About this file

The document is a Statement of Need for a firefighting skid unit to be delivered to the Department of Wildlife Resources in Charles City, Virginia. The unit must meet or exceed specific requirements for the water tank, water pump, and plumbing. The water tank must be a 250-gallon PolyTough tank or equivalent, with 1/2" thick walls and baffles per NFPA standards. The unit dimensions cannot exceed 77 inches long by 48 inches wide, and the dry weight cannot exceed 600 lbs. The water pump must be a Waterax Striker 2 or equivalent, with a minimum 13 hp, 4-cycle, electric start engine, and meet specific flow rate and pressure requirements. The unit must include various fittings, connections, and accessories such as a control panel, battery box, hose reel, and nozzle. The unit must be delivered by July 1, 2024.

The contract opportunity is for the firefighting skid unit, which will be procured by the Department of Wildlife Resources in Charles City County, Virginia. No additional details are provided regarding the pricing terms, set asides, incumbents, funding sources, or other salient information.

View the file

Other files

File Type Posted
Special Terms and Conditions.pdf PDF
General Terms and Conditions.pdf PDF
Submission checklist.docx DOCX document
DWR Agency Terms and Conditions.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Statement of Need Page 1 of 2

STATEMENT OF NEED

Firefighting skid unit

Contractor shall furnish a firefighting skid unit that meets or exceeds the following specifications. The unit is intended for firefighting applications and will be mounted in a truck. The unit shall include a water tank, a water pump, and connections as specified.

Water tank specifications:

Welded 250-gallon PolyTough tank or equivalent o 1/2" thick tank walls

Baffled to NFPA requirements Unit not to exceed size of 77 inches long and 48 inches wide Unit dry weight not to exceed 600 lbs

Water pump specifciations:

Waterax Striker 2 Pump or equivalent Minimum 13hp, 4-cycle, electric start Engine Water pump Maximum capacity:

o At least 220 PSI o At least 100 GPM

Flow rates:

o Minimum 95 GPM (367 lpm) @ 100 PSI (6.9 BAR) o Minimum 75 GPM (303 lpm) @ 150 PSI (10.3 BAR) o Minimum 55 GPM (202 lpm) @ 200 PSI (13.8 BAR)

Tank plumbing specifications:

(1) 2-1/2" NST Draft Suction

(1) 2-1/2" NST Direct Fill

(2) 1-1/2" NST Auxiliary Discharge

(1) 1" Tank fill / Recirc

(1) 1" gated pump-to-reel

Other specifications:

Waterax MCP Control Panel or equivalent

(1) Battery box (battery included)

(1) Hand guzzler/primer

(1) Hannay electric Hose Reel or equivalent o 3/4" x 100' red booster hose, top mount, rollers

(1) Viper nozzle or equivalent with pistol grip

(1) Forklift runners Welded stainless steel manifold

Statement of Need Page 2 of 2

Unit shall be delivered to:

Department of Wildlife Resources 3801 John Tyler Memorial Highway Charles City, VA 23030