Statement of Need - Convection Steamer.pdf

PDF 262 KB Posted

Attached to
Convection Steamer (Including Installation and Electrical Upgrade)
Solicitation number
FA442725Q1008
Issued by

About this file

This Statement of Need details requirements for the installation of a new convection steamer at David Grant Medical Center's Nutritional Medicine Flight. The document specifies the Vulcan Model C24ET10 or equal convection steamer with specific features including stainless steel construction, 2 compartments with 7-10 pan capacity, maximum dimensions of 5'8" H x 28" D x 3'3" W, and separate controls for each compartment.

The scope of work includes removal of the existing steamer, electrical upgrades from the current 208V 3Phase 40Amp configuration to accommodate the new unit's requirement of at least 100Amps with a 125Amp breaker, and complete installation. The electrical panel is 35-40 feet from the installation location with an existing pathway. Additional requirements include hands-on training for operation and cleaning, standard industry warranty, and the contractor must provide all necessary labor, materials, and specialized equipment. The steamer must be easily movable for routine maintenance, and the existing steamer must be turned in to MEMO prior to new installation.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Statement of Need

For

60th MDTS/Nutritional Medicine Flight

Double Stacked Floor Model Convection Steamer

Description: David Grant Medical Center (Nutritional Medicine Flight) requires the installation of a new convection steamer for food production and inpatient care services to include electrical upgrade and installation for the convection steamer to be electrically connected and operational. The steamer must be easily movable for routine maintenance.

Contractor shall provide/perform the following:

1. Energy Efficient Floor Model Convection Steamer Vulcan Model C24ET10 or Equal To.

1.1. Salient Characteristics/Features

1.1.1. Stainless steel interior, exterior, and cabinet base

1.1.2. 2 compartments/7-10 pan capacity with separate controls

1.1.3. No more than 5’8” H / 28” D / 3’3” W

1.1.4. Legs with flanged feet

1.1.5. Drain with temperature control

1.1.6. Split water connection

2. Removal of Existing Steamer

2.1. The contractor shall disconnect and remove existing steamer.

2.2. The contractor shall turn in the removed steamer to MEMO prior to installation of new

Steamer.

3. Installation

3.1. The contractor shall provide all labor, materials, and specialized equipment necessary to perform the installation of the Steamer.

4. Electrical Upgrade: The existing utilities are two circuits that are both 208Volts 3Phase 40Amp shut trip breakers. The Vulcan Model C24ET10 steamer needs at least 100Amps, pass a 125Amps breaker.

4.1. The contractor shall provide all labor, materials, and specialized equipment to upgrade the electrical connection required to install and connect the steamer.

4.2. Existing Electrical Information

4.2.1. The existing panel has the capacity to handle a 100 or 125 amp breaker

4.2.1.1. There is a space in the panel for additional breakers

4.2.2. The panel is roughly 35 – 40 feet from where the steamer will be installed

4.2.2.1. There is an existing pathway, floor and ceiling will not need to be torn up

4.2.3. The breaker needs to be shunt trip

4.2.4. The panel is within sight of the Steamer

5. Special Requirements

5.1. Training (hands-on training for proper operation and cleaning)

5.2. Standard industry warranty

6. Point of Contact after the contract is awarded:

Mr. Daniel R. Dettwiler at daniel.r.dettwiler.civ@health.mil or call 707- 423-3751 TSgt LaTara D. Wilkins at latara.d.wilkins.mil@health.mil or 707-423-3678

File details come from the government source that posted it. Updated .