Specs - AXQD232622 - Replace Fire Alarm Panel B34.pdf
PDF 243 KB Posted
- Attached to
- Replace Fire Alarm Panel, B34
- Solicitation number
- W50S8124R0001
About this file
This document is a Request for Proposals (RFP) for a firm fixed-price contract to replace the fire alarm panel at Building 34 at Barnes Air National Guard Base in Westfield, Massachusetts. The solicitation is a 100% small business set-aside, with a magnitude of construction between $25,000 and $100,000.
The Statement of Work requires the contractor to provide a new, complete fire alarm system, including wiring, raceways, devices, and other components to replace the existing system. Specific technical requirements are provided for the fire alarm control unit, notification appliances, addressable devices, power supply, and other system elements. The contractor must also provide training, maintenance manuals, and spare parts. Proposals are due on a date specified in the solicitation, and the contract award will be based on an evaluation of technical capability, past performance, and price using simplified acquisition procedures.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| W50S8124R0001.pdf | ||
| Wage Determination.txt | TXT text file | |
| Brand Name Justification_redacted.pdf | ||
| SOW_AXQD232622 - Replace Fire Alarm Panel B34.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
283170 - 1
AXQD232622 – Replace Fire Alarm Panel B34 Barnes ANG Base Westfield, MA
SECTION 283170 - FIRE ALARM SYSTEM
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes the following:
1. This work includes completion of design and providing a new, complete, fire alarm system as described herein and on the contract drawings. Include in the system wiring, raceways, pull boxes, terminal cabinets, outlet and mounting boxes, control equipment, alarm, and supervisory signal initiating devices, alarm notification appliances, supervising station fire alarm system transmitter, and other accessories and miscellaneous items required for a complete operating system even though each item is not specifically mentioned or described. Provide system complete and ready for operation. System shall comply with the requirements of IBC, ANG ETL 15-01-03, UFC 3-600-01, UFC 4-021- 01, NFPA 72, and referenced criteria.
1.2 SUBMITTALS
A. Submittals shall bear the review stamp and signature of the Fire Protection Specialist before submitting for review.
B. Shop Drawings: Annotated catalog data, in table format on the drawings, showing manufacturer's name, model, voltage, and catalog numbers for equipment and components.
Submitted shop drawings shall not be smaller than ISO A1. Prepared by NICET III Fire Alarm Technician, or higher.
1. Wiring Diagrams: Point-to-point wiring diagrams showing the points of connection and terminals used for electrical field connections in the system, including interconnections between the equipment or systems that are supervised or controlled by the system.
Diagrams shall show connections from field devices to the FACU and remote fire alarm control units, initiating circuits, switches, relays and terminals. Complete riser diagrams indicating the wiring sequence of devices and their connections to the control equipment.
Each point on the riser diagram shall be identified by type and location with device number corresponding to the point list. Include a color code schedule for the wiring.
Include floor plans showing the locations of devices and equipment.
2. System Layout: Plan view drawing showing device locations, terminal cabinet locations, junction boxes, other related equipment, conduit routing, wire counts, circuit identification in each conduit, and circuit layouts for all floors. Drawings shall comply with the requirements of NFPA 170, Fire Safety Symbols.
3. System Operation: A complete list of device addresses and corresponding messages.
4. Notification Appliances: Data on each circuit to indicate that there is at least 25 percent spare capacity for notification appliances, and 25 percent spare capacity for initiating devices. Annotate data for each circuit on the drawings.
283170 - 2
5. Amplifiers: Data to indicate that the amplifiers have sufficient capacity to simultaneously drive all notification speakers at the maximum rating plus 50 percent spare capacity.
Annotate data for each circuit on the drawings.
C. Product Data
1. Technical Data and Computer Software
2. Fire Alarm Control Unit and Mass Notification Control Unit (Combined Panel)
3. LCD, LED Display Unit
4. Terminal Cabinets
5. Manual Stations
6. Transmitters
7. Batteries
8. Battery Chargers
9. Smoke Sensors
10. Notification Appliances
11. Addressable Interface Devices
12. Amplifiers
13. Tone Generators
14. Digitized Voice Generators
15. Radio Transmitter and interface panel
D. Design Data
1. System Operation: A complete description of the system operation in matrix format on the drawings.
2. Battery Power: Battery calculations as required in paragraph Battery Power Calculations.
3. Wire Sizing/Voltage Drop Calculations.
E. Test Reports
1. Field Quality Control
2. Testing Procedures (Performance and Maintenance)
3. Smoke Sensor Testing Procedures
4. Performance Test Report
5. Acceptance Test Report
F. Certificates
1. Fire Protection Specialist
2. Installer
3. Formal Inspection and Tests
4. Final Testing
G. Manufacturer's Field Reports
283170 - 3
1. Fire Alarm/Mass Notification System: A unique identifier for each device, including the control panel and initiating and indicating devices, with an indication of test results, and signature of the factory-trained technician of the control panel manufacturer and equipment installer. With reports on preliminary tests, include printer information.
Include the NFPA 72 Record of Completion and NFPA 72 Inspection and Testing Form, with the appropriate test reports.
H. Operation and Maintenance Data
1. Operation and Maintenance (O&M) Instructions: One copy of the Operation and
Maintenance Instructions, indexed and in booklet form. The Operation and Maintenance Instructions shall be a single volume or in separate volumes, and may be submitted as a Technical Data Package. Manuals shall be approved prior to training. Original and backup copies of all software delivered for this project, on each type of CD/DVD media utilized.
2. Instruction to Government Employees: The installers training history for the employees involved in this contract.
I. Closeout Submittals
1. As-built Drawings: Furnish one electronic copy of as-built drawings and schematics. The drawings shall be prepared on uniform sized sheets not less than 30 by 42 inches with 8 by 4 inch title block. The drawings shall include complete wiring diagrams showing connections between devices and equipment, both factory and field wired. Include a riser diagram and drawings showing the as-built location of devices and equipment. The drawings shall show the system as installed, including deviations from both the project drawings and the approved shop drawings. These drawings shall be submitted within two weeks after the final acceptance test of the system.
1.3 QUALITY ASSURANCE
A. Equipment and devices shall be compatible and shall not impair reliability or operational functions of existing supervising station fire alarm/notification system. The supervising equipment is existing and consists of the following brands and models: Monaco Enterprises.
1. In NFPA publications referred to herein, consider advisory provisions to be mandatory, as though the word "shall" had been substituted for "should" wherever it appears;
interpret reference to "authority having jurisdiction" to mean the Fire Protection Engineer or Contracting Officer's Designated Representative (COR).
2. The recommended practices stated in the manufacturers literature or documentation shall be considered as mandatory requirements.
3. Devices and equipment for fire alarm service shall be listed by UL Fire Prot Dir or approved by FM App Guide.
B. Qualifications
1. Perform work specified in this section under the supervision of and certified by the Fire Protection Specialist. The Fire Protection Specialist shall be in direct employment of or under contract with the prime or subcontractor. The Fire Protection Specialist shall be a
283170 - 4 qualified and experienced FPE as defined by ANG ETL 15-01-03 and UFC 3-600-01.
The Fire Protection Specialist shall be responsible for performing and overseeing all engineering aspects of the fire alarm and mass notification system construction, including but not limited to, calculations, layout, shop drawings, equipment selection and inspections. The Fire Protection Specialist shall be responsible for the testing plan and final commissioning and testing of the system and shall certify in writing that the fire alarm system has been constructed and operates as intended in the design plans and specifications.
2. Fire Protection Specialist
A qualified FPE is defined as an individual meeting one of the following conditions:
a. Possessing a Bachelor of Science or Master of Science degree in fire protection engineering from an accredited university, plus a minimum of 5 years' work experience in fire protection engineering.
b. Obtained Professional Engineer (PE) registration by examination, National Council of Examiners for Engineering and Surveyors (NCEES) fire protection engineering examination.
c. Qualification as a GS 804-series FPE.
d. Possesses PE registration in a related discipline with a minimum of 5 years' work experience in fire protection engineering.
3. Supervisor
a. The installing Contractor shall provide the following: NICET Fire Alarm Technicians to perform the installation of the system. A NICET Level III or IV Fire Alarm Technician shall supervise the installation of the fire alarm system.
The Fire Alarm technicians supervising the installation of equipment shall be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the drawings.
4. Technician
a. The installing Contractor shall provide the following: Fire Alarm Technicians with a minimum of four years of experience utilized to assist in the installation and terminate fire alarm devices, cabinets, and panels. The Fire Alarm technicians installing the equipment shall be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the drawings.
5. Installer
a. The installing Contractor shall provide the following: Fire Alarm installer with a minimum of two years of experience utilized to assist in the installation of fire alarm devices, cabinets, and panels. A licensed electrician shall be allowed to install wire or cable and to install conduit for the fire alarm system. The Fire Alarm installer shall be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the drawings.
6. Test Personnel
283170 - 5
a. The installing Contractor shall provide the following: Fire Alarm Technicians with a minimum of eight years of experience utilized to test and certify the installation of the fire alarm devices, cabinets, and panels. The Fire Alarm technicians testing the equipment shall be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the drawings.
7. Manufacturer's Representative
a. The fire alarm equipment manufacturer's representative shall be present for the connection of wiring to the control panel. The Manufacturer's Representative shall be an employee of the manufacturer with necessary technical training on the system being installed.
8. Manufacturer
a. Components shall be of current design and shall be in regular and recurrent production at the time of installation. Provide design, materials, and devices for a protected premises fire alarm system, complete, conforming to NFPA 72, except as otherwise or additionally specified herein.
C. Regulatory Requirements
1. Requirements for Fire Protection Service
a. Equipment and material shall have been tested by UL and listed in UL Fire Prot
Dir or approved by FM and listed in FM APP GUIDE. Where the terms "listed" or "approved" appear in this specification, they shall mean listed in UL Fire Prot Dir or FM APP GUIDE. The omission of these terms under the description of any item of equipment described shall not be construed as waiving this requirement. All listings or approval by testing laboratories shall be from an existing ANSI or UL published standard. The recommended practices stated in the manufacturer’s literature or documentation must be considered as mandatory requirements.
2. Testing Services or Laboratories
a. Fire alarm and fire detection equipment shall be constructed in accordance with UL Fire Prot Dir, UL Electrical Construction, or FM APP GUIDE.
1.4 DELIVERY, STORAGE, AND HANDLING
A. Protect equipment delivered and placed in storage from the weather, humidity, and temperature variation, dirt and dust, and other contaminants.
1.5 OPERATION AND MAINTENANCE (O&M) INSTRUCTIONS
A. The Interior Fire Alarm System Operation and Maintenance Instructions shall include:
1. Operating manual outlining step-by-step procedures required for system startup, operation, and shutdown. The manual shall include the manufacturer's name, model
283170 - 6 number, service manual, parts list, and complete description of equipment and their basic operating features.
2. Maintenance manual listing routine maintenance procedures, possible breakdowns and repairs, and troubleshooting guide. The manuals shall include conduit layout, equipment layout and simplified wiring, point list and control diagrams of the system as installed.
3. The manuals shall include complete procedures for system revision and expansion, detailing both equipment and software requirements.
4. Software delivered for this project shall be provided, on each type of CD/DVD media utilized.
5. Printouts of configuration settings for all devices.
6. Routine maintenance checklist. The routine maintenance checklist shall be arranged in a columnar format. The first column shall list all installed devices, the second column shall state the maintenance activity or state no maintenance required, the third column shall state the frequency of the maintenance activity, and the fourth column for additional comments or reference.
1.6 EXTRA MATERIALS
A. Repair Service/Replacement Parts
1. Repair services and replacement parts for the system shall be available for a period of 10 years after the date of final acceptance of this work by the Contracting Officer. During guarantee period, the service technician shall be on-site within 72 hours after notification.
All repairs shall be completed within 24 hours of arrival on-site.
B. Interchangeable Parts
1. Spare parts furnished shall be directly interchangeable with the corresponding components of the installed system. Spare parts shall be suitably packaged and identified by nameplate, tagging, or stamping. Spare parts shall be delivered to the Contracting Officer at the time of the final acceptance testing.
C. Spare Parts
1. Furnish the following spare parts and accessories:
a. Two fuses for each fused circuit.
b. Two of each type of notification appliance in the system (e.g. speaker, FA strobe, MNS strobe, etc.)
c. Two of each type of initiating device included in the system (e.g. smoke detector, thermal detector, manual station, etc.)
D. Special Tools
1. Software, connecting cables and proprietary equipment, necessary for the maintenance, testing, and reprogramming of the equipment shall be furnished to the Contracting Officer.
E. Software Updates
283170 - 7
1. Furnish software updates for Fire Alarm Control Unit and Monaco Transceiver for a period of not less than 2 years after installation.
PART 2 - PRODUCTS
2.1 MATERIALS AND EQUIPMENT
A. Standard Products
1. Provide materials, equipment, and devices that have been tested by a nationally recognized testing laboratory, such as UL or FM, and listed or approved for fire protection service when so required by NFPA 72 or this specification. Select material from one manufacturer, where possible, and not a combination of manufacturers, for any particular classification of materials. Material and equipment shall be the standard products of a manufacturer regularly engaged in the manufacture of the products for at least two years prior to bid opening.
B. Nameplates
1. Major components of equipment shall have the manufacturer's name, address, type or style, model or serial number, catalog number, date of installation, installing Contractor's name and address, and the contract number provided on a new engraved plate permanently affixed to the item or equipment. Major components include, but are not limited to, the following:
a. FACU
b. Automatic transmitter/transceiver
c. Terminal cabinet
2.2 GENERAL PRODUCT REQUIREMENT
A. All fire alarm and mass notification equipment shall be listed for use under the applicable reference standards. Interfacing of Listed UL 864 or similar approved industry listing with Mass Notification Panels listed to UL 2017 or equal shall be done in a laboratory listed configuration, if the software programming features cannot provide a listed interface control. All fire alarm and mass notification equipment shall be compatible with the fire alarm control unit (FACU). If a field modification is needed, such as adding equipment like relays, the manufacturer of the panels being same or different brand from manufacturer shall provide the installing contractor for review and confirmation by the installing contractor. The installing contractor shall, as part of the submittal documents, provide this information.
B. The FACU shall be field expandable and field programmable at the panel level without the use of proprietary software, keys, hardware, or other devices. Any software, password, or other element used to program any component of the fire alarm system shall be the property of the Government, along with the installed program.
283170 - 8
2.3 SYSTEM OPERATION
A. The Addressable Interior Fire Alarm shall be a complete, supervised, noncoded, analog/addressable fire alarm system conforming to NFPA 72, and UL 864. Systems meeting only UL 2017 are not acceptable. The system shall be activated into the alarm mode by actuation of any alarm initiating device. The system shall remain in the alarm mode until the initiating device is reset and the fire alarm control panel is reset and restored to normal. The system may be placed in the alert mode by local microphones or remotely from authorized locations/users.
B. Alarm Initiating Devices
1. Connect alarm initiating devices to Class B signal line circuits (SLC) installed in accordance with NFPA 72.
a. Alarm notification appliances shall be connected to Class B notification appliance circuits (NAC) Voice Notification System installed in accordance with NFPA 72.
b. The system shall operate in the alarm mode upon actuation of any alarm initiating device. The system shall remain in the alarm mode until initiating device(s) are reset and the fire alarm control panel is manually reset and restored to normal.
Audible, and visual appliances and systems shall comply with NFPA 72. Fire alarm system components requiring power, except for e control panel power supply, shall operate on 24 Volts dc.
C. Fire Alarm Control Unit Control Unit (FACU) Functions and Operating Features
1. The system shall provide the following functions and operating features:
a. The fire alarm control unit shall provide power, annunciation, supervision, and control for the system. Addressable systems shall be microcomputer (microprocessor or microcontroller) based with a minimum word size of eight bits with sufficient memory to perform as specified. Provide electrical supervision of the primary power (AC) supply, presence of the battery, battery voltage, and placement of system modules within the control panel.
b. Provide an audible and visual trouble signal to activate upon a single break or open condition, or ground fault. The trouble signal shall also operate upon loss of primary power (AC) supply, absence of a battery supply, low battery voltage, or removal of alarm or supervisory panel modules. After the system returns to normal operating conditions, the trouble signal shall again sound until the trouble is acknowledged. A smoke detector in the process of being verified for the actual presence of smoke must not initiate a trouble condition.
c. Provide a trouble alarm silence feature that shall silence the audible trouble signal, without affecting the visual indicator.
d. Provide an alarm silencing switch at the FACU that must silence the audible and visual notification appliances. Subsequent activation of initiating devices must cause the notification appliances to re-activate.
e. Provide program capability via switches in a locked portion of the control unit to bypass the automatic notification appliance circuits, fire reporting system air handler shutdown operation features. Operation of this programming shall indicate this action on the control unit display.
f. Alarm, supervisory, and/or trouble signals shall be automatically transmitted to the
283170 - 9 supervising station.
g. Alarm functions shall override trouble or supervisory functions. Supervisory functions shall override trouble functions.
h. The system shall be capable of being programmed from the panels keyboard.
Programmed information shall be stored in non-volatile memory.
i. The system shall be capable of operating, supervising, and/or monitoring both addressable and non-addressable alarm and supervisory devices.
j. There shall be no limit, other than maximum system capacity, as to the number of addressable devices, that may be in alarm simultaneously.
k. Where the fire alarm system is responsible for initiating an action in another emergency control device or system, such as an HVAC system, the addressable fire alarm relay shall be in the vicinity of the emergency control device.
l. An alarm signal shall automatically initiate the following functions: Refer to the Fire Alarm & Mass Notification System Input/Output Functional Matrix on the contract documents.
m. A supervisory signal shall automatically initiate the following functions:
1) Visual indication of the device operated on the FACU, [Video Display unit
(VDU),] [and on the [graphic ][remote ]annunciator].[ Indication on the graphic annunciator must be by floor, zone or circuit, and type of device.]
2) Record the event on the system printer
3) Transmission of a supervisory signal to the fire department
4) Operation of a duct smoke detector must shut down the appropriate air handler in accordance with NFPA 90A in addition to other requirements of this paragraph and as allowed by NFPA 72.
5) Recording of the event electronically in the history log of the FACU.
n. A trouble condition shall automatically initiate the following functions:
1) Visual indication of the device operated on the FACU, [VideoDisplay unit (VDU),] [and on the [graphic ][remote ]annunciator].[ Indication on the graphic annunciator must be by floor, zone or circuit, and type of device.]
2) Record the event on the system printer
3) Transmission of a trouble signal to the fire department
4) Recording of the event electronically in the history log of the FACU.
o. The maximum permissible elapsed time between the actuation of an initiating device and its indication at the FACU shall be 10 seconds.
p. The maximum elapsed time between the occurrence of the trouble condition and its indication at the FACU shall not exceed 200 seconds.
q. System control equipment must be programmed to provide a 60-minute to 180-minute delay in transmission of trouble signals resulting from primary power failure.
2.4 OVERVOLTAGE AND SURGE PROTECTION
A. Signaling Line, Initiating Device, and Notification Appliance Circuit Surge Protection
1. For systems having circuits located outdoors, communications equipment shall be protected against surges induced on any circuit and shall comply with the applicable requirements of IEEE C62.41.1 and IEEE C62.41.2. Cables and conductors, that serve as communications links, shall have surge protection circuits installed at each end that meet the following waveform(s):
283170 - 10
a. A 10 microsecond by 1000 microsecond waveform with a peak voltage of 1500 volts and a peak current of 60 amperes.
b. An 8 microsecond by 20 microsecond waveform with a peak voltage of 1000 volts and a peak current of 500 amperes. Protection shall be provided at the equipment.
Additional triple electrode gas surge protectors, rated for the application, shall be installed on each wireline circuit within 3 feet of the building cable entrance. Fuses shall not be used for surge protection.
B. Provide surge protection on all 120 VAC circuits to control panels, subpanels, transmitters, amplifiers, and booster panels. Provide both UL 1449 and UL 1283 listing, in an adjacent hinged terminal box.
C. Sensor Wiring Surge Protection
1. Digital and analog inputs and outputs shall be protected against surges induced by sensor wiring installed outdoors and as shown. The inputs and outputs shall be tested with the following waveforms:
a. A 10 by 1000 microsecond waveform with a peak voltage of 1500 volts and a peak current of 60 amperes.
b. An 8 by 20 microsecond waveform with a peak voltage of 1000 volts and a peak current of 500 amperes. Fuses shall not be used for surge protection.
2.5 ADDRESSABLE INTERFACE DEVICES
A. The initiating device being monitored shall be configured as a Class B initiating device circuits.
The system shall be capable of defining any module as an alarm module and report alarm trouble, loss of polling, or as a supervisory module, reporting supervisory short, and supervisory open or loss of polling., relays for output function actuation, etc. The module shall be UL or FM listed as compatible with the control panel. The monitor module shall provide address setting means compatible with the control panel's SLC supervision and store an internal identifying code. Monitor module shall contain an integral LED that flashes each time the monitor module is polled. Pull stations with a monitor module in a common backbox are not required to have an LED.
2.6 ADDRESSABLE CONTROL MODULE
A. The control module shall be capable of operating as a relay (dry contact form C) for interfacing the control panel with other systems. The module shall be UL or FM listed as compatible with the control panel. The indicating device or the external load being controlled shall be configured as a Class B notification appliance circuits. The system shall be capable of supervising, audible, visual and dry contact circuits. The control module shall have both an input and output address.
The supervision shall detect a short on the supervised circuit and shall prevent power from being applied to the circuit. The control module shall provide address setting means compatible with the control panel's SLC supervision and store an internal identifying code. The control module shall contain an integral LED that flashes each time the control module is polled.
Control Modules shall be located in environmental areas that reflect the conditions to which they were listed.
283170 - 11
2.7 SMOKE SENSORS
A. Provide, non-proprietary, generic type addressable photoelectric smoke sensors as follows:
1. Provide analog/addressable photoelectric smoke sensors utilizing the photoelectric light scattering principle for operation in accordance with UL 268. Smoke sensors shall be listed for use with the fire alarm control panel.
2. Provide self-restoring type sensors that do not require any readjustment after actuation at the FACU to restore them to normal operation. Sensors shall be UL listed as smoke automatic fire sensors. Sensors shall have an adjustable alarm verification feature, initially set at 20 seconds.
3. Components shall be rust and corrosion resistant. Vibration shall have no effect on the sensor's operation. Protect the detection chamber with a fine mesh metallic screen that prevents the entrance of insects or airborne materials. The screen shall not inhibit the movement of smoke particles into the chamber.
4. Provide twist lock bases for the sensors. The sensors shall maintain contact with their bases without the use of springs. Provide companion mounting base with screw terminals for each conductor. Terminate field wiring on the screw terminals. The sensor shall have a visual indicator to show actuation.
5. The sensor address shall identify the particular unit, its location within the system, and its sensitivity setting. Sensors shall be of the low voltage type rated for use on a 24 VDC system.
6. An operator at the control panel, having a proper access level, shall have the capability to manually access the following information for each initiating device.
a. Primary status
b. Device type
c. Present average value
d. Present sensitivity selected
e. Sensor range (normal, dirty, etc.)
7. Adjustable alarm notification feature shall be provided with initial set point of 20 seconds
2.8 HEAT DETECTORS
Heat detectors must be analog/addressable and designed for detection of fire by [fixed temperature][combination fixed temperature and rate-of-rise principle][rate-compensating principle] in accordance with UL 521. The alarm condition must be determined by comparing detector value with the stored values.. Detectors located in areas subject to moisture, exterior atmospheric conditions, or hazardous locations [as defined by NFPA 70][ and ][as indicated], must be types approved for such locations.
2.8.1 Combination Fixed-Temperature and Rate-of-Rise Detectors
Detectors must be [surface][semi-flush] mounted in the [vertical][horizontal] orientation and supported independently of wiring connections. Detectors must be self-resetting. Detector must operate at [57.2][90] degrees C[135][194] degrees F. Detector must feature rate compensation.
[Detectors rated to operate at 57.2 degrees C135 degrees F must not respond to momentary temperature fluctuations less than 16.7 degrees C30 degrees F per minute between 16 and 38 degrees C60 and 100 degrees F].[ Detectors rated to operate at 90 degrees C194 degrees F must not respond to momentary temperature fluctuations less than 27.8 degrees C
283170 - 12
50 degrees F per minute between 16 and 66 degrees C60 and 150 degrees F.][ The detector assembly must be [weatherproof][ and ][explosionproof].]
2.8.2 Rate Compensating Detectors
Detector backbox must be [surface][flush] mounted in the [vertical][horizontal] orientation and supported independently of wiring connections. Detectors must be self-restoring and hermetically sealed.[ The detector assembly must be [weatherproof][ and ][explosionproof].]
2.8.3 Line-Type Fixed Temperature Detectors
Provide [thermostatic][ or ][thermistor] line-type heat detection cable [with weather-resistant outer covering] where indicated. Cable must be nominally rated for a temperature of [68][88][138] degrees C [155][190][280] degrees F and must operate on fixed temperature principle only.
2.8.4 Fixed Temperature Detectors
Detectors must be [surface][semi-flush] mounted in the [vertical][horizontal] orientation and supported independently of wiring connections. Detectors must be self-restoring. The detectors must have a specific temperature setting [of [57.2][ ] degrees C [135][ ] degrees F][as shown].[ The detector assembly must be [weatherproof][ and ][explosionproof].]
2.9 ELECTRIC POWER
A. Primary Power
1. Power shall be 120 VAC service for the FACU in accordance with UFC 3-520-01, NFPA 72 and as shown on the drawings.
2.10 EMERGENCY POWER SUPPLY
A. Provide for system operation in the event of primary power source failure. Transfer from normal to auxiliary (secondary) power or restoration from auxiliary to normal power shall be automatic and shall not cause transmission of a false alarm.
1. Batteries
a. Provide sealed, maintenance-free, sealed lead acid batteries as the source for emergency power to the FACU. Batteries shall contain suspended electrolyte. The battery system shall be maintained in a fully charged condition by means of a solid state battery charger. Provide an automatic transfer switch to transfer the load to the batteries in the event of the failure of primary power.
b. Capacity
1) Provide the batteries with sufficient capacity to operate the system under supervisory and trouble conditions, including audible trouble signal devices for 60 hours and audible and visual signal devices under alarm conditions for an additional 15 minutes. Battery shall also have sufficient capacity to operate the mass notification system for 60 minutes, after loss of AC power.
283170 - 13
c. Battery Power Calculations
1) Verify that battery capacity exceeds supervisory and alarm power requirements.
a) Substantiate the battery calculations for alarm, alert, and supervisory power requirements. Ampere-hour requirements for each system component and each panel component, and the battery-recharging period shall be included.
b) Provide complete battery calculations for both the alarm, alert, and supervisory power requirements. Ampere-hour requirements for each system component shall be submitted with the calculations.
c) A voltage drop calculation to indicate that sufficient voltage is available for proper operation of the system and all components, at the minimum rated voltage of the system operating on batteries.
2) For battery calculations use the following assumptions: Assume a starting voltage of 24 VDC for starting the calculations to size the batteries.
Calculate the required Amp-Hours for the specified standby time, and then calculate the required Amp-Hours for the specified alarm time. Calculate the nominal battery voltage after operation on batteries for the specified time period. Using this voltage perform a voltage drop calculation for circuit containing device and/or appliances remote from the power sources.
2. Battery Chargers
a. Provide a solid state, fully automatic, variable charging rate battery charger. The charger shall be capable of providing 150 percent of the connected system load and shall maintain the batteries at full charge. In the event the batteries are fully discharged (18 Volts dc), the charger shall recharge the batteries back to 95 percent of full charge within 48 hours. Provide pilot light to indicate when batteries are manually placed on a high rate of charge as part of the unit assembly if a high rate switch is provided.
3. Locate battery cabinets adjacent to FACU or in approved conditioned location such as an electrical room (with smoke detection if power extender panel is provided).
2.11 FIRE ALARM CONTROL UNIT (FACU)
A. The FACU shall be a Monaco MAAP-X addressable fire alarm control panel with integrated radio transceiver, point reporting and mass notification. Provide a complete control panel fully enclosed in a red lockable steel cabinet as specified herein. Operations required for testing or for normal care and maintenance of the systems shall be performed from the front of the enclosure. If more than a single unit is required at a location to form a complete control panel, the unit cabinets shall match exactly. All fire alarm and mass notification components provided shall be compatible with the panel(s) provided.
283170 - 14
1. Each control unit shall provide power, supervision, control, and logic for the entire system, utilizing solid state, modular components, internally mounted and arranged for easy access. Each control unit shall be suitable for operation on a 120 volt, 60 hertz, normal building power supply. Provide each panel with supervisory functions for power failure, internal component placement, and operations.
2. Visual indication of alarm, supervisory, or trouble initiation on the fire alarm control panel shall be by liquid crystal display or similar means with a minimum of 80 characters. The mass notification control unit shall have the capability to temporarily deactivate the fire alarm audible notification appliances while delivering voice messages.
3. Provide secure operator console for initiating recorded messages, strobes and displays;
and for delivering live voice messages. Provide capacity for at least eight pre-recorded messages. Provide the ability to automatically repeat pre-recorded messages. Provide a secure microphone for delivering live messages. Provide adequate discrete outputs to temporarily deactivate fire alarm audible notification, and initiate/synchronize strobes.
Provide a complete set of self-diagnostics for controller and appliance network. Provide local diagnostic information display and local diagnostic information and system event log file.
4. Provide output for USB flash drive for download of panel history.
B. Cabinet
1. Install control panel components in cabinets large enough to accommodate all components and also to allow ample gutter space for interconnection of panels as well as field wiring. The enclosure shall be identified by an engraved laminated phenolic resin nameplate. Lettering on the nameplate shall say "Fire Alarm Control Panel" and shall not be less than 1 inch high. Provide prominent rigid plastic or metal identification plates for lamps, circuits, meters, fuses, and switches. The cabinet shall be provided in a sturdy steel housing, complete with back box, hinged steel door with cylinder lock, and surface mounting provisions.
C. Control Modules
1. Provide power and control modules to perform all functions of the FACU. Provide audible signals to indicate any alarm, supervisory, or trouble condition. The alarm signals shall be different from the trouble signal. Connect circuit conductors entering or leaving the panel to screw-type terminals with each terminal marked for identification. Locate diodes and relays, if any, on screw terminals in the FACU. Circuits operating at 24 VDC shall not operate at less than 21.6 volts. Circuits operating at any other voltage shall not have a voltage drop exceeding 10 percent of nominal voltage.
D. Silencing Switches
1. Alarm Silencing Switch: Provide an alarm silencing switch at the FACU that shall silence the audible signal but not affect the visual alarm indicator. This switch shall be overridden upon activation of a subsequent alarm.
2. Supervisory/Trouble Silencing Switch: Provide supervisory and trouble silencing switch that shall silence the audible trouble and supervisory signal, but not extinguish the visual indicator. This switch shall be overridden upon activation of a subsequent alarm, supervision, or trouble condition. Audible trouble indication must resound automatically every 24 hours after the silencing feature has been operated if the supervisory or trouble condition still exists.
283170 - 15
E. Non-Interfering
1. Power and supervise each circuit such that a signal from one device does not prevent the receipt of signals from any other device. Circuits shall be manually reset by switch from the FACU after the initiating device or devices have been restored to normal.
F. Memory
1. Provide control unit with non-volatile memory and logic for all functions. The use of long life batteries, capacitors, or other age-dependent devices shall not be considered as equal to non-volatile processors, PROMS, or EPROMS.
G. Field Programmability
1. Provide control units and control panels that are fully field programmable for control, initiation, notification, supervisory, and trouble functions of both input and output. The system program configuration shall be menu driven. System changes shall be password protected and shall be accomplished using personal computer based equipment. Any proprietary equipment and proprietary software needed by qualified technicians to implement future changes to the fire alarm system shall be provided as part of this contract.
H. Input/Output Modifications
1. The FACU shall contain features that allow the bypassing of input devices from the system or the modification of system outputs. These control features shall consist of a panel mounted keypad. Any bypass or modification to the system shall indicate a trouble condition on the FACU..
I. Resetting
1. Provide the necessary controls to prevent the resetting of any alarm, supervisory, or trouble signal while the alarm, supervisory or trouble condition on the system still exists.
J. Instructions
1. Provide a typeset printed or typewritten instruction card mounted behind a Lexan plastic or glass cover in a stainless steel or aluminum frame. Install the frame in a conspicuous location observable from the FACU. The card shall show those steps to be taken by an operator when a signal is received as well as the functional operation of the system under all conditions, normal, alarm, supervisory, and trouble. The instructions shall be approved by the Contracting Officer before being posted.
K. Walk Test
1. The FACU shall have a walk test feature. When using this feature, operation of initiating devices shall result in limited system outputs, so that the notification appliances operate for only a few seconds and the event is indicated on the FACU or USB output, but no other outputs occur.
283170 - 16
L. History Logging
1. The control panel shall have the ability to store a minimum of 400 events in a log. These events shall be stored in a battery-protected memory and shall remain in the memory until the memory is downloaded or cleared manually. Resetting of the control panel shall not clear the memory.
M. Manual Access
1. An operator at the control unit, having a proper access level, must have the capability to manually access the following information for each initiating device.
a. Primary Status
b. Device Type
c. Present average value
d. Present sensitivity selected
e. Detector range (normal, dirty)
2.12 AMPLIFIERS, PREAMPLIFIERS, TONE GENERATORS
A. Any amplifiers, preamplifiers, tone generators, digitalized voice generators, and other hardware necessary for a complete, operational, textual audible circuit conforming to NFPA 72 shall be housed in a fire alarm control unit, terminal cabinet, or in the fire alarm control panel. The system shall automatically operate and control all building fire alarm speakers except those installed in the stairs and within elevator cabs. The speakers in the stairs and elevator cabs shall operate only when the microphone is used to deliver live messages. Each amplifier shall be single output channel.
B. Construction
1. Amplifiers shall utilize computer grade solid state components and shall be provided with output protection devices sufficient to protect the amplifier against any transient up to 10 times the highest rated voltage in the system.
2. Inputs
a. Each system shall be equipped with separate inputs from the tone generator, digitalized voice driver and panel mounted microphone. Microphone inputs shall be of the low impedance, balanced line type. Both microphone and tone generator input shall be operational on any amplifier.
3. Tone Generator
a. The tone generator shall be of the modular, plug-in type with securely attached labels to identify the component as a tone generator and to identify the specific tone it produces. The tone generator shall produce a slow whoop tone, that shall slowly ascend from low (500 hertz) to high (1200 hertz), and shall be constantly repeated until interrupted by either the digitalized voice message, the microphone
283170 - 17 input, or the alarm silence mode as specified. Each slow whoop cycle shall last approximately 4 seconds. The tone generator shall be single channel with an automatic backup generator per channel such that failure of the primary tone generator causes the backup generator to automatically take over the functions of the failed unit and also causes transfer of the common trouble relay.
4. Protection Circuits
a. Each amplifier shall be constantly supervised for any condition that could render the amplifier inoperable at its maximum output. Failure of any component shall cause automatic transfer to a designated backup amplifier, illumination of a visual "amplifier trouble" indicator on the control panel, and other actions for trouble conditions as specified.
2.13 MANUAL STATIONS
A. Provide metal or plastic, semi-flush mounted, double action, addressable manual stations, that are not subject to operation by jarring or vibration. Stations shall be equipped with screw terminals for each conductor. Stations that require the replacement of any portion of the device after activation are not permitted. Stations shall be finished in fire-engine red with molded raised lettering operating instructions of contrasting color. The use of a key or wrench shall be required to reset the station. Key shall match FACU key. Manual stations shall be mounted at 44 inches. Stations shall have a separate screw terminal for each conductor.
2.14 NOTIFICATION APPLIANCES
A. Visual Notification Appliances
1. Visual notification appliances shall conform to the applicable requirements of UL 1971 and conform to the Americans With Disabilities Act (ADA). Colored lens, such as amber, shall comply with UL 1638. The manufacturer shall have the color lens tests to the full UL 1971 polar plotting criteria, voltage drop, and temperature rise as stated in 1971. Fire Alarm Notification Appliances shall have clear high intensity optic lens, xenon flash tubes, and output white light and be marked "Fire" in red letters. Mass Notification Appliances shall have amber high intensity optic lens, xenon flash tubes, and output white light and be marked "ALERT" in red letters. The light pattern shall be disbursed so that it is visible above and below the strobe and from a 90 degree angle on both sides of the strobe. Strobe flash rate shall be 1 flash per second and a minimum of 15 candela (actual output after derating for tinted lens) based on the UL 1971 test. Strobe shall be surface mounted. Where more than two appliances are located in the same room or corridor, provide synchronized operation.
B. Connections
1. Provide screw terminals for each notification appliance. Terminals shall be designed to accept the size conductors used in this project without modification.
283170 - 18
2.15 ENVIRONMENTAL ENCLOSURES OR GUARDS
A. Environmental enclosures shall be provided to permit Fire Alarm or Mass Notification components to be used in areas that exceed the environmental limits of the listing. The enclosure shall be listed for the device or appliance as either a manufactured part number or as a listed compatible accessory for the UL category that the component is currently listed. Guards required to deter mechanical damage shall be either a listed manufactured part or a listed accessory for the category of the initiating device or notification appliance.
2.16 AUTOMATIC FIRE TRANSMITTERS
A. Radio Transmitter and Interface Panels
1. All fire alarm and mass notification components shall be compatible with the FACU as well as the base Base Station Controllers.
2. Transmitters shall be integral with the FACU, compatible with proprietary supervising station receiving equipment. Each radio alarm transmitter shall be the manufacturer's recognized commercial product, completely assembled, wired, factory tested, and delivered ready for installation and operation. Transmitters shall be provided in accordance with applicable portions of NFPA 72, Federal Communications Commission (FCC) 47 CFR 90 and Federal Communications Commission (FCC) 47 CFR 15.
Transmitter electronics module shall be contained within the physical housing as an integral, removable assembly. The proprietary supervising station receiving equipment is Monaco D21 and the transceiver shall be fully compatible with this equipment. At the contractors option, and if UL or FM listed, the transmitter may be housed in the same panel as the fire alarm and mass notification control panel. The transmitter shall be Narrowband radio, with FCC certification for narrowband operation and meets the requirements of the NTIA (National Telecommunications and Information Administration) Manual of Regulations and Procedures for Federal Frequency Management.
a. Operation: Each transmitter shall operate from 120-volt ac power. In the event of
120-volt ac power loss, the transmitter shall automatically switch to battery operation. Switchover shall be accomplished with no interruption of protective service, and shall automatically transmit a trouble message. Upon restoration of ac power, transfer back to normal ac power supply shall also be automatic.
b. Battery Power: Transmitter standby battery capacity shall provide sufficient power to operate the transmitter in a normal standby status for a minimum of 72 hours and be capable of transmitting alarms during that period.
c. Transmitter housing shall be NEMA Type 1. The housing shall contain a lock that is keyed identical to the fire alarm system for the building. Radio alarm transmitter housing shall be factory painted with a suitable priming coat and not less than two coats of a hard, durable weatherproof enamel.
d. Antenna shall be omnidirectional, coaxial, halfwave dipole antennas for radio alarm transmitters with a driving point impedance to match transmitter output. The antenna and antenna mounts shall be corrosion resistant and designed to withstand wind velocities of 100 mph. Antenna shall be installed on the nearest egress point and uppermost exterior wall of the building on a stand-off bracket. Protect the antenna from physical damage.
e. Software Upgrades: Provide system security software upgrades as available for a
283170 - 19 minimum period of 5 years.
3. Signals to Be Transmitted to the Base Receiving Station
a. The following signals shall be sent by point to the base receiving station: Refer to the Fire Alarm/Mass Notification Input/Output Functional Matrix and Fire Department approval.
2.17 WIRING
A. Alarm Wiring
1. All wiring shall be installed in minimum 3/4 inch rigid metallic conduit or EMT. Flexible metal or liquid tight conduit shall be limited to 6 foot length and shall only by used in areas of extreme vibration and to connect to devices mounted in removable ceiling tiles.
NFPA 70 accepted fire alarm cables that are not installed in raceways are not permitted.
2. The SLC wiring shall be solid copper cable in accordance with the manufacturers requirements. Copper signaling line circuits and initiating device circuit field wiring shall be No. 14 AWG size twisted and shielded solid conductors at a minimum. Visual notification appliance circuit conductors, that contain audible alarm appliances, shall be solid copper No. 14 AWG size conductors at a minimum. Speaker circuits shall be copper No. 16 AWG size twisted and shielded conductors at a minimum. Wire size shall be sufficient to prevent voltage drop problems. Circuits operating at 24 VDC shall not operate at less than the UL listed voltages for the sensors and/or appliances. Power wiring, operating at 120 VAC minimum, shall be a minimum No. 12 AWG solid copper having similar insulation. Acceptable power-limited cables are FPL, FPLR or FPLP as appropriate with red colored covering. Nonpower-limited cables shall comply with NFPA 70.
PART 3 - EXECUTION
3.1 INSTALLATION OF FIRE ALARM INITIATING DEVICES AND NOTIFICATION
APPLIANCES
A. FACU
1. Locate the FACU where indicated on the drawings. Surface mount the enclosure with the top of the cabinet 6 feet above the finished floor or center the cabinet at 5 feet, whichever is lower.