About this file

This specifications document outlines the technical requirements for a diesel generator procurement by the State of California (Contract P25-0815) to power equipment with complete installation services. The generator must be rated at 250 kW at 0.8 power factor with 480Y, 3-phase, 4-wire, 60 Hz voltage configuration. The unit shall feature a diesel engine operating at 1800 RPM with ADEM A4 electronic engine controller and EPA Emergency Stationary certification, along with IBC seismic and UL2200 compliance. The generator includes an LC5034 frame with single bearing design, automatic voltage regulator, PMG excitation system, and sound-attenuated enclosure rated at 75 dBA at 23 feet with aluminum construction. The fuel system must incorporate a UL-142 double-walled fuel tank with 660-gallon capacity providing 24-hour runtime at full load, complete with low fuel alarms and tank leak control.

Installation services encompass removal of the existing generator via crane, modification of electrical stub-up and concrete pad infrastructure, placement of the new generator with crane, electrical system installation, disposal of the existing unit, initial fuel tank fill, and comprehensive generator testing. The control panel must be NFPA 110 compliant utilizing a GCCP 1.2 digital control panel with remote annunciator panel capability and a single 600-amp UL-listed circuit breaker rated at 100 percent with load-sensing/instantaneous functions. Additional specifications include 24V lead-acid engine-starting battery with UL-listed charger at 10ADC maximum charging current, jacket water heater for expedited cold starts, seismic-rated integra isolators, critical grade exhaust silencer with flex connector and rain cap, and NFPA 110 alarm contacts.

View the file

Other files

File Type Posted
Informal_Competitive_RFQ_--_P25-0815.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Generator Specifications

Rating: 250 kW at 0.8 PF Voltage: 480Y, 3-phase, 4-wire, 60 Hz Engine: Diesel, 1800 RPM, ADEM A4 Electronic Engine Controller Certification: EPA Emergency Stationary Certified, IBC Seismic, UL2200

Cooling System:

Unit Mounted Radiator

Starting System:

Electric Starting Motor 24V Lead Acid Engine-Starting Battery UL Listed Battery Charger:

10ADC Maximum Charging Current NFPA 110 Alarm Contacts

Jacket Water Heater (to facilitate quicker starting times) Alternator End & Attachments:

LC5034 Frame Generator, Single Bearing, Rated for 105°C Temperature Rise Automatic Voltage Regulator Space Heater PMG Excitation System

Enclosure & Mounting System:

Sound Attenuated Enclosure rated at 75 dBA at 23 feet, Aluminum Construction (Exhaust elbow and vent pipe extensions shipped loose for installation in field by Contractor) Seismic rated integra isolators

Exhaust System:

Critical grade exhaust silencer with flex connector, NBG kits, and raincap

Fuel System:

UL-142 Double Walled Fuel Tank Base with 660 Gallon Capacity (24-hr run time @ 100% load) Fuel Level Alarms: Low Fuel, Tank Leak

Control Panel:

GCCP 1.2 Digital Control Panel NFPA 110 Compliant Remote Annunciator Panel (requires Belden 9841 cable; cable by others) Circuit Breakers:

Qty. (1)600A Circuit Breaker, UL-Listed, 100% Rated, with LS/I (S or I) Functions

INSTALLATION

EXTENDED DESCRIPTION:

One Lot Labor and Materials to perform the following:

• Remove existing generator with crane

• Modify existing electrical stub up and concrete pad for new generator

• Set new generator with crane

• Install electrical for new generator

• Dispose existing generator

• Initial fuel tank fill

• Test generator