STRUCTURAL_GENERAL_NOTES.docx
DOCX document 24 KB Posted
- Attached to
- RWBS CRANE MODIFICATION
- Solicitation number
- QQ-2026-126
- Issued by
- Collier County, Florida
About this file
Summary of Structural General Notes for Raw Water Booster Station Crane Modifications
This is a structural general notes document prepared by Tetra Tech for Collier County, Florida, pertaining to modifications to the Raw Water Booster Pump Station scheduled for April 2026. The project involves relocating an existing overhead bridge crane system to provide improved access to piping and valves within the facility by addressing interference from hurricane strengthening structural elements. The scope of work includes demolition of existing aluminum structural components, installation of new galvanized steel framing, relocation of crane angle stops, and modifications to existing concrete masonry unit (CMU) walls and reinforced concrete beams. Key structural elements being modified include an existing aluminum I-beam column (I10x8.65), a 14"x32" concrete beam, and various aluminum plates, brackets, and rectangular tubes. The contractor is required to conduct a mandatory site visit prior to bid submission and verify existing conditions through field measurements and non-destructive testing, specifically rebar scanning of the CMU wall to confirm #5 reinforcement at 16 inches on center. All discrepancies between field conditions and the original 1990 and 2013 design drawings must be reported to the engineer of record before fabrication and construction commence.
The project adheres to the 2023 Florida Building Code (8th Edition) and ASCE/SEI 7-22 standards, with design criteria including a basic design wind speed of 170 miles per hour for Risk Category IV structures and an Exposure Category C environment. All structural steel shall be hot-dip galvanized and comply with specified ASTM standards, including ASTM A992 Grade 50 for wide flanges, ASTM A325-N high-strength bolts, and AWS D1.1 welding code requirements. Critical installation requirements include manufacturer-trained personnel for adhesive anchor installation per ACI 318-14 standards, with all anchors approved for use in cracked concrete and seismic applications. A proof-loading program must be established and conducted by the engineer of record, with proof loads not exceeding 50 percent of expected peak loads or 80 percent of anchor yield strength. Shop drawings, erection plans, and fabrication drawings must be submitted for approval prior to construction, and all connections shall be designed as simple shear connections per AISC standards with minimum reaction capacities of 10 kips where not otherwise specified.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RWBS_CRANE_MODIFICATION.pdf | ||
| Insurance_Requirements_Template.docx | DOCX document | |
| 100%_PLans.pdf | ||
| Final_RWBS_CRANE_MODIFICATION_-.pdf | ||
| Rwbs_crane_building_modification_project_pictures.msg | MSG file | |
| PO_Terms_and_Conditions.pdf | ||
| Quick_Quotes_Instructions_Version_1_.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Raw Water Booster Station – Crane Modifications April 2026
STRUCTURAL GENERAL NOTES
1. THESE GENERAL NOTES PRESENT AND/OR SUMMARIZE KEY PROJECT INFORMATION FOR THE DRAWING READER'S CONVENIENCE.
SEE ALSO INDIVIDUAL DRAWING NOTES AND PROJECT SPECIFICATIONS FOR FURTHER DETAILS AND REQUIREMENTS.
2. ALL REFERENCED STANDARDS HEREIN ARE TO MOST RECENT ISSUE IN EFFECT AS OF THE DATE OF THESE DOCUMENTS, UNLESS
NOTED OTHERWISE IN PROJECT SPECIFICATIONS OR ON THE DRAWING.
3. ALL EXISTING DIMENSIONS SHOWN WITH THE ± SYMBOL ARE APPROXIMATE AND SHALL BE FIELD VERIFIED BY THE CONTRACTOR
BEFORE FABRICATION AND CONSTRUCTION.
4. DIMENSIONS MARKED WITH A "X" SHALL BE DETERMINED BY EQUIPMENT MANUFACTURER AND COORDINATED BY CONTRACTOR
5. SUBMIT SHOP DRAWINGS, PROJECT DATA AND SAMPLES AS SPECIFIED IN PROJECT SPECIFICATIONS.
CONCRETE POST-INSTALLED ANCHORS
1. ADHESIVE ANCHORS
A. APPROVED SYSTEMS INCLUDE HILTI HIT-RE 500 V3 (ICC ESR 3814) OR HILTI HIT-HY 200 ADHESIVE WITH HAS/HIT-V THREADED ROD WITH SAFESET TECHNOLOGY (ICC ESR 3187) OR EQUAL CONSIDERING LOAD RESISTANCE, IN-SERVICE AND INSTALLATION TEMPERATURE, AVAILABILITY OR COMPREHENSIVE INSTALLATION INSTRUCTIONS, AND CREEP. ADHESIVE ANCHORS SHALL BE APPROVED FOR USE WITH CRACKED CONCRETE PER AC 308. CURRENT ICC-ESR SHALL BE SUBMITTED.
B. ALL PERSONNEL INSTALLING ANCHORS SHALL BE TRAINED BY THE MANUFACTURER ON PROPER INSTALLATION TECHNIQUE.
TRAINING DOCUMENTATION FROM THE MANUFACTURER SHALL BE AVAILABLE ON REQUEST.
C. HOLE SIZES AND INSTALLATION SHALL BE IN ACCORDANCE WITH MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS
(MPII)
D. ADHESIVE FOR REBAR AND ANCHORS SHALL HAVE BEEN TESTED IN ACCORDANCE WITH ACI 355.4 AND ICC-ES AC308 FOR CRACKED CONCRETE AND SEISMIC APPLICATIONS. DESIGN ADHESIVE BOND STRENGTH SHALL BE BASED ON ACI 355.4 TEMPERATURE CATEGORY A WITH INSTALLATIONS INTO WATER SATURATED HOLES DRILLED USING A CARBIDE DRILL BIT INTO
CONCRETE THAT HAS BEEN CURED FOR AT LEAST 21 DAYS.
E. ANY ADHESIVE ANCHOR INSTALLED HORIZONTALLY OR IN A VERTICALLY INCLINED PLANE SHALL BE INSTALLED BY CERTIFIED ADHESIVE ANCHOR INSTALLER, PER ACI 318-14 17.8.2.2, AND SHALL BE INSPECTED PER ACI 318-14 17.8.2.4.
F. FILL IN ALL ABANDONED HOLES WITHIN 2" OF NEW ANCHOR LOCATIONS.
G. WHERE REQUIRED, A PROGRAM FOR ON-SITE PROOF LOADING, THAT IS, PROOF LOADING PROGRAM, TO BE CONDUCTED AS PART OF THE SPECIAL INSPECTION AND SHALL BE ESTABLISHED BY THE ENGINEER OR DESIGN PROFESSIONAL OF RECORD AND
SHALL CONFORM TO THE FOLLOWING MINIMUM REQUIREMENTS:
a. FREQUENCY OF PROOF LOADING BASED ON ANCHOR TYPE, DIAMETER, AND EMBEDMENT.
b. PROOF LOADS BY ANCHOR TYPE, DIAMETER, EMBEDMENT, AND LOCATION.
c. ACCEPTABLE DISPLACEMENTS AT PROOF LOAD.
d. REMEDIAL ACTION IN THE EVENT OF FAILURE TO ACHIEVE PROOF LOAD OR EXCESSIVE DISPLACEMENT.
UNLESS OTHERWISE DIRECTED BY THE ENGINEER OR DESIGN PROFESSIONAL OF RECORD, PROOF LOADS SHALL BE APPLIED AS CONFINED TENSION TESTS (4.7.2.3). PROOF LOADS LEVELS SHALL NOT EXCEED THE LESSER OF 50 PERCENT OF THE EXPECTED PEAK LOAD BASED ON ADHESIVE BOND STRENGTH, OR 80 PERCENT OF THE ANCHOR YIELD STRENGTH.
MAINTAIN THE PROOF LOAD AT THE REQUIRED LOAD LEVEL FOR A MINIMUM OF 10 SECONDS.
2. EQUIPMENT ANCHORS:
A. SIZE, LENGTH, AND LOCATION OF EQUIPMENT ANCHORS SHALL BE PROVIDED BY EQUIPMENT MANUFACTURER.
STRUCTURAL STEEL
1. REFERENCES
A. AISC STEEL CONSTRUCTION MANUAL, 14TH EDITION
B. AWS D1.1 STRUCTURAL WELDING CODE - STEEL
2. MATERIALS
A. GRADE STEEL
WIDE FLANGES ASTM A992, GRADE 50
CHANNELS, ANGLES, AND PLATES ASTM A36
SHEAR CONNECTOR PLATES ASTM A572, GRADE 50
STRUCTURAL PIPE ASTM A53, GRADE B, Fy=35 KSI ROUND HSS ASTM A500, GRADE B, Fy=42 KSI SQUARE OR RECTANGLE HSS ASTM A500, GRADE C, Fy=50 KSI
B. WELDED STUDS: ASTM A108, GRADE 60
C. ANCHOR BOLTS: ASTM F1554, GRADE 55, WELDABLE.
D. STRUCTURAL BOLTS: ASTM A325-N
E. WELDS: E70XX ELECTRODES
3. CONNECTIONS
A. AISC MANUAL STANDARD CONNECTIONS UNLESS NOTED OTHERWISE. HIGH-STRENGTH BOLTS: ASTM A325-N, 3/4" UNLESS NOTED OTHERWISE. BEARING TYPE INSTALLED IN CONFORMANCE WITH "SPECIFICATIONS FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS", RESEARCH COUNCIL ON RIVETED AND BOLTED STRUCTURAL JOINTS. UNLESS NOTED OTHERWISE, STANDARD AISC "USUAL GAGE" DIMENSIONS SHALL BE USED FOR LOCATING HOLES FOR BOLTS, EXPANSION ANCHORS, ETC. IN
ALL ANGLES, BEAM FLANGES, ETC.
B. THE ASSEMBLY SURFACE, INCLUDING THOSE ADJACENT TO THE WASHER, SHALL BE FREE OF MILL SCALE, OIL, PAINT OR OTHER
COATINGS.
C. ALL HIGH STRENGTH BOLTS SHALL BE TIGHTENED TO A BOLT TENSION NOT LESS THAN THAT SPECIFIED IN THE AISC MANUAL.
FULL TENSIONING SHALL BE BY THE TURN OF NUT METHOD, BY A DIRECT TENSION INDICATOR, OR BY PROPERLY CALIBRATED WRENCHES. PROVIDE HARDENED WASHERS UNDER THE NUT OR BOLT HEAD, WHICHEVER IS THE ELEMENT TURNED IN
TIGHTENING.
D. WELDING - PERFORM ALL WELDING IN ACCORDANCE WITH AWS D1.1 CODE, LATEST EDITION, WELDS SHALL BE MADE ONLY BY
OPERATORS CERTIFIED BY AWS IN PERFORMING THE TYPE OF WORK INDICATED.
E. ALL BEAMS SHALL HAVE SIMPLE SHEAR CONNECTIONS DESIGNED TO SUPPORT 1/2 THE TOTAL UNIFORM LOAD LISTED IN THE AISC MANUAL OF STEEL CONSTRUCTION OR THE REACTION NOTED ON THE DRAWINGS, WHICHEVER IS GREATER.
F. WHERE INDICATED ON THE DRAWINGS, CONNECTIONS SHALL BE DESIGNED FOR THE REACTIONS SHOWN. WHERE NO REACTIONS ARE INDICATED, REFER TO NOTE "E" ABOVE OR DESIGN FOR A MINIMUM REACTION OF 10 KIPS.
4. TOLERANCES: AISC CODE OF STANDARD PRACTICE (LATEST EDITION)
5. SHOP DRAWINGS
A. SUBMIT ERECTION AND FABRICATION SHOP DRAWINGS
1. REFERENCES:
A. ICC INTERNATIONAL BUILDING CODE, 2018 EDITION, RISK CATEGORY IV IN ACCORDANCE WITH TABLE 1604.5
B. STATE BUILDING CODE: 2023 FLORIDA BUILDING CODE, 8TH EDITION
C. ASCE/SEI 7-22 - MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
2. DEAD LOADS:
ROOF DEAD LOAD = (SELF WEIGHT)
ROOF COLLATERAL* LOAD = 25 PSF UNO
DEAD LOAD AVAILABLE TO RESIST UPLIFT = SELF WEIGHT OF STRUCTURAL FRAMING ONLY
FLOOR DEAD LOAD = (SELF WEIGHT)
FLOOR COLLATERAL* LOAD = 25 PSF UNO
A. *COLLATERAL LOAD INCLUDES PROVISION FOR HANGING LOADS INCLUDING SPRINKLERS, DUCTWORK, PLUMBING, CEILING
AND OTHER COMPONENTS. REFER TO DRAWINGS FOR CONCENTRATED LOADING.
3. LIVE LOADS (UNO):
BUILDING ROOFS UNO = 20 PSF
4. WIND LOAD:
BASIC DESIGN WIND SPEED, V = 170 MPH
NOMINAL DESIGN WIND SPEED, Vasd = 132 (Vult*√0.6) MPH
RISK CATEGORY = IV
WIND EXPOSURE CATEGORY = C
DIRECTIONALITY FACTOR, Kd = 0.85 TOPOGRAPHIC FACTOR, Kzt = 1.0 INTERNAL PRESSURE COEFFICIENT, GCpi = ± 0.18
FACTORED COMPONENTS AND CLADDING WIND PRESSURES (PSF)
WALLS 10 SF 50 SF 100 SF
INTERIOR ZONE -67.1/+61.9 -60.7/+55.5 -58.0/+52.8
END ZONE * -82.6/+61.9 -69.8/+55.5 -64.3/+52.8
*END ZONE IS CONSIDERED TO BE LOCATED WITHIN 3'-4" OF BUILDING WALL CORNER
DESIGN CRITERIA
CHKD:
DRWN:
PROJ:
DESN:
www.tetratech.com A B C D E F 2 3 4 5 6 7 Bar measures 1 inch, otherwise drawing is not to scale
S. JENKINS
B. FOX
J.BURKETT
S-001
COLLIER COUNTY, FL
COLLIER COUNTY RAW WATER BOOSTER
PUMP STATION IMPROVEMENTS
GENERAL NOTES
ENGINEERING BUSINESS NO. 2429
1000 CHEVROLET WAY STE. 102
ESTERO, FLORIDA 33928
TEL: (239) 390-1467
NOT FOR
CONSTRUCTION
MARK DATE DESCRIPTION BY
1. INFORMATION SHOWN FOR THE EXISTING FACILITY ON THESE DRAWINGS WERE TAKEN FROM THE DRAWINGS THAT WERE:
PREPARED FOR: COLLIER COUNTY
PREPARED BY: CONSOER, TOWNSEND, & ASSOCIATES, INC
ENTITLED: RAW WATER BOOSTER PUMP STATION
DATED: 7/20/90
PREPARED FOR: COLLIER COUNTY
PREPARED BY: TRC WORLDWIDE ENGINEERING
ENTITLED: RAW WATER BOOSTER PUMP STATION PHASE 2: STRENGTHENING
DATED: 02/13
2. WORK SHOWN ON THESE PLANS ASSUMES THAT THE ORIGINAL CONSTRUCTION WAS PERFORMED IN ACCORDANCE WITH THE ABOVE INDICATED ORIGINAL DRAWINGS INCLUDING (BUT NOT LIMITED TO) DIMENSIONS, ELEVATIONS, MEMBER SIZES, MATERIALS, DETAILS, ETC. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE CONDITIONS RELATING TO THE EXISTING STRUCTURE AND TO NOTIFY THE ENGINEER OF ANY DISCREPANCIES
OR CONFLICTS.
3. PRIOR TO SUBMISSION OF BIDS, THE CONTRACTOR SHALL HAVE VISITED THE SITE AND BE THOROUGHLY ACQUAINTED WITH THE SCOPE OF THE WORK INDICATED ON THE DRAWINGS. FAILURE TO COMPLY WITH THIS REQUIREMENT SHALL NOT CONSTITUTE A BASIS FOR CLAIMS FOR ADDITIONAL COMPENSATION.
4. PRIOR TO STARTING FABRICATION AND CONSTRUCTION, CONTRACTOR SHALL VERIFY THE REINFORCEMENT IN THE CMU WALL USING NON-DESTRUCTIVE TESTING SUCH AS REBAR SCANNING. VERTICAL REINFORCEMENT IN THE WALL SHALL BE #5 @ 16" OC. MODIFICATIONS TO THE FRAMING WERE PERFORMED BASED ON THE EXISTING CMU WALL VERTICAL REINFORCEMENT. IF THE EXISTING CMU WALL VERTICAL REINFORCEMENT DOES NOT MATCH THE INFORMATION PROVIDED IN THE DRAWINGS, NOTIFY THE ENGINEER.
MODIFICATION OF EXISTING STRUCTURE
SHEET NOTES:
1. ALL DIMENSIONS ARE BASED ON THE ORIGINAL DRAWINGS DATED JULY 20, 1990,
PREPARED BY CONSOER, TOWNSEND & ASSOCIATES, INC AND DRAWINGS DATED
FEBRUARY 2013, PREPARED BY TRC WORLDWIDE ENGINEERING. THE CONTRACTOR IS
REQUIRED TO CONDUCT A FIELD VISIT, VERIFY ALL DIMENSIONS, AND NOTIFY THE
ENGINEER OF RECORD OF ANY CONFLICTS PRIOR TO THE COMMENCEMENT OFWORK.
2. FOR ALL EXISTING PROCESS AND PIPING EQUIPMENT REFER TO RECORD DRAWINGS
3. ALL NEW STEEL SHALL BE HOT DIP GALVANIZED.
16' - 3" ± A B 1' - 1" 31' - 9 1/2" ± 1' - 1" A S-101 0' - 0" B S-102
T/SLAB
EXISTING 4" CMU
VENEER
EXISTING
8" CMU UNDER HUNG
BRIDGE CRANE
(VIF)
10' - 6" ±
(VIF)
6' - 0" ±
EXISTING
14"x14" CONC
COLUMN, TYP
EXISTING
ALUMINUM
COLUMNS, TYP
(VIF)
33' - 11 1/2" ±
EXISTING 4" CMU VENEER
EXISTING 8" CMU
RELOCATE BRIDGE CRANE
ANGLE STOP AS
REQUIRED - REQUIRES
TWO NEW BOLT HOLES IN
RAIL FLANGE
RELOCATE BRIDGE CRANE
ANGLE STOP AS REQUIRED
C S-102
DEMO
SECTION
NEW
FRAMING
B S-102 C S-102
DEMO
SECTION
NEW
FRAMING
D S-102 ________ D S-102
(E) RUNWAY BEAM
(E) RUNWAY BEAM
A B A S-101 1' - 1" ±
(VIF)
31' - 9 1/2" ± 1' - 1" ±
(VIF)
33' - 11 1/2" ± 16' - 3" ±
T/EX HOLLOWCORE
(VIF)
10' - 6" ±
(VIF)
6' - 0" ±
EXISTING ALUMINUM
COLUMNS, TYP
(E) RUNWAY BEAM
(E) RUNWAY BEAM
EXISTING 14"x32" CONC
BEAM, TYP
21' - 4" C S-102 D S-102
(VIF)
2' - 6"
(VIF)
5' - 0" ± D S-102
EXISTING BRIDGE
CRANE
T/EXISTING FOOTING
-2' - 6"
T/ EXISTING SLAB
0"
B/EXISTING BEAM
18' - 0"
T/ EXISTING
HOLLOWCORE
21' - 4" A B
(E) RAIL
(E) 14"x32" CONCRETE BEAM
NOTE:
ALL EXISTING ELEMENTS
NOT SHOWN REFER TO
RECORD DRAWINGS
S-102 D EXISTING ALUMINUM COL I10x8.65 N
CHKD:
DRWN:
PROJ:
DESN:
www.tetratech.com A B C D E F 2 3 4 5 6 7 Bar measures 1 inch, otherwise drawing is not to scale Copyright: Tetra Tech 0' 4' 8' 4'
SCALE: 1/4" = 1'-0"
1/15/2026 2:25:45 PMAutodesk Docs://200-08486-24001 Collier Co Bridge Crane Add/S_200-08486-24001 CCBC A_remodel.rvt 200-08486-24001
S. JENKINS
B. FOX
J.BURKETT
S-101
COLLIER COUNTY, FL
COLLIER COUNTY RAW WATER BOOSTER
PUMP STATION IMPROVEMENTS
PLANS AND ELEVATIONS
ENGINEERING BUSINESS NO. 2429
1000 CHEVROLET WAY STE. 102
ESTERO, FLORIDA 33928
TEL: (239) 390-1467
NOT FOR
CONSTRUCTION
SCALE: 1/4" = 1'-0"
EXISTING PARTIAL FLOOR PLAN
SCALE: 1/4" = 1'-0" S-101
A SOUTH WALL ELEVATION
SCALE: 1/4" = 1'-0"
EXISTING PARTIAL ROOF PLAN
MARKDATE DESCRIPTION BY
B/EXISTING BEAM
18' - 0"
T/ EXISTING
HOLLOWCORE
21' - 4" S-102 C
CUT AND REMOVE
ALUMINUM RECT TUBE
6X12X1/4" AT TOP OF CAP
PLATE AND GRIND TOP OF
PLATE SMOOTH
REMOVE ALUMINUM PLATE,
BRACKET, AND RECT TUBE.
STAINLESS STEEL EPOXY
ANCHORS, WASHERS AND
NUTS SHALL BE RE-USED
5 1/4"
TRIM AND REMOVE EXISTING
ALUMINUM CAP PLATE AND
TRIANGULAR STIFFENER TO
EXTENTS SHOWN
EXISTING ALUMINUM
PL1/2x16x1'-4" SHALL
BE REMOVED
EXIST. 14"x32" BEAM EXISTING PL 1/4"x8"x0'-8"
ONE EA SIDE OF RECT TUBE
SHALL BE REMOVED
3" 9" 1' - 0" EXISTING (4) 3/4" DIAx7"
EMBED SS EPOXY ANCHOR W/
SS PL 1/4x2x2" PLATE
WASHER SHALL BE RE-USED
EXISTING RECT TUBE
6x12x1/4" TO BE REMOVED 15' - 8"
EXISTING CAP PL
1/2"x7"x 1'-6 1/2" EXISTING ALUMINUM COL I10x8.65
1/4" TRIANGULAR STIFF PL.
T/ EXIST CAP PL
EXISTING 8" CMU. #5@16" O.C.
VERT REINF TO BE FIELD
VERIFIED PRIOR TO COMMENCING
WITH COLUMN MODIFICATIONS.
REFER TO MODIFICATIONS OF
EXISTING STRUCTURE NOTES ON
SHEET S-001
B/EXISTING BEAM
18' - 0"
T/ EXISTING
HOLLOWCORE
21' - 4" 1' - 4" 1' - 4" 2" 1' - 0" 2" 2" 1' - 0" 2" PL 1/2" x 16"x16" GALV. STEEL
OVERSIZE HOLES
FOR EXISTING SS 3/4"
DIA BOLTS
HSS 4x4x1/2" GALV STEEL PL1/2"x7"x1'-1 1/4" GALV STEEL, REFER TO PLATE DETAIL 1/S-102
15' - 8" 10" 2' - 4" 6"
T/ EXIST CAP PL
1' - 2" 3/16 3/16
SEE NOTE
1/2" THK STIFFENER PL,
GALV STEEL (BOTH SIDES)
1/4" CAP PL
GALV STEEL
B/EXISTING BEAM
18' - 0"
T/ EXISTING
HOLLOWCORE
21' - 4" PL 1/2" x 16"x16" GALV STEEL
RE-USE EXISTING STAINLESS
STEEL EPOXY ANCHORS,
WASHERS AND NUTS, (4) 3/4"DIAx7"
EMBED SS EPOXY ANCHOR
HSS 4x4x1/2"
GALV. STEEL
PL1/2"x7"x1'-1 1/4" GALV
STEEL, REFER TO
PLATE DETAIL 1/S-102
D S-102 15' - 8" 1' - 4" 6" 2' - 4" 4' - 0" 3 3/4" 3"
FIELD DRILL HOLES FOR
5/8" DIA BOLTS IN
EXISTING CAP
PL1/2"x7"x1'-1 1/4" BELOW.
5 1/2" 1/2"
1/4" CAP PL GALV STEEL
2" 7 1/2"
T/ EXIST CAP PL
1/2" THK STIFFENER PL,
(BOTH SIDES)
EXISTING 8" CMU. #5@16" O.C.
VERT REINF TO BE FIELD
VERIFIED PRIOR TO COMMENCING
WITH COLUMN MODIFICATIONS.
REFER TO MODIFICATIONS OF
EXISTING STRUCTURE NOTES ON
SHEET S-001
7" 1' - 1 1/4" 3 1/2" 1 1/2" 4" 1 1/2" 7 1/2" 5 3/4" 1 1/2" 3" 6 1/2" 2 1/4" EXIST ALUMINUM COL I10x8.65 AND CAP PL1/2"x7"x1'-6 1/2" (CUT TO 1'-1 1/4") BELOW (6) 5/8"ø SS
BOLTS W/ WASHER
HSS 4x4x1/2" GALV STEEL 3" 3 1/2"
1/2" STIFFENER PL
GALV STEEL
3/16 3/16 3/16 PL1/2"x7"x1'-1 1/4" GALV STEEL
SCALE: 3/4" = 1'-0" S-102
B DEMO SECTION
SCALE: 3/4" = 1'-0" S-102
C SECTION -NEW CONNECTION
SCALE: 3/4" = 1'-0" S-102
D SECTION
CHKD:
DRWN:
PROJ:
DESN:
www.tetratech.com A B C D E F 2 3 4 5 6 7 Bar measures 1 inch, otherwise drawing is not to scale Copyright: Tetra Tech
SCALE: 3/4" = 1'-0"
0' 1' 2' 3' 1'
SCALE: 1 1/2" = 1'-0"
0' 1' 1' 1/15/2026 2:25:48 PMAutodesk Docs://200-08486-24001 Collier Co Bridge Crane Add/S_200-08486-24001 CCBC A_remodel.rvt 200-08486-24001
S. JENKINS
B. FOX
J.BURKETT
S-102
COLLIER COUNTY, FL
COLLIER COUNTY RAW WATER BOOSTER
PUMP STATION IMPROVEMENTS
SECTIONS & DETAILS
ENGINEERING BUSINESS NO. 2429
1000 CHEVROLET WAY STE. 102
ESTERO, FLORIDA 33928
TEL: (239) 390-1467
NOT FOR
CONSTRUCTION
SCALE: 1 1/2" = 1'-0" S-102
1 HSS PLATE DETAIL
MARK DATE DESCRIPTION BY
NOTE: PROVIDE CORROSION INHIBITING COATING BETWEEN
ALL DISIMILAR METALS THAT ARE IN CONTACT AND
ON SS BOLT THREADS
File details come from the government source that posted it. Updated .