Statement of Work - Hangar 46 Battery.pdf
PDF 195 KB Posted
- Attached to
- Hangar 46 Battery Shop Electrical Upgrade Federal contract opportunity
- Solicitation number
- FA442724Q0166
About this file
The document is a Statement of Work (SOW) for an electrical upgrade to the battery shop in Hangar 46 at Travis Air Force Base. The contractor shall upgrade 10 electrical panel circuit breakers, wiring, and outlets to support a 30A equipment requirement for the battery chargers. The work includes pulling new 10-gauge wire, replacing 20A breakers with 30A breakers, and replacing receptacles. The contractor must have California electrical certification and complete the work within 8-10 weeks after contract award.
The related federal contract opportunity is a Firm Fixed Price contract solicitation for the Hangar 46 Battery Shop Electrical Upgrade, with a solicitation number of FA442724Q0166. Interested vendors shall submit quotes in accordance with the Instructions to Offerors by 20 September 2024 9:00 AM PST. The contracting agency is the 60th Contracting Squadron at Travis Air Force Base, which is part of the Department of the Air Force Air Mobility Command.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 1 Atch 1 - FA442724Q0166.pdf | ||
| AMENDMENT 1 - QUESTIONS.pdf | ||
| Combined Synopsis Solicitation - FA442724Q0166.pdf | ||
| WD 2015-5655 Rev. 21.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Specifications/Item Listing (Commodity) Statement of Work (SOW) for Hangar 46 Bay F Battery Shop Electrical Upgrade
60th Maintenance Squadron/Electrical and Environmental battery shop has a requirement to repair, inspect, and charge aircraft battery assemblies. To perform normal maintenance on aircraft batteries they must be recharged and tested for their next use. Travis battery shop needs to be relocated to a new facility that does not have adequate infrastructure to fulfill this requirement. The designated work center for the battery shop is currently wired with ten 20A circuits for battery chargers. The chargers require a minimum 30A circuit. This causes battery shop personnel and equipment to remain in its current location for maintenance and storage. This facility was originally designed to support older equipment with limited space for upgrades. The new facility was designed for the integration of the KC-46 aircraft in addition to the C-5 and C-17.
Adding this increased workload to an already limited repair shop will cause unnecessary delays in the asset repair cycle.
Description: The contractor shall upgrade 10 electrical panel circuit breakers, wiring, and outlets to support a 30A equipment requirement.
Minimum Salient Characteristics:
*Pull out existing 12-gauge wire and pull in10-gauge wire through existing conduit.
*Replace existing 20A breakers with 30A circuit breakers *Replace 10 L6-20 receptacles with L6-30 receptacles *Rewire the existing contactors using 10-gauge wire *Test and verify all receptacles
Special Regulations:
Contractor must follow California and Travis AFB electrical regulations and codes Contractor must be able to obtain access to base Contractor must be able to obtain all required permits and inspections
Qualifications/Certifications:
Contractor shall have California electrical certification and provide documentation.
Delivery: Contractor shall install service within 8-10 weeks after contract award.
Point of Contact: After contract award TSgt Trygve Anderson (707) 424-2295/ Trygve.Anderson@us.af.mil MSgt Eric Theisinger (707) 424-2669 or (815)-488-1870/ Eric.Theisinger@us.af.mil
Service Address: 461 Hangar Ave, Hangar 46F Travis AFB CA, 94535
File details come from the government source that posted it. Updated .