This award notice announces that contract 6973GH-20-C-00042 was awarded on March 20, 2020 to Prow'ess Construction Corp. for the refurbishment of the QBE Air Route Surveillance Radar Facility located in Bedford, VA. The contract amount is $241,495. The contracting agency is the Department of Transportation Federal Aviation Administration Franchise Acquisition Services. Questions regarding the announcement can be directed to the contracting officer, Janice Hammonds.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Department of Transportation Federal Aviation Administration Southern Regional Office

Dated August 8, 2019

Submitted By:

Engineering Services, Infrastructure Engineering;

Project Engineer .......................................……….................Micah Brantley

Specification For

“REFURBISHMENT OF

QBE AIR ROUTE SURVAILLANCE RADAR FACILITY

IN BEDFORD, VA”

DIVISION 1 – GENERAL REQUIREMENTS

SECTION 1A – SUMMARY OF WORK

1A.1 GENERAL: This specification along with project drawings, codes, and standards, covers the requirements to refurbish the QBE Air Route Surveillance Radar

(ARSR).

1A.2 SCOPE OF WORK: The work consists of but is not limited to the following:

A. Equipment Building Roofing

1. Install a Sikalastic® RoofPro (Decothane®) waterproofing system over existing 27’x55’metal roof according to Section 07 56 00: Fluid-Applied Roofing

B. Breezeway Siding and Roofing

1. Demo and dispose of existing roof material.

2. Demo and dispose of existing siding and trim materials.

3. Demo and dispose of deteriorated wall and roof sheathing.

4. Repair all wall opening in exterior of building with ½” plywood (flush the existing sheathing).

5. Install new ½” plywood sheathing over existing roof sheathing.

6. Repair replace any deteriorated roof, wall, fascia or soffit structure and install nailers as needed to accommodate the new roof panels, siding panels and accessories

7. Install new Max-Rib II roof panels as per Sheet 9 of the installation manual.

8. Install new Max-Rib II wall panels as per Sheet 2 of the installation manual.

9. Install rodent guard/ base trim as per sheet 2 of the installation manual.

10. Install outside corner trim as per sheet 3 of the installation manual.

11. Install door and opening trim as per sheet 5/6 of the installation manual.

12. Install eave and inside closure as per sheet 9 of the installation manual.

13. Install soffit and vented eave as per sheet 10 of the installation manual.

14. Install gable / rake trim as per sheet 11/12 of the installation manual.

15. Install ridge cap as per sheet 14 of the installation manual.

16. Install all other accessories necessary to complete the installation.

C. Asphalt Crack and Joint Sealing

1. Identify, clean, dry, and prepare cracks and joints greater than 1/4″ wide and less than 3/4″ for repair.

2. Apply elastomeric hot applied sealant to cracks and joints according to

SECTION 32 01 17.61: Crack and Joint Sealing for Asphalt Pavements.

D. Asphalt Sealing

1. Apply (2) coats of engineered resin emulsion sealcoat slurry to parking lot and access road per manufacturer Neyra Force SEALING SPECIFICATION (attached).

E. Lighting

1. Remove and replace (20) 2x4 lighting fixtures with Lumination™ LED Luminaires 2’ x 4’ Recessed Troffer BR24 Series lighting fixtures in the Main Equipment room (specification sheet attached).

2. Remove and replace (5) 2x4 lighting fixtures with Lumination™ LED Luminaires 2’ x 4’ Recessed Troffer BR24 Series lighting fixtures in the Transmitter room.

3. Remove and replace (5) 2x4 lighting fixtures with Lumination™ LED Luminaires 2’ x 4’ Recessed Troffer BR24 Series lighting fixtures in the Engine Generator room.

4. Remove and replace (4) 2x4 lighting fixtures with Lumination™ LED Luminaires 2’ x 4’ Recessed Troffer BR24 Series lighting fixtures in the UPS room.

5. Remove and replace (5) 2x4 lighting fixtures with Lumination™ LED Luminaires 2’ x 4’ Recessed Troffer BR24 Series lighting fixtures in the Kitchen.

6. Remove and replace (4) 2x4 lighting fixtures with Lumination™ LED Luminaires 2’ x 4’ Recessed Troffer BR24 Series lighting fixtures in the Breezeway.

F. Fencing and Gate

1. Demo 75’ of existing chain link fencing at entrance to the facility. See Figure 1.

2. Demo existing pedestrian gate, lock, and lock pedestal.

3. Install new 7’ high Galvanized fence with 1’ of barbed wire.

4. Install new pedestrian gate with mechanical keyless gate lock.

G. Retaining Wall

1. Remove approximately 75’ of existing curbing at the entrance gate to the facility. See Figure 1

2. Excavate for adequate drainage and construction of a new block wall.

3. Design and build wall 75’ in length and 35” tall according to manufacturer’s specifications. The contractor is responsible for exact measurements.

4. Manufacturer recommended fabric, drainpipe and clean rock to be placed behind entire wall.

5. Backfill top, edges and any low areas, with topsoil, caused by excavation or construction.

Figure 1.

H. Painting

1. Properly remove all peeling paint, scaling, rust and debris from all surfaces to be painted.

2. Properly collect and dispose of all paint. Assume all paint to be lead based.

3. Removal and disposal of any lead based paint or lead-containing paint shall be done in accordance with state and federal guideline for such work.

4. All existing items, cabling, antennas, lightning protection, obstruction light, adjacent building….etc. shall be protected during the process.

5. Surround structures (buildings, vehicles, airplanes etc…) shall be protection at all times from overspray. No spray painting will be allowed in winds over 3 miles per hour).

6. Paint entire tower structure two coats of Sherman Williams DTM Acrylic Coating (B66) per specifications.

7. Color scheme will match existing colors

1A.3 COORDINATION: The project resident engineer (RE) shall coordinate between the contractor and the System Support Center (SSC) office manager and the facility employees. All coordination shall be through the project Resident Engineer (RE).

1A.4 MATERIAL: The contractor shall furnish all material, equipment, and labor to complete the job, except material shown on the government furnished property list.

The use of brand names or equal products in this specification does not constitute a requirement that they are the only materials that meet the specifications in this contract. They are used as an illustration of known acceptable sources or products.

1A.6 MATERIAL STORAGE: The contractor shall store all material in such a manner that they are protected from damage due to external elements including climate and weather conditions. Contractor furnished materials shall not be stored inside the FAA equipment building.

1A.7 INGRESS AND EGRESS TO WORK AREAS: Ingress and egress to the work areas shall be as shown on the construction safety plan or as directed by the resident engineer. Security precautions against unauthorized entry to the site or building shall be maintained.

1A.8 CLEANING:

A. Work Area. The contractor shall keep the work area clean. All rubbish and waste resulting from the execution of work shall be removed and properly disposed at the end of each day or as directed by the resident engineer. The terne-coated metal pans shall not be disposed in a landfill but recycled as appropriate, in accordance with federal, state and local regulations.

B. Waste Packing Material: Immediately after unpacking, all packing material, case lumber, excelsior and any other rubbish, flammable or otherwise, shall be removed from the building and the premises.

C. Final Clean Up: Upon completion of work and before final inspection, the contractor shall remove his working tools, equipment, debris, rubbish, and unused materials from the building site.

D. Disposal: Disposal of rubbish, debris, and gravel will be offsite at contractor’s expense.

1A.11 CONTRACTOR’S LIABILITY: Damage to existing facilities and equipment caused by the contractor shall be reported to the resident engineer without delay.

The contractor will be responsible for the repair of all damaged areas of the building or equipment at the contractor’s expense. All repairs shall be accomplished to the satisfaction of the resident engineer.

1A.12 WORKMANSHIP: All work shall be accomplished by experienced workers in accordance with the highest standards of the various work trades involved.

1A.13 PRE-CONSTRUCTION CONFERENCE: The contractor shall attend a pre-construction conference prior to starting work at a location agreed to by the contractor and the contracting officer.

1A.14 SITE VISIT: Bidders are encouraged to visit the site and carefully examine the areas in question as to conditions that may affect proper execution of the work. All dimensions and quantities shall be determined or verified by the contractor. No claims for extra costs will be allowed because of lack of full knowledge of the existing conditions.

1A.18 WORK PERMITS:

All construction and working permits required by local and state agencies shall be procured by the contractor at no expense to the FAA.

1A.19 ASBESTOS FREE CERTIFICATION:

The Contractor shall provide to the Contracting Officer (CO) a signed statement stating that to the best of his/her knowledge; no asbestos-containing building materials were used during the renovation and modernization of this facility.

If the FAA suspects the presence of asbestos, the FAA will sample the suspect material to verify that no asbestos-containing material was utilized. This testing shall be performed at the expense of the FAA. If asbestos-containing material is subsequently found during the sampling of the building materials, the Contractor shall remove and replace the product or material at his/her expense. In addition, the Contractor shall incur the costs of the original testing and/or any re-testing that may be necessary.

The Contractor shall submit to the CO Material Safety Data Sheets (MSDS), prior to construction, for all materials and/or products to be utilized during the course of the project accomplishment. During the course of the project, both the RE and the Contractor shall routinely check products utilized on-site to ensure only products that have had MSDS submitted are utilized. Copies of all MSDS shall be turned over to the local FAA office for their records.

If the Contractor does not submit the required information described above, the FAA shall have a complete building survey performed by a qualified testing firm prior to acceptance. The cost of the survey and any subsequent removal/replacement of any asbestos-containing material shall be deducted from the Contractor's payment.

The contractor shall remove all containers of unused chemicals from the worksite upon completion of work, except where specified by the resident engineer.

1A.20 HAZARDOUS MATERIAL AND SAFETY:

The contractor shall be responsible for safety on the work site. It is responsibility of the contractor to eliminate hazards that may result in tripping, electrical shock, fire, falling objects, environmental hazards, vehicular accidents etc. The contractor shall comply with all safety precautions required by OSHA. The contractor shall have two l5 lb. Class B and C fire extinguishers at the work area through the progress of welding, metal cutting, or any other process involving a spark or fire hazard.

Fall protection is required for work 6 feet and higher above ground level. Body belts are not allowed per FAA orders.

DIVISION 7 – MOISTURE PROTECTION

SECTION 07 56 00 FLUID APPLIED ROOFING

PART 1

GENERAL

1.01 SUMMARY

A. This section specifies all labor, materials, transportation, equipment and services necessary to install a Sikalastic® RoofPro (Decothane®) waterproofing system, on structural concrete, plywood, metal, or other approved substrate by manufacturer and shown on the drawings and described herein.

B. Sections Included

Section 07 56 00: Fluid-Applied Roofing

C. Related Sections

Section 07 60 00: Flashing and Sheet Metal

Section 22 14 26.13: Roof Drains

1.02 REFERENCES

A. Factory Mutual (FM Global) - Approval Guide B. American Society for Testing and Materials (ASTM) - Annual Book of ASTM Standards C. National Roofing Contractors Association (NRCA) D. American Society of Civil Engineers (ASCE)

1.03 DEFINITIONS

A. Roofing Terminology: Refer to ASTM D1079 and the glossary of the National Roofing

Contractors Association (NRCA) Roofing and Waterproofing Manual for definitions of roofing terms related to this section.

1.04 PERFORMANCE REQUIREMENTS

A. Provide an installed roofing membrane that does not permit the passage of water, and will withstand the design pressures calculated in accordance with the most current revision of ASCE 7.

B. Manufacturer shall provide all primary waterproofing materials that are physically and chemically compatible when installed in accordance with manufacturers current application requirements.

1.05 SUBMITTALS

A. Provide product data sheets for each type of product indicated in this section.

B. Provide manufacturers standard details and approved shop drawings for the specified system.

C. Installer shall provide written documentation from the manufacturer of their authorization to install the system, and eligibility to obtain the warranty specified in this section.

D. Certification showing full time quality control of production facilities and that each batch of material is tested to ensure conformance with the manufacturer's published physical properties.

E. Certification that the waterproofing membrane meets FM Global Approval Standard 4470 for Class I roof covers, on non-combustible substrates, with a Class 1-990 wind uplift rating, a hail rating of SH and is ASTM E-108-00 Class A approved at a slope of 1 in 12.

F. Manufacturer’s certification that all waterproofing system products meet current Volatile Organic Compound (VOC) regulations as established by the State in which they are being installed; and stating total VOC content, in grams per litre, for all system components (i.e. primers, adhesives, coatings, etc.).

1.06 QUALITY ASSURANCE

A. Manufacturer’s Qualifications: Manufacturer shall demonstrate qualifications to supply materials of this section by certifying the following:

Membrane Manufacturer must show evidence that the specified membrane has been manufactured by the same organization or direct affiliate for fifteen (15) years.

Membrane Manufacturer shall have available an in-house technical staff to assist the contractor, when necessary, in application of the products and final inspection of the assembly.

B. Installer’s Qualifications: The Contractor shall demonstrate qualifications to perform the work of this Section by submitting the following documentation:

Certification or license by the waterproofing membrane manufacturer as a trained applicator of the product the installer intends to use.

C. Source Limitations: All components listed in this section shall be provided by a single manufacturer or approved by the primary waterproofing manufacturer.

D. Final Inspection

Manufacturers representative shall provide a comprehensive final inspection after completion of the waterproofing system. All application errors must be addressed and final punch list completed.

1.07 REGULATORY REQUIREMENTS

A. All work shall be performed in a safe, professional manner, conforming to all federal, state and local codes.

B. All waterproofing system components shall meet current VOC regulations as established by the State in which they are being installed; and stating total VOC content, in grams per litre, for all system components (i.e. primers, adhesives, coatings, etc.)

1.09 DELIVERY, STORAGE AND HANDLING

A. Deliver all waterproofing materials to the site in original containers, with factory seals intact.

B. Store all pail goods in their original undamaged containers in a clean, dry location within their specified temperature range.

C. Do not expose materials to moisture in any form before, during, or after delivery to the site. Reject delivery of materials that show evidence of contact with moisture.

D. Remove manufacturer supplied plastic covers from materials provided with such. Use

“breathable” type covers such as canvas tarpaulins to allow venting and protection from weather and moisture. Cover and protect materials at the end of each work day.

Do not remove any protective tarpaulins until immediately before the material will be installed.

E. Materials shall be stored above 55°F (12.6°C) a minimum of 24 hours prior to application.

1.10 PROJECT CONDITIONS

A. Weather

Proceed with waterproofing only when existing and forecasted weather conditions permit.

Membrane installation can proceed when ambient temperatures are above 40°F

(4.4°C), provided the substrate temperarture is a minimum of 5°F above the dew point.

It is recommended that overnight temperatures be above 40°F (4.4°C) when applying the membrane system. Consult with the manufacturer for cold weather installation procedures when ambient temperatures are expected to fall below the minimums established herein.

B. All surfaces to receive the membrane shall be free from visible water, dew, frost, snow and ice.

C. Application of membrane should be conducted in well ventilated areas.

D. Over its service life, do not expose membrane to a constant temperature below -58°F (-

50°C) or in excess of 176°F (80°C) (i.e., hot pipes and vents or direct steam venting, etc.).

E. Sikalastic RoofPro (Decothane) is non-flammable and VOC compliant. Consult container or packaging labels and Material Safety Data Sheets (MSDS) for specific safety information.

F. Sikalastic RoofPro (Decothane) is resistant to gasoline, paraffin, fuel oil, mineral spirits, and moderate solutions of acids and alkalis, acid rain and detergents. Some low molecular weight alcohols can soften. Any exposure to foreign materials or chemical discharges must be presented to membrane manufacturer for evaluation to determine any impact on the waterproof membrane assembly performance prior to warranty issuance.

G. Contractor shall ensure adequate protection during installation of the waterproofing system. Sikalastic RoofPro (Decothane) may be applied to properly prepared concrete decks, at a wet film thickness of 15-20 mils, for use as a temporary waterproofing barrier. Sikalastic RoofPro (Decothane) applied as a temporary waterproofing membrane does not have to be removed prior to installation of the specified waterproofing system.

1.11 WARRANTY

A. Each warranty varies in scope and terms. Contact Sika for exact warranty terms and conditions to meet the specific project requirements.

B. Warranties available from the manufacturer:

Watertightness Warranties; includes labor and material. Duration 20 Years.

**CONTACT SIKA FOR EXACT WARRANTY TERMS AND CONDITIONS.**

PART 2

PRODUCTS

2.01 ACCEPTABLE MANUFACTURER

A. Sika Coporation 201 Polito Avenue Lyndhurst, NJ 07071 Phone: 800-933-7452 Fax: 201-922-6225 www.sikaconstruction.com

B. Substitutions: As approved in writing prior to receipt of bid and membrane must meet or exceed the performance requirements set forth in 2.04C and ASTM D7311-07.

2.03 SEALANTS and PRIMERS

A. A rapid curing, water-based primer consisting of two components for brick, concrete unit masonry (CMU), wallboard, exterior grade gypsum sheathing and previously coated surfaces, Sika Bonding Primer.

B. A two-component, solvent free, epoxy primer and damp proof membrane, which is designed to be applied to damp or new concrete with high moisture drive prior to the application of Decothane systems, Sikalastic DTE Primer.

C. A two-component, rapid curing, high solids, solvent based, dampproof primer designed for sealing cementitious substrates, Sika Concrete Primer (Quick Cure Primer).

D. A two-component, cyclo-aliphatic, amine cured material with a high level of corrosion resistance for metal, modified bitumen surfaces, and chemically treated wood, Sikalastic EP Primer/Sealer (Epoxy Primer).

E. A single component, polyurethane based primer for the reactivation of existing Sikalastic RoofPro (Decothane) systems prior to overcoating, Sika Reactivation Primer.

F. One part polyurethane sealant suitable for sealing reglet terminations, cracks and providing a suitable transition between the waterproofing system and roof penetrations prior to the installation of the membrane system. Meets or exceeds ASTM C-920-87, Type S, Grade NS, Class 25, Sikaflex® 1a, or equal as approved by membrane manufacturer.

2.04 FLUID APPLIED MEMBRANE MATERIALS

A. A conformable, random woven fiberglass mat for total reinforcement of the roofing/waterproofing membrane system, which provides greater impact resistance and greater resistance to excessive thermal and structural movement while maintaining elasticity and membrane film integrity, Sika Reemat.

B. A nylon mesh for local reinforcement of the roofing/waterproofing membrane at structural cracks, expansion joints, and transitions between dissimilar materials, Sika Flexitape Heavy.

C. A single component, cold, fluid applied, moisture triggered, aliphatic, polyurethane meeting the following physical properties and ASTM D7311-07: Standard Specification for Liquid Applied, Single Component, Moisture-Triggered, Aliphatic Polyurethanes used in Roofing, Sikalastic 601 BC and Sikalastic 621 TC (Decothane EC and Decothane SP).

LIQUID PROPERTY REQUIREMENTS

PHYSICAL PROPERTIES

ASTM REQUIREMENTS

VISCOSITY D2196 5 to 20 Pa.s (pascal.seconds)

VOLUME SOLIDS D2697 76% minimum WEIGHT SOLIDS D1644 83% minimum SAG RESISTANCE D4400 No sag at 700 micrometers

(0.028 in. / 28 mil)

DIVISION 9 – FINISHES

SECTION 9 – PAINTING

9-1 PAINTING

9 1.1 General: This section covers furnishing all labor, materials, tools, and accessories required to complete the painting of the galvanized steel tower, stair enclosure and other items as listed in the description of work. Color to be selected by FAA Representative.

9 1.2 Applicable Documents:

9 1.2.1.1 FEDERAL SPECIFICATIONS:

TT P 102 Paint, Oil Alkyd, Exterior, Ready Mixed, White and Tints

TT P 636 Primer Coating, Alkyd, Wood and Ferrous Metals

TT P 641 Primer Coating; Zinc Dust Zinc Oxide (for galvanized surfaces)

TT P 645 Primer, Paint; Zinc Chromate, Alkyd Type

9 1.2.1.2 Federal Standards:

FAA STD. 003 Painting Systems for Structures

FAA STD. 012 Paint Systems for Structures

Federal STD. 595 Colors

9 1.3 Materials:

9 1.3.1 Paint: All painting materials shall be the first quality products of a name brand paint company's which meet the requirements of the applicable Federal or FAA Standards. Deliver all painting and finishing materials in original containers with seals unbroken and labels intact. All materials shall be used strictly in accordance with manufacturer's label directions. No materials other than those specified or approved by the R.E. shall be stored on the site. All paint on any one surface shall be the product of the same manufacturer.

Known Acceptable Source: Sherman Williams DTM Acrylic Coating (B66).

9 1.4 Installation and Preparation of Surfaces:

9 1.4.1 Galvanized Metal: Galvanized surfaces shall be preped to remove all loose paint, scaling and rust. A tarp shall be place below the working are to catch all debris. All lead-based paint chips shall be properly disposed of. All cut, scarred, corroded, or abraded spots shall be, immediately upon detection, thoroughly wire brushed, cleaned, smoothed, and spot primed with zinc dust zinc oxide primer. A primer designed for use on galvanized surfaces shall be utilized.

9 1.4.2 Paint Application: The painting work shall be hand brushed, rolled or sprayed, except where otherwise permitted or designated by the RE, with the materials flowed on in such a manner as to ensure smooth, even uniform coats free of dirt, runs, brush marks, sags, and laps. When completed, the painting shall represent a first class, workmanlike appearance. Where the work is executed in contras¬ting color tones, each color shall be cut to neat, true lines against the adjoining colors.

Do not apply exterior paint in damp, rainy weather or until the surface has dried thoroughly from the effects of such weather. The tempera¬ture of the surface to be painted and of the surrounding air shall be maintained between 45 F and 90 F during the application and drying period. Surface to be painted shall be clean, dry, smooth, and protected from dampness. Each coat of paint shall be applied smoothly, worked out evenly, and allowed to dry complete¬ly before the subsequent coat is applied.

Finished work shall be uniform and of the approved color. It shall completely cover the surface, be smooth, and be free from runs, sags, clogging, or excessive flooding.

Make edges of paint adjoining other materials or colors sharp and clean. All painting shall be completed according to the manufacturer's written instructions.

9 1.4.3 Color Schedule: The Contractor shall submit for Resident Engineer approval samples for each color required.

9 1.4.4: Spray painting may be accomplished only during wind velocity conditions of 0 to 5 mph. For wind velocity conditions over 5 mph, protection shall be provided to keep wind from depositing paint on nearby structures, including parked vehicles and passing airplanes. Contractor shall be solely and totally responsible for any clean up, repainting or other adjustments required by paint being deposited by wind of any velocity on any structures, vehicles or air¬planes.

9 1.5 Quality Assurance:

9-1.5.1 Inspection: All work, where a coat of material has been applied, must be inspected and approved by the Resident Engineer prior to the application of the succeeding specified coat.

DIVISION 32 – EXTERIOR IMPROVEMENTS

SECTION 32 01 17.61 –

CRACK AND JOINT SEALING FOR ASPHALT PAVEMENTS

PART 1 GENERAL

1.01 SECTION INCLUDES

Elastomeric hot applied crack and joint sealing in asphalt or portland cement concrete.

1.02 RELATED SECTIONS

A. [Section 32 17 23.13 Pavement Marking]

C. [Section 32 12 36.19 Pavement Sealing]

D. [Section 32 01 17.01 Repairing Asphalt Concrete Pavements]

E. [ ]

1.03 REFERENCES

American Society for Testing and Materials (ASTM)

1. D 6690-01 Specification for hot applied crack and joint sealant 2 1190 Specification for Concrete Joint Sealant, Hot Applied Elastic Type

2. D 3405 Specification for Joint Sealants, Hot Applied, for Concrete and

Asphalt

3. D 5329 Test Methods for Sealants and Fillers, Hot Applied, for Joints and Cracks in Asphalt and Portland Cement Concrete Pavements

1.4 SYSTEM DESCRIPTION

A. Provide installation of sealant.

1.05. SUBMITTALS

Product Data

1. Submit manufacturer's printed Product Data Sheet.

A.

Certification

1. Contractor to submit a letter stating that equipment used to heat the material meets requirements of this specification.

B. Test Reports

1. Upon request the contractor will submit manufacturer's test results on products used.

1.7 PROJECT/SITE CONDITIONS

A. ENVIRONMENTAL REQUIREMENTS

1. Apply sealant only to clean, dry, properly prepared cracks and joints.

2. At ambient temperatures below forty (40) degrees F. use a hot compressed air lance to achieve clean, dry, warm space for sealant installation.

1.8 EXISTING CONDITIONS

A. Cracks and joints under one quarter (1/4) inch width are not covered under this specification unless stipulated in writing by Architect/Engineer.

B. Cracks and joints under one quarter (1/4) inch are to be addressed by means of routing and/or the use of a hot compressed air jet to remove all loose materials and assure the sidewalls of cracks are clean and dry.

PART 2 PRODUCTS

THE SPECIFIER MAY CHOOSE TO HAVE A CLOSED PROPRIETARY

SPECIFICATION [ B ] OR AN OPEN PROPRIETARY SPECIFICATION [ C ] BY

SELECTING ONE OF THE FOLLOWING:

2.1 MANUFACTURER

A. Neyra Industries, Inc., Cincinnati, Ohio: Thermo-Seal PLS, Thermo-Seal

Spec+Plus DF

1. Materials are listed as a standard of quality.

[ B. No substitutions allowed.]

[ C. No other material will be acceptable unless approved by Architect/Engineer in writing ten (10) days prior to bid date.]

2.2 MATERIALS

A. Sealant: Thermo-Seal PLS or Thermo-Seal Spec+Plus DF

1. A hot applied elastomeric crack/joint sealant for asphalt and concrete pavements.

2.3 EQUIPMENT

A. Melt down the sealant in a kettle or melter constructed as a double boiler.

The space between the inner and outer shells filled with a high flash heat transfer oil or other indirect heating means.

B. The kettle to be used must have constant agitation any time material is over three hundred (300) degrees F. The kettle must have temperature monitoring capabilities.

C. Roofing kettles or other direct fired melters are not acceptable for these materials.

PART 3 EXECUTION

3.1 EXAMINATION

A. Inspect existing pavement for conditions and defects that will adversely affect quality of work and which cannot be put into acceptable condition through normal preparatory work as specified.

B. Starting installation constitutes contractors acceptance of surface as suitable for installation.

3.2 PREPARATION

A. Cracks

1. Remove vegetation and all incompressibles from cracks and joints by means of hot compressed air lance.

2. Cracks and joints less than one quarter (1/4) inch in width must be routed to a minimum one half (1/2) inch by one half (1/2) inch in shape.

B. Sealant

1. Prepare sealant in specified equipment.

2. Heat sealant according to manufacturer's Product Data Sheet.

3.3 APPLICATION

A. Install heated sealant directly into cracks and joints not to exceed a four (4) inch wide band.

B. Control thickness to one eighth (1/8) inch above pavement surface.

C. Finished sealed cracks and joints will be uniformly level and all "sinkers" will be refilled to achieve flush to one eighth (1/8) inch concave surface appearance.

3.4 PROTECTION

A. Care must be taken to keep the public from work area while sealant is being installed and traffic should not be allowed to cross sealant filled cracks and joints for a period of ten (10) minutes.

B. Failure to follow manufacturer's printed recommendations could result in a severe burn hazard.

3.5 SCHEDULE

END OF SECTION

Last Updated 6-3-2015

NEYRA FORCE SEALING SPECIFICATION

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Engineered resin emulsion sealcoat slurry over new and/or aged asphalt concrete paving.

1.02 RELATED SECTIONS

A. 32 17 23.13 Pavement Marking

B. 32 01 17.61 Crack Sealing

1.03 REFERENCES

A. American Society for Testing and Materials (ASTM)

1. C 136 Method of Sieve Analysis of Fine and Coarse Aggregates

2. D 2939 Method for Testing Emulsified Bitumens used as Protective

Coatings

3. D 244 Standard Specification for Emulsified Asphalt

4. D 3910 Practices for Design, Testing, and Construction of Slurry Seal

1.04 SYSTEM DESCRIPTION

A. Provide two applications of the coating (emulsion slurry) in all areas.

B. Provide third coat in high traffic areas as shown in schedule and on drawings.

1.05 SUBMITTALS

A. Product Data

1. Submit manufacturer's printed Product Data Sheet.

A. Certification

Submit copy of certificate from manufacturer stating applicator is their authorized installer.

B. Certificate of Authenticity

Submit a certificate executed by the manufacturer of the sealer stating the specific product was placed on the pavement.

1.07 PROJECT/SITE CONDITIONS

A. ENVIRONMENTAL REQUIREMENTS

1. Apply coating when pavement temperature is at least fifty (50) degrees

Fahrenheit and air temperature is fifty (50) degrees Fahrenheit and rising.

2. Apply coating during dry weather and when rain is not anticipated within eight (8) hours after application is completed.

PART 2 PRODUCTS

2.01 MANUFACTURER

A. Neyra Industries, Inc., Cincinnati, Ohio: Neyra Force

2.02 MATERIALS

A. Sealer: Neyra Force

1. A high solids petroleum resin.

2. Minimum 47% solids – with ash of non volatile in a range of 34%-38%

3. Maximum dilution of 30 parts water per 100 parts Neyra Force

B. Crack Sealant: Thermo-Seal PLS

1. Hot applied, elastomeric type crack sealant compatible with pavement coating.

C. Pavement Primer: Polyprime (Priming is not required to obtain manufacturers warranty but may be recommended depending on condition of pavement.

1. Acrylic based primer compatible with pavement coating.

D. Sand: As recommended in printed data sheets by sealer manufacturer.

1. Washed, dry silica sand free of dust, trash, clay, organic materials or other contaminants.

2. Gradation: To have an American Foundry Society grain fineness number that is no less than fifty (50) and no more than seventy (70), when tested in accordance with ASTM C 136.

E. Mixing Water

1. Potable and free from harmful soluble salts.

2. Temperature of the water: minimum fifty (50) degrees F.

2.03 EQUIPMENT

A. Use equipment that keeps the mixture homogeneous at all times and is capable of applying required coating weights evenly over entire width of application mechanism in order to provide a uniformly coated surface.

2.04 MIXES

A. Add three (3) to five (5) pounds of sand to the emulsion and mix with power equipment to a homogeneous condition. (Sand to be added after water)

B. Add water to the coating mix as required for application not to exceed thirty

(30) percent of emulsion.

PART 3 EXECUTION

3.01 EXAMINATION

A. Inspect existing pavement surfaces for conditions and defects that will adversely affect quality of work, and which cannot be put into an acceptable condition through normal preparatory work as specified.

B. Do not place coating over unsound oil spots softened by fuel or oil. If this condition exists, notify Architect/Engineer/owner.

C. Starting installation constitutes Contractor's acceptance of surface as suitable for installation.

SPECIFIER SHOULD SELECT ONE OR BOTH SECTIONS UNDER PREPARATION

BASED ON JOB REQUIREMENTS. (AGED/NEW PAVEMENT)

3.02 PREPARATION - AGED PAVEMENT

[ A. Repairing Asphalt Concrete Pavement: Repair areas shown in schedule.]

[ B. Crack Sealing: Apply crack sealant as detailed in Section 32 01 17.61.]

C. Cleaning

1. Clean pavement surface prior to applying coating.

D. Protection

1. Protect adjacent curbs, walks, fences, and other items from receiving coating.

E. Priming Oil Spots

1. Clean oil spots and treat with primer.

2. (If priming is required apply Polyprime at a rate of .03-.06 gallons per square yard, as per Polyprime data sheet.)

3.03 PREPARATION - NEW PAVEMENT

A. Curing

1. Allow new asphalt to cure at least thirty (30) days before applying pavement coating.

B. Cleaning

1. Clean pavement surface prior to applying primer coat and coating.

C. Protection

1. Protect adjacent curbs, walks, fences, and other items from receiving primer and coating.

3.04 APPLICATION

A. Apply all coats uniformly at a rate of 0.14 - 0.17 gallons per square yard per coat using mixed diluted material.

B. Allow each coat to cure sufficiently to take traffic without scuffing.

C. Allow final coat to cure a minimum of twenty four (24) hours under good drying conditions before allowing traffic.

3.05 CLEANING AFTER APPLICATION

A. Remove any coating from surfaces other than those requiring coating.

3.06 PROTECTION

A. Barricade coated areas until the coating has dried sufficiently for traffic.

3.08 SCHEDULE

END OF SECTION

1. PRODUCT NAME

Neyra Force®

2. MANUFACTURER

Neyra Industries, Inc.

10700 Evendale Drive Cincinnati, Ohio 45241

Limitations:

In the liquid state, Neyra Force must be protected from freezing. Do not store where temperature exceeds 120°F.

4. INSTALLATION

Preparatory Work:

The aspha l t sur face must be structurally sound, surface cured and free from all loose or foreign matter prior to the application of Neyra Force.

Methods:

Neyra Force can be applied by spray, squeegee, brush or mechanical equipment designed for this purpose.

Due to the heavy body of the Neyra Force slurry mix, application by means of specialized equipment is recommended.

This equipment can be of two types, high volume positive displacement airless spray or mechanical squeegee. Both types must be capable of keeping material thoroughly mixed and homogenous throughout the application process.

All equipment used must be capable of supplying a sufficient quantity of material for uniform application over the entire width of the application mechanism to provide a uniformly coated surface.

Mix Design:

Neyra Force is a highly concentrated material intended to be to be mixed with water and mineral aggregate to form a ready to use pavement sealer.

Do not over dilute.

3. PRODUCT DESCRIPTION

Neyra Force is a petroleum resin emulsion specifically formulated as a weather protective, water resistant coating for all asphalt surfaces.

Packaging:

Bulk shipments made in tank trucks.

Color:

In the liquid state, Neyra Force is a reddish brown emulsion. When dry, Neyra Force is a deep black coating.

Basic Uses:

Neyra Force extends the service life and reduces maintenance costs of asphalt pavements, protecting them from the destructive effects of water, sunlight and oxidation. When mixed and applied according to manufacturer’s recommendations, Neyra Force provides a new looking, long lasting surface that is easy to clean.

Composition:

Neyra Force is a concentrated, mineral colloid stabilized emulsion fortified with our proprietary blend of high molecular weight polymer and petroleum resins. This binder base is emulsified in our high temperature, high shear, state-of-the art manufacturing process. The superior fusion of the quality raw materials creates a homogeneous coating capable of high sand loads, providing an exceptionally tough, long lasting, skid resistant surface.

• Superior Bond: Neyra Force is chemically reinforced to enhance the adhesion to the asphalt pavement, rejuvenating the surface and preventing raveling.

• Tough & Durable: Contains proprietary high molecular weight petroleum resin which creates tough and long lasting protection.

• Protect & Beautify: Neyra Force forms a tight seal creating an impenetrable barrier that protects against the destructive effects of sun, water & chemicals, giving your pavement a deep black color and making it easier to clean.

• Environmentally Friendly: Neyra Force is a low VOC, non-flammable coating that emits no obnoxious odors or fumes and contains no coal tar.

All sand used should be clean, dry, pure silica sand, free of contaminants.

Medium fine sand with an A.F.S. rating of 50 to 70 gives best results. There should be no more than 2% retained on 30 mesh or coarser, no more than 10% retained on 140 mesh and no more than 0.3% retained on 200 mesh.

Application:

For use over sound asphalt pavement, the following application procedures are recommended for best results:

Use only Neyra additives specifically designed for Neyra Force. Do not use other additives. They are not chemically compatible with Neyra Force and will degrade the emulsion.

One gallon of concentrate will cover 90 square feet per coat. Multiply square yards of surface x 0.1 to determine gallons of concentrate per coat.

Per 100 gallons of Neyra Force Water Sand Yield 30 gal. 300-500 lbs. 144 -153 gal.

Application Rate per Coat Gal/SY

Concentrate .10

Mix .13 - .15

.011

.014 - .016

Gal/SF

Neyra Force Product Data 106-15

Professional Grade

Phone: 513-733-1000 Toll-Free: 800-543-7077 Fax: 513-733-3989 Email: info@neyra.com Website: www.neyra.com

Product Data 106-15

Coverage rates can vary with the application method and the age, texture, and porosity of the pavement to be sealed. For low to moderate traffic areas, we recommend applying two full sand slurry coats. For high traffic areas, a third coat is advised. For highly oxidized surfaces, a primer, Polyprime (Product Data Sheet 155) is recommended. Each coat must be dry before additional applications. On a typical parking lot, a combination of application systems could be used. For example, two coats for the parking stalls and a third for the drive lanes where most of the wear occurs.

Application must be made when ambient temperatures and pavement temperatures are above 50°F. Good drying conditions above 50°F are required during the subsequent 8 hours and no temperatures below 50°F should be anticipated for 48 hours. Night time application is not recommended.

It is recommended that the area over which the application is made be opened to use only after trial shows it to be sufficiently dried to accept regular traffic. Lower temperatures, high humidity, clouds or shade and lack of air movement slow drying time.

Precautions:

Do not apply Neyra Force over sealers which contain gilsonite. Neyra Force is not recommended for use on portland cement concrete.

Keep out of reach of children.

Container should be closed when not in use. Contains petroleum distillates. Avoid breathing vapor or prolonged contact with skin or eyes. Flush immediately with water.

New asphalt should be allowed to cure for a minimum of 30 days prior to application and must not exhibit ribboning, crawling, nor show oil rings when 1 gal. of clean water is poured onto the surface.

Protect wet Neyra Force at all times from freezing and rain.

Consult specific Neyra material safety data sheet before use.

5. MAINTENANCE

As a rule, a clean, well marked parking lot is safer and will last longer.

Occasional flushing with water or the use of a contract cleaning service will help to retain an attractive appearance.

6. TECHNICAL DATA

Applicable Standards:

Neyra Force meets the composition and performance standards listed below when tested according to the following ASTM methods:

Environmental Considerations:

N ey r a Fo rc e i s c o n s i d e re d non-hazardous when tested according to the EPA’s TCLP (Toxicity

Drying Time:

When tested according to ASTM D2939, “set to touch” in 1 hour, exhibit “final set” in less than 8 hours.

Non‑Flammability:

The cured coat ing shows no tendency to flash or ignite.

Adhesion & Resistance to Water:

The cured coating exhibits no penetration, blistering, loss of adhesion, nor tendency to re-emulsify after immersion for 24 hours.

Physical Composition:

Neyra Force meets the following requirements when tested according to ASTM D2939:

Max Min

Non-Volatiles %

Ash of Non-Volatiles %

Specific Gravity

- 47

Requirements

Water % 53 -

1.1

Neyra Force

Characteristic Leaching Procedure).

Neyra Force is a water based material containing less than 10g/L (0.08 lbs./gal.)

VOC content.

7. TECHNICAL SERVICES

Material safety data sheets, product and application recommendations, as well as assistance with special situations and field service are available upon request. Special project submittals are available through Customer Service.

8. WARRANTY

The above spec i f i ca t ions on product usage are believed to be true and accurate. Neyra Industries, Inc. Guarantees that all materials manufactured comply with quality standards as described in the product data sheets. Because the application, handling, weather, workmanship,and equipment are beyond the control of this manufacturer, only the quality of the products as shipped is guaranteed. In no case will the liability of Neyra Industries, Inc. exceed the purchase price of the shipped materials.

9. ADDITIONAL INFORMATION

Neyra Industries, Inc. manufactures a full line of asphalt pavement maintenance and recreational surface products as well as application equipment sold and distributed nationally at our plants and through distributors and contractors.

To find the supplier most convenient to you, please contact us.

Caution: Application of this product in marginal weather conditions or improper mix designs can result in premature wear or product failure.

Sampling of Bitumous Materials Standard Test Methods for Emulsified Asphalts Testing of Bitumous Materials Standard Test Methods for Emulsified Bitumens used as Protective Coatings

D140:

D244:

D529:

D2939:

Neyra Industries, Inc.

10700 Evendale Drive Cincinnati, Ohio 45241

Phone:

Toll Free:

Fax:

Email:

Website:

513-733-1000 800-543-7077 513-733-3989 info@neyra.com www.neyra.com

1. PRODUCT NAME

AcrylaSealTM

2. MANUFACTURER

Neyra Industries, Inc.

10700 Evendale Drive Cincinnati, Ohio 45241

• Ready to Use: A convenient, fast and easy one-component system.

• Good Adhesion: A penetrating surfactant formulation ensures bonding to the surface.

• Excellent Resilience: A superior synthetic polymer compound provides elasticity. Contains no asphalt – will not track.

• Fast Setting: Less waiting time required before sealcoating.

• Rubberized: Improves pliability in adverse weather conditions.

• Less Shrinkage: A high solids formulation prevents abnormal shrinkage.

Phone:

Toll Free:

Fax:

Email:

Website:

513-733-1000 800-543-7077 513-733-3989 info@neyra.com www.neyra.com

3. PRODUCT DESCRIPTION

AcrylaSeal is a cold applied, fuel resis-tant, high solids acrylic crack sealant. It is formulated to be fast setting and re-main flexible over a wide range of tem-peratures. Recommended for asphalt and concrete surfaces.

Composition:

As shipped, AcrylaSeal is an acrylic emulsion.

Limitations:

Do not allow to freeze. Do not store in direct sunlight or where temperature exceeds 120°F.

4. INSTALLATION

Preparatory Work:

Crack must be dry, clean and free of dust and loose material.

Methods:

May be used directly from 1 gal.

spouted jug, pour pot or suitable mechanized equipment.

Mix Design:

Use full strength, do not dilute.

Application:

Fill crack with AcrylaSeal; squeegee any excess flush with pavement surface.

Allow to dry.

One gal. of AcrylaSeal fills the follow-ing approximate lineal feet:

Precautions:

Keep out of reach of children.

Container should be closed when not in use. Avoid breathing vapor or prolonged contact with skin or eyes.

Consult specific Neyra material safety data sheet before use.

5. MAINTENANCE

Tools and equipment may be cleaned promptly with water.

6. TECHNICAL DATA

Applicable Standards:

AcrylaSeal Pourable Crack Sealant meets the performance standards of

ASTM D1190.

Environmental Considerations:

AcrylaSeal is considered non-hazardous when tested according to the EPA’s TCLP (Toxicity Characteristic Leaching Procedure). AcrylaSeal is a water-based material containing less than 50g/L (.42 lbs./gal.) VOC content.

Performance Requirements:

Refer to chart on reverse.

7. TECHNICAL SERVICE

Material safety data sheets, product and application recommendations, as well as assistance with special situations and field service are available upon re-quest.

1/2” 200 100 50

1/4” 400 200 100

1/8” 800 400 200

1/8” 1/4” 1/2” Width

Depth

AcrylaSealAcrylaSealAcrylaSealAcrylaSealAcrylaSeal Product Data 142-05

Acrylic Pourable Crack SealantAcrylic Pourable Crack SealantAcrylic Pourable Crack SealantAcrylic Pourable Crack SealantAcrylic Pourable Crack Sealant

Professional Grade

Packaging:

Available in 1 gal. spouted jugs.

Color:

AcrylaSeal is available in black and gray.

Basic Uses:

AcrylaSeal provides a tough, resistant barrier against moisture for cracks up to ½” in width on asphalt and concrete pavements.

8. WARRANTY

The above specifications on product usage are believed to be true and accu-rate. Neyra Industries, Inc. guarantees that all materials manufactured comply with quality standards as described in the product data sheets. Because the application, handling, weather, workman-ship and equipment are beyond the con-trol of this manufacturer, only the qual-ity of the products as shipped is guar-anteed. In no case will the liability of Neyra Industries, Inc. exceed the pur-chase price of the shipped materials.

9. ADDITIONAL INFORMATION

Neyra Industries, Inc. manufactures a full line of asphalt pavement maintenance and recreational surface products as well as application equipment sold and dis-tributed nationally at our plants and through distributors. To find the sup-plier most convenient to you, please contact us.

Neyra Industries, Inc.

10700 Evendale Drive Cincinnati, Ohio 45241

Phone:

Toll Free:

Fax:

Email:

Website:

513-733-1000 800-543-7077 513-733-3989 info@neyra.com www.neyra.com

PERFORMANCE REQUIREMENTS

* Note 1: Recovery measured after 100% elongation.

Test ResultsASTM Test Method

Elongation, PercentD 638

Recovery, PercentNote 1*

Low Temperature FlexibilityD1737

D5 Penetration 25

D1190 0Flow at 1400 F

Gasoline ResistanceD466

G53 Artificial Weathering (1,000 Hours)

-100 F, 1/2” Mandrel, Pass

24 Hour Immersion, Pass

250% @ 730 F 200% @ 320 F

90% @ 730 F 90% @ 320 F

No Cracking No Loss of Adhesion

No Blistering

Product Data 142-05

AcrylaSealAcrylaSealAcrylaSealAcrylaSealAcrylaSeal resins, select oils and stabilizers.

Thermoflex contains extremely durable, high temperature resistant elastomeric compounds.

Limitations:

Do not overheat material. Do not apply to wet or dirty cracks. Not recommended for cracks over 1" wide.

Do not store in direct sunlight or where temperature exceeds 120°F.

4. INSTALLATION

Preparatory Work:

Crack or joint must be properly pre-pared prior to installation of Thermoflex by means of routing and/or the use of a hot compressed air jet to remove all incompressibles and assure the sidewalls of crack are clean and dry.

Methods:

Thermoflex should be heated in a ves-sel designed for heating hot pour crack sealants. Some means of agitation and monitoring of temperature are recom-mended. The range of safe heating tem-perature for the product is between 350-400°F. Overheating Thermoflex beyond this recommended range can degrade the material and create a fire hazard. Thermoflex is suitable for use in a direct fire melter or an oil-jacketed double boiler. It is also an excellent product for use through pumping type kettles.

Precautions:

Extreme care must be taken with hot applied sealants. A long sleeved shirt, long pants, gloves and face protection must be worn. Severe burn hazard.

Keep out of reach of children. Consult specific Neyra material safety data sheet before use.

1. PRODUCT NAME

ThermoflexTM

2. MANUFACTURER

Neyra Industries, Inc.

10700 Evendale Drive Cincinnati, Ohio 45241

Phone:

Toll Free:

Fax:

Email:

Website:

513-733-1000 800-543-7077 513-733-3989 info@neyra.com www.neyra.com

3. PRODUCT DESCRIPTION

Thermoflex is a premium, single com-ponent, hot applied, asphalt/rubber joint and crack sealant. Furnished as a solid, it is an elastomeric sealant which is com-patible with and bonds aggressively to clean and dry concrete or asphalt pave-ments. It is designed to be effective in a wide range of climates. It is a true di-rect fire product capable of being re-heated and is especially effective under sealcoats, slurry seals and overlays be-cause it will not bleed through.

Product Data 147-06

Professional Grade ThermoflexThermoflexThermoflexThermoflexThermoflex Crack Crack Crack Crack Crack /Joint Thermo-Sealant/Joint Thermo-Sealant/Joint Thermo-Sealant/Joint Thermo-Sealant/Joint Thermo-Sealant

3/4” 12 5.5 4.5

1/2” 16 8 5.5

1/4” 32 16 12

1/4” 1/2” 1” Width

Depth

1”

3/4”

4.5

234.58

Mix Design:

Blocks of Thermoflex are formulated as a single component system. Do not add to or mix with any other material.

Application:

Install heated sealant directly into cracks/joints not to exceed a 4 inch wide band. Thickness should be controlled to not more than 1/8 inch above pave-ment surface. Finished sealed cracks and joints will be uniformly level. Refill to achieve a flush to 1/8 inch concave sur-face appearance. One lb. of Thermoflex will fill the following lineal feet:

Packaging:

Available in 30 lb. white cardboard boxes. One skid contains 70 boxes.

Color:

Ther…