Attachment 0003 - MIL-DTL-53126 (4A M60).pdf

PDF 101 KB Posted

Attached to
NSN: 6150-01-598-5289, Distribution System M60 Federal contract opportunity
Solicitation number
SPRBL1-20-Q-0012
Issued by
Defense Logistics Agency Land and Maritime

View the file

Other files for this federal contract opportunity

Other files attached to NSN: 6150-01-598-5289, Distribution System M60, newest first.
File Type Posted
A19-SPRBL1-20-Q-0012-0002 01-07-2020.pdf PDF
SPRBL120Q0012-0001.pdf PDF
SPRBL1-20-Q-0012.pdf PDF
Exhibit A - Technical Requirements Document.pdf PDF
Attachment 0002 - MIL-DTL-53126A.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMSC N/A FSC 6150

Distribution Statement A. Approved for public release, distribution is unlimited.

INCH-POUND

MIL-DTL-53126/4A

16 October 2012

SUPERSEDING

MIL-E-53126(ME)

20 April 1992

DETAIL SPECIFICATION SHEET

POWER DISTRIBUTION, ILLUMINATION SYSTEMS, ELECTRICAL

DISTRIBUTION SYSTEM, 60 AMPS/PHASE (A/P)

This specification is approved for use within US Army Research Development and Engineering Command, Communications and Electronics Research and Development Center, Product Realization Directorate, Department of the Army and is available for use by all Departments and Agencies of the Department of Defense.

The requirement for acquiring the product described herein shall consist of this specification sheet and MIL-DTL-53126.

1 SCOPE

1.1 Scope. This specification sheet covers the detail requirements for the Power Distribution Illumination Systems Electrical (PDISE), Type IV, model: M60, NSN: 6150-01-307-9445.

2 APPLICABLE DOCUMENTS

2.1 Drawings. The following Government drawings form a part of this specification sheet to the extent specified herein. Unless otherwise specified, the issues are those cited in the solicitation.

DRAWING# NOMENCLATURE DRAWING # NOMENCLATURE

CECOM & PM-MEP Drawings - Cage Code: 97403 and 30554

13229E6352 Distribution System, Electrical, Single Phase, 60 Amperes/Phase

13229E6340 Connector Assembly 40 AMP/PH Input Plug

(Copies of drawings required by contractors in connection with specific acquisition functions should be obtained from: PROJECT MANAGER-MOBILE ELECTRIC POWER, 5850 Delafield Road, Bldg 324 FT BELVOIR VA 22060-5809.)

Source: http://assist.dla.mil -- Downloaded: 2019-02-04T13:23Z Check the source to verify that this is the current version before use.

3 REQUIREMENTS

3.1 Requirements. The M60, Type IV, PDISE shall be a self-contained, free-standing, man portable unit. The system shall be capable of distributing 60 Amps of current to all its outputs simultaneously, as specified herein.

Type III – 60 ampere distribution system

3.2 Design. The M60 PDISE shall be IAW TA13229E6352 and as specified herein.

3.2.1 Dimensions. The M60 PDISE shall not be greater than the following dimensions:

Length (Inches) Width (Inches) Height (Inches)

24.00 21.00 18.00

3.2.2 Weight. The M60 PDISE shall weigh no more than 45 pounds.

3.2.3 M60 PDISE inputs. The M60 PDISE shall have a single phase input capable of handling 60 A/P.

3.2.3.1 Input circuit interrupter. The input circuit for the M60 PDISE shall be protected from overload by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit.

3.2.3.1.1 Input connector. The M60 PDISE shall have a 60 ampere, single phase, male, input receptacle IAW 13229E6340.

3.2.4 M60 PDISE outputs The M60 PDISE shall have the following output circuits and connectors:

Quantity Output Rating Ouput Connector P/N*

1 60 Amp, 1 phase M90556C32405P

6 20 Amp, 1 phase M3406D16-10S

*Note: See 3.3.16.1 in MIL-DTL-53126.

3.2.4.1 Output circuit interrupters. Each output circuit shall be protected by a properly sized circuit breaker interrupter. The circuit breaker shall act as a switch to activate/deactivate the circuit.

3.2.5 Type IV accessories. The unit shall be provided with the following accessories:

Quantity Description Reference*

1 Input interface cable assembly, rated at 60 amperes 3.3.18.1*

1 60 A/P cable assembly 3.3.18.5*

3 20 A/P cable assemblies (25 ± 0.25 feet long) 3.3.18.6*

3 20 A/P cable assemblies (50 ± 0.25 feet long) 3.3.18.6*

2 Transition cable assemblies 3.3.18.8*

6 Cinching Strap 3.3.19.1*

2 Double strap assemblies 3.3.19.3*

1 Receptacle assembly 3.3.17*

1 In-Line GFCI 3.3.18.10*

1 Container 2.1

*Note: See requirement paragraph referenced MIL-DTL-53126.

CARRYING

STRAPS

CINCHING

STRAPS

CARRYING

STRAPS

MARKING TAG

(WHITE)

JOINING

STRAP

1.50 STK

10.00

27.75

4.75 3x 1.50

JOINING

STRAP

BB

LINE NEUT

BB BB

GND

G2

A

N

G1

J2 OUTPUT

FEED THRU

J2G6GND

J2A4LINE

J2N4NEUT

J2G6GND

60 A 1 PHASE

INPUT J1

J1G6GND

J1N4NEUT

J1A4CB1

G1

N

A

G2 J1G6GND

CB1

CB14LINE

20 A 1 PHASE

OUTPUT J3

J3C12GND

J3B12NEUT

J3A12CB3

C

B

A

CB3

CB312LINE

20 A 1 PHASE

OUTPUT J5

J5C12GND

J5B12NEUT

J5A12CB5

C

B

A

CB5

CB512LINE

CB8

J8

C

B

A

OUTPUT

20 A 1 PHASE

J8C12GND

J8B12NEUT

J8A12CB8 CB812LINE

CB6

A

B

C

J6 OUTPUT

20 A 1 PHASE

J6A12CB6

J6B12NEUT

J6C12GND

CB612LINE

CB4

A

B

C

J4 OUTPUT

20 A 1 PHASE

J4A12CB4

J4B12NEUT

J4C12GND

CB412LINE

DS1NBB DS1CB1

DS1

LIGHT BRACKET

CIRCUIT BREAKER

MOUNTING PANEL

TOP COVER

CHASSIS GROUND

J7 OUTPUT

20 A 1 PHASE CB7

CB712LINE

C

B

A

J5C12GND

J7B12NEUT

J7A12CB7

3.3 This specification sheet had no superseding “base”. The original publication of this specification was a performance specification that was used in-house by CR4. Since this specification is now a detailed military specification, this specification sheet is deemed necessary to capture the unique characteristics desired in the end item.

3.4 Changes from previous issues: Marginal notations are not used in this revision to identify changes with respect to the previous issue because this detail specification sheet although a part of the base document, was not published because it was a document with limited circulation and coordination that was used essentially by CR4.

Concluding Material

Custodian:

Preparing Activity:

Army - CR4 Army - CR4 (Project 6150-2012-013)

Review Activities:

DLA – GS

Note: The activities listed above were interested in this document as of the date of this document.

Since organization and responsibilities can change, you should verify the currency of the information above using the ASSIST Online database at https://assist.dla.mil.

1 SCOPE
1.1 Scope. This specification sheet covers the detail requirements for the Power Distribution Illumination Systems Electrical (PDISE), Type IV, model: M60, NSN: 6150-01-307-9445.
2 APPLICABLE DOCUMENTS
2.1 Drawings. The following Government drawings form a part of this specification sheet to the extent specified herein. Unless otherwise specified, the issues are those cited in the solicitation.
NOMENCLATURE
3 REQUIREMENTS
3.1 Requirements. The M60, Type IV, PDISE shall be a self-contained, free-standing, man portable unit. The system shall be capable of distributing 60 Amps of current to all its outputs simultaneously, as specified herein.
3.2 Design. The M60 PDISE shall be IAW TA13229E6352 and as specified herein.
3.2.1 Dimensions. The M60 PDISE shall not be greater than the following dimensions:
3.2.2 Weight. The M60 PDISE shall weigh no more than 45 pounds.
3.2.3 M60 PDISE inputs. The M60 PDISE shall have a single phase input capable of handling 60 A/P.
3.2.3.1 Input circuit interrupter. The input circuit for the M60 PDISE shall be protected from overload by a properly sized circuit breaker. The circuit breaker shall act as a switch to activate/deactivate the circuit.
3.2.3.1.1 Input connector. The M60 PDISE shall have a 60 ampere, single phase, male, input receptacle IAW 13229E6340.
3.2.4 M60 PDISE outputs The M60 PDISE shall have the following output circuits and connectors:
*Note: See 3.3.16.1 in MIL-DTL-53126.
3.2.4.1 Output circuit interrupters. Each output circuit shall be protected by a properly sized circuit breaker interrupter. The circuit breaker shall act as a switch to activate/deactivate the circuit.
3.2.5 Type IV accessories. The unit shall be provided with the following accessories:
*Note: See requirement paragraph referenced MIL-DTL-53126.

3.3 This specification sheet had no superseding “base”. The original publication of this specification was a performance specification that was used in-house by CR4. Since this specification is now a detailed military specification, this specificatio...

Reference*
Description
Quantity
3.3.18.1*
Input interface cable assembly, rated at 60 amperes
1
3.3.18.5*
60 A/P cable assembly
1
3.3.18.6*
20 A/P cable assemblies (25 ± 0.25 feet long)
3
3.3.18.6*
20 A/P cable assemblies (50 ± 0.25 feet long)
3
3.3.18.8*
Transition cable assemblies
2
3.3.19.1*
Cinching Strap
6
3.3.19.3*
Double strap assemblies
2
3.3.17*
Receptacle assembly
1
3.3.18.10*
In-Line GFCI
1
2.1
Container
1

File details come from the government source that posted it. Updated .