This is a Statement of Requirements for an Alaska 2.5-Ton Environmental Control Unit (ECU) with wheel kit, model AKS-BF166, detailing technical specifications for a US Coast Guard procurement.

The ECU operates on 120/208v or 127/230v power at 60Hz with three-phase, 4-wire plus ground configuration, consuming maximum 8.4kW for heating and 7.5kW for cooling. The unit measures 24.38" x 35" x 42" and weighs 420 lbs, featuring stackable aluminum construction up to 4 units high. Key performance specifications include operational temperature range of -50F to +132F, 1100 CFM air flow, and cooling capacity of 30,500 Btu/hr at 80F/50%RH. Notable features include R-407C refrigerant, forklift pockets, 27ft power cable with military-spec connector, 6kW heater, scroll compressor, and corrosion-resistant coatings. The unit includes a 5-year warranty, technical manual, and spare parts kit. Each ECU ships in an export-grade wood crate and can be maintained by personnel with minimal specialized training.

View the file

Other files

File Type Posted
RFQ 70Z08425QDL940005.pdf PDF
Sole Source_Redacted.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Statement of Requirements

Alaska 2.5-Ton ECU, 60Hz, with Wheel Kit

(AKS-BF166)

2023 Model Specifications

1. Power Requirements

• Voltage 120/208v, 127/230v

• Frequency 60 Hz

• Number of phases 3 (Three)

• Number of wires 4 plus ground

• Maximum power consumption, heating 8.4 kW

• Maximum power consumption, cooling 7.5 kW

2. Physical Dimensions

• Height 24.38”

• Width 35”

• Depth 42”

• Weight 420 lbs. (including all items below)

3. Stacking Capability

• Structural aluminum cabinet that will allow for stacking ECUs up to 4 high.

• ECUs can be locked to other ECUs when stacked.

• (24) ECUs can be loaded on (1) 463L aircraft pallet

• Total height of 96.75” when stacked 4 high (ECUs nest for stacking)

4. Performance Specifications

• Operational Temperature Range: -50F to +132F

• Static Pressure 1”

• Air Flow 1100 CFM

Return Air Condition ECU cooling

Capacity (60Hz)

Ambient Temperature

80 Fdb/50%RH 30,500 Btu/hr 125 F

75Fdb/50%RH 30,000 Btu/hr 125 F

Proprietary and Confidential 2

5. Features

• Aluminum cabinet, primed and powder coated (inside and outside)

• R-407C refrigerant

• (4) Sets of forklift pockets

• (1) Aluminum mesh return air and (1) fresh air filter

• (2) 12” diameter x 34” long insulated ducts (stored within the ECU cabinet)

• (1) 27ft power cable with a MIL-C-22992, Class L, 60-amp connector

• (1) 6kW low watt density resistance heater

• (1) Scroll compressor

• (1) Hot gas, by-pass valve

• (1) Micro channel condenser coil with corrosion protection coating.

• (1) Power relay that monitors correct phasing, loss of phase, low voltage, and high voltage.

• (1) Set of stainless steel and FluoroKote #1 coated hardware

• (4) Solid wheels with locking brakes.

• (1) Maintenance-free, low noise, direct drive backward inclined airfoil impeller for high efficiency operation.

• (1) Quick connect, field replaceable, plug-and-play wiring harness.

• (1) 9’ long flexible drain hose for draining the condensate away from the ECU

• (1) Piping and wiring diagram on the cabinet.

• Corrosion resistance coatings on the following components:

o Fan blade hubs o Blower hub o Motor shafts o Copper pipes

• (1) Export grade wood crate

6. Power Consumption Chart (maximum) @ 208V, 60 Hz, 3P, 4 wire & ground

Component FLA

Heating Mode, 8kW 26 amps

Cooling Mode 20.8 amps

7. Maintenance

• Maintenance can be performed by personnel with minimal specialized training using common tools. Routine maintenance, repair, and inspection tasks can be performed by qualified HVAC technicians.

8. Certifications

• Certified by a Nationally Recognized Testing Lab for UL1995 requirements and includes CSA C22.2 No. 236-05 certification

9. Warranty

• 5-year, non-prorated warranty.

10. Tech Manual

• Each ECU includes one commercial tech manual.

11. Spare parts

• Each ECU includes one spare parts kit consisting of the following items:

o One compressor/heater contactor o One blower/fan contactor o One blower/fan overload protection relay o One spring latch and striker assembly