Specifications.pdf

PDF 894 KB Posted

Attached to
Fencing and Concrete Foundation Replacement Federal contract opportunity
Solicitation number
1232SA25R0010
Issued by
Department of Agriculture Agricultural Research Service

About this file

The file is a detailed technical specifications document for a sheep housing barn improvement project at the USDA National Animal Disease Center in Ames, Iowa. The specifications cover multiple sections including demolition, site improvements, concrete work, custom penwork, pen and stall equipment, plumbing, and electrical systems. Key requirements include removing existing waterers and fence portions, installing new wire fences with wood posts, pouring concrete foundations, creating custom metal components, installing nipple waterer systems for sheep, and completing associated plumbing and electrical infrastructure.

The technical specifications provide comprehensive instructions for contractors, including materials specifications, installation methods, quality control processes, and execution standards. Sections detail requirements for materials like galvanized steel, copper piping, concrete mixtures, and electrical components. The documentation specifies precise installation techniques, such as setting fence posts, welding metal components, laying piping, and ensuring proper electrical connections, with an emphasis on durability, functionality, and compliance with industry standards like ASTM, NFPA, and NEC regulations.

View the file

Other files for this federal contract opportunity

Other files attached to Fencing and Concrete Foundation Replacement, newest first.
File Type Posted
Drawings - Amendment 02.pdf PDF
Specifications - Amendment 02.pdf PDF
SF30 - Amendment 02.pdf PDF
Statement of Work - Updated Amendment 02.pdf PDF
SF-30 - Amendment 01.pdf PDF
Site Visit Sign-In Sheet - June 18.pdf PDF
Site Visit Sign In Sheet - June 17.pdf PDF
SF-1442.pdf PDF
Calculation of Self-Performed Work.pdf PDF
ARS-372.pdf PDF
Statement of Work.pdf PDF
ARS-371.pdf PDF
Wage Determination.pdf PDF
Drawings.pdf PDF
Contractor Certification Regarding EMR.pdf PDF
Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION 01000

GENERAL REQUIREMENTS

1. SCOPE OF WORK

A. The Work as defined in these Contract Documents consists of remodeling Buildings 232 and

233 for use in housing sheet at the USDA National Animal Disease Center (NADC), Ames, Iowa 50010. The work shall include all demolition, utilities, concrete, building construction, mechanical and electrical systems as shown on the Drawings and specified herein.

2. DEFINITIONS

A. The Contracting Officer (CO) is the Government’s official representative on this solicitation/project.

B. A Contracting Officer’s Representative (COR) will be appointed to assist the CO and be the principal contact with the CONTRACTOR during this project.

The COR will not have authority to approve any material changes in the contract terms and conditions, such as changed conditions, modifications, change orders, extension of completion date, etc.

C. The OWNER as referenced in the technical specifications and on the Drawings, is the US

Government and is represented by the CO and COR.

3. CONSTRUCTION AREA/SITE ACCESS

A. Access to the OWNER’S site is controlled by security fence and visitor check-in/check-out system. CONTRACTOR’S employees shall sign in and out at the NCAH guard station (Gate #1) each workday. All CONTRACTOR’S vehicles and those of his employees entering the Center compound shall display visitor tags provided by NADC.

B. The CONTRACTOR shall use service roads and access routes approved by the COR.

C. The CONTRACTOR shall maintain a list of employees on the jobsite and a log of the hours worked. The log will be kept in an accessible location approved by the COR. Wage rates, EEO poster and wage poster may be displayed on a board at the same location.

D. Work shall be confined to the area identified on the Drawings. Unless accompanied by a NADC employee, the CONTRACTOR, Subcontractors, and their employees shall not enter facilities not specifically, part of this project. Reasons include, but are not limited to, disease control and safety and health requirements.

E. CONTRACTOR’S employee parking will be on gravel roadway adjacent to the work sites or as arranged with the COR.

4. COORDINATION

A. CONTRACTOR shall coordinate his activities and provide information as required for other portions of the Project.

B. The CONTRACTOR shall recognize that the OWNER's facilities will remain in operation during the construction period. Animals will relocate from work site prior to work commencing.

C. The CONTRACTOR shall maintain exits and passageways in a continually usable condition and inform the COR of potential conflict.

E. The CONTRACTOR shall provide the CO with a Construction Schedule at the beginning of construction activities. The schedule shall meet the CO’s requirement for occupancy of the facility. The schedule shall be updated by the CONTRACTOR no less than once monthly.

5. FIELD ENGINEERING

A. The soil type under this building has been assumed to have a soil bearing capacity of 2500 pounds per square foot.

B. OWNER shall employ a testing laboratory to perform needed soil testing and inspection if deemed necessary. CONTRACTOR may choose to employ a testing laboratory.

C. CONTRACTOR shall:

1. Lay out site of the Work relative to existing features shown on Drawings.

2. Verify grade lines and levels shown on Drawings and report any inconsistencies to

COR before starting work.

6. EXISTING FACILITIES

A. Any damage caused by the CONTRACTOR to existing facilities shall be replaced by the CONTRACTOR at no expense to the OWNER.

B. Underground Utilities

1. Existing Utilities and Structures

a. The CONTRACTOR shall verify the locations of existing utilities before starting trench cutting operations. Excavation shall be performed by hand digging around utilities to locate and prevent rupture or breaking of lines.

Cost of repairing any damages to existing utilities shall be paid by the CONTRACTOR without expense to the OWNER or university.

b. Existing utilities shall be adequately protected from damage due to construction by CONTRACTOR. This shall include any hand digging required, shoring, planking, support material, temporary fill or protection necessary for utilities to remain in continuous service. Temporary support and maintenance of all underground utilities encountered shall be furnished by the CONTRACTOR under the direction of the CO.

c. Existing utilities which are shown on the drawings or field located and are damaged by the CONTRACTOR shall be repaired or replaced, at the COR’s sole option, entirely at the cost of the CONTRACTOR. Where damage necessitates a utility outage, CONTRACTOR shall work continuously on a 24-hour, around the clock basis until the damaged utility is placed into service again. All costs to be the responsibility of the CONTRACTOR.

d. If existing utilities are encountered during construction which are not shown on plans, and which have not been field located prior to encountering same, CONTRACTOR shall immediately stop work in that area and notify COR. COR will decide as to nature of utility and direct CONTRACTOR as to what action is to be taken.

e. No valve, switch or other control of the existing utility systems shall be operated for any purpose by the CONTRACTOR without prior approval of the COR.

f. CONTRACTOR shall document on as-built drawings the location and invert elevations of encountered utilities and every 50 feet of new utility installations.

Measurements shall be taken in plan from permanent structures such as exterior building walls. Final acceptance of contract shall be contingent upon as built approval from the COR.

C. Lawn Areas

1. CONTRACTOR's vehicles may not be driven into lawn areas without prior approval of the COR. The CONTRACTOR shall be held responsible for damages if these procedures are not followed.

2. Lawn areas which are disturbed by construction shall be repaired by and paid for by the CONTRACTOR.

7. REGULATORY REQUIREMENTS

A. Perform all Work in accordance with the latest editions of the Uniform Building Code with all current revisions.

B. Where references are made to Federal, State, technical association or other specifications and standards, the latest editions that are in effect at the date shown on the Drawings and Specifications shall apply. If such specifications or standards are revised prior to completion of any part of the Work to which such revision would pertain, CONTRACTOR may, if approved by COR perform such Work in accordance with the revised specifications or standards.

C. SAFETY AND HEALTH

1. The work shall be governed by applicable provisions of the general law, including the latest amendments of the following:

William-Steiger Occupational Safety & Health Act of 1970, Public Law 91-596.

Part 1910 - Occupational Safety & Health Standards, Chapter XVII of Title 29, Code of Federal Regulations.

Part 1518 - Safety and Health Regulations for Construction, Chapter XIII of Title 29, Code of Federal Regulations.

D. ACCIDENT PREVENTION

1. The safety provisions of applicable laws, building and construction codes shall be observed. Machinery, equipment and all hazards shall be guarded or eliminated in accordance with the safety provisions of the latest edition of the Manual of Accident Prevention in Construction, published by the associated General Contractors of America, to the extent that such provisions are not in contravention of applicable laws.

E. Fire Protection

1. During the construction period provide fire protection. Provide one (1) U.L. listed multipurpose dry chemical fire extinguisher (2A20BC) rating on each floor. This requirement is in addition to the OWNER's present equipment.

2. Shields of noncombustible material shall be used when welding or cutting is done.

3. Preparation of flammable compounds inside the building is prohibited.

4. Gasoline and other flammable and volatile fluids having low flash point and ignition temperatures shall not be stored or handled in the building except in U.L. listed safety cans. Reserve flammable liquids in barrels should be stored well away from the structure and kept under lock and key.

8. CONSTRUCTION CONFERENCES

A. Weekly progress meetings shall be held at the jobsite with the COR.

9. SHOP DRAWINGS AND SUBMITTALS

A. Where called for in the Technical Specifications, the CONTRACTOR shall submit Shop Drawings and Technical Submittals for review and approval by The COR prior to delivery of materials to the site.

B. The CONTRACTOR shall submit a minimum of one (1) copies of all Shop Drawings, samples, or other required submittals to the COR for review. Two (2) copies will be retained by the COR for NADC and CO files, and for project inspection. Submittals delivered to COR in PDF format via email.

C. Contracting Officer’s Representative (COR) review is for general conformance with design concept and Contract Documents. Markings for comments shall not be construed as releasing CONTRACTOR from compliance with Contract Documents. CONTRACTOR is responsible for details and accuracy, for confirming and correlating quantities and dimensions, for selection of fabrication processes, for technique of assembly, and for performing work in a safe manner.

10. SUBSTITUTION

A. General

1. The solicitation assumes all items in the CONTRACTOR’S bid are in compliance with the Drawings and Technical Specifications. Prior approval of substitutions or additional products are handled as a modification of the solicitation by the CO.

2. CONTRACTORS are reminded this approval process requires time for the CO to consult technical resources and judge the merits of any proposed substitution.

Substitutions may not be considered if adequate time is not available to notify plan holders in a timely manner.

B. Substitutions After Letting

1. COR will consider only those proposals for substitutions that are accompanied by complete technical data and all other required information.

2. COR will consider substitutions for those products specifically required under the following conditions. Proposed substitution:

a. Is shown by written evidence or certified as superior to what was specified as to construction, efficiency, and utility.

b. Is accompanied by written evidence of equality or difference in availability.

c. Is accompanied by written evidence of equality or savings in price, and if difference in price, Contract shall be altered by Change Order to credit OWNER with all savings. OWNER will not be liable for additional costs due to substitutions.

d. Shall be coordinated throughout the Work by CONTRACTOR.

3. Decisions of COR are final with respect to approval of substitutions.

C. Contract Closeout Submittals

1. Instruction Manual

a. Upon completion of the Work and before final acceptance, prepare a loose-leaf binder containing all installation, instruction, and maintenance manuals and literature supplied with equipment and materials incorporated in the Work.

b. Include manufacturer's operating and maintenance instructions and parts lists, clearly designated for types and models provided.

c. Include electric panel as-installed wiring diagrams, including for each circuit: Number of poles, amperage of breakers, wire sizes, and all items on the circuit.

d. Furnish the binder to COR, who will review the contents for completeness and forward it to OWNER.

2. Maintenance Manuals

a. The CONTRACTOR shall, before final acceptance, submit three (3) copies of a bound manual for all new equipment, including full maintenance and operating instructions, parts inventory, sources of purchase and similar information.

b. The CONTRACTOR shall, upon delivery of new equipment at the project site, provide to the OWNER, one (1) copy of the maintenance and operating instructions.

11. CONSTRUCTION FACILITIES

A. CONTRACTOR may provide temporary office and may provide storage facilities as required for protection of materials and equipment in a location as directed by the COR.

B. CONTRACTOR may provide temporary telephone service to job site.

C. CONTRACTOR shall provide sanitary facilities (Kybo or similar) for employees. CONTRAC- TOR shall be responsible for regular service of such facilities and maintain them in an orderly condition.

D. Water and electrical power is available at the Site. CONTRACTOR needs to establish temporary power and water. CONTRACTOR shall provide all hoses and power cords necessary to complete the work.

E. No other utilities will be provided by the OWNER

12. MEASUREMENTS

A. Use figured dimensions on the plans in place of sealing. Before ordering any material or doing any work, the CONTRACTOR shall verify all measurements at the site and shall be responsible for the correctness of same. No extra compensation will be allowed on account of differences between actual dimensions and the measurement as shown on the Drawings;

any difference which may be found shall be submitted to the COR for consideration before proceeding with the work.

13 REMOVALS OF DEBRIS AND CLEAN-UP

A. Debris generated by demolition activity shall be removed from the job site on the same day it is generated. Disposal shall be the responsibility of the CONTRACTOR.

END OF SECTION

SECTION 01070

ABBREVIATIONS AND SYMBOLS

1. AGENCIES, ASSOCIATIONS, &

SOCIETIES

AAMA American Architectural Manufacturers Association ACI American Concrete Institute ADA Americans with Disabilities Act AEIC Association of Edison Illuminating Companies AGA American Gas Association AIA American Institute of Architects AISI American Iron and Steel Institute AISC American Institute of Steel Construction AMCA Air Movement and Control Association ANSI American National Standards Institute, Inc.

ARI Air Conditioning and Refrigeration Institute ASA American Standards Association ASHRAE American Society of Heating, Refrigeration and Air Conditioning Engineers ASME American Society of Mechanical Engineers ASTM American Society of Testing and Materials AWS American Welding Society AWG American Wire Gauge BAS Building Automation System (used interchangeably with BMS) BMS Building Management System CRSI Concrete Reinforcing Steel Institute CSI Construction Specification Institute FGMA Flat Glass Marketing Association FS Federal Specification GSA General Services Administration ICEA Insulated Cable Engineers Association IEEE Institute of Electrical and Electronic Engineers NBFU National Board of Fire Underwriters NBS National Bureau of Standards NEC National Electrical Code NEMA National Electrical Manufacturers Association NRCA National Roofing Contractors Association NRDTI National Roof Deck Technical Institute NSF National Sanitation Foundation NSPE National Society of Professional Engineers

NUCC Northeast Underground Committee OSHA Occupational Safety and Health Act PDI Plumbing and Drainage Institute PS Product Standard (NBS) PVC Polyvinyl Chloride SMACNA Sheet Metal and Air Conditioning Contractors National Association TCA Tile Council of America UL Underwriters' Laboratories, Inc.

WUCC Western Underground Committee

2. ABBREVIATIONS & SYMBOLS

/ Angle @ At AB Anchor Bolt ADJ Adjustable AL Aluminum ALT Alternate AMP Ampere APPROX Approximate ATM Atmosphere AUTO Automatic AVG Average B Beam BHP Brake Horsepower BL Building Line BLDG Building BLDR Builder BM Benchmark BP Base Plate BTU British Thermal Unit BTUH British Thermal Unit Per Hour C Celsius/Centigrade/ Channel/Coil CAB Cabinet CAP Capacity CF Ceiling Fan CFH Cubic Feet Per Hour CFM Cubic Feet Per Minute CFT Cubic Feet CI Cast Iron CIP Clean-In-Place CJ Control Joint CL Centerline CLG Ceiling CNVR Conveyor CO Cleanout COL Column COMP Compressor CONC Concrete CONST Construction CONT Continuous

01070 - 2 3/22/2025 USDA/NADC

Sheep Housing Barn Improvements

COP Coefficient of Performance CPVC Chlorinated PVC CTR Center CU Cubic CW Cold Water DAM Damper DB Dry Bulb Temperature DBL Double DF Drinking Fountain DIA Diameter DIAG Diagonal DIF Diffuser DIM Dimension DIV Division DN Down DS Downspout DTL Detail DW Drain Waste Vent DWG Drawing EER Energy Efficiency Ratio EJ Expansion Joint ELEC Electrical ELEV Elevation/Elevator EMER Emergency EQUIP Equipment EXP Expansion EXT Exterior F Fahrenheit FA Fire Alarm FD Floor Drain FDN Foundation FE Fire Extinguisher FH Fire Hydrant FLR Floor FPM Feet Per Minute FPS Feet Per Second FRP Fiberglass-Reinforced-Plastic FT Feet FTG Footing FUR Furnace GA Gauge GAL Gallon GALV Galvanized GB/GYP Gypsum Board GFCI Ground Fault Current Interrupter GPH Gallons Per Hour GPM Gallons Per Minute GRD Grade H Height/Humidistat HB Hose Bibb HDCP Handicapped HDW Hardware HE Heat Exchanger HOR Horizontal HP Horsepower HR Hour

HVAC Heating, Ventilating & Air Conditioning

HW Hot Water HZ Hertz ID Inside Diameter IE Invert Elevation IN/" Inches INSUL Insulation INT Interior KSI Kips Per Square Inch KV Kilovolt KVA Kilovolt Ampere KW Kilowatt KWH Kilowatt-Hours L Length/Light LAB Laboratory LAM Laminated LAV Lavatory LB Pound LFT Linear Foot LH Latent Heat LKR Locker LVR Louver M Motor MAX Maximum MECH Mechanical MFGR Manufacturer MH Manhole MIN Minimum/Minute MISC Miscellaneous MO Masonry Opening MPH Miles Per Hour MS Motor Starter MTG Mounting NC Normally Closed NIC Not In Contract/Not Included NO Normally Open NPT National Pipe Thread NTS Not To Scale OC On Center OD Outside Diameter OPG Opening OZ Ounce PB Pushbutton PCF Pounds Per Cubic Foot PE Polyethylene PH Phone/Phase PL Property Line PLBG Plumbing PNL Panel PR Pressure Regulator PRV Pressure Reducing Valve PSF Pounds Per Square Foot PSI Pounds Per Square Inch PT Point/Pint PVC Poly Vinyl Chloride

R Regulator/Relay/Riser RA Return Air RAD Radius REC Receptacle REF Refrigerator REIN Reinforcing RET Return RM Room RO Rough Opening RPBP Reduced Pressure Backflow

Preventer RPM Revolutions Per Minute RR Return Register/Restroom S Sanitary Sewer SA Supply Air SCH Schedule SD Supply Diffuser SECT Section SG Supply Grille SH Shower/Sensible Heat SHT Sheet SIM Similar SJ Steel Joist SQ Square SR Supply Register SS Stainless Steel STD Standard STL Steel STRUC Structure/Structural SUSP Suspended SW Switch SYM Symmetrical T Telephone/Thermostat TEMP Temperature/Tempered TIM Timer TRANS Transformer TYP Typical UH Unit Heater UR Urinal VAC Volts/Volts Alternating Current VAC Vacuum VAV Variable Air Volume VB Vacuum Breaker VDC Volts Direct Current VEL Velocity VENT Ventilator VERT Vertical VF Ventilation Fan VOL Volume W Water/Width W/ With WB Wet Bulb Temperature WF Wide Flange WG Water Gauge WH Water Heater W/O Without

WP Weatherproof WWF Welded Wire Fabric YD Yard

SECTION 02050

DEMOLITION

PART 1 GENERAL

1.01 SUMMARY

A. Section Includes

1. Removal of existing waterers

2. Removal of cross-alley concrete

3. Removal of outside above ground portions of lot fence

B. The locations of demolition have been generally described on the Drawings. Other demolition as required for the work shall be done as per these Specifications.

PART 2 PRODUCTS - No products required under this Section.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verification of Conditions

1. Examine Specifications and Drawings for description of work to be done.

2. Examine areas and conditions where Work under this Section will be done. Verify with COR extent and limits of demolition to be performed.

3.02 PREPARATION

A. Protection

1. Protect materials, items, and finishes not being removed from as much damage as possible.

2. Protect site around demolition from unnecessary damage and disruption.

3. Saw cut concrete before using jack hammer, if used.

3.03 DEMOLITION

A. Technique

1. Use means and equipment approved for this purpose by governmental agencies having jurisdiction.

B. Disposal

1. OWNER has first priority for retaining all demolished materials.

2. Demolished materials not retained by OWNER become the property of the

CONTRACTOR and shall be disposed of off-site.

SECTION 02800

SITE IMPROVEMENTS

A. Section Includes

1. New wire fences with wood posts.

B. Products Installed but not Furnished Under this Section

1. Preservative treated wood products: Posts, braces, rails, etc.

1.02 REFERENCES

A. ASAE

1. ASAE EP250.2, Specifications for Farm Fence Construction.

2. ASTM A116, Standard Specification for Metallic-Coated Steel Woven Wire Fabric

3. ASTM A121 Zinc-Coated (Galvanized) Steel Barbed Wire

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Stay-Tite Fence Manufacturing, 1409 Freiheit Road, New Braunfels, TX 78130, 888-223-

B. Max-Flex Fence Systems, U.S. Route 219, Linside, WV 24951, 800-356-5458

C. Keystone Steel & Wire , 7000 SW Adams Street, Peoria, IL 61641, 800-447-6444

D. United States Steel Corporation; 600 Grant Street, Pittsburgh, PA 15219. 412-433-1121

E. Whole Fence & Supply, 7963 Garden Road, Holland, OH 43528, 866-857-1676

2.02 MATERIALS

A. Woven Wire 7-bar, 26-inch, (0.66m) field fence

1. Top and bottom wires No. 10 ASW ga.

2. Filler and stay wires No. 12-1/2 ASW ga. at 6 inches.

3. Smooth double dipped galvanized steel wire.

B. Barbed Wire 2-strand twisted

1. No. 12-1/2 ASW ga. galvanized steel wire.

2. 4-point barbs No. 14 ASW ga. galvanized steel wire at approximately 4 inches (100 mm).

3. Conform to ASTM A 121 zinc coated steel barbed

4. Coating class

a. Class 1 for 12-1/2 ga.

b. Class 3 for 13-1/2 and 15-1/2 ga.

5. No untwisting of wire with alternating twist direction under a tensile force of:

a. 950 pounds for 12-1/2 ga. wire.

b. 850 pounds for 13-1/2 ga. wire.

02800 - 2 3/22/2025 USDA/NADC

c. 750 pounds for 15-1/2 ga. wire.

C. Bracing No. 9 smooth galvanized soft wire.

D. Smooth Line Wire. No. 9 ga. coated steel wire meeting Class 1 zinc coated wire of

ASTM A116.

E. Wood Posts

1. Species. Use of the following species of wood for all posts, unless otherwise shown on the Drawings.

Southern Yellow Pine Posts shall be given a preservative treatment in accordance with the method specified as full length treatment.

2. Quality

a. Post should be peeled, sound, straight-grained, free of decay, cracks and splits.

b. Shakes must not be in excess of 1/4 inch (6 mm) wide and 3 feet (0.9 m) long.

c. Checks permitted, provided they are not injurious.

3. Manufacture

a. Outer bark completely removed.

b. Inner bark removed from all post surfaces to be treated, except inner bark may remain in depressions.

F. Wood Braces

1. Use cleats, gate stops, and braces in the sizes shown on the Drawings

2. Use the same species and quality specified for the posts or approved by the Engineer

a. Free from knots larger than one-third the width of the piece

b. Braces may be made of posts of suitable length or of sawed lumber

c. Treat all cleats, gate stops, and any braces.

G. Staples

1. No. 9 galvanized steel wire

2. 1-1/2 inches (37 mm) long softwood posts

PART 3 EXECUTION

3.01 ERECTION, INSTALLATION, APPLICATION

A. General Fence Construction

1. Overall

a. Plumb the finished fence taut, true to line and ground contour.

2. Clearing fence line

a. Clear fence site of obstructions

b. Grade surface irregularities

c. Minimum clearance width 2 feet (0.60 m) each side of the fence centerline

d. Remove all stumps, brush, rocks, trees, or other obstructions

3. Setting posts

a. Minor variation in depth permitted to allow for alignment of post tops

b. Holes for wood posts shall be dug to full depth with a tolerance of plus or minus 3 inches

c. Wood post to be set plumb on the side on which the wire is to be fastened.

d. Posts set with the large end down

e. Backfill with concrete or sound earth thoroughly rammed in place

f. Bent or otherwise damaged posts shall be removed and replaced.

g. The tops of all posts shall be a uniform height above the ground

h. After the fence has been erected, the tops of wood posts shall be cut off to the proper elevation

i. An intersection post shall be set in line with intersection fences shown on the Drawings and braced in line with the intersection fence.

j. Both intersecting fences shall be connected to the intersection post

k. Set posts full depth and do not cut posts off to eliminate rock or other excavation

l. Remove rock where it is encountered, to provide full-depth and full-size holes.

The diameter of the holes must be at least 6 inches (150 mm) larger than the diameter of the posts.

4. Bracing

a. Horizontal braces: Install per ASAE EPP250, Fig 2 and Section 3.

1) Fasten with 3/8” x 4” steel dowels.

2) Install wire diagonals for corner/end sections.

b. Spike the wooden brace into the end, corner, anchor, or gate posts and into the next intermediate posts about 6 inches (150 mm) from the top of the respective posts.

c. Loop a cable made of a double strand of galvanized soft wire around the end, corner, anchor, or gate post near the ground and around the next intermediate post about 12 inches (300 mm) from the top.

d. After the cable has been stapled in this position, twist it until tight.

e. The staples used to hold the cable shall be not less the 1-1/2 inches (37 mm) long.

f. Leave the tool used for twisting the cable in place to permit later adjustment of bracing if found necessary.

5. Installing wire

a. Install longitudinal wires parallel and draw them uniformly taut. The vertical stay wires of the woven wire fencing should be straight and vertical.

b. Wrap the woven wire once around the post and wrap barbed wire at the end and gate posts.

c. Staple the longitudinal wire at least three times and ties these wire ends with a snug, tight twist.

d. After the fence has been erected, saw off the tops of the wood posts with a 1-to-3 pitch.

e. The bottom wire of the wire fencing must clear the found by not more than 4 inches (100 mm) or less than 1 inch (25 mm) at all locations.

f. Each horizontal strand of wire shall be wrapped completely around the end, corner, gate or intermediate braced post and securely wound about the wire leading up to the post.

g. The wire fabric shall be stretched taut and securely fastened to each post with the bottom of the fabric approximately 2 inches above ground.

h. Line posts shall not be used as stretching anchorage, unless they are anchored.

i. Firmly attach fence to each wood post by at least one staple for each horizontal strand.

6. Barbed wire

a. Install all lengths of each strand to uniform tension, uniformly spaced, and effectively anchored at corners and ends.

b. Splices in wire lengths between corners will not be acceptable.

c. Fasten each strand/post intersection with a staple.

7. Existing fence connections

a. Wherever the new fence joins an existing fence, either at a corner or at the intersection of straight fence lines, set a corner or anchor post at the junction, braced and anchored the same as herein described for corner posts.

8. Cleaning up. Remove all tools, building, equipment, debris, and excess material used during construction.

SECTION 03300

CONCRETE

1.01 REFERENCES

A. ACI

1. ACI 301-72, Specifications for Structural Concrete for Buildings

2. ACI 318-83, Building Code Requirements for Reinforced Concrete

3. ACI 347-78, Recommended Practice for Concrete Formwork

B. ASTM

1. ASTM A 615-84a, Specification for Deformed and Plain Billet-Steel Bars for

Concrete Reinforcement

3. ASTM C 31-84, Method of Making and Curing Concrete Test Specimens in the Field

4. ASTM C 33-85, Specification for Concrete Aggregates

5. ASTM C 39-84, Test Method for Compressive Strength of Cylindrical Concrete Specimens

6. ASTM C 138-81, Test Method for Unit Weight, Yield, and Air Content

(Gravimetric) of Concrete

7. ASTM C 143-78, Test Method for Slump of Portland Cement Concrete

8. ASTM C 150-85, Specification for Portland Cement

9. ASTM C 172-82, Method of Sampling Fresh Concrete

10. ASTM C 173-78, Test Method for Air Content of Freshly Mixed Concrete by the Volumetric Method

11. ASTM C 260-77, Specification for Air-Entraining Admixtures for Concrete

12. ASTM C 309-81, Specification for Liquid Membrane-Forming Compounds for

Curing Concrete

13. ASTM C 827-82, Test Method for Early Volume Change of Cementitious Mixtures

14. ASTM C 920-86. Specification for Elastomeric Joint Sealants

15. ASTM E 329-77, Recommended Practice for Inspection and Testing Agencies for Concrete, Steel, and Bituminous Materials as Used in Construction

16. ASTM C 1116-89 Specification for fiber-reinforced concrete and shotcrete

1.02 SUBMITTALS

A. Quality Control Submittals

1. Concrete strength reports: Submit 1 copies of results to COR immediately after testing. Include exact location of Work where sampled batch was deposited. Include detailed information on storage and curing of strength test specimens prior to testing.

1.03 QUALITY ASSURANCE

A. Field Samples

1. Work closely with COR to determine desired concrete finish. Prepare a small portion of each section requiring a different finish for observation by OWNER. After approval of the finish by COR, this sample section will be the reference other sections will be compared to.

2. Notify COR in sufficient time before placing concrete to allow COR to observe the beginning of each placement.

A. Portland Cement: ASTM C 150, Type I

B. Air-Entraining Admixtures: ASTM C 260

C. Mixing Water: Potable

D. Aggregates

1. Normal weight concrete: ASTM C 33

2. Coarse aggregate: Crushed stone

E. Reinforcement

1. Reinforcing bars: ASTM A 615

2. Bar grades, unless shown otherwise on Drawings.

No. 3 - No. 5: Grade 40

F. Anchor Bolts

1. 3/4” diameter, 3” embedment required

2. 10,400 lbs. minimum tension, 20,100 lbs. minimum shear

3. Carbon steel bolt by Rawl or equivalent by Hilti or MKT Fastering

G. Concrete cure and seal

1. Curing and sealer-membrane compound: Type I, Class B vehicle, meeting

ASTM C 309, to harden, dustproof, and protect against oil, grease, dilute acids, mineral salts, and fungus, Cure and Seal, by Symons.

2.03 ACCESSORIES

A. Floor control joint: Plastic tear-strip joint formers 1/4 - 1/5 slab thickness.

1. Zipcap #831, by Greenstreak.

2. Crack Controller #047, by Harbour

3. Crack Inducer, by Progress.

2.04 MIXES

A. Concrete

1. 28-day compressive strength

a. Curbs: 3000 psi

b. Slabs and all other: 3500 psi

2. Durability

a. Air entrained:

Maximum coarse aggregate Entrained air 1 ½” - 2 ½” 5% air + 1% ¾” – 1” 6% air + 1% 3/8” - ½” 7 1/2% air + 1%

b. Water-Cement ratio: Not to exceed 0.48.

3. Slump: 4” + 1”

4. Maximum coarse aggregate size: 1/5 least clearance between forms, or 3/4 minimum clear spacing between bars and forms.

5. Proportions

a. Select proportions with Method 1 or Method 2 of Section 3.8.2 of ACI 301-72.

b. Select mix to fill forms and around reinforcement without segregation or excessive bleeding of free water to the surface.

B. Patching Mortar: Use same materials as in concrete, except omit coarse aggregate in mix of up to 1 part cement, 2 1/2 parts sand, and no more water than required for handling and placing. Substitute white portland cement for some gray portland cement, as determined by trial batch, for color matching on exposed concrete.

C. One-part, pourable (gun-grade) sealant for expansion and control joints.

1. Self-leveling; ASTM C 920 Type S, Grade P, Class 25.

2. White, Vulkem 45, by Mameco.

3. Limestone or gray color, Sonolistic SL1, by Sonneborn.

3.01 PREPARATION

A. Surface Preparation

1. Before placing concrete, clean concrete mixing and transporting equipment of debris and ice.

2. Clean placement site of debris and free water.

3. Remove unsound material from set concrete before placing new concrete.

B. Subgrade preparation

1. If compacted condition of subgrade is altered during excavation, compact as required.

2. Use sand fill leveler. Screed level and compact with vibratory compactor. Wet sand as necessary for good compaction.

3.03 ERECTION, INSTALLATION, APPLICATION

A. Formwork

1. Design

a. Provide formwork that safely supports vertical and lateral loads that might be applied until such loads can be safely supported by the hardened concrete.

b. Construct forms to obtain a completed structure as shown on Drawings within tolerances of ACI 301-72, unless otherwise specified on Drawings.

c. Use commercially manufactured wall form accessories that will be partly or wholly embedded in concrete.

d. Select wall form ties that leave metal at least ¾” from concrete surface and have no appreciable spalling after forms are removed.

3. Installation

a. Clean forms of accumulated grout, mortar, and foreign material before placing concrete.

b. Before placing reinforcement or concrete, coat forms with a release agent that will prevent moisture absorption and prevent bond with concrete.

c. Prevent excess release agent from contacting hardened concrete against which fresh concrete will be placed. Clean excess and puddled release agent from forms.

4. Form removal

a. Remove forms in conformance with ACI 347-78.

b. When surface or finishing repair is required on relatively fresh concrete, remove forms as soon as concrete has hardened sufficiently to resist damage.

c. Remove top forms on sloping surfaces as soon as concrete is stiff enough to prevent sagging; perform repairs or treatment promptly.

B. Reinforcement

1. Bar laps

a. Stagger laps where possible, with no more than 50% of laps at one location.

b. Where laps are not shown on Drawings:

Bar Size 3 4 5 6 7 8 Minimum Lap, inches 20 20 26 33 45 59

2. Cleaning and Bending Reinforcement

a. When concrete is placed, see that metal reinforcement is free from ice, rust, mill scale, or other coatings that would destroy or reduce bond.

b. Bend bars cold. Do not field-bend bars partly embedded in concrete except as shown on Drawings or specifically permitted by ENGINEER.

3. Placing Reinforcement

a. Place reinforcement accurately according to Drawings, and adequately secured in position with concrete, metal or other approved chairs, spacers, or ties.

b. Protect reinforcement by concrete thickness shown on Drawings. Where not otherwise shown, minimum concrete thickness over reinforcement:

Concrete exposed to weather or soil: 1 ½” for #5 bars and smaller, 2” for larger bars.

Slabs and walls not exposed to ground or weather: ¾”.

In all cases, twice the diameter of the bars.

4. Splices in Reinforcement

a. As noted on Drawings, as specified, or as authorized by ENGINEER.

b. Do not weld crossing bars (tack welds).

C. Joints and Embedded Items

1. Construction joints

a. Locate construction joints only at designated control joints unless specifically approved by COR.

b. Continue reinforcement across joints. Provide longitudinal keys, ½” deep minimum. Clean and remove laitance from joint surfaces before placing adjoining concrete.

2. Control Joints (C.J.)

a. Locate as shown on Drawings.

b. In floors: Place control joint former after screeding. Remove top tear strip before floating.

3. Inserts and anchors

a. Drill and place anchors to secure posts to concrete as required and accurately placed for proper completion of other work.

D. Concrete Placement

1. General

a. Convey concrete from mixer to delivery place without materials separation or loss.

b. Use chuting, pumping, and pneumatic conveying equipment sized and designed for practically continuous concrete flow at delivery end without materials separation.

c. Use no re-tempered or contaminated concrete.

d. Deposit concrete as near as practical to its final position to avoid separation by re-handling or flowing.

e. Place concrete at a rate to assure plasticity and flow between bars.

f. Place concrete continuously until a panel or section is complete.

g. Thoroughly consolidate and vibrate concrete around reinforcement, embedded fixtures, and form corners.

h. Level, screed, and float concrete to a compact and dense surface free from low and high spots.

2. Curing compound: Spray one coat as soon as surface water has dissipated.

a. 200 sq. ft/gal on smooth surfaces. Increase coverage on textured surfaces.

b. Follow manufacturer’s precautions for protecting workers and the public.

3. Keep concrete moist at least 5 days after placement. Longer curing may be required when air temperature is below 50oF. Concrete may be covered with poly or wet burlap to help keep concrete moist.

E. Finishing Exposed Formed Concrete Surfaces

1. Fill holes immediately. Wet and rub exposed surfaces with a stone to a uniform color and texture without adding cement slurry and within one day of removing forms.

2. Where shown on Drawings, chamfer corner and edges; rub edges to ¾” radius.

3. Crown curbs.

F. Finishing Surfaces Not Cast Against Formwork

1. Initial: Do no finishing while free water is on the surface. Immediately after screeding, bull float slabs before excess moisture or bleeding water appears. When water sheen disappears, and concrete surface will support the operation, hand or machine float.

2. Tooled joints and edges, if used: Tool after initial set; retool after float if needed.

3. Final finish to meet descriptions on Drawings.

a. Broom Finish: After float finish, lightly draw a broom over surface and in the direction of the slope to form a textured finish. Retool joints and edges.

H. Cold Weather Requirements

1. Use no frozen, snowy, or icy materials. Use no salt or other chemicals to prevent freezing. Remove snow and ice from forms, reinforcement, fillers, and ground in contact with concrete.

2. Place only concrete with a temperature of at least 50oF in forms. Maintain concrete at 50oF or higher for 5 days, or longer if required to ensure adequate concrete curing.

3. Maintain housing, covering, or other protection for 24 hours after stopping artificial heating.

I. Hot Weather Requirements

1. Prevent concrete from drying before finishing operations.

2. Place concrete with a temperature below 90oF maximum and low enough to prevent flash set, cold joints, or loss of slump.

J. Tolerances

1. Plane surfaces: Within ¼” of a 10’ straight-edge in all orientations.

2. Grooved surfaces: 1” maximum variance in distance between grooves.

3.04 FIELD QUALITY CONTROL

A. Tests

1. Have tests performed by a testing laboratory acceptable to OWNER at CONTRACTOR’S expense.

2. Test and inspect concrete materials and operations as Work progresses.

3. Testing agency shall meet requirements of ASTM E 329.

4. Have testing agency review or check-test proposed materials and mix design for compliance with specifications.

5. Conduct concrete strength tests during construction:

a. Secure composite samples according to ASTM C 172. Take each sample at random from a different concrete batch. Select batch numbers at random before commencing concrete placement.

b. Mold and cure 3 specimens from each sample according to ASTM C 31.

c. Test specimens according to ASTM C 39. Test 1 specimen at 7 days for information and 2 specimens at 28 days for acceptance.

d. Acceptance test results: Average strength of two 28-day specimens, except discard results for a specimen evidencing improper sampling, molding, or testing.

e. Make at least one strength test for each 50 cubic yards, or fraction, of each concrete mix design placed in a day.

f. Determine slump for each sample and whenever concrete consistency appears to vary, using ASTM C 143.

g. Determine concrete sample air content as requested by ENGINEER using either ASTM C 173 or ASTM C 138. ENGINEER will require no more than 3 tests unless test results show abnormalities in air content.

h. Determine concrete temperature of each sample taken for strength test.

B. Site Observations

1. Notify COR at least 24 hours before a concrete pour.

2. Do not pour concrete without approval from ENGINEER.

3.05 ADJUSTING, CLEANING

A. Remove forms as soon as practical after placement.

B. Minor Defects: Repair surface defects, including exposed tie holes, immediately.

C. Major Defects

1. Surface defects deeper than 1” and greater than 1 sq. ft. in area are defective.

Remove and repair if requested by COR.

2. Floors designated as sloped on Drawings are defective if water remains standing on the surface. Remove and replace if requested by COR.

3. Honeycombed and other defective concrete: Remove down to sound concrete.

Chip edges perpendicular to the surface or slightly undercut; do not feather edges. To prevent absorption of water from grout, dampen an area to be patched, and a 6” area surrounding it.

4. Mix patching mortar in advance, mix frequently without adding water, and use when it has reached the stiffest consistency that permits placing.

5. After surface water has evaporated from surface to be patched, brush on bond coat.

Apply patching mortar when bond coat loses its water sheen.

6. Thoroughly consolidate mortar into place and strike off slightly higher than surrounding surface. Leave undisturbed for at least 1 hour before final finishing. Keep patch damp for 7 days.

7. Do not finish patches on exposed walls with metal tools.

D. Exposed tie holes: Clean, dampen, and fill solid with patching mortar.

SECTION 11810

CUSTOM PENWORK

A. ASTM

1. ASTM A 36-84a, Specification for Structural Steel.

2. ASTM A 53-84a, Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated

Welded and Seamless.

3. ASTM A 123-78, Specification for Zinc (Hot-Galvanized) Coatings on Products

Fabricated from Rolled, Pressed, and Forged Steel Shapes, Plates, Bars, and Strip.

4. ASTM A 153-82, Specification for Zinc Coating (Hot Dip) on Iron and Steel Hardware.

5. ASTM A 307-84, Specification for Carbon Steel Externally Threaded Standard

Fasteners.

6. ASTM A 366-72, Specification for Steel, Carbon, Cold-Rolled Sheet, Commercial

Quality.

7. ASTM A 513-84a, Specification for Electric-Resistance Welded Carbon and Alloy

Steel Mechanical Tubing.

8. ASTM A 563-84, Specification for Carbon and Alloy Steel Nuts.

9. ASTM B 633-78, Specification for Electrodeposited Coatings of Zinc on Iron and

Steel.

1.02 SYSTEM DESCRIPTION

A. Performance Requirements: Some components shown on the Drawings are diagrammatical only. Fabricator is responsible for proper operation of hinges, latches, etc.

1.03 SUBMITTALS

A. Shop Drawings

1. Shop Drawings for approval prior to fabrication: Include plan view and dimensional drawings of each fabricated unit. Show vent hole and rust sleeve locations, fastener and hardware details, etc.

B. Samples

1. Gate and fencing samples showing welds, vent hole locations, cropped and mitered joints, galvanized finish, pipe bends and rust shields.

C. Quality Control Submittals: Samples, as submitted, become standards for accepting or rejecting materials and workmanship.

1.04 QUALITY ASSURANCE

A. Qualifications

1. Suppliers are asked to submit the following information.

a. Brochures, catalogs, and similar information describing products and services normally supplied.

b. Small sample, or samples, of gate or fencing showing welds, vent hole locations, cropped and mitered joints, galvanized finish, pipe bends and rust shields.

c. Evidence of the steel quality and yield strength normally used.

B. Certifications

11810 - 2 3/22/2025 USDA/NADC

1. Certify with steel mill slips or other approved method that raw materials for fabricated steel comply with requirements.

1.05 DELIVERY, STORAGE, AND HANDLING

A. Packing and Shipping: Label each component or group of identical components with temporary identification corresponding to shop drawings.

B. Storage and Protection

1. Handle with care: Do not bend, puncture, or crush containers or contents; minimize handling of bundles to protect finishes.

2. Store protected from weather and away from mud.

A. EIP Manufacturing, 2677 221st Street, Earlville, IA 52041, 563092307315

B. Farmaster, PO Box 569, Columbus, NE 68601, 402-564-3111

C. Franklin Equipment, Inc. 330 South Cedar, Monticello, IA 62310, 319-465-3561

D. Keehn Marketing, Inc., PO Box 577, Watertown, SD 57201, 605-886-2120

E. Kencove Farm Fence, 344 Kendall Road, Blairsville, PA 15717-8707, 800 KENCOVE

F. Midwest Water Jet, 7061 North 600 West, Michigan City, IN 46360, 219-872-4581

G. Ranchmaster, PO Box 569, Columbus, NE 68601, 402-564-3111

H. Rohn Industries, Inc., 6718 W. Plank Road, PO Box 2000, Peoria, IL 61656, 309-697-4400.

I. Two-W Livestock Equipment, Inc. Box 430, Nanton, Alberta, Canada, 403-464-2133

A. High Carbon Steel: Minimum 50,000 psi yield stress, ASTM 513 Type 1.

B. Schedule 40 Steel Pipe: Minimum 35,000 psi yield stress, minimum 60,000 psi tensile stress, ASTM A 53 Type F.

C. Flat Sheet Steel: Minimum 27,500 psi yield stress, minimum 50,000 psi tensile stress, ASTM A 366.

D. 1/2” diameter rods: Minimum 36,000 psi yield stress, minimum 58,000 psi tensile stress, ASTM A 36.

E. Other Steel: Minimum 36,000 psi yield stress, minimum 58,000 psi tensile stress, ASTM A

36.

F. Clamps: Cast or stamped, size and weight as required for purpose shown.

I. Bolts: Galvanized, ASTM A 153, A 307, and A 563.

J. Plastic Rust Sleeves

1. Plastic, on components set in concrete.

2. PVC pipe cut in half and placed as tightly as possible around post.

K. Gates and Fence Panels

1. Fence supported by posts, held by rods

2. Gates supported by posts, held by latch and hinges

L. Posts

1. Construct and attach loops as per Drawings

2. 8-foot-long metal brace.

2.03 FABRICATION

A. Shop Assembly

1. Shop assembly to verify fit. Fabricate work in largest practical units.

2. Fabricate and finish assemblies with smooth surfaces without burrs, rough edges, sharp corner edges, or projecting hardware.

3. Fabricate assemblies to protect against trapping dirt and moisture.

4. Fabricate assemblies to eliminate field welding except, where permitted on

Drawings.

5. Welding

a. Use electrodes recommended for materials being joined.

b. Thoroughly penetrate both materials being joined.

c. Weld full depth or to depth indicated on Drawings.

d. Grind away slag and rough or sharp spots before galvanizing.

6. Grind smooth steel sliding surfaces on hinges and latches to assure smooth operation.

7. Provide vent holes as required for galvanizing, locate to avoid trapping dirt and moisture when units are installed. To extent possible, utilize interior vent system through pipe connections.

8. Install rust sleeves on galvanized components set in concrete.

B. Shop/Factory/Finishing

1. Galvanize components after welding or fabricating that will damage galvanized finish.

2. Hot Dipped Galvanizing: Minimum 2 oz per sq ft, ASTM A 123.

3. Electro Galvanizing: Minimum thickness 0.3 mil, ASTM B 633 Type II.

4. Clean, pickle, and properly prepare surfaces prior to galvanizing.

5. Remove slag, impurities, needle points, and burrs immediately after removal from galvanizing tank.

6. Grind smooth surfaces that cause pain when rubbed with bare hand.

7. Provide uniform surface finish in color and spangle.

2.04 SOURCE QUALITY CONTROL

A. Tests, Inspection

1. Ship galvanized components after inspection by fabricator.

B. Verification of Performance

1. Contact COR before shipping components with questionable performance.

11810 - 4 3/22/2025 USDA/NADC

3.01 ERECTION, INSTALLATION, APPLICATION

A. Installation

1. Verify dimensions before field assembly and installation.

2. Set units plumb, square, and true to line in locations shown on drawings.

3. Support and stabilize posts set in concrete.

4. Protect galvanized finishes from concrete splatter.

5. Adjust gates, gate hardware, and other moving assemblies for smooth operation without sagging or binding.

6. Electrically ground metal parts set in concrete; see Section 16450.

3.02 ADJUSTING, CLEANING

A. Lubricate all moving parts for smooth operation in place.

B. Adjust hinges, latches, and attachments for smooth operation and neat appearance.

USDA/NADC

Sheep Housing Barn Improvements 3/22/2025 11820 - 1

SECTION 11820

PEN AND STALL AND CAGE EQUIPMENT

A. ASTM

1. ASTM A 123-78, Specification for Zinc (Hot-Galvanized) Coatings on Products Fabricated from Rolled, Pressed, and Forged Steel Shapes, Plates, Bars, and Strip

2. ASTM A 153-82, Specification for Zinc Coating (Hot Dip) on Iron and Steel Hardware

3. ASTM B 633-78, Specification for Electrodeposited Coatings of Zinc on Iron and Steel

4. ASTM A 36-84a, Specification for Structural Steel

5. ASTM A 518-84a, Specification for Electric Resistance Welded Carbon and Alloy Steel

Mechanical Tubing

6. ASTM A 307-84, Specification for Carbon Steel Externally Threaded Standard

Fasteners

7. ASTM A 563-84, Specification for Carbon and Alloy Steel Nuts

1.02 SYSTEM DESCRIPTION

A. Performance Requirements: Some components shown on the Drawings are diagrammatical only. Fabricator is responsible for proper operation of hinges, latches, etc.

1.03 DELIVERY, STORAGE, AND HANDLING

A. Storage and Protection

1. Handle with care: Do not bend, puncture, or crush containers or contents; minimize handling of bundles to protect finishes.

2. Store protected from weather and away from mud.

1.04 PROJECT CONDITIONS

A. Field Measurements: Verify fabrication dimensions with field measurements before setting in concrete.

A. Farmaster Products/Div of Behlen Mfg. Co., POB 569, Columbus, NE 68602-0569, 402- 564-3111.

B. Franklin Equipment, Inc.; 339 South Cedar St., Monticello, IA 52310. 319-465-3561.

C. Merrill Equipment Co; 2209 Sturdevant Street, Merrill, WI 54452. 715-536-2471.

D. Palco Livestock Equipment, Inc; 1108 11th St., Belle Plaine, IA 52208, 800-227-7875 or

319-444-2501 E. Behlen Country, 2600 College Ave, POB 115, Goshen, IN 46526, 219-533-3131

2.02 MANUFACTURED UNITS

A. Welded Steel Tubing Gates

1. Standard-duty farm gates; 1-1/2” galvanized steel tubing, welded connections; 50” high by length shown on Drawings.

2. Model Series TG-100-S, by Universal. Approved similar unit by: Farmaster or Franklin.

11820 - 2 3/22/25 USDA/NADC

3. Mitered or coped and welded construction.

4. Round top corner design.

5. Six horizontal rails and 50” overall height.

6. Gate length = opening length less 4 inches.

7. Vertical stiffeners at maximum of 5’ spacing.

8. Adjustable threaded 3/4” hinges, 2 per gate.

9. Chain latch mechanism.

2.03 COMPONENTS

A. Provide all fittings, hardware, etc. needed to install, anchor, and use the items of this Section.

2.04 FABRICATION

A. Shop Assembly

1. Fabricate and finish assemblies with smooth surfaces without burrs, rough edges, sharp corner edges, or projecting hardware.

2. Fabricate assemblies to protect against trapping dirt and moisture.

3. Fabricate assemblies to eliminate field welding.

4. Grind smooth steel sliding surfaces on hinges and latches to assure smooth operation.

5. Provide vent holes as required for galvanizing, locate to avoid trapping dirt and moisture when units are installed.

B. Shop/Factory/Finishing

1. Galvanize components after welding or fabricating that will damage galvanized finish.

2. Hot Dipped Galvanizing: Minimum 2 oz per sq ft, ASTM A 123.

3. Electro Galvanizing: Minimum thickness 0.3 mil, ASTM B 633 Type II.

4. Clean, pickle, and properly prepare surfaces prior to galvanizing.

5. Remove slag, impurities, needle points, and burrs immediately after removal from galvanizing tank.

6. Grind smooth surfaces that cause pain when rubbed with bare hand.

7. Provide uniform surface finish in color…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .