SECTION C -- DESCRIPTIONS AND SPECIFICATIONS

PMIS #306453

C.1 STATEMENT OF WORK

STATEMENT OF WORK

FACILITIES (Water Treatment Systems) Auto Dialers

LAKE MEAD NATIONAL RECREATION AREA (NRA)

Part I – Purpose

The purpose of this work order is to enable the National Park Service (NPS) to obtain quality replacement auto dialers for water and wastewater treatment systems parkwide. The new units shall be replacements of existing RACO Verbatim four channel systems. Purchased by the contractor delivered to NPS. The new units will be instated by NPS personnel.

These areas are within Lake Mead National Recreation Area. A map of this area may be viewed at: http://www.nps.gov/lame/lmnra.pdf.

All systems are in good condition.

Part II – Background These units are used parkwide for alarm notifications by way of phone landlines of events such as power outages, high level and low level in the water treatment systems.

Part III – Description This project entails the procurement of 21, 4 channel auto dialers, similar or equal to specifications/features of RACO Verbatim auto dialers. This auto dialer shall continuously monitors preset alarm points. If it senses an alarm condition at a monitored point, the system automatically dials a list of up to 16 pre-programed telephone numbers, calling until it gets an answer. When the call is answered and acknowledged, the system reports the alarm location and status via voice messages that are digitally pre-recorded. Anything that can be spoken is is accurately stored in memory, from names and numbers to technical terms and detailed instructions. Shall work with any standard touch-tone phone, and talk to personnel using built-in microphone. Unit shall have back-up battery that provides up to 20 hours of continuous operation in the event of power loss.

-Alarm inputs: 4 -Alarm notifications: 16: 60 digits each -Relay outputs: 4 -Sound monitor: built-in microphone -Power monitor: no -Power: 120 VAC -Backup power: 6V, 4-Ah battery, 20 hour battery life -Dimensions: 11.875”H x 9.75”W x 5”D – must fit into existing housing units -Operating temperature: 20 to 130F

The procurement will include the following:

21, 4 channel auto dialers.

Contractor Requirements Deliver 21 new auto dialers.

Performance Period: Delivery 90 days.

Delivery Address: Lake Mead National Recreation Area, 101 Katzebach Drive, Boulder City, NV 89005.