SWGR Elec. Dwg.pdf
PDF 611 KB Posted
- Attached to
- GPO 5th Floor SID Smartcard Room Design/Build Construction Federal contract opportunity
- Solicitation number
- 040ADV-25-R-0001-06
- Issued by
- Government Publishing Office
About this file
This file contains electrical single-line diagrams (sheets E-602, E-603, and E-604) for the GPO Main Building electrical upgrade project. The diagrams show the power distribution system including transformers, switchgear, circuit breakers, and associated equipment specifications.
Key technical details include: Two 1000/1500kVA transformers (XFMR-12B1 and XFMR-12B2) rated at 13.2kV-480/277V with 110kV BIL and Z=7.0%; switchgear USG-12B rated at 4000A located in the third floor switchgear room; a 75HP fire pump and 1HP jockey pump system with 2-hour fire rated feeders; UPS systems rated at 300kVA with VRLA batteries; and multiple distribution panels and switchboards throughout the building. The drawings include detailed specifications for circuit breakers, surge protection devices, grounding requirements, and conductor sizes. General notes emphasize coordination of shutdowns with the owner and proper separation of power and control wiring.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 040ADV-25-R-0001-006 SF-30 (Signed).pdf | ||
| Layout by Floor Type.pdf | ||
| Additional Questions_040ADV-25-R-0001.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2500AT
2500AF
2500AT
2500AF
'XFMR-12B2'
1000 / 1500kVA, 13.2kV-480/277V, 110kV BIL, Z=7.0%, CAST COIL
SPD
SPD
500AT
1600AF
1600AT
1600AF
500AT
1600AF
3456789
2000A G
SWITCHGEAR 'USG-12A'
(THIRD FLOOR SWITCHGEAR ROOM)
SWITCHGEAR 'USG-12B'
(THIRD FLOOR SWITCHGEAR ROOM)
2000A G
TYPE 1 SURGE
PROTECTION DEVICE
TYPE 1 SURGE
PROTECTION DEVICE
4000A, 480V, 3Ø, 3W, 100KAIC 4000A, 480V, 3Ø, 3W, 100KAIC
1 2 3 4 5 6 7 8 9
DMR
DMM
PLC
DMR
DMM
PLC
'XFMR-12A1'
1000 / 1500kVA, 13.2kV-480/277V, 110kV BIL, Z=7.0%, CAST COIL
'XFMR-12A2'
1000 / 1500kVA, 13.2kV-480/277V, 110kV BIL, Z=7.0%, CAST COIL
ELECTRICAL DISTRIBUTION SINGLE LINE
SCALE: NOT TO SCALE
A1
REFER TO
SHEET E-603 FOR
CONTINUATION
B1
REFER TO
SHEET E-603 FOR
CONTINUATION
400AT
800AF
800AT
1600AF
SPARE
800AT
1600AF
SPARE
800AT
1600AF
SPARE
800AT
1600AF
SPARE
800AT
1600AF
SPARE
1600AT
1600AF
500AT
1600AF
500AT
1600AF
400AT
800AF
800AT
1600AF
SPARE
800AT
1600AF
SPARE
800AT
1600AF
SPARE
800AT
1600AF
SPARE
800AT
1600AF
SPARE
2500AT
2500AF
2500AT
2500AF
N.O.
52-TA
4000AT
4000AF
N.C.
52-TB
'MCB-12A1'
1200A, 15kV, 750MVA, 3Ø, 3W
'MCB-12B1'
1200A, 15kV, 750MVA, 3Ø, 3W
'MCB-12B2'
1200A, 15kV, 750MVA, 3Ø, 3W
4000A, 480/277V, 3Ø, 4W, 100KAIC 4000A, 480/277V, 3Ø, 4W, 100KAIC
4000A N
2000A G
11 SETS - (3)#500KCMIL,
#500KCMIL GND, IN 3-1/2"C 11 SETS - (3)#500KCMIL,
#500KCMIL GND, IN 3-1/2"C
A2
REFER TO
SHEET E-603 FOR
CONTINUATION
B2
REFER TO
SHEET E-603 FOR
CONTINUATION
2 S
ET
S
3) #2
KC
MI
L, #2
GN
D, IN
2- 1/2
"C
4000AT
4000AF
4000A N
2000A G
4000AT
4000AF
'NP-12A1'
60KAIC
'NP-12A2'
60KAIC
'NP-12B1'
60KAIC
'NP-12B2'
60KAIC
SWITCHGEAR 'LV-12A'
(FOURTH FLOOR SUBSTATION ROOM)
SWITCHGEAR 'LV-12B'
(FOURTH FLOOR SUBSTATION ROOM)
GENERAL NOTES
1. CONTRACTOR SHALL COORDINATE ALL SHUTDOWNS WITH OWNER.
CONTRACTOR SHALL HAVE A THOROUGH UNDERSTANDING OF THE EXISTING
POWER DISTRIBUTION SYSTEM AND ITS LOADS AND BE ABLE TO
IDENTIFY/DISCUSS ALL IMPACTS OF REQUESTED SHUTDOWNS/CUTOVERS
WITH THE OWNER. ALL OWNER CONCERNS MUST BE ADDRESSED
SATISFACTORILY PRIOR TO APPROVAL OF EACH SHUTDOWN / CUTOVERS.
2. REFER TO FLOOR PLANS FOR ACTUAL LOCATION OF EQUIPMENT.
3. ANY CONTROL, COMMUNICATIONS, MONITORING, ETC. WIRING SHALL BE RUN
IN DEDICATED RACEWAYS, INDEPENDENT OF POWER WIRING.
4. PROVIDE CORE DRILL THROUGH FLOOR SLABS FOR CONDUIT RUNS AS
REQUIRED. CORE DRILL LOCATIONS SHALL BE COORDINATED WITH AND
APPROVED BY THE STRUCTURAL ENGINEER.
DRAWING NOTES:
SURGE PROTECTION DEVICE SHALL BE LOCATED IN A SEPARATE BARRIER
WITHIN THE SWITCHGEAR. RUN (1)#2 DISCHARGE GROUND TO SWITCHGEAR
GROUND BUS.
PROVIDE PROVISIONS FOR FUTURE SWITCHGEAR BUSBAR CONNECTIONS.
REFER TO GROUNDING RISER DIAGRAM ON DRAWING E-506 FOR ADDITIONAL
INFORMATION ON NEUTRAL TO GROUND BONDING.
REFER TO ELECTRICAL CONDUIT PLANS FOR CONDUIT ROUTING FROM INCOMING
13.2kV SWITCHGEARS TO 'SUBSTATION-12A' AND 'SUBSTATION-12B'.
FIRE PUMP, FIRE PUMP CONTROLLER, AND JOCKEY PUMP LOCATED IN BUILDING
'A' BASEMENT FIRE PUMP ROOM. REFER TO DRAWING E-401 FOR EQUIPMENT
FLOOR PLAN LOCATIONS.
FIRE PUMP FEEDER ASSEMBLY SHALL HAVE A MINIMUM 2 HOUR FIRE RATING PER
UL 2196.
BUS TAP CONNECTION FOR FIRE PUMP SHALL BE PROVIDED IN A DEDICATED
SECTION OF THE SUBSTATION LINE-UP.
PROVIDE POWER CONNECTION TO JOCKEY PUMP INTERNAL FUSED DISCONNECT
SWITCH. PROVIDE POWER CONNECTION BETWEEN JOCKEY PUMP CONTROLLER
AND MOTOR. COORDINATE REQUIREMENTS WITH APPROVED SHOP DRAWINGS.
PROVIDE POWER CONNECTION TO FIRE PUMP CONTROLLER/ ATS INTEGRAL
MOLDED-CASE SWITCHES. PROVIDE POWER CONNECTION BETWEEN FIRE PUMP
CONTROLLER AND MOTOR. COORDINATE REQUIREMENTS WITH APPROVED
SHOP DRAWINGS.
PROVIDE FUSED DISCONNECT SWITCH FOR FIRE PUMP DISCONNECT. FUSED
DISCONNECT SWITCH SHALL BE SUITABLE FOR USE AS SERVICE EQUIPMENT AND
SHALL BE LOCKABLE IN THE CLOSED POSITION PER NEC 695.
REFER TO
SHEET E-601 FOR
CONTINUATION
(3
KC
MI
L, #2
G
ND
, IN
3-
1/2 "C
B4
(3
KC
MI
L, #2
G
ND
, IN
3-
1/2 "C
5 S
ET
S
3) #5
KC
MI
L, #5
KC
MI
L G
ND
, IN
3-
1/2 "C
A4
REFER TO
SHEET E-604 FOR
CONTINUATION
A3
REFER TO
SHEET E-604 FOR
CONTINUATION
5 S
ET
S
3) #5
KC
MI
L, #5
KC
MI
L G
ND
, IN
3-
1/2 "C
B3
REFER TO
SHEET E-604 FOR
CONTINUATION
2 S
ET
S
3) #2
KC
MI
L, #2
GN
D, IN
2- 1/2
"C
2 S
ET
S
3) #2
KC
MI
L, #2
GN
D, IN
2- 1/2
"C
2 S
ET
S
3) #2
KC
MI
L, #2
GN
D, IN
2- 1/2
"C
N.C.
200AT
1200AF
4000AT
4000AF
N.C.
52-UA
4000AT
4000AF
N.C.
52-UB
1 1
2 2
S.A.
'MCB-12A2'
1200A, 15kV, 750MVA, 3Ø, 3W
N.C.
52-LVA
N.C.
52-LVB
N.C.
NP-A1
N.C.
NP-A2
N.C.
NP-B1
N.C.
NP-B2
11 SETS - (3)#500KCMIL,
#500KCMIL GND, IN 3-1/2"C
(3
1/0
1/0 G
ND
IN
2"
C, 2-
HR
R
AT
ED
(3
1/0
1/0 G
ND
IN
2"
C, 2-
HR
R
AT
ED
4 4 4 4
REFER TO
SHEET E-601 FOR
CONTINUATION
REFER TO
SHEET E-601 FOR
CONTINUATION
REFER TO
SHEET E-601 FOR
CONTINUATION
REFER TO
SHEET E-604 FOR
CONTINUATION
(3
1/0
1/0 G
ND
IN
2"
C, 2-
HR
R
AT
ED
FIRE PUMP
(75 HP)
JOCKEY PUMP
(1 HP)
(3)#12, #12 GND
IN 3/4"C
(3)#12, #12 GND
IN 3/4"C
4000AT
4000AF
600AF
1000AS
'XFMR-12B1'
1000 / 1500kVA, 13.2kV-480/277V, 110kV BIL, Z=7.0%, CAST COIL
(3)#1/0, #1/0 GND,
IN 2"C, 2-HR RATED
(3)#1/0, #1/0 GND,
IN 2"C, 2-HR RATED
'FPD-12B'
(FOURTH FLOOR
SUBSTATION ROOM)
480V, 3Ø, 3W, 100KAIC
'FPD-12A'
(FOURTH FLOOR
SUBSTATION ROOM)
480V, 3Ø, 3W, 100KAIC
7 7
TYPE 1 SURGE
PROTECTION DEVICE
SPD
SPD
TYPE 1 SURGE
PROTECTION DEVICE
600AF
1000AS
FIRE PUMP
CONTROLLERJP
REFER TO
SHEET E-604 FOR
CONTINUATION
JOCKEY PUMP
CONTROLLER
10 10
52N.C.
200AT
1200AF
S.A.
52N.C.
200AT
1200AF
S.A.
52N.C.
200AT
1200AF
S.A.
Sheet Identification
Seal
Client/Owner/Project Address
M A
I N
G
P O
E L
E C
T R
I C
A L
U P
G R
A D
E
CallisonRTKL Inc.
Issue Drawing Log
2101 L Street, NW Suite 200
Washington, D.C. 20037
Tel: 202 833 4400
Fax: 202 887 5168
Project No: 3026089
CallisonRTKL Project No: 000-160045.00
© 2017 CallisonRTKL Inc.
USGPO
735 N. Capitol Street, NW
Washington, DC 20401
11/16/16 SCHEMATIC DESIGN
Consultant
02/03/17 PROGRESS REVIEW
03/16/17 ISSUED FOR 100% CD
ELECTRICAL
SINGLE LINE
E-602
2000A
500A G
1000A, 208/120V, 3Ø, 4W, 22KAIC
'PDU-A1'
(8TH FLOOR UPS ROOM)
300kVA, 480V-208Y/120V, K-13
1000A, 208/120V, 3Ø, 4W, 22KAIC
2000A N
500A G
UPS DISTRIBUTION SINGLE LINE
SCALE: NOT TO SCALE
'PDU-B1'
300kVA, (8TH FLOOR UPS ROOM)
480V-208Y/120V, K-13
500AT
800AF
500AT
600AF
GENERAL NOTES
1. CONTRACTOR SHALL COORDINATE ALL SHUTDOWNS WITH OWNER.
CONTRACTOR SHALL HAVE A THOROUGH UNDERSTANDING OF THE EXISTING
POWER DISTRIBUTION SYSTEM AND ITS LOADS AND BE ABLE TO
IDENTIFY/DISCUSS ALL IMPACTS OF REQUESTED SHUTDOWNS/CUTOVERS WITH
THE OWNER. ALL OWNER CONCERNS MUST BE ADDRESSED SATISFACTORILY
PRIOR TO APPROVAL OF EACH SHUTDOWN / CUTOVERS.
2. REFER TO FLOOR PLANS FOR ACTUAL LOCATION OF EQUIPMENT.
3. ANY CONTROL, COMMUNICATIONS, MONITORING, ETC. WIRING SHALL BE RUN IN
DEDICATED RACEWAYS, INDEPENDENT OF POWER WIRING.
4. PROVIDE CORE DRILL THROUGH FLOOR SLABS FOR CONDUIT RUNS AS
REQUIRED. CORE DRILL LOCATIONS SHALL BE COORDINATED WITH AND
APPROVED BY THE STRUCTURAL ENGINEER.
7. REFER TO PROPOSED DATA CENTER PHASING SEQUENCE ON DRAWING E-301 -
E-303.
DRAWING NOTES:
PROVIDE NAMEPLATE FOR EXISTING 'RDC' PANEL. REFER TO DETAIL #4 ON
DRAWING E-501 FOR ADDITION INFORMATION.
INSTALLATION OF UPS AND ASSOCIATED WIRING SHALL BE PHASED WITH
DEMOLITION OF EXISTING UPS SYSTEM SUCH THAT A MINIMUM OF ONE (1) UPS IS
SUPPLYING POWER TO THE DATA CENTER AT ALL TIMES. REFER TO DRAWING
ED-601 FOR ADDITIONAL INFORMATION.
COORDINATE INSTALLATION OF FEEDER TO THE 'RDC' PANELS LOCATED IN THE
DATA CENTER WITH EXISTING EQUIPMENT LOCATED BELOW THE DATA CENTER'S
RAISED ACCESS FLOOR.
COORDINATE CABLE AND CONDUIT CONNECTION BETWEEN UPS AND BATTERY
CABINETS WITH UPS MANUFACTURER. TYPICAL FOR EACH BATTERY CABINET.
FINAL CABLE AND CONDUIT SIZE REQUIREMENTS SHALL BE COORDINATED WITH
THE APPROVED UPS SHOP DRAWING.
REFER TO ELECTRICAL CONDUIT PLANS FOR CONDUIT ROUTING FROM
SWITCHGEARS USG-12A/B TO UPS SYSTEM.
CONTRACTOR SHALL PROVIDE DRY-CONTACT, WIRING, AND CONDUIT FROM UPS
TO SWITCHGEARS' 'USG-12A' AND 'USG-12B' CONTROL INTERFACE FOR STATUS
MONITORING OF THE UPSs. REFER TO SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
UPS SHALL BE CAPABLE OF PROVIDING AN INTERNAL LOCAL NEUTRAL SYSTEM
REFERENCE INDEPENDENT OF THE BUILDING GROUNDING SYSTEM.
PROVIDE 100% RATED CIRCUIT BREAKERS. TYPICAL FOR ALL PDU CIRCUIT
BREAKERS.
400AT
400AF
500A, 208/120V, 3Ø, 4W, 10KAIC
EX.
PANEL
'RDC-A1'
EX.
PANEL
'RDC-A2'
EX.
PANEL
'RDC-A3'
EX.
PANEL
'RDC-A4
EX. 'RDC-A1'
(8TH FLOOR DATA CENTER)
400AT
400AF
EX.
PANEL
'RDC-B1'
EX.
PANEL
'RDC-B2'
EX.
PANEL
'RDC-B3'
225A
EX.
PANEL
'RDC-B4
EX. 'RDC-B1'
(8TH FLOOR DATA CENTER)
225A225A225A225A225A225A225A
2 S
ET
S
3) #3
KC
MI
L, #1 /0
GN
D, IN
3"
C
400AT
400AF
250AT
250AF
SPARESPARE
400AT
400AF
250AT
250AF
SPARE SPARE
500A, 208/120V, 3Ø, 4W, 10KAIC
1 1
ST ST ST STSTST
A1
REFER TO
SHEET E-602 FOR
CONTINUATION
15 MIN. VRLA
BATTERY IN
MATCHING
CABINET
A2
'UPS-A'
(8TH FLOOR UPS ROOM)
300KVA, 0.9PF
480V-480V, 3Ø, 3W, 65KAIC
2 S
ET
S
3) #2
KC
MI
L, #2
GN
D, IN
2- 1/2
"C
B1
15 MIN. VRLA
BATTERY IN
MATCHING
CABINET
B2
'UPS-B'
(8TH FLOOR UPS ROOM)
300KVA, 0.9PF
480V-480V, 3Ø, 3W, 65KAIC
2 S
ET
S
3) #2
KC
MI
L, #2
GN
D, IN
2- 1/2
"C
REFER TO
SHEET E-602 FOR
CONTINUATION
REFER TO
SHEET E-602 FOR
CONTINUATION
REFER TO
SHEET E-602 FOR
CONTINUATION
2 SETS - (2)#350KCMIL,
#3/0 GND, IN 3"C
PROVIDE CONTROL CIRCUIT
TO 'USG-12A' AND 'USG-12B'
CONTROL INTERFACE
PROVIDE CONTROL CIRCUIT
TO 'USG-12A' AND 'USG-12B'
CONTROL INTERFACE
7 7
500AT
600AF
600A, 480V, 3Ø, 3W, 65KAIC
500AT
600AF
LOAD BANK
500AT
600AF
500AT
600AF
E1
500AT
600AF }
(2) SPACE
400AF500AT
600AF
SPARE
(5
0K
CM
IL,
#3 /0
GN
D, IN
4"
C
(5
0K
CM
IL,
#3 /0
GN
D, IN
4"
C
SWITCHBOARD 'UPS-A-MBM'
(8TH FLOOR UPS ROOM)
500AT
600AF
600A, 480V, 3Ø, 3W, 65KAIC
500AT
600AF
LOAD BANK
500AT
600AF
500AT
600AF
E1
500AT
600AF }
(2) SPACE
400AF500AT
600AF
SPARE
SWITCHBOARD 'UPS-A-MBM'
(8TH FLOOR UPS ROOM)
2 S
ET
S
3) #3
KC
MI
L, #1 /0
GN
D, IN
3"
C
}250AF
SPACE
}250AF
SPACE
42 SETS - (2)#350KCMIL,
#3/0 GND, IN 3"C
8 (TYP.) 8
(TYP.)
E2 E2600A, 480V, 3Ø, 3W, 65KAIC
600A, 480V, 3Ø, 3W, 65KAIC
300A G
300A G
300A G
300A G
Sheet Identification
Seal
Client/Owner/Project Address
M A
O
E L
E C
T R
I C
A L
U P
G R
A D
E
CallisonRTKL Inc.
Issue Drawing Log
2101 L Street, NW Suite 200
Washington, D.C. 20037
Tel: 202 833 4400
Fax: 202 887 5168
Project No: 3026089
CallisonRTKL Project No: 000-160045.00
© 2017 CallisonRTKL Inc.
USGPO
735 N. Capitol Street, NW
Washington, DC 20401
11/16/16 SCHEMATIC DESIGN
Consultant
02/03/17 PROGRESS REVIEW
03/16/17 ISSUED FOR 100% CD
ELECTRICAL
E-603
'XFMR-DP-12A1'
225kVA, 480-480/277V, Z=5.75%
(4
0, #1 /0
GN
D, IN
4"
C
5 2 1
PANEL 'DP-12A1'
(THIRD FLOOR SWITCHGEAR ROOM)
350AT
400AF
30AT(3P)
100AF
90AT(3P)
100AF
20AT(1P)
100AF
200A G
A4
REFER TO
SHEET E-602 FOR
CONTINUATION
(3
1/0 G
ND
IN
3/
4" C
GENERAL NOTES
1. CONTRACTOR SHALL COORDINATE ALL SHUTDOWNS WITH OWNER.
CONTRACTOR SHALL HAVE A THOROUGH UNDERSTANDING OF THE
EXISTING POWER DISTRIBUTION SYSTEM AND ITS LOADS AND BE ABLE
TO IDENTIFY/DISCUSS ALL IMPACTS OF REQUESTED
SHUTDOWNS/CUTOVERS WITH THE OWNER. ALL OWNER CONCERNS
MUST BE ADDRESSED SATISFACTORILY PRIOR TO APPROVAL OF EACH
SHUTDOWN / CUTOVERS.
2. REFER TO FLOOR PLANS FOR ACTUAL LOCATION OF EQUIPMENT.
3. ANY CONTROL, COMMUNICATIONS, MONITORING, ETC. WIRING SHALL
BE RUN IN DEDICATED RACEWAYS, INDEPENDENT OF POWER WIRING.
4. PROVIDE CORE DRILL THROUGH FLOOR SLABS FOR CONDUIT RUNS AS
REQUIRED. CORE DRILL LOCATIONS SHALL BE COORDINATED WITH
AND APPROVED BY THE STRUCTURAL ENGINEER.
DRAWING NOTES:
REFER TO DETAIL #4 ON DRAWING E-504 FOR SPD INSTALLATION.
COORDINATE WITH SPD MANUFACTURE ON EXACT BREAKER
AMPERAGE AND CABLING REQUIREMENTS.
REFER TO ELECTRICAL CONDUIT PLANS FOR CONDUIT ROUTING
FROM SWITCHGEARS USG-12A/B TO 1600A SWITCHBOARDS.
(3
2, #8
G
ND
, IN
1-
1/2 "C
'XFMR-RP-12A1'
45kVA, 480-208/120V, Z=5.75%
150A
(4
1/0
6 G
ND
IN
2" C
PANEL
'RP-12A1'
1600A N
1600A, 480V, 3Ø, 3W, 42KAIC
SWITCHBOARD 'SBD-12A'
(FIRST FLOOR POWER BRANCH)
1600AT
1600AF
800A G
SWITCHBOARD 'SBD-12B'
(FIRST FLOOR POWER BRANCH)
1600AT
1600AF
A3 B3
20AT(1P)
100AF
ELECTRICAL DISTRIBUTION SINGLE LINE
SCALE: NOT TO SCALE
35AT(3P)
100AF
100AT(3P)
100AF
(6) SPACE
20AT(1P)
100AF
(1) SPARE
20AT(3P)
100AF
(6) SPARE
3RD FLOOR
LIGHTING
'LCD-1'
3RD FLOOR
LIGHTING
'LCD-2'
60AT(3P)
100AF
(3
4, #1
/0
GN
D, IN
1- 1/2
"C
2 2
20AT(1P)
100AF
}100AF(3P)
400A N
20AT(1P)
100AF
20AT(1P)
100AF
LIGHT WELL
LIGHTING
4TH FLOOR
LIGHTING
'LCD-3'
4THFLOOR
LIGHTING
'LCD-4'
400A, 480/277V, 3Ø, 4W, 18KAIC
'XFMR-DP-12B1'
225kVA, 480-480/277V, Z=5.75%
5 2 1
PANEL 'DP-12B1'
(THIRD FLOOR SWITCHGEAR ROOM)
350AT
400AF
30AT(3P)
100AF
90AT(3P)
100AF
20AT(1P)
100AF
200A G
B4
(3
1/0 G
ND
IN
3/
4" C
(3
2, #8
G
ND
, IN
1-
1/2 "C
'XFMR-RP-12B1'
45kVA, 480-208/120V, Z=5.75%
150A
PANEL
'RP-12B1'
20AT(1P)
100AF
35AT(3P)
100AF
15AT(3P)
100AF
3RD FLOOR
LIGHTING
'LCD-4'
3RD FLOOR
LIGHTING
'LCD-3'
20AT(1P)
100AF
400A N
20AT(1P)
100AF
4TH FLOOR
LIGHTING
'LCD-2'
4THFLOOR
LIGHTING
'LCD-1'
400A, 480/277V, 3Ø, 4W, 18KAIC
(6) SPACE
20AT(1P)
100AF
(1) SPARE
20AT(3P)
100AF
(5) SPARE
}100AF(3P)
THIRD FLOOR
SWITCHGEAR ROOM
THIRD FLOOR
SWITCHGEAR ROOM
REFER TO
SHEET E-602 FOR
CONTINUATION
REFER TO
SHEET E-602 FOR
CONTINUATION
REFER TO
SHEET E-602 FOR
CONTINUATION
20AT(1P)
100AF
100A
(4
1/0
8 G
ND
IN
2" C
PANEL
'HP-12B1'
EIGHTH FLOOR
UPS ROOM
'XFMR-RP-12A2'
15kVA, 480-208/120V, Z=5.75%
50A
PANEL
'RP-12A2'
EIGHTH FLOOR
UPS ROOM
(4
6, #8
G
ND
IN
1- 1/2
"C
(4
1/0
8 G
ND
IN
2" C
(3
8 G
ND
IN
3/ 4"
C
'XFMR-RP-12B2'
15kVA, 480-208/120V, Z=5.75%
50A
PANEL
'RP-12B2'
EIGHTH FLOOR
UPS ROOM
(4
6, #8
G
ND
IN
1- 1/2
"C
DMM
60AT(3P)
100AF
(3
4, #1
/0
GN
D, IN
1- 1/2
"C
DMM
800AT(3P)
800AF
(3) SPARE
800AT(3P)
800AF
(8) SPARE
800AT(3P)
800AF
(3) SPARE
800AT(3P)
800AF
(8) SPARE
1600A N
1600A, 480V, 3Ø, 3W, 42KAIC
800A G
(4
0, #1 /0
GN
D, IN
4"
C
20AT(3P)
100AF
3RD FLOOR
HALLWAY
LIGHTING
JP
REFER TO
SHEET E-602 FOR
CONTINUATION
CU-1
(11.8 kW)
(3
8, #1
0 G
ND
IN
1" C
(3
8, #1
0 G
ND
IN
1" C
35AF
60AS
CU-2
(11.8 kW)
(3
8, #1
0 G
ND
IN
1" C
(3
8, #1
0 G
ND
IN
1" C
35AF
60AS100A
(4
1/0
8 G
ND
IN
2" C
PANEL
'HP-12A1'
EIGHTH FLOOR
UPS ROOM
(3
8 G
ND
IN
3/ 4"
C
SPD
TYPE 2
SPD
SPD
TYPE 2
SPD
SPD
TYPE 2
SPD
SPD
TYPE 2
SPD
Sheet Identification
Seal
Client/Owner/Project Address
M A
O
E L
E C
T R
I C
A L
U P
G R
A D
E
CallisonRTKL Inc.
Issue Drawing Log
2101 L Street, NW Suite 200
Washington, D.C. 20037
Tel: 202 833 4400
Fax: 202 887 5168
Project No: 3026089
CallisonRTKL Project No: 000-160045.00
© 2017 CallisonRTKL Inc.
USGPO
735 N. Capitol Street, NW
Washington, DC 20401
11/16/16 SCHEMATIC DESIGN
Consultant
02/03/17 PROGRESS REVIEW
03/16/17 ISSUED FOR 100% CD
ELECTRICAL
E-604
| GPO - Main Electrical Upgrade - Drawings Combined (2018-02-12) |
| G-000 |
| GPO - Main Electrical Upgrade - Arch Combined (2018-02-12) |
| GPO - Main Electrical Upgrade - Arch Combined (2018-02-12) |
| Sheets |
| A-001 - GENERAL INFORMATION |
| A-002 |
| Sheets |
| A-002 - INDEX SHEET |
| GPO - Main Electrical Upgrade - Arch Combined (2018-02-12) |
| Sheets |
| A-012 - 2ND FLOOR EGRESS |
| A-013 - 3RD FLOOR EGRESS |
| A-014 - 4TH FLOOR EGRESS |
| A-101 - CONSTRUCTION PLAN - 1ST FLOOR |
| A-102 - CONSTRUCTION PLAN - 2ND FLOOR |
| A-103 - CONSTRUCTION PLAN - 3RD FLOOR |
| A-104 - CONSTRUCTION PLAN - 4TH FLOOR |
| A-105 - CONSTRUCTION, RCP & FINISH PLANS- 8TH FLOOR |
| D-102 - DEMOLITION PLAN - 2ND FLOOR |
| D-103 - DEMOLITION PLAN - 3RD FLOOR |
| D-104 - DEMOLITION PLAN - 4TH FLOOR |
| A-106 |
| Sheets |
| A-106 - ROOF PLAN |
| GPO - Main Electrical Upgrade - Arch Combined (2018-02-12) |
| Sheets |
| A-202 - REFLECTED CEILING PLAN - 2ND FLOOR |
| A-203 - REFLECTED CEILING PLAN - 3RD FLOOR |
| A-204 - REFLECTED CEILING PLAN - 4TH FLOOR |
| A-302 - FINISH PLAN - 2ND FLOOR |
| A-303 - FINISH PLAN - 3RD FLOOR |
| A-304 - FINISH PLAN - 4TH FLOOR |
| A-402 - BUILDING SECTION |
| A-500 - STAIR DETAILS |
| A-501 - ARCHITECTURAL DETAILS AND DOOR SCHEDULE |
| A-502 - PARTITION TYPES & DETAILS |
| A-503 - ARCHITECTURAL DETAILS |
| A-504 - ADDITIONAL DETAILS |
| GPO - Main Electrical Upgrade - Structural Combined (2018-02-12) |
| GPO - Main Electrical Upgrade - Structural Combined (2018-02-12) |
| S-001 |
| S-002 |
| S-101 |
| S-102 |
| S-103 |
| GPO - Main Electrical Upgrade - Structural Combined (2018-02-12) |
| S-201 |
S-202
| GPO - Main Electrical Upgrade - Mechanical Combined (2018-02-12) |
| GPO - Main Electrical Upgrade - Mechanical Combined (2018-02-12) |
| GPO - Main Elec Upgrade |
| MD-100 MD-100 (1) |
| M-100 |
| M-101 |
| M-102 |
| GPO - Main Electrical Upgrade - Mechanical Combined (2018-02-12) |
| GPO - Main Electrical Upgrade - Drawings Combined (2018-02-12).pdf |
| GPO - Main Electrical Upgrade - Arch Combined (2018-02-12) |
| A-002 |
| Sheets |
| A-002 - INDEX SHEET |
| A-106 |
| Sheets |
| A-106 - ROOF PLAN |
| GPO - Main Electrical Upgrade - Electrical Combined (2018-02-12) |
| GPO - Main Electrical Upgrade - Electrical Combined (2018-02-12) |
| GPO - Main Electrical Upgrade - Electrical 100% CD (2017-03-16) |
| E-001 ELECTRICAL LEGEND AND ABBREVIATIONS |
| E-002 ELECTRICAL LEGEND AND FIXTURE SCHEDULE |
| ED-101 ELECTRICAL POWER PLAN - FIRST FLOOR - DEMOLITION |
| ED-102 ELECTRICAL POWER PLAN - SECOND FLOOR - DEMOLITION |
| ED-103 ELECTRICAL POWER PLAN - THIRD FLOOR - DEMOLITION |
| ED-104 ELECTRICAL POWER PLAN - EIGHTH FLOOR - DEMOLITION |
| ED-105 ELECTRICAL POWER PLAN - ROOF - DEMOLITION |
| E-101 ELECTRICAL POWER PLAN - SECOND FLOOR |
| E-102 ELECTRICAL POWER PLAN - THIRD FLOOR |
| E-103 ELECTRICAL POWER PLAN - FOURTH FLOOR |
| E-104 ELECTRICAL POWER PLAN - EIGHTH FLOOR |
| E-105 |
| GPO - Main Electrical Upgrade - Electrical Combined (2018-02-12) |
| GPO - Main Electrical Upgrade - Electrical 100% CD (2017-03-16) |
| E-110 ELECTRICAL CONDUIT PLAN - BASEMENT |
| E-111 ELECTRICAL CONDUIT PLAN - BASEMENT |
| E-112 ELECTRICAL CONDUIT PLAN - FIRST AND SECOND FLOOR |
| E-113 ELECTRICAL CONDUIT PLAN - THIRD FLOOR |
| E-114 ELECTRICAL CONDUIT PLAN - FOURTH FLOOR |
| E-115 ELECTRICAL CONDUIT PLAN - SEVENTH FLOOR |
| E-121 ELECTRICAL LIGHTING PLAN - THIRD FLOOR |
| E-122 ELECTRICAL LIGHTING PLAN - FOURTH FLOOR |
| E-123 ELECTRICAL LIGHTING PLAN - EIGHTH FLOOR |
| E-201 ELECTRICAL SWITCHGEAR ELEVATIONS |
| E-202 ELECTRICAL SWITCHGEAR ELEVATIONS |
| E-301 ELECTRICAL PHASING PLAN - UPS ROOM |
| E-302 ELECTRICAL PHASING PLAN - UPS ROOM |
| E-303 ELECTRICAL PHASING PLAN - UPS ROOM |
| E-401 |
| GPO - Main Electrical Upgrade - Electrical Combined (2018-02-12) |
| GPO - Main Electrical Upgrade - Electrical 100% CD (2017-03-16) |
| E-501 ELECTRICAL DETAILS |
| E-502 ELECTRICAL DETAILS |
| E-503 ELECTRICAL DETAILS |
| E-504 ELECTRICAL DETAILS |
| E-505 ELECTRICAL DETAILS |
| E-506 ELECTRICAL DETAILS |
| ED-601 ELECTRICAL SINGLE LINE - DEMOLITION |
| GPO - Main Electrical Upgrade - Drawings Combined (2018-02-12).pdf |
| GPO - Main Electrical Upgrade - Arch Combined (2018-02-12) |
| A-002 |
| Sheets |
| A-002 - INDEX SHEET |
| A-106 |
| Sheets |
| A-106 - ROOF PLAN |
| GPO - Main Electrical Upgrade - Electrical Combined (2018-02-12) |
| E-601 |
| GPO - Main Electrical Upgrade - Drawings Combined (2018-02-12).pdf |
| GPO - Main Electrical Upgrade - Arch Combined (2018-02-12) |
| A-002 |
| Sheets |
| A-002 - INDEX SHEET |
| A-106 |
| Sheets |
| A-106 - ROOF PLAN |
| GPO - Main Electrical Upgrade - Electrical Combined (2018-02-12) |
| GPO - Main Electrical Upgrade - Electrical Combined (2018-02-12) |
| GPO - Main Electrical Upgrade - Electrical 100% CD (2017-03-16) |
| E-602 ELECTRICAL SINGLE LINE |
| E-603 ELECTRICAL SINGLE LINE |
| E-604 ELECTRICAL SINGLE LINE |
| E-901 ELECTRICAL PANEL SCHEDULES |
| E-902 ELECTRICAL PANEL SCHEDULES |
| GPO - Main Electrical Upgrade - Fire Protection Combined (2018-02-12) |
| GPO - Main Electrical Upgrade - Fire Protection Combined (2018-02-12) |
| FP-100 |
| GPO - Main Electrical Upgrade - Fire Pump Combined (2018-02-12) |
| FP001 |
| FP101 |
| FP102 |
File details come from the government source that posted it. Updated .