Specs qty 9.pdf

PDF 213 KB Posted

Attached to
FCC HAZELTON - WATER HEATING SYSTEM PRODUCT ONLY
Solicitation number
15B12124Q00000016
Issued by

About this file

This document appears to be a set of specifications for an indirect plate and frame water heater and associated pumps required by the Federal Correctional Complex (FCC) in Hazelton, Pennsylvania. The solicitation is for a quantity of 9 indirect plate and frame water heaters and 9 pumps to accompany them. Key requirements include maximum unit dimensions, ASME compliance, temperature control capabilities, warranty, and pump specifications. Vendors must have active SAM.gov registration and provide their Unique Entity Identifier (UEI). Quotes must be valid for at least 30 days after the bid close date of November 27, 2023 at 2 PM EDT. Quotes and bids are to be submitted to specific email addresses at FCC Hazelton. Additional details are provided on the domestic water heating system requirements, including flow rates, temperatures, and usage. This appears to be a product-only solicitation, not a full performance-based contract.

View the file

Other files

File Type Posted
HW tank Specs.pdf PDF
Pump Specs.pdf PDF
15B12124Q00000016.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FCC Hazelton requires a quan�ty of 9 each indirect plate and frame water heater plus9 each pumps to accompany the water heaters. Vendors are required to have ac�ve SAM.Gov registra�on and to provide their UEI. This requirement is for product ONLY. All quotes and bids are required to be submited to Kelly Brown, Supervisory Contract Specialist with FCC Hazelton at k1roberts@bop.gov (Note: that is a number one a�er the K) AND HAX-ProcurementProp- S@bop.gov. Quotes must be valid for at least 30 days a�er close of bids on November 27, 2023 at 2 PM EDT. Specific product requirements below and example spec sheets atached.

Indirect Plate And Frame Water Heater: (4)

Dimensions cannot Exceed: 63” Height Max; 22” Width max; 61” Base Length – MUST FIT THROUGH STANDARD 36” door. Product should not exceed 1200 lbs – Lite Weight Preferred

FEATURES:

ASME DOUBLE WALL HEAT EXCHANGER

• 316L Stainless Steel

• 150 psi Working Pressure

DIGITAL DISPLAY

• DHW Set Point Range 90°F to 180°F

ADVANCED TEMPERATURE CONTROL

MODULATING CONTROL VALVE

SCALE REDUCING PUMP

AUTOMATIC AIR VENT

ASME TEMPERATURE & PRESSURE RELIEF

VALVE

• 210°F and 150 psi

ADJUSTABLE HIGH LIMIT

WYE STRAINERS - DOMESTIC PIPING AND

BOILER PIPING

ISOLATION VALVES - DOMESTIC PIPING

AND BOILER PIPING

MODBUS COMMUNICATION

WARRANTY

• 5-Year limited warranty/1-Year limited parts

• Warranty for product only without services requirement

Pump: (4) Specifica�ons must meet all below requirements for pump withsystem control and monitoring key Conditions of Service Pump Data Motor Data Flow: 130 US GPM Head: 32 ft Efficiency: 68.6 % Liquid: Water Temperature: 60 °C NPSH required: ft

Maximum operating pressure: 12 bar Liquid temperature range: -10 .. 110 °C Maximum ambient temperature: 40 °C Flange standard: GF Pipe connection: GF65 Product number: On request

P1 max: 29 .. 1385 W Mains frequency: 60 Hz Enclosure class: X4D Insulation class: F

SUGGESTED SPECIFICATION

The Indirect Plate and Frame shall be constructed of a 316 stainless steel plate with EPDM gaskets. Maximum unit dimensions shall be: Length ___61_inches, Width ___22___inches and Height __63______ inches.

The Indirect Plate and Frame shall be a double wall. The plate and frame shall be constructed in accordance with the ASME Boiler and Pressure Vessel Code requirements, stamped and registered with the Na�onal Board of Boiler and Pressure Vessel Inspectors .

The Indirect Plate and Frame shall have a 150 psi working pressure and be supplied with an ASME temperature and pressure relief valve. Standard equipment shall include Wye Strainers, Isola�on Valves, Automa�c Air Vent, Scale Reduc�on Pump, Adjustable High Limit and drain valve The temperature control shall provide + or – 4 degrees Fahrenheit accuracy with up to a 50% change in load. Setpoint range between 90 and 180 F. Modbus communica�on shall be standard equipment. The modula�ng valve shall have a 1000 to 1 turndown. The Indirect Plate and Frame shall be suitable for use with polypropylene glycol, up to 50% concentra�on. The de-rate associated with the glycol will vary per glycol manufacturer.

mailto:k1roberts@bop.gov mailto:HAX-ProcurementProp-S@bop.gov

Specific Gravity: 0.985 ADDITIONAL INFORMATION: Domes�c inlet temp Set point. DHW set point 90 to 180 degrees. GPH for all units together or for each if separated. GPH is for each unit. Each system will supply at minimum hot water to 64-cells, 10-showers, 2-mop closet and 1-staff restroom. Boiler water entering temp 160-180 degrees. Boiler water Leaving temp 120-140 degrees BTU I am looking for specifics on this. -These units are in use 24/7-365 if that helps.

For singled cell showers, 10 to be used at a �me with a maximum of up to 128.

File details come from the government source that posted it. Updated .