This document provides details for a federal contract opportunity to improve military family housing at Stearley Heights in Kadena Air Base, Okinawa, Japan. The solicitation seeks to provide whole-house interior and exterior modernization, renovation, and repair of 130 single family dwelling units. The work includes restoration and repair of unit lots, building systems, and building spaces. It will provide all management, tools, design, supplies, equipment, transportation, labor and services necessary for the improvements to the family housing units. The solicitation number is W912HV21B0003 and was issued by the Department of the Army Corps of Engineers Engineering District Japan. The projected contract value is between 2.5 and 10 billion Japanese yen. The deadline to submit bids was not specified in the document.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FY21 Improve Family Housing Stearley Heights 19AF0002 Kadena, Okinawa, Japan
SECTION 09 29 00
GYPSUM BOARD
08/16
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI A108.11 (1992; Reaffirmed 2005) Specifications for Interior Installation of Cementitious Backer Units
ASTM INTERNATIONAL (ASTM)
ASTM C1002 (2018) Standard Specification for Steel Self-Piercing Tapping Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs
ASTM C1047 (2014a) Standard Specification for Accessories for Gypsum Wallboard and Gypsum Veneer Base
ASTM C1178/C1178M (2013) Standard Specification for Glass Mat Water-Resistant Gypsum Backing Panel
ASTM C1396/C1396M (2017) Standard Specification for Gypsum Board
ASTM C475/C475M (2017) Standard Specification for Joint Compound and Joint Tape for Finishing Gypsum Board
ASTM C840 (2018b) Standard Specification for Application and Finishing of Gypsum Board
ASTM C954 (2018) Standard Specification for Steel Drill Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Steel Studs from 0.033 in. (0.84 mm) to
0.112 in. (2.84 mm) in Thickness
ASTM D226/D226M (2017) Standard Specification for Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing
ASTM D3273 (2016) Standard Test Method for Resistance to Growth of Mold on the Surface of Interior Coatings in an Environmental Chamber
SECTION 09 29 00 Page 1
W912HV-21-B-0003 RTA
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2010; Version 1.1) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
GREEN SEAL (GS)
GS-36 (2013) Adhesives for Commercial Use
GYPSUM ASSOCIATION (GA)
GA 214 (2010) Recommended Levels of Gypsum Board Finish
GA 216 (2010) Application and Finishing of Gypsum Panel Products
Japan Adhesive Industry Association (JAIA)
JAIA 4VOC 4VOC Standard Product for Regulating Indoor Air Pollution Control
JAPANESE INDUSTRIAL STANDARDS (JIS)
JIS A5430 Fiber Reinforced Cement Boards
JIS A6005 Asphalt Roofing Felts
JIS A6901 Gypsum Boards
JIS A6914 Jointing Materials for Gypsum Plasterboards
JIS B1125 Self Drilling Tapping Screws
JIS Z2911 Methods of Test for Fungus Resistance
MINISTRY OF LAND, INFRASTRUCTURE, TRANSPORTATION AND TOURISM (MLIT)
MLIT Certification Fire Resistive Assemblies
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2017) Adhesive and Sealant Applications
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
UL Fire Resistance (2014) Fire Resistance Directory
SECTION 09 29 00 Page 2
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-03 Product Data
Cementitious Backer Units
Glass Mat Water-Resistant Gypsum Tile Backing Board
Water-Resistant Gypsum Backing Board
Accessories
Submit for each type of gypsum board and for cementitious backer units.
Gypsum Board
Recycled Content for Gypsum Board;
VOC Content of Joint Compound;
SD-04 Samples
Predecorated Gypsum Board; G
Submit for each color and pattern of predecorated gypsum board.
Where colors are not indicated, submit color selection samples of not less than eight of the manufacturer's standard colors.
SD-07 Certificates
Asbestos Free Materials; G
Certify that gypsum board types, gypsum backing board types, cementitious backer units, and joint treating materials do not contain asbestos.
Indoor Air Quality for Gypsum Board;
Indoor Air Quality for Non-aerosol Adhesives;
Indoor Air Quality for Aerosol Adhesives;
SD-08 Manufacturer's Instructions
Safety Data Sheets
SD-10 Operation and Maintenance Data
Manufacturer Maintenance Instructions
SECTION 09 29 00 Page 3
1.3 CERTIFICATIONS
1.3.1 Indoor Air Quality Certifications
Submit required indoor air quality certifications in one submittal package.
1.3.1.1 Adhesives and Sealants
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold, F 4-Star and JAIA 4VOC registered or provide certification or validation by other third-party program that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
1.4 DELIVERY, STORAGE, AND HANDLING
1.4.1 Delivery
Deliver materials in the original packages, containers, or bundles with each bearing the brand name, applicable standard designation, and name of manufacturer, or supplier.
1.4.2 Storage
Keep materials dry by storing inside a sheltered building. Where necessary to store gypsum board and cementitious backer units outside, store off the ground, properly supported on a level platform, and protected from direct exposure to rain, snow, sunlight, and other extreme weather conditions. Provide adequate ventilation to prevent condensation. Store per manufacturer's recommendations for allowable temperature and humidity range. Do not store gypsum wallboard with materials which have high emissions of volatile organic compounds (VOCs) or other contaminants. Do not store panels near materials that may offgas or emit harmful fumes, such as kerosene heaters, fresh paint, or adhesives. Do not use materials that have visible moisture or biological growth.
1.4.3 Handling
Neatly stack gypsum board and cementitious backer units flat to prevent sagging or damage to the edges, ends, and surfaces.
1.5 QUALIFICATIONS
Furnish type of gypsum board work specialized by the installer with a minimum of 3 years of documented successful experience.
1.6 ENVIRONMENTAL REQUIREMENTS
Do not expose the gypsum board to excessive sunlight prior to gypsum board application. Maintain a continuous uniform temperature of not less than 10 degrees C and not more than 27 degrees C for at least one week prior to the application of gypsum board work, while the gypsum board application is being done, and for at least one week after the gypsum board is set.
Shield air supply and distribution devices to prevent any uneven flow of air across the plastered surfaces. Provide ventilation to exhaust moist
SECTION 09 29 00 Page 4 air to the outside during gypsum board application, set, and until gypsum board jointing is dry. In glazed areas, keep windows open top and bottom or side to side 75 to 100 mm. Reduce openings in cold weather to prevent freezing of joint compound when applied. For enclosed areas lacking natural ventilation, provide temporary mechanical means for ventilation.
In unglazed areas subjected to hot, dry winds or temperature differentials from day to night of 10 degrees C or more, screen openings with cheesecloth or similar materials. Avoid rapid drying. During periods of low indoor humidity, provide minimum air circulation following gypsum boarding and until gypsum board jointing complete and is dry.
PART 2 PRODUCTS
2.1 MATERIALS
Conform to specifications, standards and requirements specified. Provide gypsum board types, gypsum backing board types, cementitious backing units, and joint treating materials manufactured from asbestos free materials only. Submit Safety Data Sheets and manufacturer maintenance instructions for gypsum materials including adhesives.
2.1.1 Gypsum Board
ASTM C1396/C1396M or JIS A6901 . Gypsum board must contain a minimum of 10 percent post-consumer recycled content, or a minimum of 40 percent post-industrial recycled content. Provide data identifying percentage of recycled content for gypsum board. Provide gypsum wall board and panels meeting the emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type, or JAIA 4VOC and F 4-Star. Provide certification or validation of indoor air quality for gypsum board.
2.1.1.1 Regular
1200 mm wide, 12.5 mm thick, tapered edges.
2.1.1.2 Type X (Special Fire-Resistant)
1200 mm wide, 15.9 mm thick, square or tapered edges.
2.1.1.3 Mold Resistant / Anti-Microbial Gypsum
ASTM D3273 or JIS Z2911 . 1200 mm wide, 12.5 mm thick, square, tapered or beveled edges.
2.1.2 Gypsum Backing Board
ASTM C1396/C1396M or JIS A6901 , gypsum backing board must be used as a base in a multilayer system.
2.1.2.1 Regular
1200 mm wide, 12.5 mm thick, square, tapered or beveled edges.
2.1.2.2 Type X (Special Fire-Resistant)
1200 mm wide, 12.5 mm thick, square, tapered or beveled edges.
SECTION 09 29 00 Page 5
2.1.3 Regular Water-Resistant Gypsum Backing Board
ASTM C1396/C1396M
2.1.3.1 Regular
1200 mm wide, 12.5 mm thick, tapered or beveled edges.
2.1.4 Glass Mat Water-Resistant Gypsum Tile Backing Board
ASTM C1178/C1178M or with a water absorption rate of less than 5%
2.1.4.1 Regular
1200 mm wide, 12.5 mm thick, square, tapered or beveled edges.
2.1.4.2 Type X (Special Fire-Resistant)
1200 mm wide, 12.5 mm thick, square, tapered or beveled edges.
2.1.5 Predecorated Gypsum Board
2.1.6 Cementitious Backer Units
In accordance with the Tile Council of America (TCA) Handbook or JIS A5430 .
2.1.7 Joint Treatment Materials
ASTM C475/C475M or JIS A6914 . Product must be low emitting VOC types with VOC limits not exceeding 50 g/L. Provide data identifying VOC content of joint compound. Use all purpose joint and texturing compound containing inert fillers and natural binders, including lime compound. Pre-mixed compounds must be free of antifreeze, vinyl adhesives, preservatives, biocides and other slow releasing compounds.
2.1.7.1 Embedding Compound
Specifically formulated and manufactured for use in embedding tape at gypsum board joints and compatible with tape, substrate and fasteners.
2.1.7.2 Finishing or Topping Compound
Specifically formulated and manufactured for use as a finishing compound.
2.1.7.3 All-Purpose Compound
Specifically formulated and manufactured to serve as both a taping and a finishing compound and compatible with tape, substrate and fasteners.
2.1.7.4 Setting or Hardening Type Compound
Specifically formulated and manufactured for use with fiber glass mesh tape.
2.1.7.5 Joint Tape
Use cross-laminated, tapered edge, reinforced paper, or fiber glass mesh tape recommended by the manufacturer.
SECTION 09 29 00 Page 6
2.1.8 Fasteners
2.1.8.1 Screws
ASTM C1002, Type "G", Type "S" or Type "W" or JIS B1125 steel drill screws for fastening gypsum board to gypsum board, wood framing members and steel framing members less than 0.84 mm thick. ASTM C954 or JIS B1125 steel drill screws for fastening gypsum board to steel framing members 0.84 to
2.84 mm thick. Provide cementitious backer unit screws with a polymer coating.
2.1.9 Adhesives
Provide non-aerosol adhesive products used on the interior of the building (defined as inside of the weatherproofing system) meeting either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of SCAQMD Rule 1168 or JAIA 4VOC registered and F 4-Star. Provide aerosol adhesive products used on the interior of the building (defined as inside of the weatherproofing system) meeting either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of GS-36 or JAIA 4VOC registered and F 4-Star. Provide certification or validation of indoor air quality for non-aerosol adhesives applied on the interior of the building (inside of the weatherproofing system). Provide certification or validation of indoor air quality for aerosol adhesives used on the interior of the building (inside of the weatherproofing system).
2.1.9.1 Adhesive for Fastening Gypsum Board to Metal Framing
Not permitted.
2.1.10 Shaftwall Liner Panel
2.1.11 Accessories
ASTM C1047. Fabricate from corrosion protected steel designed for intended use. Accessories manufactured with paper flanges are not acceptable. Flanges must be free of dirt, grease, and other materials that may adversely affect bond of joint treatment. Provide prefinished or job decorated materials.
2.1.12 Asphalt Impregnated Building Felt
Provide a 6.7 kg asphalt moisture barrier over glass mat covered or reinforced gypsum sheathing. Conforming to ASTM D226/D226M Type 1 (No.
15) or JIS A6005 for asphalt impregnated building felt.
2.1.13 Water
Provide clean, fresh, and potable water.
SECTION 09 29 00 Page 7
PART 3 EXECUTION
3.1 EXAMINATION
3.1.1 Framing and Furring
Verify that framing and furring are securely attached and of sizes and spacing to provide a suitable substrate to receive gypsum board and cementitious backer units. Verify that all blocking, headers and supports are in place to support plumbing fixtures and to receive soap dishes, grab bars, towel racks, and similar items. Do not proceed with work until framing and furring are acceptable for application of gypsum board and cementitious backer units.
3.1.2 Masonry and Concrete Walls
Verify that surfaces of masonry and concrete walls to receive gypsum board applied with adhesive are dry, free of dust, oil, form release agents, protrusions and voids, and any other foreign matter. Do not proceed with work until surfaces are acceptable for application of gypsum board with adhesive.
3.1.3 Building Construction Materials
Do not install building construction materials that show visual evidence of biological growth.
3.2 APPLICATION OF GYPSUM BOARD
Apply gypsum board to framing and furring members in accordance with ASTM C840 or GA 216 and the requirements specified. Apply gypsum board with separate panels in moderate contact; do not force in place. Stagger end joints of adjoining panels. Neatly fit abutting end and edge joints.
Use gypsum board of maximum practical length; select panel sizes to minimize waste. Cut out gypsum board to make neat, close, and tight joints around openings. In vertical application of gypsum board, provide panels in lengths required to reach full height of vertical surfaces in one continuous piece. Lay out panels to minimize waste; reuse cutoffs whenever feasible. Surfaces of gypsum board and substrate members may be bonded together with an adhesive, except where prohibited by fire rating(s). Treat edges of cutouts for plumbing pipes, screwheads, and joints with water-resistant compound as recommended by the gypsum board manufacturer. Minimize framing by floating corners with single studs and drywall clips. Provide type of gypsum board for use in each system specified herein as indicated.
3.2.1 Adhesive Application to Interior Masonry or Concrete Walls
Apply in accordance with ASTM C840, System VI or GA 216 .
3.2.2 Application of Gypsum Board to Steel Framing and Furring
Apply in accordance with ASTM C840, System VIII or GA 216 .
3.2.3 Arches and Bending Radii
Apply gypsum board in accordance with ASTM C840, System IX or GA 216 .
SECTION 09 29 00 Page 8
3.2.4 Gypsum Board for Wall Tile or Tile Base Applied with Adhesive
In dry areas (areas other than tubs, shower enclosures, saunas, steam rooms, gang shower rooms), apply glass mat water-resistant gypsum tile backing board or water-resistant gypsum backing board in accordance with ASTM C840, System X or GA 216 .
3.2.5 Control Joints
Install expansion and contraction joints in ceilings and walls in accordance with ASTM C840, System XIII or GA 216 . Fill control joints between studs in fire-rated construction with firesafing insulation to match the fire-rating of construction.
3.3 APPLICATION OF CEMENTITIOUS BACKER UNITS
3.3.1 Application
In wet areas (tubs, shower enclosures, saunas, steam rooms, gang shower rooms), apply cementitious backer units in accordance with ANSI A108.11 .
Place a 7.6 kg asphalt impregnated, continuous felt paper membrane behind cementitious backer units, between backer units and studs or base layer of gypsum board. Place membrane with a minimum 150 mm overlap of sheets laid shingle style.
3.3.2 Joint Treatment
ANSI A108.11 .
3.4 FINISHING OF GYPSUM BOARD
Tape and finish gypsum board in accordance with ASTM C840, GA 214 and GA 216 . Finish plenum areas above ceilings to Level 1 in accordance with GA 214 . Finish water resistant gypsum backing board, ASTM C1396/C1396M , to receive ceramic tile to Level 2 in accordance with GA 214 . Finish walls and ceilings to receive a heavy-grade wall covering or heave textured finish before painting to Level 3 in accordance with GA 214 . Finish walls and ceilings without critical lighting to receive flat paints, light textures, or wall coverings to Level 4 in accordance with GA 214 . Unless otherwise specified, finish all gypsum board walls, partitions and ceilings to Level 5 in accordance with GA 214 . Provide joint, fastener depression, and corner treatment. Tool joints as smoothly as possible to minimize sanding and dust. Do not use self-adhering fiber glass mesh tape with conventional drying type joint compounds; use setting or hardening type compounds only. Provide treatment for water-resistant gypsum board as recommended by the gypsum board manufacturer. Protect workers, building occupants, and HVAC systems from gypsum dust.
3.4.1 Uniform Surface
Wherever gypsum board is to receive eggshell, semigloss or gloss paint finish, or where severe, up or down lighting conditions occur, finish gypsum wall surface in accordance to GA 214 Level 5. In accordance with GA 214 Level 5, apply a thin skim coat of joint compound to the entire gypsum board surface, after the two-coat joint and fastener treatment is complete and dry.
SECTION 09 29 00 Page 9
3.5 SEALING
Seal openings around pipes, fixtures, and other items projecting through gypsum board and cementitious backer units as specified in Section 07 92 00 JOINT SEALANTS. Apply material with exposed surface flush with gypsum board or cementitious backer units.
3.6 FIRE-RESISTANT ASSEMBLIES
Wherever fire-rated construction is indicated, provide materials and application methods, including types and spacing of fasteners, in accordance with the specifications contained in UL Fire Resistance or MLIT Certification for the Design Number(s) indicated. Joints of fire-rated gypsum board enclosures must be closed and sealed in accordance with UL test requirements or GA requirements. Seal penetrations through rated partitions and ceilings tight in accordance with tested systems.
3.7 PATCHING
Patch surface defects in gypsum board to a smooth, uniform appearance, ready to receive finishes.
3.8 SHAFTWALL FRAMING
Install the shaftwall system in accordance with the system manufacturer's published instructions. Coordinate bucks, anchors, blocking and other items placed in or behind shaftwall framing with electrical and mechanical work. Patch or replace fireproofing materials which are damaged or removed during shaftwall construction.
-- End of Section --
SECTION 09 29 00 Page 10
SECTION 09 30 10
CERAMIC, QUARRY, AND GLASS TILING
08/17
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI A136.1 (2008 Reaffirmed 2013) American National Standard Specifications for Organic Adhesives for Installation of Ceramic Tile
ANSI A137.1 (2012) American National Standards Specifications for Ceramic Tile
ASTM INTERNATIONAL (ASTM)
ASTM C33/C33M (2018) Standard Specification for Concrete Aggregates
ASTM C144 (2018) Standard Specification for Aggregate for Masonry Mortar
ASTM C150/C150M (2018) Standard Specification for Portland Cement
ASTM C206 (2014) Standard Specification for Finishing Hydrated Lime
ASTM C207 (2018) Standard Specification for Hydrated Lime for Masonry Purposes
ASTM C373 (2018)Standard Test Methods for Determination of Water Absorption and Associated Properties by Vacuum Method for Pressed Ceramic Tiles and Glass Tiles and Boil Method for Extruded Ceramic Tiles and Non-tile Fired Ceramic Whiteware Products
ASTM C648 (2004; R 2009) Breaking Strength of Ceramic Tile
ASTM C847 (2014a) Standard Specification for Metal Lath
ASTM C1026 (2013; R 2018) Standard Test Method for Measuring the Resistance of Ceramic and Glass Tile to Freeze-Thaw Cycling
ASTM C1027 (2009; R 2017) Standard Test Method for
SECTION 09 30 10 Page 1
Determining Visible Abrasion Resistance of Glazed Ceramic Tile
ASTM D226/D226M (2017) Standard Specification for Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing
ASTM D2103 (2015) Standard Specification for Polyethylene Film and Sheeting
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2010; Version 1.1) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
Japan BioPlastics Association (JBPA)
GreenPLA GreenPLA Positive List (PL) Formulation Standards
Japan Adhesive Industry Association (JAIA)
JAIA 4VOC 4VOC Standard Product for Regulating Indoor Air Pollution Control
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2017) Adhesive and Sealant Applications
TILE COUNCIL OF NORTH AMERICA (TCNA)
TCNA Hdbk (2017) Handbook for Ceramic, Glass, and Stone Tile Installation
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SECTION 09 30 10 Page 2
SD-02 Shop Drawings
Detail Drawings; G , SD-03 Product Data
Porcelain Tile; G , Recycled Content for Porcelain Tile;
Mosaic Tile; G, Recycled Content for Mosaic Tile;
Setting-Bed; G , Mortar, Grout, and Adhesive; G , SD-04 Samples
Tile; G , Accessories; G , Transition Strips; G , Grout; G , SD-07 Certificates
Indoor Air Quality for Sealants;
SD-08 Manufacturer's Instructions
Maintenance Instructions
SD-10 Operation and Maintenance Data
Installation; G ,
1.3 CERTIFICATIONS
1.3.1 Indoor Air Quality Certifications
1.3.1.1 Adhesives and Sealants
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification , JAIA 4VOC and F-Star or validation by other third-party programs that products meet the requirements of this Section.
Provide current product certification documentation from certification body.When product does not have certification, provide validation that product meets the indoor air quality product requirments cited in this Section.
1.3.2 Bio Based Products
Provide products in accordance with USDA Certified Bio-Based Product List
SECTION 09 30 10 Page 3 or JBPA GreenPLA when applicable.
1.4 QUALITY ASSURANCE
Provide installers having a minimum of two years experience with a company specializing in performing the type of work described. Each type and color of tile to be provided from a single source. Each type and color of mortar, adhesive, and grout to be provided from the same source.
1.5 DELIVERY, STORAGE, AND HANDLING
Ship tiles in sealed packages and clearly marked with the grade, type of tile, producer identification, and country of origin. Deliver materials to the project site in manufacturer's original unopened containers with seals unbroken and labels and hallmarks intact. Protect materials from weather, and store them under cover in accordance with manufacturer's printed instructions.
1.6 ENVIRONMENTAL REQUIREMENTS
Do not perform ceramic tile work unless the substrate and ambient temperature is at least 10 degrees C and rising. Maintain temperature above 10 degrees C while the work is being performed and for at least 7 days after completion of the work. When temporary heaters are used, ventilate the area to the outside to avoid carbon dioxide damage to new tilework.
1.7 WARRANTY
Provide manufacturer's standard performance guarantees or warranties that extend beyond a 1-year period.
1.8 EXTRA MATERIALS
Supply an extra 2 percent of each type tile used in clean and marked cartons.
PART 2 PRODUCTS
2.1 TILE
Provide tiles that comply with ANSI A137.1 and are standard grade tiles..
Provide a minimum breaking strength of 57 kg for wall tile and 113 kg for floor tile in accordance with ASTM C648. Provide exterior building tile for cold climate projects that is approved by the manufacturer for exterior use when tested in accordance with ASTM C1026. Provide floor tiles with a wet dynamic coefficient of friction (DCOF) value of 0.42 or greater when tested in accordance with ANSI A137.1 requirements. Provide glazed floor tile with a Class IV-Commercial classification as rated by the manufacturer when tested in accordance with ASTM C1027 for visible abrasion resistance as related to foot traffic. For materials like tile, accessories, and transition strips submit samples of sufficient size to show color range, pattern, type and joints. Submit manufacturer's catalog data.
2.1.1 Porcelain Tile (PFT-1, PFT-2, PBT-1, PBT-2, PWT-1)
Provide unglazed, rectified porcelain tile (PFT-1), bullnose(PBT-1) base and trim pieces with color extending uniformly through the body of the
SECTION 09 30 10 Page 4 tile. Provide tile with a V2 aesthetic classification. Blend tiles in factory and in a packages to have same color range and continuous blend for installation. Provide nominal tile size(s) of 600 by 600 mm and 9 mm thick. Provide a 0.50 percent maximum water absorption in accordance with
ASTM C373.
Provide unglazed, rectified porcelain tile (PFT-2), bullnose (PBT-2) base and trim pieces with color extending uniformly through the body of the tile. Provide tile with a V2 aesthetic classification. Blend tiles in factory and in a packages to have same color range and continuous blend for installation. Provide nominal tile size(s) of 305 by 305 mm and 8 mm thick. Provide a 0.50 percent maximum water absorption in accordance with
ASTM C373.
Provide unglazed, rectified porcelain tile (PWT-1) with color extending uniformly through the body of the tile. Provide tile with a V2 aesthetic classification. Blend tiles in factory and in a packages to have same color range and continuous blend for installation. Provide nominal tile size(s) of 305 by 610 mm and 9 mm thick. Provide a 0.50 percent maximum water absorption in accordance with ASTM C373.
Provide Porcelain Tiling Materials that contain a minimum of 10 percent recycled content. Provide data identifying percentage of recycled content for porcelain tile.
2.1.2 Mosaic Tile (PFT-3, PWT-2)
Furnish unglazed, mosaic tile (PFT-3)composed of porcelain. Provide tile with a V1 aesthetic classification. Blend tiles in factory and in a packages to have same color range and continuous blend for installation.
Provide nominal tile size(s) of 25 by 25 mm. Provide porcelain mosaics with a water absorption up to 0.50 percent when tested in accordance with
ASTM C373.
Furnish unglazed, mosaic tile (PWT-2)composed of porcelain. Provide tile with a V1 aesthetic classification. Blend tiles in factory and in a packages to have same color range and continuous blend for installation.
Provide nominal tile size(s) of 75 by 152 mm thick. Provide porcelain mosaics with a water absorption up to 0.42 percent when tested in accordance with ASTM C373.
Provide Mosaic Tiling Materials that contain a minimum of 3 percent recycled content. Provide data identifying percentage of recycled content for mosaic tile.
2.2 SETTING-BED
Submit manufacturer's catalog data. Compose the setting-bed of the following materials:
2.2.1 Aggregate for Concrete Fill
Conform to ASTM C33/C33M for aggregate fill. Do not exceed one-half the thickness of concrete fill for maximum size of coarse aggregate.
2.2.2 Portland Cement
Conform to ASTM C150/C150M for cement, Type I, white for wall mortar and
SECTION 09 30 10 Page 5 gray for other uses.
2.2.3 Sand
Conform to ASTM C144 for sand.
2.2.4 Hydrated Lime
Conform to ASTM C206 for hydrated lime, Type S or ASTM C207, Type S.
2.2.5 Metal Lath
Conform to ASTM C847 for flat expanded type metal lath, and weighing a minimum 1.4 kg/square meter.
2.3 WATER
Provide potable water.
2.4 MORTAR, GROUT, AND ADHESIVE
2.4.1 Dry-Set Portland Cement Mortar
TCNA Hdbk.
2.4.2 Latex-Portland Cement Mortar
TCNA Hdbk.
2.4.3 Ceramic Tile Grout
TCNA Hdbk; petroleum-free and plastic-free commercial portland cement grout.
2.4.4 Organic Adhesive
TCNA Hdbk, Type I. Water-resistant. Comply with ANSI A136.1 .
2.4.5 Epoxy Resin Grout
TCNA Hdbk. Prohibited unless specifically indicated otherwise.
2.4.6 Furan Resin Grout
TCNA Hdbk and consist of an intimate mixture of furfuryl-alcohol resin with carbon filler and catalyst. Prohibited unless specifically indicated otherwise.
2.4.7 Sealants
Comply with applicable regulations regarding toxic and hazardous materials and as specified. Grout sealant must not change the color or alter the appearance of the grout. Refer to Section 07 92 00 JOINT SEALANTS.
Provide sealants used on the interior of the building (defined as inside of the weatherproofing system) meeting either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of SCAQMD Rule 1168 or JAIA 4 and F 4-Star.Provide certification or
SECTION 09 30 10 Page 6 validation of indoor air quality for sealants.
2.5 SUBSTRATES
2.5.1 Cementitious Backer Board
Provide cementitious backer units, for use as tile substrate over wood sub-floors, in accordance with TCNA Hdbk. Furnish 12.7 mm thick cementitious backer units.
2.6 TRANSITION STRIPS (FTS-1)
Provide anodized aluminum transitions between tile and carpet or resilient flooring. Provide types as recommended by flooring manufacturer for both edges and transitions of flooring materials specified. Provide transition strips that comply with 36 CFR 1191 requirements. See Interior Finish Legend for FTS-1 sailent characteristic requirements and basis of design.
2.7 MEMBRANE MATERIALS
Conform to ASTM D226/D226M, Type 1 for 33 kg waterproofing membrane, asphalt-saturated building felt. Conform to ASTM D2103ASTM D4068 for polyethylene film.
2.8 COLOR, TEXTURE, AND PATTERN
Provide color, pattern and texture in accordance with the Interior Finish Legend Color listed is not intended to limit the selection of equal colors from other manufacturers. Provide floor patterns as specified on the drawings.
PART 3 EXECUTION
3.1 PREPARATORY WORK AND WORKMANSHIP
Inspect surface to receive tile in conformance to the requirements of TCNA Hdbk for surface conditions for the type setting bed specified and for workmanship. Provide variations of tiled surfaces that fall within maximum values shown below:
TYPE WALLS FLOORS
Dry-Set Mortar 3 mm in 2.4 meter 3.0 mm in 3 meter
Organic Adhesives 3 mm in 2.4 meter 1.5 mm in 1 meter
Latex Portland Cement Mortar 3 mm in 2.4 meter 3.0 mm in 3 meter
Epoxy 3 mm in 2.4 meter 3.0 mm in 3 meter
3.2 GENERAL INSTALLATION REQUIREMENTS
Do not start tile work until roughing in for mechanical and electrical work has been completed and tested, and built-in items requiring membrane waterproofing have been installed and tested. Close space, in which tile
SECTION 09 30 10 Page 7 is being set, to traffic and other work. Keep closed until tile is firmly set. Do not start floor tile installation in spaces requiring wall tile until after wall tile has been installed. Apply tile in colors and patterns indicated in the area shown on the drawings. Install tile with the respective surfaces in true even planes to the elevations and grades shown. Provide special shapes as required for sills, jambs, recesses, offsets, external corners, and other conditions to provide a complete and neatly finished installation. Solidly back tile bases and coves with mortar. Do not walk or work on newly tiled floors without using kneeling boards or equivalent protection of the tiled surface. Keep traffic off horizontal portland cement mortar installations for at least 72 hours.
Keep all traffic off epoxy installed floors for at least 40 hours after grouting, and heavy traffic off for at least 7 days, unless otherwise specifically authorized by manufacturer. Dimension and draw detail drawings at a minimum scale of 6 mm = 300 mm. Include drawings of pattern at inside corners, outside corners, termination points and location of all equipment items such as thermostats, switch plates, mirrors and toilet accessories mounted on surface. Submit drawings showing ceramic tile pattern elevations and floor plans. Submit manufacturer's preprinted installation instructions.
Do not install building construction materials that show visual evidence of biological growth.
3.3 INSTALLATION OF WALL TILE
Install wall tile in accordance with the TCNA Hdbk, method and with grout joints as recommended by the manufacturer for the type of tile. Install thinner wall tile flush with thicker wall tile applied on same wall and provide installation materials as recommended by the tile and setting materials manufacturer's to achieve flush installation.
3.3.1 Workable or Cured Mortar Bed
Install tile over workable mortar bed or a cured mortar bed at the option of the Contractor. Install a 0.102 mm polyethylene membrane, metal lath, and scratch coat. Conform to TCNA Hdbk for workable mortar bed, materials, and installation of tile. Conform to TCNA Hdbk for cured mortar bed and materials.
3.3.2 Dry-Set Mortar and Latex-Portland Cement Mortar
Use Latex-Portland Cement to install tile in accordance with TCNA Hdbk.
Use Latex Portland Cement when installing porcelain ceramic tile.
3.3.3 Organic Adhesive
Conform to TCNA Hdbk for the organic adhesive installation of ceramic tile.
3.3.4 Furan Mortar and Grout
Conform to TCNA Hdbk for furan mortar and grout installation.
3.3.5 Ceramic Tile Grout
Prepare and install ceramic tile grout in accordance with TCNA Hdbk.
Provide and apply manufacturer's standard product for sealing grout joints in accordance with manufacturer's recommendations.
SECTION 09 30 10 Page 8
3.4 INSTALLATION OF FLOOR TILE
Install floor tile in accordance with TCNA Hdbk method and with grout joints as recommended by the manufacturer for the type of tile. Install shower receptors in accordance with TCNA Hdbk method B414 .
3.4.1 Workable or Cured Mortar Bed
Install floor tile over a workable mortar bed or a cured mortar bed at the option of the Contractor. Conform to TCNA Hdbk for workable mortar bed materials and installation. Conform to TCNA Hdbk for cured mortar bed materials and installation. Provide minimum 6.35 mm to maximum 9.53 mm.
3.4.2 Dry-Set and Latex-Portland Cement
Use Latex-Portland cement mortar to install tile directly over properly cured, plane, clean concrete slabs in accordance with TCNA Hdbk. Use Latex Portland cement when installing porcelain ceramic tile.
3.4.3 Resinous Grout
When resinous grout is indicated, grout quarry tile with either furan or epoxy resin grout. Rake and clean joints to the full depth of the tile and neutralize when recommended by the resin manufacturer. Install epoxy resin grout in conformance with TCNA Hdbk. Install resin grout in accordance with manufacturer's printed installation instructions. Provide a coating of wax applied from the manufacturer on all tile installed and furan resin. Follow manufacturer's printed installation instructions of installed resin grout for proportioning, mixing, installing, and curing.
Maintain the recommended temperature in the area and on the surface to be grouted. Protect finished grout of grout stain.
3.4.4 Ceramic Tile Grout
Prepare and install ceramic tile grout in accordance with TCNA Hdbk.
Provide and apply manufacturer's standard product for sealing grout joints in accordance with manufacturer's recommendations.
3.4.5 Waterproofing
Shower pans are specified in Section 22 00 00 PLUMBING, GENERAL PURPOSE.
Conform to the requirements of Section 07 12 00 BUILT-UP BITUMINOUS WATERPROOFING for waterproofing under concrete fill.
3.4.6 Concrete Fill
Provide a 24.1 MPa concrete fill mix to dry as consistency as practicable. Compose concrete fill by volume of 1 part Portland cement to 3 parts fine aggregate to 4 parts coarse aggregate, and mix with water to as dry a consistency as practicable. Spread, tamp, and screed concrete fill to a true plane, and pitch to drains or levels as shown. Thoroughly damp concrete fill before applying setting-bed material. Reinforce concrete fill with one layer of reinforcement, with the uncut edges lapped the width of one mesh and the cut ends and edges lapped a minimum 50 mm.
Tie laps together with 1.3 mm wire every 250 mm along the finished edges and every 150 mm along the cut ends and edges. Provide reinforcement with support and secure in the centers of concrete fills. Provide a continuous mesh; except where expansion joints occur, cut mesh and discontinue across such joints. Provide reinforced concrete fill under the setting-bed where
SECTION 09 30 10 Page 9 the distance between the under-floor surface and the finished tiles floor surface is a minimum of 50 mm, and of the same thickness that the mortar setting-bed over the concrete fill with the thickness required in the specified TCNA Hdbk method.
3.5 INSTALLATION OF TRANSITION STRIPS
Install transition strips where indicated, in a manner similar to that of the ceramic tile floor and as recommended by the manufacturer. Provide thresholds full width of the opening. Install head joints at ends not exceeding 6 mm in width and grouted full.
3.6 EXPANSION JOINTS
Form and seal joints as specified in Section 07 92 00 JOINT SEALANTS.
3.6.1 Walls
Provide expansion joints at control joints in backing material. Wherever backing material changes, install an expansion joint to separate the different materials.
3.6.2 Floors
Provide expansion joints over construction joints, control joints, and expansion joints in concrete slabs. Provide expansion joints where tile abuts restraining surfaces such as perimeter walls, curbs and columns and at intervals of 7 to 11 m each way in large interior floor areas and 3 to 5 m each way in large exterior areas or areas exposed to direct sunlight or moisture. Extend expansion joints through setting-beds and fill.
3.7 CLEANING AND PROTECTING
Upon completion, thoroughly clean tile surfaces in accordance with manufacturer's approved cleaning instructions. Do not use acid for cleaning glazed tile. Clean floor tile with resinous grout or with factory mixed grout in accordance with printed instructions of the grout manufacturer. After the grout has set, provide a protective coat of a noncorrosive soap or other approved method of protection for tile wall surfaces. Cover tiled floor areas with building paper before foot traffic is permitted over the finished tile floors. Provide board walkways on tiled floors that are to be continuously used as passageways by workmen.
Replace damaged or defective tiles. Submit copy of manufacturer's printed maintenance instructions.
-- End of Section --
SECTION 09 30 10 Page 10
SECTION 09 65 00
RESILIENT FLOORING
08/10
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM D4078 (2002; R 2015) Water Emulsion Floor Polish
ASTM E648 (2017a) Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source
ASTM F710 (2019) Standard Practice for Preparing Concrete Floors to Receive Resilient Flooring
ASTM F1482 (2015) Installation and Preparation of Panel Type Underlayments to Receive Resilient Flooring
ASTM F1700 (2018a) Standard Specification for Solid Vinyl Floor Tile
ASTM F1869 (2016) Standard Test Method for Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride
ASTM F2169 (2015; E 2016) Standard Specification for Resilient Stair Treads
ASTM F2170 (2019) Standard Test Method for Determining Relative Humidity in Concrete Floor Slabs Using in situ Probes
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2010; Version 1.1) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
GREEN SEAL (GS)
GS-36 (2013) Adhesives for Commercial Use
Japan Adhesive Industry Association (JAIA)
JAIA 4VOC 4VOC Standard Product for Regulating
SECTION 09 65 00 Page 1
Indoor Air Pollution Control
Japan BioPlastics Association (JBPA)
GreenPLA GreenPLA Positive List (PL) Formulation Standards
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2017) Adhesive and Sealant Applications
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Resilient Flooring and Accessories; G , SD-03 Product Data
Resilient Flooring and Accessories; G , Adhesives
SD-04 Samples
Resilient Flooring and Accessories; G , SD-06 Test Reports
Moisture, Alkalinity and Bond Tests; G , SD-07 Certificates
Indoor Air Quality for Luxury Vinyl Tile;
Indoor Air Quality for Adhesives;
SD-08 Manufacturer's Instructions
Surface Preparation; G , Installation; G , SD-10 Operation and Maintenance Data
SECTION 09 65 00 Page 2
Resilient Flooring and Accessories; G ,
1.3 CERTIFICATES
1.3.1 Bio Based Products
Provide products in accordance with USDA Certified Bio-Based Product List or JBPA GreenPLA when applicable.
1.3.2 Indoor Air Quality
Submit required indoor air quality certifications and validations in one submittal package.
1.3.2.1 Floor Covering Materials
Provide Luxury Vinyl Tile, and wall base products certified to meet indoor air quality requirements by FLOORSCORE, UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold, JAIA 4VOC registered and F 4-Star, or provide certification by other third-party programs. Provide current product certification documentation from certification body.
1.3.2.2 Adhesives, Caulking and Sealants
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold, JAIA 4VOC registered and F 4-Star, or provide certificationor validation by other third-party programs that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
1.4 DELIVERY, STORAGE, AND HANDLING
Deliver materials to the building site in original unopened containers bearing the manufacturer's name, style name, pattern color name and number, production run, project identification, and handling instructions. Store materials in a clean, dry, secure, and well-ventilated area free from strong contaminant sources and residues with ambient air temperature maintained above 20 degrees C and below 30 degrees C, stacked according to manufacturer's recommendations. Protect materials from the direct flow of heat from hot-air registers, radiators and other heating fixtures and appliances. Observe ventilation and safety procedures specified in the MSDS. Do not store luxury vinyl tile near materials that may offgas or emit harmful fumes, such as kerosene heaters, fresh paint, or adhesives.
1.5 ENVIRONMENTAL REQUIREMENTS
Maintain areas to receive resilient flooring at a temperature above 20 degrees C and below 30 degrees C for 3 days before application, during application and 2 days after application, unless otherwise directed by the flooring manufacturer for the flooring being installed. Maintain a minimum temperature of 13 degrees C thereafter. Provide adequate ventilation to remove moisture from area and to comply with regulations limiting concentrations of hazardous vapors.
SECTION 09 65 00 Page 3
1.6 SCHEDULING
Schedule resilient flooring application after the completion of other work which would damage the finished surface of the flooring.
1.7 WARRANTY
Provide manufacturer's standard performance guarantees or warranties that extend beyond a one year period.
1.8 EXTRA MATERIALS
Provide extra flooring material of each color and pattern at the rate of 5 tiles for each 1000 tiles installed. Provide extra wall base material composed of 6 m of each type, color and pattern. Package all extra materials in original properly marked containers bearing the manufacturer's name, brand name, pattern color name and number, production run, and handling instructions. Provide extra materials from the same lot as those installed. Leave extra stock at the site in location assigned by Contracting Officer.
PART 2 PRODUCTS (Resilient Flooring and Accessories)
2.1 LUXURY VINYL TILE (LVT-1)
Conform to ASTM F1700 Class III printed film with a minimum wear layer thickness 0.50 mm (20 mil) and minimum overall thickness 4.5 mm, Type B (embossed). Provide 25 cm x 100 cm plank tile. Provide tile with a factory protective finish that enhances cleanability and durability.
Provide Luxury Vinyl Tile that is free of ortho phthalates, added formaldeyde and heavy metal stabilizers.
Provide certification of indoor air quality for Luxury Vinyl Tile.
2.2 STAIR TREADS (RST-1)
Conform to ASTM F2169, Type TS (vulcanized thermoset rubber) . Conform to ASTM F2169 for surface of treads Class 2 raised stud pattern . Provide a one piece nosing/treadwith a 50 mm non-slip strip.
2.3 MOULDING (LT-1)
Provide tapered mouldings of rubber and types as recommended by flooring manufacturer for both edges and transitions of flooring materials specified. Provide vertical lip on moulding of maximum 6 mm. Provide bevel change in level between 6 and 13 mm with a slope no greater than 1:2. Provide landing trim (LT-1) at landing edge of stairs at locations as indicated in the drawings. Provide landing trim with salient characteristics as identified in the Interior Finish Legend.
2.4 ADHESIVES
Provide adhesives for flooring, base and accessories as recommended by the manufacturer and comply with local indoor air quality standards. Submit manufacturer's descriptive data, documentation stating physical characteristics, and mildew and germicidal characteristics.
Provide non-aerosol adhesive products used on the interior of the building
SECTION 09 65 00 Page 4
(defined as inside of the weatherproofing system) that meet either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of SCAQMD Rule 1168 , or JAIA 4VOC and 4-Star . Provide aerosol adhesives used on the interior of the building that meet either emissions requirements of CDPH SECTION 01350 (use the office or classroom requirements, regardless of space type) or VOC content requirements of GS-36, or JAIA 4VOC and 4-Star . Provide certification or validation of indoor air quality for adhesives.
2.5 SURFACE PREPARATION MATERIALS
Provide surface preparation materials, such as panel type underlayment, lining felt, and floor crack fillers as recommended by the flooring manufacturer for the subfloor conditions. Comply with ASTM F1482 for panel type underlayment products.
2.6 POLISH/FINISH
Provide polish finish as recommended by the manufacturer and conform to ASTM D4078 for polish.
2.7 CAULKING AND SEALANTS
Provide caulking and sealants in accordance with Section 07 92 00 JOINT
SEALANTS.
2.8 MANUFACTURER'S COLOR, PATTERN AND TEXTURE
Provide color, pattern and texture for resilient flooring and accessories as indicated on the Interior Finish Legend and selected from manufacturer's standard colors. Provide floor patterns as specified on the drawings. Provide flooring in any one continuous area or replacement of damaged flooring in continuous area from same production run with same shade and pattern. Submit scaled drawings indicating patterns (including location of patterns and colors) and dimensions. Submit manufacturer's descriptive data and three samples of each indicated color and type of flooring, base, mouldings, and accessories sized a minimum 60 by 100 mm.
Submit Data Package 1 in accordance with Section 01 78 23 OPERATION AND
MAINTENANCE DATA.
2.9 FIRE RESISTANCE TESTING REQUIREMENTS
Provide a minimum average critical radiant flux of 0.22 watts per square centimeter for flooring in corridors and exits when tested in accordance with ASTM E648.
PART 3 EXECUTION
3.1 EXAMINATION
Examine and verify that site conditions are in agreement with the design package. Report all conditions that will prevent a proper installation.
Do not take any corrective action without written permission from the Government. Work will proceed only when conditions have been corrected and accepted by the installer. Submit manufacturer's printed installation instructions for all flooring materials and accessories, including preparation of substrate, seaming techniques, and recommended adhesives.
SECTION 09 65 00 Page 5
3.2 SURFACE PREPARATION
Provide a smooth, true, level plane for surface preparation of the flooring, except where indicated as sloped. Floor to be flat to within
4.75 in 3048 mm. Prepare subfloor in accordance with flooring manufacturer's recommended…