Specifications for Replacement Self Cleaning Filter
The unit shall be designed and fabricated to the latest version of the ASME Section VII Div 1 Boiler and Pressure Vessel Code and have the required U-Stamp
The unit shall come with the following documents Pressure Vessel, Heat Exchanger, & Dewar Design & Fabrication Documentation:
o Photo or Etching of Pressure Vessel Data Plate o Manufacturer’s Data Reports (U-forms for ASME B&PV vessels) o Fabrication Drawings o Repair or Alteration History ( R-forms for ASME B&PV vessels) o Operating History o Design Calculations And Specifications* o Mill Test Reports & Impact Testing Results* o Inspection & NDE Reports* o Hydrostatic or Pneumatic Test Reports* o WPS, PQR, and WPQ*
The vessel shall be designed for cooling tower water usage The vessel shall be designed for a MAWP or 150-psig @ 200F The filter assembly shall have a 100-micron efficiency rating The filter assembly shall have a minimum capacity of 500-gpm The filter assembly will be mounted vertically Inlet and Outlet nozzles shall have 6” Class 150# Raised Face flanges located 34.5” apart (Note, if the nozzles distance dimension is not met then the cost of modifying existing piping will be a contributing factor in the cost decision)
Inlet and Outlet nozzle loads shall be required to support its own water filled weight