, RECOMMEND PRACTICE FOR FIRE FLOW TESTING AND MARKING OF HYDRANTS, 2019 EDITION.
NFPA 241, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS, 2022 EDITION.
NFPA 170, FIRE SAFETY SYMBOLS, 2024 EDITION.
NFPA 101, LIFE SAFETY CODE, 2024 EDITION.
NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATION SYSTEMS, 2024 EDITION.
NFPA 80, STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES, 2022 EDITION.
NFPA 72, NATIONAL FIRE ALARM CODE, 2022 EDITION.
NFPA 70, NATIONAL ELECTRIC CODE, 2023 EDITION.
NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES 2022 EDITION.
NFPA 13R, STANDARD FOR THE INSTALLATION OF SPRINKLERS IN LOW RISE RESIDENTIAL OCCUPANCIES, 2022 EDITION.
NFPA 1, FIRE CODE, 2024 EDITION.
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) - LATEST EDITIONS
UFC 4-010-01, DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS, CHANGE 1, 1 OCTOBER 2013.
UFC 3-601-02, OPERATION AND MAINTENANCE: INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS, 8 SEP 2010.
UFC 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES, CHANGE 6, 6 MAY 2021.
UFC 3-580-01, TELECOMMUNICATIONS INTERIOR INFRASTRUCTURE PLANNING AND DESIGN, CHANGE 1, 1 JUNE 2016.
UFC 3-520-01, INTERIOR ELECTRICAL SYSTEMS, 26 OCTOBER 2015.
UFC 3-400-02, DESIGN: ENGINEERING WEATHER DATA, 28 FEB 2003.
UFC 3-301-01, STRUCTURAL ENGINEERING, 11 APR 2023, CHANGE 1, 2 OCT 2023.
UFC 3-230-01, WATER STORAGE, DISTRIBUTION AND TRANSMISSION, 1 NOV 2012, CHANGE 2, 1 JUL 2014.
UFC 1-300-02, UNIFIED FACILITIES GUIDE SPECIFICATIONS (UFGS) FORMAT STANDARD, 1 APRIL 2014.
UFC 1-200-02, HIGH PERFORMANCE AND SUSTAINABLE BUILDING REQUIREMENTS
UFC 1-200-01, GENERAL BUILDING REQUIREMENTS, CHANGE 3, 26 FEB, 2024
UNIFIED FACILITIES CRITERIA (UFC)
REFERENCED CODES AND STANDARDS:
CODE ANALYSIS
• DOORS FROM HANGAR BAYS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL. UFC 4-211-01 § 3-3.1.9
• DOORS SHALL SWING IN THE DIRECTION OF TRAVEL WHERE SERVING MORE THAN 50 PERSONS. NFPA 101 § 7.2.1.4.2
• NOT LESS THAN 32" FOR DOOR CLEAR WIDTH NFPA 101 § 7.2.1.2.4
• NOT LESS THAN 36" FOR ANY MEANS OF EGRESS NFPA 101 § 7.3.4.1 (2)
MINIMUM WIDTH:
• STORAGE, SPRINKLERED: 50 FEET NFPA 101 TABLE A7.6
• EXISTING HOTELS AND DORMITORIES, SPRINKLERED: 50 FEET NFPA 101 § 29.2.5.3
DEAD-END LIMITS
• STORAGE, SPRINKLERED: 100 FEET NFPA 101 TABLE 42.2.5
• EXISTING HOTELS AND DOMRITORIES, SPRINKLERED: 50 FEET NFPA 101 §29.2.5.2.1
COMMON PATH OF TRAVEL
• STORAGE: 400 FEET NFPA 101 TABLE 42.2.6
• EXISTING HOTEL AND DORMITORY, SPRINKLERED: 125 FEET NFPA 101 §29.2.6.2
TRAVEL DISTANCE TO AN EXIT
WHEN TRAVEL DISTANCE TO AN EXIT ON THAT STORY IS NOT IN EXCESS OF COMMON PATH TRAVEL LIMITATIONS.
• STORIES USED EXCLUSIVELY FOR MECHANICAL EQUIPMENT: SINGLE MEANS OF EGRESS FROM STORY NFPA 101 § 7.12.2
AREAS OF REFUGE WILL BE PROVIDED. NFPA 101 § 7.5.4.1.1
• ACCESSIBLE MEANS OF EGRESS - NOT LESS THAN 2 MEANS OF EGRESS WILL BE PROVIDED. NO NFPA 101 § 7.5.4.1
• OCCUPANT LOAD 1-500: NOT LESS THAN 2 MEANS OF EGRESS REQUIRED NFPA 101 § 7.4.1.1
MINIMUM NUMBER OF MEANS OF EGRESS
MEANS OF EGRESS REQUIRED; SEE LIFE SAFETY PLANS FOR EGRESS PROVIDED
STORAGE A, B, OR C A, B, OR C A, B, OR C CLASS I OR II
BUSINESS A, B, OR C A, B, OR C A, B, OR C CLASS I OR II
RESIDENTIAL A OR B A OR B A, B, OR C CLASS I OR II
EXITS EXIT ACCESS
CORRIDORS
ROOMS AND
ENCLOSED SPACES
INTERIOR FINISH
FLOOR
GROUP
WITH SPRINKLER SYSTEM
INTERIOR WALL, CEILING, AND FLOOR FINISHES: NFPA 101 CHAPTER 10 TABLE A.10.2.2
• PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED IN ACCORDANCE WITH UFC 3-600-01
FIRE EXTINGUISHERS
IN NFPA 13R AND UFC 3-600-01.
• AUTOMATIC SPRINKLER SYSTEMS MUST COMPLY WITH THE RESIDENTIAL DESIGN CRITERIA UFC 3-600-01 § 9-7.3.1.1
CONSTRUCTION GREATER THAN 5,000 SQ FT.
• AUTOMATIC SPRINKLER PROTECTION IS REQUIRED FOR SINGLE-STORY, TYPE III, IV, AND V UFC 3-600-01 § 9-7.2.1.3
• AUTOMATIC SPRINKLER PROTECTION IS REQUIRED THROUGHOUT.
AUTOMATIC SPRINKLER PROTECTION
RESTRICTIVE FIRE ALARM REQUIREMENTS SHALL APPLY TO ALL OCCUPANCIES.
• OCCUPANCIES ARE MIXED OCCUPANCIES (NON-SEPARATED), THE MOST NFPA 101 § 6.1.14.3
• RESIDENTIAL OCCUPANCY - REQUIRED NFPA 101 § 29.3.4
• INDUSTRIAL OCCUPANCY - REQUIRED FOR OCCUPANCIES WITH MORE THAN 100 OCCUPANTS. NFPA 101 § 40.3.4
• STORAGE OCCUPANCY - NO REQUIREMENT NFPA 101 § 42.3.4.1.3
• MANUAL PULL STATION AT ALL EXIT DOORS UFC 3-600-01
GENERAL FIRE ALARM SYSTEM REQUIREMENTS (UFC-3-600-01, NFPA 70, NFPA 72, ABA AND UFC 4-010-01)
FIRE ALARM
ACTIVE FIRE PROTECTION SYSTEMS (SHALL COMPLY WITH UFC 3-600-01 CH.9):
• DIMENSIONS OF FIRE LANES AND TURNAROUNDS COMPLY WITH NFPA 1.
FOR FIRE DEPARTMENT INGRESS AND WITHIN 150FT OF FIRE DEPARTMENT CONNECTIONS.
• ONE MEANS OF PAVED ALL-WEATHER GROUND ACCESS NO FARTHER THAN 33 FEET FROM AN EXTERIOR DOOR ACCESSIBLE
FIRE DEPARTMENT VEHICLE ACCESS (UFC 3-600-01 §9-1 AND UFC 4-211-01; SEE CODE SITE PLAN)
• STORAGE USE; 300 SQ.FT./PERSON GROSS FLOOR AREA
• RESIDENTIAL USE; 200 SQ.FT./PERSON GROSS FLOOR AREA
NFPA 101 TABLE 7.3.1.2
OCCUPANCY LOAD FACTORS
FULLY SPINKLERED.
• STAIRS - 0.3 INCHES PER OCCUPANT FOR DOORS IN BUILDINGS THAT ARE NFPA 101 TABLE 7.3.3.1
THAT ARE FULLY SPRINKLERED.
• LEVEL COMPONENTS (DOORS) - 0.2 INCHES PER OCCUPANT FOR DOORS IN BUILDINGS NFPA 101 TABLE 7.3.3.1
OCCUPANCY CAPACITY FACTORS:
WITH SECTION 903.3.1.1.
THROUGHOUT BY AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE
2. AREAS OF REFUGE ARE NOT REQUIRED AT STAIRWAYS IN BUILDINGS EQUIPPED
IN ACCORDANCE WITH SECTION 903.3.1.1.
IN BUILDINGS EQUIPPED THROUGHOUT BY AN AUTOMATIC SPRINKLER SYSTEM
1. THE CLEAR WIDTH OF 48 INCHES BETWEEN HANDRAILS IS NOT REQUIRED
EXCEPTION:
2. INTERIOR EXIT STAIRWAYS COMPLYING WITH SECTIONS 1007.3 & 1009.
1. ACCESSIBLE ROUTES COMPLYING WITH SECTION 1104.
IN DESIGN ARE LISTED)
WAY AND SHALL CONSIST OF ONE OR MORE OF THE FOLLOWING (ONLY THOSE INCLUDED
• EACH REQUIRED ACCESSIBLE MEANS OF EGRESS SHALL BE CONTINUOUS TO A PUBLIC IBC § 1007.3
ACCESSIBLE PORTION OF THE SPACE SHALL BE SERVED BY NOT LESS THAN TWO
REQUIRED BY SECTION 1015.1 OR 1021.1 FROM ANY ACCESSIBLE SPACE, EACH
ACCESSIBLE MEANS OF EGRESS. WHERE MORE THAN ONE MEANS OF EGRESS ARE
• ACCESSIBLE MEANS OF EGRESS SHALL BE PROVIDED WITH NOT LESS THAN ONE IBC 1007.1
MEANS OF EGRESS.
• ACCESSIBLE MEANS OF EGRESS SHALL COMPLY WITH THE IBC §1007 ACCESSIBLE ABA F207.1
THE 2015 EDITION WILL BE USED.
EGRESS AND ACCESSIBILITY.UTILIZE THE ABA.WHERE THE ABA REFERENCES THE IBC, § 2-10 & 2-11
• PER UFC 1-200-01 §2-11, DELETE CHAPTER 10 & 11 OF THE IBC FOR MEANS OF UFC 1-200-01
ACCESSIBLE MEANS OF EGRESS
MEANS OF EGRESS (CONTINUED):
08/22/2024
T
-2 T
D -2
T D
-2
T D
-1 T
D -1
T D
-1
T D
-3 T
D -3
T D
-4 T
D -4
T D
-4
COMM
47 SF
LAUNDRY
127 SF
BEDROOM
124 SF
BEDROOM
125 SF
KITCHEN
62 SF
VENDING
97 SF
LIVING RM
167 SF
LIVING RM
168 SF
LIVING RM
177 SF
BEDROOM
113 SF
BEDROOM
113 SF
R.R
72 SF
R.R
69 SF
LIVING RM
177 SF
KITCHEN
62 SF
BEDROOM
125 SF
LIVING RM
168 SF
R.R
44 SF
BEDROOM
125 SF
LIVING RM
163 SF
R.R
40 SF
R.R
40 SF
R.R
40 SF
32" 0.2
32" 0.2
32" 0.2
32" 0.2
32" 0.2
32" 0.2
32" 0.2
32" 0.2
73" 0.3
74" 0.3
EXIT WIDTH [INCHES]
EXIT DOOR TAG
LINE TYPES FOR MEANS OF EGRESS:
TRAVEL DISTANCE
COMMON PATH
COMPONENT SYMBOL
LIFE SAFETY SYMBOLS:
TD
CP
EXIT DISCHARGE ARROW
EXIT DISCHARGE
A
B
C
CAPACITY FACTOR [INCHES PER OCCUPANT]
EXIT CAPACITY [OCCUPANTS]
FIRE EXTINGUISHER
(ABC EXTINGUISHER)
1. FOR EXIT LIGHT AND EMERGENCY LIGHTING, SEE
ELECTRICAL LIGHTING DRAWINGS (E SERIES).
LIFE SAFETY NOTES:
EXISTING EXIT SIGN
1 2 3 4 5
D
C
B
A
NO. REVISIONS DATE
Defense Supply Center Richmond
DLA Installation Management Richmond
6090 Strathmore Road
Richmond, VA 23237
DESIGNED BY:
DRAWN BY:
SCALE:
CHECKED BY:
CIVIL
ELECTRICAL
MECHANICAL
ARCHITECTURAL
STRUCTURAL
PROJECT NO.
DRAWING NO.
DATE
AS NOTED
SHEET NAME.
BUILDING NAME.
PLAN NORTH
613 NW LOOP 410, STE 700
SAN ANTONIO, TX 78216
(210) 841-2800
HDR ENGINEERING, INC
TEXAS P.E. FIRM
REGISTRATION NO. F-754
K. LE
C. HABY
J. JANOTA
J. CORONADO
D
C
B
A
1 2 3 4 5
D. EMANUS
RM
JM
22 AUG 2024
10356006
G-101
LIFE SAFETY PLAN
BLDG 97 VOQ RENOVATION
22 AUG 2024
1/4" = 1'-0"A1
LIFE SAFETY PLAN
MEANS OF EGRESS
EGRESS
PATH ID OCCUPANCY SPRINKLER PROVIDED
MAXIMUM
PERMITTED NFPA 101 REF
TD-1 STORAGE YES 27' - 0" 400' - 0" TABLE 42.2.6
TD-2 EXISTING HOTELS AND
DORMITORIES
YES 37' - 0" 125' - 0" 29.2.6.2
TD-3 EXISTING HOTELS AND
DORMITORIES
YES 30' - 0" 125' - 0" 29.2.6.2
TD-4 EXISTING HOTELS AND
DORMITORIES
YES 35' - 6" 125' - 0" 29.2.6.2
LEGEND
TOTAL 23
162 BEDROOM HOTEL AND DORMITORY 125 200 1
161 R.R. HOTEL AND DORMITORY 40 200 1
160 LIVING RM HOTEL AND DORMITORY 163 200 1
152 BEDROOM HOTEL AND DORMITORY 125 200 1
151 R.R. HOTEL AND DORMITORY 44 200 1
150 LIVING RM HOTEL AND DORMITORY 168 200 1
143 BEDROOM HOTEL AND DORMITORY 113 200 1
142 R.R. HOTEL AND DORMITORY 73 200 1
141 KITCHEN HOTEL AND DORMITORY 62 200 1
140 LIVING RM HOTEL AND DORMITORY 177 200 1
133 BEDROOM HOTEL AND DORMITORY 113 200 1
132 R.R. HOTEL AND DORMITORY 69 200 1
131 KITCHEN HOTEL AND DORMITORY 62 200 1
130 LIVING RM HOTEL AND DORMITORY 177 200 1
122 BEDROOM HOTEL AND DORMITORY 125 200 1
121 R.R. HOTEL AND DORMITORY 40 200 1
120 LIVING RM HOTEL AND DORMITORY 168 200 1
112 BEDROOM HOTEL AND DORMITORY 124 200 1
111 R.R. HOTEL AND DORMITORY 40 200 1
110 LIVING RM HOTEL AND DORMITORY 167 200 1
102 COMM IT EQUIPMENT ROOM 47 300 1
101 LAUNDRY STORAGE (GROSS) 127 300 1
100 VENDING STORAGE (GROSS) 97 300 1
ROOM # ROOM DESCRIPTION OCCUPANT USE TYPE
AREA
(SQ SF)
OCCUPANT
LOAD FACTOR
(SQ SF/PERSON)
OCCUPANT
LOAD
OCCUPANT LOAD SCHEDULE
SHEET KEYNOTES
GENERAL STRUCTURAL NOTES
G1. SCOPE
THE NOTES ON THIS SHEET AND THE STANDARD STRUCTURAL DETAILS ARE GENERAL AND
APPLY TO THE ENTIRE PROJECT WHETHER SPECIFICALLY CALLED OUT OR NOT, EXCEPT
WHERE THERE ARE SPECIFIC INDICATIONS TO THE CONTRARY ON STRUCTURAL SHEETS. IF
THERE ARE QUESTIONS, THEY SHALL BE SUBMITTED TO THE CONTRACTING OFFICER AND
ANSWERED IN WRITING PRIOR TO CONSTRUCTION.
G2. APPLICABLE SPECIFICATIONS AND CODES
A. INTERNATIONAL BUILDING CODE, IBC 2021 WITH APPLICABLE EDITIONS OF THE CODE
REFERENCED STANDARDS.
B. UFC 1-200-01 WITH CHANGE 3, DATED 26 FEB 2024
C. UFC 3-301-01 WITH CHANGE 1, DATED 2 OCT 2023
D. ACI 318-19
E. ASCE 7-16 WITH SUPPLEMENT 1
F. ANSI/AWC NDS 2018 WITH 2018 NDS SUPPLEMENT
G3. DESIGN CRITERIA
1. APPLIES TO ALL STRUCTURES (UNO)
A. DEAD LOAD:
1. ACTUAL TRIBUTARY STRUCTURE WEIGHT
B. LIVE LOAD:
1. PRIVATE ROOMS AND COORIDORS: 40 PSF
2. UNINHABITABLE ATTIC WITHOUT STORAGE: 10 PSF
3. LAUNDRY ROOMS: 75 PSF
4. ROOF: 20 PSF (NOT REDUCIBLE)
C. WIND:
1. ULTIMATE WIND SPEED (Vult): 113 MPH
2. NOMINAL WIND SPEEP (VASD): 88 MPH
3. RISK CATEGORY: II
3. EXPOSURE: C
4. ALL STRUCTURES ARE ENCLOSED
D. SEISMIC:
1. RISK CATEGORY: II
2. IMPORTANCE FACTOR: 1.00
3. SPECTRAL RESPONSE ACCELERATION, SS = 0.214
4. SPECTRAL RESPONSE ACCELERATION, S1 = 0.054
5. SITE CLASS: D (ASSUMED)
6. SEISMIC DESIGN CATEGORY: B
7. SPECTRAL RESPONSE COEFFICIENT, SDS = 0.228
8. SPECTRAL RESPONSE COEFFICIENT, SD1 = 0.086
9. BASIC SEISMIC FORCE RESISTING SYSTEM: LIGHT-FRAME (WOOD) WALLS SHEATEHD
WITH WOOD STRUCTURAL PANELS (ASSUMED)
10. ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE
11. DESIGN BASE SHEAR: 2.0 KIPS
12. SEISMIC RESPONSE COEFFICIENT, = 0.035
13. RESPONSE MODIFICATION FACTOR, = 6.5
E. SNOW LOAD:
1. GROUND SNOW LOAD (pg) = 20 PSF
2. SLOPED ROOF SNOW LOAD (ps) = 13 PSF
3. EXPOSURE FACTOR = 0.9
4. IMPORTANCE FACTOR = 1.0
5. THERMAL FACTOR = 1.0
6. SLOPED ROOF FACTOR = 1.0
7. FROST DEPTH = 18 INCHES
G4. AT THE TIME OF THIS DESIGN, NO GEOTECHNICAL REPORT WAS PREPARED FOR THIS PROJECT.
THE FOLLOWING ASSUMED VALUE WAS USED DURING DESIGN BASED ON THE AS-BUILT DRAWINGS OF ADJACENT STRUCTURES AND IBC TABLE 1806.2. CONTRACTOR SHALL VERIFY SOIL CONDITIONS WITH AN OPEN-HOLE INSPECTION BY A QUALIFIED GEOTECHNICAL ENGINEER PRIOR TO CONSTRUCTION
AND PLACEMENT OF SOIL SUPPPORTED CONCRETE.
ALLOWABLE SOIL BEARING = 1,500 PSF (GRAVITY)
2,000 PSF (SEISMIC/WIND)
LATERAL BEARING PRESSURE = 100 PSF
COEHSION = 130 PSF
G5. SAFETY
SAFETY AND STRUCTURE STABILITY DURING CONSTRUCTION ARE THE SOLE RESPONSIBILITY
OF THE CONTRACTOR. STRUCTURES HAVE BEEN DESIGNED TO RESIST THE DESIGN LIVE
LOADS ONLY AS A COMPLETED STRUCTURE.
G6. OPENINGS
OPENINGS FOR PIPES, DUCTS, CONDUITS, ETC. ARE NOT ALL SHOWN ON THE
STRUCTURAL DRAWINGS. COORDINATE AND PROVIDE OPENINGS AS REQUIRED TO
ACCOMMODATE ALL WORK SHOWN OR SPECIFIED IN THE CONTRACT DOCUMENTS AND
OTHERWISE REQUIRED FOR THE FURNISHING OF A FUNCTIONALLY COMPLETE PROJECT.
REINFORCE AROUND OPENINGS PER STANDARD STRUCTURAL DETAILS UNLESS OTHERWISE
SHOWN.
G7. STANDARD DETAILS
THE STANDARD DETAILS DEPICT TYPICAL DETAILING TO BE USED ON THIS PROJECT. IF
CONDITIONS ARE NOT EXPLICITLY SHOWN ON THE DRAWINGS THEY SHALL BE MADE
SIMILAR TO THE STANDARD DETAILS. OBTAIN APPROVAL OF THE CONTRACTING OFFICER IN WRITING
FOR SIMILAR CONDITIONS PRIOR TO CONSTRUCTION.
G8. THE CONTACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS OF EXISTING
CONSTRUCTION AS REQUIRED TO COORDINATE NEW CONSTRUCTION. SUBMIT REQUIRED
CHANGES FOR APPROVAL.
G9. CONTRACTOR TO SUBMIT FOR REVIEW ALL EQUIPMENT SIZES, OPERATING WEIGHTS,
VIBRATION FORCES, SUPPORT LOCATIONS, ALONG WITH ANY FLOOR OPENINGS, NOTCHES,
AND RECESSES REQUIRED BY SUCH EQUIPMENT. CONCRETE SUPPORT PADS AND/OR
FRAMING REQUIRED TO SUPPORT SAID EQUIPMENT SHALL NOT BE FABRICATED AND
PLACED UNTIL THE CONCRETE SUPPORT PADS AND/OR FRAMING IS APPROVED TO
SUPPORT THE EQUIPMENT.
CONCRETE
C1. DESIGN STRENGTHS:
F'c = 4,000 PSI Fy = 60,000 PSI
C2. CONCRETE COVER
UNLESS OTHERWISE NOTED, PROVIDE CONCRETE COVER FOR REINFORCING AS FOLLOWS:
CONCRETE DEPOSITED AGAINST EARTH: 3"
CONCRETE IN CONTACT WITH GROUND: 1 1/2"
CONCRETE NOT IN CONTACT WITH GROUND:
SLABS: 3/4"
BEAMS: 1 1/2"
SEE DRAWINGS FOR EXCEPTIONS
C3. SEE SPECIFICATIONS FOR REINFORCING PLACEMENT REQUIREMENTS.
C4. REFER TO OTHER DISCIPLINE DRAWINGS PRIOR TO CONSTRUCTION FOR EMBEDDED ITEMS
AND PENETRATIONS NOT SHOWN ON STRUCTURAL DRAWINGS. AS REQUIRED TO
ACCOMMODATE ALL WORK SHOWN OR SPECIFIED IN THE CONTRACT DOCUMENTS AND
OTHERWISE REQUIRED FOR THE FURNISHING OF A FUNCTIONALLY COMPLETE PROJECT.
REINFORCE AROUND OPENINGS PER STANDARD STRUCTURAL DETAILS UNLESS OTHERWISE
SHOWN.
C5. PROVIDE 3/4" CHAMFERS AT ALL EXPOSED EDGES NOT ALL CHAMFERS MAY BE SHOWN
ON DRAWINGS.
C6. FIELD ADJUST REINFORCING AT OPENINGS AND EMBEDDED ITEMS AS INDICATED.
C7. ANCHOR BOLTS NOT SPECIFIED BY ENGINEER SHALL BE DESIGNED AND CERTIFIED BY A
REGISTERED PROFESSIONAL ENGINEER , RETAINED BY THE CONTRACTOR, IN ACCORDANCE WITH APPLICABLE PROJECT AND CODE REQUIREMENTS. SUBMIT AS A SHOP DRAWING FOR REVIEW AND APPROVAL BY THE CONTRACTING OFFICER. COORDINATE LOCATION, SIZE AND EMBEDMENT PRIOR
TO CASTING CONCRETE.
C8. ABSOLUTELY NO WELDING OF REINFORCING BARS OR TORCHING TO BEND REINFORCING
BARS SHALL BE ALLOWED WITHOUT SPECIFIC APPROVAL FROM THE CONTRACTING OFFICER.
C10. ALL CAST IN PLACE AND POST-INSTALLED ANCHORS INDICATED IN THE STRUCTURAL
DOCUMENTS SHALL COMPLY WITH CHAPTER 17 OF ACI 318 AND CHAPTER 19 OF THE
IBC. ALL EXPANSION AND ADHESIVE ANCHORS SHALL HAVE THE ICC REPORT SHOWING
EQUIVALENT LOAD CAPACITY. SUBMIT AND INSTALL PER THE ICC EVALUATION REPORT.
CONSTRUCTION AT EXISTING STRUCTURES
CE1. WHERE DRILL AND EPOXY REINFORCING OR ANCHORS ARE INSTALLED CONTRACTOR SHALL NOT
DAMAGE EXISTING REINFORCING. IF REQUIRED CONTRACTOR SHALL HAVE EXISTING CONCRETE
INVESTIGATED USING GROUND PENETRATING RADAR TO LOCATE EXISTING REINFORCING.
CE2. EXISTING CONCRETE SURFACES TO BE JOINED WITH NEW CONCRETE SHALL BE ROUGHENED TO A 1/4" AMPLITUDE, THOROUGHLY CLEANED BY SAND BLASTING, AND APPLY BONDING AGENT JUST
PRIOR TO PLACEMENT OF NEW CONCRETE.
CE3. WHERE EXISTING REINFORCING IS TO BE PRESERVED, CONTRACTOR SHALL STRAIGHTEN AND SAND
BLAST REINFORCING JUST PRIOR RO PLACEMENT OF NEW CONCRETE.
WOOD
W1. ALL LUMBER SHALL BE GRADED BY AN AGENCY CERTIFIED BY THE AMERICAN LUMBER STANDARDS
COMMITTEE. AT TIME OF CONSTRUCTION, MOISTURE CONTENT SHALL NOT EXCEED 19%.
W2. WOOD SHALL BE GRADE MARKED DOUGLAS FIR AND AS FOLLOWS:
a. HORIZONTAL FRAMING: NO. 2
b. STUDS: NO. 2
c. SILLS AND BLOCKING: NO. 2
d. POSTS AND COLUMNS: NO. 2
e. BEAMS: NO. 2
W3. ALL PRESSURE TREATED LUMBER SHALL BE MARKED PER AWPA STANDARD U1 AND MEET OR EXCEED WATERBORNE PRESERVATIVES WOTH RETENTION OF 0.25 PCF FOR ABOVE FROUND AND 0.40 PCF FOR
SOIL AND GROUND CONTACT USE.
W4. ALL WOOD IN CONTACT WITH CONCRETE SHALL BE PRESERVATIVE-TREATED. ALL BOLTS IN CONTACT
WITH PRESSURE TREATED WOOD TO BE HOT DIPPED GALVANIZED.
W5. PLYWOOD SHEATHING SHALL BE DOUGLAS FIR PLYWOOD STRUCTURAL 1, CONFORMING TO DOC PS1
OR PS2. ALL PLYWOOD SHALL BE GRADE MARKED "DFPA STRUCTRUAL 1, EXPOSURE 1"
W6. PLYWOOD NAILING SHALL BE APPROVED BY THE INSPECTOR AND CONTRACTING OFFICER OR
ARCHITECT, PRIOR TO COVERING UP.
W7. FRAMING HARDWARE SHALL BE AS MANUFACTURED BY SIMPSON STRONG TIE OR APPROVED EQUAL.
FASTENERS TO BE FURNISHED BY THE MANUFACTURER AND ALL HOLES TO BE FILLED.
W8. MACHINE APPLIED NAILING IS SUBJECT TO A SATISFACTORY JOBSITE DEMONSTRATION FOR EACH
PROJECT AND THE APPROVAL BY THE CONTRACTING OFFICERS. THE APPROVAL IS SUBJECT TO
CONTINUED SATISFACTORY PERFORMANCE. IF NAIL HEADS PENETRATE THE OUTER PLY MORE THAN
WOULD BE NORMAL FOR A HAND HAMMER, OR IF MINIMUM ALLOWANCE EDGE DISTANCE ARE NOT
MAINTAINED, THE PERFORMANCE WILL BE DEEMED UNSATISFACTORY.
W9. PROVIDE PLATE WASHERS UNDER ALL BOLTS NUTS AND HEADS.
W10. RETIGHTEN BOLTS PRIOR TO CLOSING IN.
W11. ALL NAILING SHALL CONFORM TO TABLES SET FORTH IN CHAPTER 23 OF THE INTERNATIONAL BUILDING
CODE EXCEPT AT SPECIFICALLY DETAILED CONNECTIONS. USE ONLY COMMON NAILS.
W12. ALL FRAMING MEMBERS SHALL BE ERECTED WITH NATURAL OR BUILT-IN CAMBER UP UNLESS NOTED
OTHERWISE.
NEW DRAIN PIPE.
SEE PLUMBING FOR
REQUIREMENTS
EXIST REINF
TOOLED JOINT, TYP
ROUGHEN TO A MIN 1/4"
AMPLITUDE AND APPLY
BONDING AGENT
W6xW6-4x4 PLACED MID-DEPTH
NEW 10MIL VAPOR BARRIER
AT NEW INFILL SLAB.
OVERLAP 3" MIN WITH EXIST
VAPOR BARRIER AND TAPE
UNDISTURBED SUBGRADE
PROVIDE PIPE BEDDING IN
ACCORDANCE WITH ASTM
D2321 CLASS II. SOIL TYPES
INCLUDE GW, GP, SW, AND SP
AS CLASSIFIED IN ASTM D2487.
COMPACT TO MINIMUM 85%
STANDARD PROCTOR.
DO NOT UNDERMINE
EXIST SLAB
WORK OF DEMOLITION/ NEW WORK
REFERENCE PLUMBING FOR EXTENTS
AND LOCATIONS AS REQ'D FOR PLUMBING
SAND LAYER BELOW NEW CONC. SAND
SHALL BE CLASSIFIED AS SW OR SP BY
ASTM D2487.
V .I .F
B A
C K
F
IL
L
M
IN
/2
M
IN
1 2 3 4 5
D
C
B
A
NO. REVISIONS DATE
Defense Supply Center Richmond
DLA Installation Management Richmond
6090 Strathmore Road
Richmond, VA 23237
DESIGNED BY:
DRAWN BY:
SCALE:
CHECKED BY:
CIVIL
ELECTRICAL
MECHANICAL
ARCHITECTURAL
STRUCTURAL
PROJECT NO.
DRAWING NO.
DATE
AS NOTED
SHEET NAME.
BUILDING NAME.
613 NW LOOP 410, STE 700
SAN ANTONIO, TX 78216
(210) 841-2800
HDR ENGINEERING, INC
TEXAS P.E. FIRM
REGISTRATION NO. F-754
K. LE
C. HABY
J. JANOTA
J. CORONADO
D
C
B
A
2 3 4 51
D. EMANUS
CM
CM
22 AUG 2024
10356006
S-001
GENERAL STRUCTURAL NOTES
DSCR BUILDING 97 VOQ RENOVATION
22 AUG 2024
NTSA3
SLAB REPAIR DRAIN INFILL
DN
UP
COMM
LAUNDRY
BEDROOM
BEDROOM
KITCHEN
VENDING
LIVING RM
LIVING RM
LIVING RM
BEDROOM
BEDROOM
R.R
R.R
LIVING RM
KITCHEN
141 BEDROOM
LIVING RM
R.R
BEDROOM
LIVING RM
R.R
R.R
R.R
1 1
2 2
4 4
4 4 4 4
7 7
7 7
9 9 9
9 9
9 9
A-102 C2
A-102 C1
A-201
A3
A-201
C1
A-201
B1
1. (*) INDICATES EXISTING DIMENSION TO BE FIELD VERIFIED BY CONTRACTOR.
2. EXSITING BUILDING INFORMATION IS AS INDCIATED ON THE AS-BUILT
DRAWINGS. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER OF
ANY DISCREPANCIES.
3. THE EXISTING LAYOUTS INDICATED ON THESE PLANS ARE BASED ON EXISTING
PLANS AND LIMITED FIELD OBSERVATION. CONTRACTOR TO FIELD VERIFY
EXISTING CONDITIONS AS NEEDED PRIOR TO ANY CONSTRUCTION.
4. BASE DESIGN TO UPDATE ITEMS REQUIRED BY CODE, REPLACEMENT OF
MATERIALS AT WATER DAMAGED AREAS, GENERAL PAINT REFRESH, AND
PATCH AND REPAIR OF ANY OTHER DAMAGED AREAS INCLUDING CASEWORK.
5. OPTION 1 DESIGN INCLUDES BASE DESIGN AND ADDITIONAL UPGRADES,
INCLUDING NEW SIDING, WINDOW BLINDS, FANS, LIGHTING FIXTURES, LVT
FLOORING, CASEWORK REPAIR AND PAINTING, NEW ENTRY DOORS AND
STORM DOORS, AND WALL BASE.
1 2 3 4 5
D
C
B
A
NO. REVISIONS DATE
Defense Supply Center Richmond
DLA Installation Management Richmond
6090 Strathmore Road
Richmond, VA 23237
DESIGNED BY:
DRAWN BY:
SCALE:
CHECKED BY:
CIVIL
ELECTRICAL
MECHANICAL
ARCHITECTURAL
STRUCTURAL
PROJECT NO.
DRAWING NO.
DATE
AS NOTED
SHEET NAME.
BUILDING NAME.
GENERAL SHEET NOTES
PLAN NORTH
613 NW LOOP 410, STE 700
SAN ANTONIO, TX 78216
(210) 841-2800
HDR ENGINEERING, INC
TEXAS P.E. FIRM
REGISTRATION NO. F-754
K. LE
C. HABY
J. JANOTA
J. CORONADO
D
C
B
A
1 2 3 4 5
D. EMANUS
MB
VV
22 AUG 2024
10356006
AD101
FIRST FLOOR PLAN DEMOLITION
DSCR BUILDING 97 VOQ RENOVATION
22 AUG 2024
1/4" = 1'-0"A1
FIRST FLOOR PLAN DEMOLITION
1 REMOVE EXISTING, DAMAGED FLOORING
2 REMOVE EXISTING WINDOW BLINDS FOR
OPTION 1 SCOPE OF WORK
3 REMOVE EXISTING SHELVING
4 REMOVE EXISTING WINDOW VALANCES.
PATCH AND REPAIR HOLES REMAINING FROM
REMOVAL OF VALANCES. PAINT COLOR TO
MATCH WALL
5 RELOCATE EXISTING WASHER AND DRYER
6 DEMO PORTION OF WALL FOR
COORDINATION OF NEW CONDUIT FOR NEW
FACU POWER CONNECTION
7 REMOVE ALL EXISTING EXTERIOR SIDING
FOR OPTION 1 SCOPE OF WORK. IF OPTION 1
IS NOT CHOSEN, PATCH AND REPAIR
EXTERIOR SIDING PER MINIMUM CODE
REQUIREMENTS OUTLINED IN THE IEBC, UFC
1-200-01, AND UFC-3-190-06
8 REMOVE EXISTING DOOR KNOBS
THROUGHOUT THE UNIT FOR OPTION 1
SCOPE OF WORK. IF REMOVAL OF EXISTING
DOOR KNOBS REQUIRES REPAIR OF DOOR,
PATCH HOLES, SAND PATCHES AND ANY
OTHER DAMAGE AND PAINT TO SPECIFIED
PAINT COLOR
9 REMOVE EXISTING DOOR AND STORM DOOR,
OPTION 1. PATCH AND REPAIR ROUGH
OPENING TO ACCEPT NEW DOOR AND
STORM DOOR, TYP.
10 REMOVE EXISTING 12" DEEP OPEN
FLOOR-TO-CEILING SHELVING. PATCH AND
REPAIR WALL, CEILING, AND FLOOR LEFT
OVER FROM REMOVAL OF REMOVAL OF
SHELVING. MATCH WALL, CEILING TEXTURE
AND PAINT TO EXISTING. BASEBOARD
HEATER TO REMAIN AND KEPT PROTECTED
DURING CONSTRUCTION
11 REMOVE EXISTING COIN-OPERATED WASHER
AND DRYER. RELOCATE TO STORAGE IN
WAREHOUSE 4. PATCH AND REPAIR DRYER
VENT OPENING ON EXTERIOR WALL
12 REMOVE EXISTING TOILET
13 REMOVE AND RELOCATE TOILET PAPER
DISPENSER. PATCH AND REPAIR REMAINING
HOLES FROM REMOVAL OF DISPENSER.
REMOVE EMPTY WALL BOX IN ROOM 142 AND
PATCH WITH NEW DRYWALL AND TILE TO
MATCH EXISTING
COMM
LAUNDRY
BEDROOM
BEDROOM
122 KITCHEN
VENDING
LIVING RM
LIVING RM
LIVING RM
BEDROOM
BEDROOM
R.R
R.R
LIVING RM
KITCHEN
BEDROOM
LIVING RM
R.R
BEDROOM
LIVING RM
R.R
R.R
R.R
1 1
1 1
1 1
A-201
A3
A-201
C1
A-201
B1
10 SF
15 SF
35 SF
10 SF
10 SF
6 SF
10 1/2" 4' - 1"
/2
/2
/2
2' - 3"
2' - 9 1/2"
/2
/2
2' - 6"
9" 1' - 6"
15 SF 12 SF
8 SF 11 SF11 SF10 SF
1. (*) INDICATES EXISTING DIMENSION TO BE FIELD VERIFIED BY CONTRACTOR.
2. EXSITING BUILDING INFORMATION IS AS INDCIATED ON THE AS-BUILT
DRAWINGS. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER OF
ANY DISCREPANCIES.
3. THE EXISTING LAYOUTS INDICATED ON THESE PLANS ARE BASED ON EXISTING
PLANS AND LIMITED FIELD OBSERVATION. CONTRACTOR TO FIELD VERIFY
EXISTING CONDITIONS AS NEEDED PRIOR TO ANY CONSTRUCTION.
4. BASE DESIGN TO UPDATE ITEMS REQUIRED BY CODE, REPLACEMENT OF
MATERIALS AT WATER DAMAGED AREAS, GENERAL PAINT REFRESH, AND
PATCH AND REPAIR OF ANY OTHER DAMAGED AREAS INCLUDING CASEWORK.
5. OPTION 1 DESIGN INCLUDES BASE DESIGN AND ADDITIONAL UPGRADES,
INCLUDING NEW SIDING, WINDOW BLINDS, FANS, LIGHTING FIXTURES, LVT
FLOORING, CASEWORK REPAIR AND PAINTING, NEW ENTRY DOORS AND
STORM DOORS, AND WALL BASE.
REMOVE EXISTING CEILING MOUNTED FAN /
LIGHT FIXTURE. PATCH AND REPAIR ANY
REMAINING HOLES LEFT OVER FROM
EXISTING FIXTURE. LEAVE JUNCTION BOX
INTACT
DEMOLITION LEGEND
REMOVE EXISTING RECESSED CEILING LIGHT
FIXTURE. PATCH AND REPAIR WHERE
REQUIRED.
REMOVE EXISTING SURFACE MOUNTED LIGHT
FIXTURE. PATCH AND REPAIR ANY REMAINING
HOLES LEFT OVER FROM EXISTING FIXTURE
AND/OR BALLAST. FINISH CEILING TO MATCH
EXSITING TEXTURE AND PAINT COLOR.
REMOVE EXISTING WALL MOUNTED ENTRY
LIGHT FIXTURE. PATCH AND ANY REMAINING
HOLES LEFT OVER FROM EXISTING FIXTURE.
FINISH WALL TO MATCH COLOR.
REFER TO SHEET KEYNOTE FOR HATCH
DESIGNATION.
1 2 3 4 5
D
C
B
A
NO. REVISIONS DATE
Defense Supply Center Richmond
DLA Installation Management Richmond
6090 Strathmore Road
Richmond, VA 23237
DESIGNED BY:
DRAWN BY:
SCALE:
CHECKED BY:
CIVIL
ELECTRICAL
MECHANICAL
ARCHITECTURAL
STRUCTURAL
PROJECT NO.
DRAWING NO.
DATE
AS NOTED
SHEET NAME.
BUILDING NAME.
GENERAL SHEET NOTES
PLAN NORTH
613 NW LOOP 410, STE 700
SAN ANTONIO, TX 78216
(210) 841-2800
HDR ENGINEERING, INC
TEXAS P.E. FIRM
REGISTRATION NO. F-754
K. LE
C. HABY
J. JANOTA
J. CORONADO
D
C
B
A
1 2 3 4 5
D. EMANUS
MB
VV
22 AUG 2024
10356006
AD105
FIRST FLOOR REFLECTED CEILING PLAN DEMOLITION
DSCR BUILDING 97 VOQ RENOVATION
22 AUG 2024
1/4" = 1'-0"A1
FIRST FLOOR REFLECTED CEILING PLAN DEMOLITION
1 REMOVE CEILING FOR ACCESS ENTRY
POINTS FOR DEMOLITION AND INSTALLATION
OF PLUMBING WORK
2 REMOVE DAMAGED CEILING
COMM
LAUNDRY
BEDROOM
BEDROOM
KITCHEN
VENDING
LIVING RM
LIVING RM
LIVING RM
BEDROOM
BEDROOM
R.R
R.R
LIVING RM
KITCHEN
BEDROOM
LIVING RM
R.R
BEDROOM
LIVING RM
R.R
R.R
R.R
3 3
4 45 5
140130
120110
112 122
121111
152 162
161151
150 160100
131A 141A
160A150A
140A
140B
142A 132A
130B
120A110A
130A
143A133A
C3
A-101
22 22
22 22 22 22
22 22
22 22 22 22
33 33 33 33
A-201
A2
106' - 5"
35' - 3" 45' - 9" 25' - 5"
A-102 C2 3' - 0"
/2
A-102 C1
A-201
A3
A-201
C1
A-201
B1
4444 44
44 44
7" MIN. - 9" MAX.7" MIN. - 9" MAX.
51 41
W
D
A. PAINT COLOR SW 7015 - REPOSE GRAY - PT1
B. PAINT COLOR SW 7017 - DORIAN GRAY - PT2
C. PAINT COLOR SW 9143 - CADET - PT3
D. PAINT COLOR SW 7005 - PURE WHITE - PT4
E. PAINT COLOR SW 7615 - SEA SERPENT - PT5
F. PAINT COLOR SW 6237 - DARK NIGHT - PT6
G. CORNER GUARDS - INPRO FLEXIBLE, CLEAR, VINYL,
90 DEGREE CORNER GUARDS, 1" WING, 4'-0" H
H. LUXURY VINYL TILE - TARKETT iD LATITUDE WOOD LVT 6" x 48" PLANK, COLOR TBD - LVT1
I. CERAMIC TILE - CERAMIC TILE TO MATCH
EXISTING
J. TRANSITION STRIP - JOHNSONITE WHEELED TRAFFIC
VINYL TRANSITION STRIP CTA-22-L PEARL
FINISH LEGEND - BASE DESIGN
NOTE: IN ACCORDANCE WITH OPEN SOURCING REQUIREMENTS,
THE FOLLOWING SCHEDULE LISTS THE BASIS OF DESIGN FOR
INTERIOR FINISHES. REQUESTS FOR ALTERNATE SOURCING IN
COMPLIANCE WITH THE BUY AMERICA ACT AND ALL OTHER
FEDERAL REGULATIONS MAY BE SUBMITTED FOR REVIEW AND
CONSIDERATION.
01_LEVEL_FF
0' - 0"
INTERIOREXTERIOR
CL
DOOR
TILE TO LVT
/4
M
A X
1/2"2"
EXTERIOR
INTERIOR
/4
/2
INTERIOREXTERIOR
3/4"1"
DOOR HARDWARE SCHEDULE
HARDWARE
SET 1
HARDWARE
SET 2
DOOR NO. 100, 110, 120, 130, 140, 150, 160, ENTRY DOOR, OPTION 01
DOOR NO. 132, 133, 142, 143, ABA HARDWARE, BASE AND OPTION 01
BUTTS:
LOCKSET:
MISC:
IVES 5BB1HW 4-1/2" x 4-1/2" FULL MORTISE, SATIN NICKEL, HIGH FREQ. USE SCHLAGE CO-100 STANDALONE ELECTRONIC KEYPAD PRIVACY LOCKSET, ABA COMPLIANT ATHENS
LEVER, MECHANICAL KEY BACKUP, 626 SATIN CHROME
ZERO INTERNATIONAL ABA COMPLIANT 5" RABBETED ALUMINUM THRESHOLD 65AE36, BULB TYPE
WEATHERSTRIPPING, DOOR VIEWER, DOOR GUARD, DOOR BELL KIT
BUTTS:
LOCKSET:
MISC:
IVES 5BB1 4-1/2" x 4-1/2" FULL MORTISE, SATIN NICKEL
SCHLAGE DELFAYO F40 DEL 619 ABA COMPLIANT LEVER BED & BATH PRIVACY LOCKSET,
STANDARD TRIM, SATIN NICKEL
WALL / HINGE STOP
DOOR TYPES
TYPE 01 -
EXTERIOR 3-PANEL
TYPE 02 -
INTERIOR FLUSH
EXTERIOR STORM DOOR
R E
F S
C H
E D
U L E
REF. SCHEDULE
6 5/8"
4 3/4"
R E
F S
C H
E D
U L E
REF. SCHEDULE
R E
F S
C H
E D
U L E
REF. SCHEDULE
4 3/16"
RETRACTABLE
GLAZING / SCREEN
SOLID
1. (*) INDICATES EXISTING DIMENSION TO BE FIELD VERIFIED BY CONTRACTOR.
2. EXSITING BUILDING INFORMATION IS AS INDCIATED ON THE AS-BUILT
DRAWINGS. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER OF
ANY DISCREPANCIES.
3. THE EXISTING LAYOUTS INDICATED ON THESE PLANS ARE BASED ON EXISTING
PLANS AND LIMITED FIELD OBSERVATION. CONTRACTOR TO FIELD VERIFY
EXISTING CONDITIONS AS NEEDED PRIOR TO ANY CONSTRUCTION.
4. BASE DESIGN TO UPDATE ITEMS REQUIRED BY CODE, REPLACEMENT OF
MATERIALS AT WATER DAMAGED AREAS, GENERAL PAINT REFRESH, AND
PATCH AND REPAIR OF ANY OTHER DAMAGED AREAS INCLUDING CASEWORK.
5. OPTION 1 DESIGN INCLUDES BASE DESIGN AND ADDITIONAL UPGRADES,
INCLUDING NEW SIDING, WINDOW BLINDS, FANS, LIGHTING FIXTURES, LVT
FLOORING, CASEWORK REPAIR AND PAINTING, NEW ENTRY DOORS AND
STORM DOORS, AND WALL BASE.
1 2 3 4 5
D
C
B
A
NO. REVISIONS DATE
Defense Supply Center Richmond
DLA Installation Management Richmond
6090 Strathmore Road
Richmond, VA 23237
DESIGNED BY:
DRAWN BY:
SCALE:
CHECKED BY:
CIVIL
ELECTRICAL
MECHANICAL
ARCHITECTURAL
STRUCTURAL
PROJECT NO.
DRAWING NO.
DATE
AS NOTED
SHEET NAME.
BUILDING NAME.
GENERAL SHEET NOTES
PLAN NORTH
613 NW LOOP 410, STE 700
SAN ANTONIO, TX 78216
(210) 841-2800
HDR ENGINEERING, INC
TEXAS P.E. FIRM
REGISTRATION NO. F-754
K. LE
C. HABY
J. JANOTA
J. CORONADO
D
C
B
A
1 2 3 4 5
D. EMANUS
MB
VV
22 AUG 2024
10356006
A-101
FIRST FLOOR PLAN - BASE DESIGN
DSCR BUILDING 97 VOQ RENOVATION
22 AUG 2024
1/4" = 1'-0"A1
FIRST FLOOR PLAN - BASE DESIGN
DOOR SCHEDULE
DOOR
NO. TYPE
DOOR
FIRE
RATING
FRAME
HARDWARE COMMENTS:
SIZE
FINISH MATERIAL
DETAILS
WIDTH HEIGHT THICKNESS HEAD JAMB SILL
100 26 3' - 0" 6' - 8" 0' - 1 3/8" PT WD C1/A-101 C2/A-101 C3/A-101 1 OPTION 1- REPLACED DOOR AND HARDWARE, NO STORM DOOR, FLIP DOOR SWING
101 02 3' - 0" 6' - 8" 0' - 2" PT WD C1/A-101 C2/A-101 C3/A-101 NO HARDWARE CHANGES, RELOCATE AND ROTATE DOOR AND FRAME
110 01 3' - 0" 6' - 8" 0' - 1 3/8" PT WD C1/A-101 C2/A-101 C3/A-101 1 OPTION 1- REPLACED DOOR AND HARDWARE
120 01 3' - 0" 6' - 8" 0' - 1 3/8" PT WD C1/A-101 C2/A-101 C3/A-101 1 OPTION 1- REPLACED DOOR AND HARDWARE
130 01 3' - 0" 6' - 8" 0' - 1 3/8" PT WD C1/A-101 C2/A-101 C3/A-101 1 OPTION 1- REPLACED DOOR AND HARDWARE, ABA; BASE - ABA HARDWARE
132 02 3' - 0" 6' - 8" 0' - 2" PT WD C1/A-101 C2/A-101 C3/A-101 2 ABA HARDWARE
133 02 2' - 10" 6' - 8" 0' - 2" PT WD C1/A-101 C2/A-101 C3/A-101 2 ABA HARDWARE
140 01 3' - 0" 6' - 8" 0' - 1 3/8" PT WD C1/A-101 C2/A-101 C3/A-101 1 OPTION 1- REPLACED DOOR AND HARDWARE, ABA; BASE - ABA HARDWARE
142 02 3' - 0" 6' - 8" 0' - 2" PT WD C1/A-101 C2/A-101 C3/A-101 2 ABA HARDWARE
143 02 2' - 10" 7' - 0" 0' - 2" PT WD C1/A-101 C2/A-101 C3/A-101 2 ABA HARDWARE
150 01 3' - 0" 6' - 8" 0' - 1 3/8" PT WD C1/A-101 C2/A-101 C3/A-101 1 OPTION 1- REPLACED DOOR AND HARDWARE
151 02 2' - 10" 6' - 8" 0' - 2" PT WD C1/A-101 C2/A-101 C3/A-101 2 ABA HARDWARE
160 01 3' - 0" 6' - 8" 0' - 1 3/8" PT WD C1/A-101 C2/A-101 C3/A-101 1 OPTION 1- REPLACED DOOR AND HARDWARE
3" = 1'-0"C3
TYP. EXTERIOR DOOR
THRESHOLD
3" = 1'-0"C4
FLOOR TRANSITION
DETAILS
3" = 1'-0"C2
JAMB - WOOD DOOR
3" = 1'-0"C1
HEAD - WOOD DOOR
SHEET KEYNOTES
1 PAINT WALL - PT3, FINISH G3
2 REPLACE ALL DOOR KNOBS WITH ABA
COMPLIANT DOOR LEVER SETS
THROUGHOUT THE UNIT
3 PATCH, REPAIR AND PAINT EXISTING
CASEWORK, FINISH G3
4 REPLACE ALL EXISTING CORNER
GUARDS THROUGHOUT THE UNIT
WITH NEW, TYP.
5 INSTALL NEW LUXURY VINYL TILE
FLOORING
6 AT AREAS OF DAMAGED TILE,
REMOVE DAMAGED TILE AND
REPLACE TILE TO MATCH EXISTING.
ENSURE PROPER INSTALLATION IS
MET TO PROVIDE ADEQUATE
WATERPROOF BARRIER
7 PAINT TRIM, INTERIOR DOORS, TYP.
ALL ROOMS - PAINT COLOR PT4,
FINISH G5
8 NEW WOOD ENTRY DOOR - OPTION 1
9 NEW ALUMINUM STORM DOOR -
OPTION 1
10 DOOR THRESHOLD
11 EXPANSION JOINT
12 SELF-ADHERING FLASHING
13 TERMINATION BAR
14 WATERPROOFING MEMBRANE
15 CRUSHED GRAVEL
16 CENTERLINE OF TRANSITION STRIP
17 DOOR AS SCHEDULED WHERE
OCCURS
18 TILE
19 TRANSITION PROFILE WITH VISIBLE
SURFACE
20 LVT
21 NEW FLOOR SINK
22 EXISTING PTAC UNIT
23 STORM DOOR AS SCHEDULED
24 EXISTING PARTITION
25 JOINT SEALANT, EACH SIDE AND ALL
AROUND, TYP.
26 DOOR AS SCHEDULED
27 NEW ALUMINUM DRIP CAP
28 NEW FIBER CEMENT PANEL BOARD,
OPTION 1
29 AIR BARRIER
30 THROUGH WALL FLASHING WITH 1"
DRIP EDGE
31 WOOD TRIM
32 ALUMINUM DOOR HINGE FOR STORM
DOOR
33 FLOOR TRANSITION LOCATION, REF.
C3/A-101
34 EXISTING PANELBOARD "SP" TO
REMAIN
35 NEW ELECTRICAL PANEL, REF. ELEC
36 WALL MOUNTED IT CABINET, REF.
TELECOMMUNICATIONS
37 NEW PEX MANIFOLD, REF. PLUMBING
38 EXISTING FLOOR DRAIN
39 EXISTING WATER SOFTENER
40 EXISTING WATER HEATER
41 SAFETY SWITCH, REF. ELEC
42 EXISTING GRAB BAR
43 NEW 18" DEEP OPEN
FLOOR-TO-CEILING BUILT-IN
SHELVING
44 REPLACE EXISTING CABINET
HARDWARE KNOBS WITH NEW
HARDWARE PULLS. PATCH, REPAIR,
AND PAINT HOLES FROM PREVIOUS
KNOBS
45 RELOCATED TOILET PAPER
DISPENSER 18" A.F.F.
46 NEW TOILET WITH FLUSH CONTROLS
ON OPEN SIDE
47 MOVE REAR WALL GRAB BAR 6"
TOWARDS BATHTUB. REPLACE TILE
WITH LIKE MATERIALS AT HOLES OF
REMOVAL OF EXISTING GRAB BAR
48 MOVE TOWEL BAR, TOWEL RING,
SHELF TO 48" A.F.F. PATCH AND
REPAIR DRYWALL HOLES WHERE
COMPONENTS WERE REMOVED
49 NEW ABA COMPLIANT SHOWER
SPRAY UNIT WITH VERTICAL
ADJUSTABLE-HEIGHT VERTICAL BAR
50 NEW 24" CONTROL END WALL GRAB
BAR TO MATCH EXISTING HEIGHT.
PATCH, REPAIR, AND SEAL BATHTUB
ENCLOSURE AND WALL TO PREVENT
LEAKAGE INTO WALL CORE
51 RELOCATED WASHER AND DRYER
52 PAINT FRONT DOOR PT6, FINISH G5
COMM
LAUNDRY
BEDROOM
BEDROOM
KITCHEN
VENDING
LIVING RM
LIVING RM
LIVING RM
BEDROOM
133 BEDROOM
R.R
R.R
LIVING RM
KITCHEN
BEDROOM
LIVING RM
R.R
BEDROOM
LIVING RM
R.R
R.R
R.R
22 2
2 2
6 67 7
4 4 4 4
4 4
4 4
8 8 9
4 4 44
C3
A-101
12 12
12 12 12 12
12 12
12 12 12 12
140130
120110
112 122
121111
152 162
161151
150 160100
131A 141A
160A150A
140A
140B
142A 132A
130B
120A110A
130A
143A133A
141414
15 15
15 15
15 15
A-201
A2
35' - 3" 45' - 9" 25' - 5"
106' - 5"
A-102 C2
A-102 C1
A-201
A3
A-201
C1
A-201
B1
7" MIN. - 9" MAX.7" MIN - 9" MAX.
W
D
1. (*) INDICATES EXISTING DIMENSION TO BE FIELD VERIFIED BY CONTRACTOR.
2. EXSITING BUILDING INFORMATION IS AS INDCIATED ON THE AS-BUILT
DRAWINGS. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER OF
ANY DISCREPANCIES.
3. THE EXISTING LAYOUTS INDICATED ON THESE PLANS ARE BASED ON EXISTING
PLANS AND LIMITED FIELD OBSERVATION. CONTRACTOR TO FIELD VERIFY
EXISTING CONDITIONS AS NEEDED PRIOR TO ANY CONSTRUCTION.
4. BASE DESIGN TO UPDATE ITEMS REQUIRED BY CODE, REPLACEMENT OF
MATERIALS AT WATER DAMAGED AREAS, GENERAL PAINT REFRESH, AND
PATCH AND REPAIR OF ANY OTHER DAMAGED AREAS INCLUDING CASEWORK.
5. OPTION 1 DESIGN INCLUDES BASE DESIGN AND ADDITIONAL UPGRADES,
INCLUDING NEW SIDING, WINDOW BLINDS, FANS, LIGHTING FIXTURES, LVT
FLOORING, CASEWORK REPAIR AND PAINTING, NEW ENTRY DOORS AND
STORM DOORS, AND WALL BASE.
A. PAINT COLOR SW 7015 - REPOSE GRAY - PT1
B. PAINT COLOR SW 7017 - DORIAN GRAY - PT2
C. PAINT COLOR SW 9143 - CADET - PT3
D. PAINT COLOR SW 7005 - PURE WHITE - PT4
E. PAINT COLOR SW 7615 - SEA SERPENT - PT5
F. PAINT COLOR SW 6237 - DARK NIGHT - PT6
G. EXTERIOR DOOR - TRIMLITE 36" x 80" 3-PANEL PREHUNG
ENTRY DOOR WITH SATIN NICKEL HINGES, MODEL
3068LHISPSF3PSHK491615M
H. CORNER GUARDS - INPRO FLEXIBLE, CLEAR, VINYL, 90
DEGREE CORNER GUARDS, 1" WING, 4'-0" H
I. LUXURY VINYL TILE - TARKETT iD LATITUDE WOOD LVT 6" x 48" PLANK, COLOR TBD - LVT1
J. FLOOR BASE - MOULDINGS ONE 4" x 7/8" WOOD
BASEBOARD 2032 - PAINT COLOR PT4 - FINISH…
This is the start of the file's text. The full file is on GovTribe.