This document is a Statement of Work for CAT Generator Maintenance services at the USDA's Southern Research Station in Stoneville, Mississippi. The contractor will perform 11 monthly inspections and services, as well as one annual inspection, service, and load bank test on the generator. The work includes walk-around inspections, battery maintenance, fluid level checks, and various other preventative maintenance tasks. The annual service will also include oil/filter changes, transfer switch inspection, and a 2-hour load bank test. The contract is for a one-year period with a potential option to extend. The government will not provide any equipment or materials, and the contractor is responsible for removing all waste. This is a small business set-aside opportunity, and interested small businesses in all socioeconomic categories are encouraged to respond to the sources sought notice with information to support the set-aside. No quotes, bids, or proposals are being accepted at this time.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
US Department of Agriculture (USDA)
Statement of Work
Stoneville/Cat Generator Maintenance April 30, 2024
Contents
| Project | 3 |
| General Information | 3 |
| 1.0 Scope of Work | 3 |
| 2.0 Background | 3 |
| Contractor Requirements | 3 |
| 3.0 Technical Requirements / Tasks | 3 |
| 4.0 Government Furnished | 3 |
| 5.0 Deliverables / Schedule | 3 |
| 6.0 Travel | 4 |
| 7.0 Contractor’s Key Personnel | 4 |
| 8.0 Security Requirements | 4 |
| 9.0 Data Rights | 4 |
| 10.0 Section 508 – Electronic and Information Technology Standards | 4 |
| Attachment | 4 |
Project Stoneville/CAT Generator Maintenance
General Information
1.0 Scope of Work
Under this contract the generator maintenance will be made available to unit RWU-SRS-4155 432 Stoneville Road, Stoneville, MS 38776. The contractor will perform 11 monthly inspections and services. Also, one annual inspection, service and load bank test to the generator. All waste materials shall become property of the contractor and be removed from Government premises.
2.0 Background.
SRS-4155 is required to have maintenance and service performed on the CAT generator monthly and one annual inspection and service. Maintenance on the item has been performed monthly and annually since purchase.
Contractor Requirements
3.0 Technical Requirements / Tasks
Monthly Work Items:
Contractor shall do a walk around visual inspection and will report any rust, damage to exterior, loose railings, etc., to the Forest Service Safety Representative, Chris Kirk. Contractor will clean and load test batteries. Battery replacement will require additional cost. Contractor will inspect fan belts, adjust, and grease fan drive, check all fluid levels, and top off if necessary. Contractor will inspect the following: operation of jacket water heater, control/engine wiring, and transfer switch. Contractor will check operation of battery charger and coolant quality. The contractor will also provide detailed inspection documentation once services are completed.
Annual Work Items:
Contractor will do a walk around visual inspection, check and record all fluid levels, clean, fill and load test batteries. Contractor will check operation of jacket water heater and battery charger. Contractor will inspect control panel wiring, inspect fanbelt, and adjust if necessary, and inspect transfer at switch. Contractor will start unit and verify proper frequency and voltage, as well as test operation of alarms and shutdowns. Contractor will pull engine oil sample for analysis, replace oil and oil filters, replace antifreeze as needed at an additional cost, replace fuel and air filters, lubricate fan drive and generator bearing, clean transfer switch, check wire connections and clean control panel. Contractor will submit a detailed evaluation report and connect load bank and test for 2 hours under normal load. The annual service and inspection will be done in May and the annual report will be submitted thereafter.
4.0 Government Furnished
Contractor will perform maintenance/services to the generator located at the Southern Research Station, 432 Stoneville Road, Stoneville, MS 38776.
5.0 Deliverables / Schedule
Key Deliverables
| Item No. |
| Deliverable |
| Objective |
| Due |
| 1 |
| Monthly inspection & |
Service
| Provide maintenance to generator |
| monthly |
| 2 |
| Annual inspection, service & load bank test |
| 1 time annual inspect, service and load bank test. |
| Annually until contract expires |
6.0 Travel
N/A
7.0 Contractor’s Key Personnel
Generator technician.
8.0 Security Requirements
N/A
9.0 Data Rights
N/A
10.0 Section 508 – Electronic and Information Technology Standards N/A