Specifications and Plans - 2025-10-10_IDOT_JibCraneFoundation.pdf
PDF 379 KB Posted
- Attached to
- Repair Shop Concrete Footing
- Solicitation number
- 645-RFQ-2226-2026
- Issued by
- Story County, Iowa
About this file
This document is a structural engineering drawing set for a new jib crane foundation project for the Iowa Department of Transportation, located at 800 Lincoln Way in Ames, Iowa. The drawing (Sheet S100) provides detailed specifications for constructing a new foundation for a jib crane, including precise technical requirements for concrete placement, steel reinforcement, and foundation design. The design adheres to the 2015 International Building Code (IBC) and incorporates design standards from the American Concrete Institute (ACI) and American Institute of Steel Construction (AISC).
The foundation design specifies a 6'-6" x 6'-6" x 2'-0" footing with #7 rebar at 12" on center, top and bottom, and #5 x 1'-0" dowels at 24" on center around the perimeter. The design accounts for a jib crane live load of 2,000 pounds and assumes a net allowable soil bearing pressure of 1,500 psf. The foundation must be fastened to the new foundation per manufacturer's recommendations, with provisions for an approved subgrade and potential replacement of sand with 6" granular fill. The drawing includes comprehensive notes on excavation, backfill, soil compaction, and construction requirements to ensure structural integrity and compliance with engineering standards.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1346549-event.pdf | ||
| Photo.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CAST-IN-PLACE CONCRETE
1. ALL CONCRETE SHALL CONFORM TO THE LATEST REQUIREMENTS OF THE AMERICAN
CONCRETE INSTITUTES PUBLICATIONS: ACI 301, ACI 305.1, ACI 306.1, ACI 315, AND ACI 318
UNLESS NOTED OTHERWISE.
2. CONCRETE COMPRESSIVE STRENGTH (28 DAY)(F'c)
FOOTINGS 4000 PSI
3. CONCRETE REINFORCEMENT STANDARDS:
DEFORMED BARS ASTM A615 Fy = 60 KSI
SYNTHETIC MACRO FIBER REINFORCING ASTM C1116
EPOXY COATED REINFORCING ASTM A775 Fy = 60 KSI
4. ALL CONCRETE SHALL BE STONE AGGREGATE UNLESS NOTED OTHERWISE. SUBMIT MIX DESIGN
AND DOCUMENTATION FOR APPROVAL PER ACI 318.
5. REINFORCEMENT PROTECTION
A. CONCRETE PLACED AGAINST EARTH - 3"
B. CONCRETE PLACED IN FORMS BUT EXPOSED TO WEATHER OR EARTH:
a. BARS #5 AND SMALLER - 1 1/2"
b. BARS LARGER THAN #5 - 2"
C. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND:
a. SLABS, WALLS, AND JOISTS - 3/4"
b. BEAMS, COLUMNS - 1 1/2"
6. WHERE REQUIRED, DOWELS SHALL MATCH THE SIZE, NUMBER AND SPACING OF THE MAIN
REINFORCING UNLESS NOTED OTHERWISE.
7. ALL SPLICES, STANDARD HOOKS, AND DEVELOPMENT LENGTHS TO BE PER THE REFERENCED
EDITION OF ACI 318. MAKE BARS CONTINUOUS AROUND CORNERS. ALL SPLICES SHALL BE BY
CONTACT LAP.
8. ALL SPLICES SHALL BE A CLASS "B" TENSION SPLICE AS DEFINED IN ACI 318. PROVIDE LAP
SPLICES LENGTHS AS FOLLOWS:
LAP SPLICE LENGTHS GIVEN, ASSUME CLEAR SPACING BETWEEN BARS OF 2 BAR DIAMETERS,
AND A MINIMUM CLEAR COVER OF 1 BAR DIAMETER. TOP BARS ARE DEFINED AS HORIZONTAL
BARS WITH MORE THAN 12" ON FRESH CONCRETE BENEATH THE BARS.
9. WALLS AND GRADE BEAMS SHALL NOT HAVE JOINTS IN A HORIZONTAL PLANE, UNLESS
APPROVED BY THE ENGINEER.
10. CONSTRUCTION JOINTS IN STRUCTURAL CONCRETE WORK MUST BE MADE AT CENTER OF
SPAN OR AT CENTER OF SUPPORT WITH VERTICAL BULKHEADS AND HORIZONTAL KEYS,
UNLESS OTHERWISE SHOWN.
11. THERE SHALL BE NO ADDITIONAL OPENINGS LARGER THAN 10" IN CONCRETE WALLS AND SLABS
NOT SHOWN. REFER TO CONCRETE OPENING DETAIL FOR ADDITIONAL REINFORCEMENT
AROUND OPENINGS.
12. REINFORCING STEEL SHALL BE SECURELY FASTENED INTO FORMS PRIOR TO POURING
CONCRETE. WET SETTING OF REINFORCING STEEL WILL NOT BE ACCEPTED PER ACI.
13. CONCRETE MIX - FOOTINGS
COARSE AGGREGATE 100% PASSING 1" SIEVE
FINE AGGREGATE 100% PASSING 3/8" SIEVE
WATER/CEMENT RATIO 0.45
SLUMP 4" +/- 1"
AIR CONTENT 6% +/- 1.5%
BAR SIZE
#3 #4 #5 #6 #7 #8 #9 #10 #11
TYPICAL
19" 25" 31" 37" 54" 62" 70" 79" 87"
TOP BARS
25" 33" 41" 49" 71" 81" 91" 102" 114"
4000 PSI
GENERAL NOTES
1. THE GENERAL STRUCTURAL NOTES ARE INTENDED TO SUPPLEMENT THE DRAWINGS.
2. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ALL PROJECT DRAWINGS AND
SPECIFICATIONS. REFER TO ALL DRAWINGS FOR THE COORDINATION OF THE WORK IN THIS
PROJECT.
3. THE INTENT OF THESE PLANS AND NOTES IS TO PRESENT THE PROJECT REQUIREMENTS.
MAJOR DETAILS HAVE BEEN SHOWN ON THE DRAWINGS. HOWEVER, CERTAIN MINOR DETAILS
MUST BE WORKED OUT IN THE FIELD OR SHOP DRAWING PROCESS BY THE CONTRACTOR.
4. UNLESS NOTED OTHERWISE, DETAILS SHOWN ON DRAWINGS ARE TO BE CONSIDERED TYPICAL
FOR ALL SIMILAR CONDITIONS.
5. THE STRUCTURE IS DESIGNED TO BE STABLE AND SELF-SUPPORTING AFTER THE BUILDING IS
FULLY ERECTED AND ALL CONNECTIONS ARE COMPLETED. UNLESS NOTED OTHERWISE, THE
DRAWINGS DO NOT INDICATE THE MEANS AND METHODS OF CONSTRUCTION. IT IS SOLELY THE
CONTRACTOR'S RESPONSIBILITY TO DETERMINE THE ERECTION PROCEDURE AND SEQUENCING
TO ENSURE THE SAFETY OF THE BUILDING AND ITS COMPONENT PARTS DURING ERECTION.
THIS INCLUDES THE ADDITION TEMPORARY BRACING, GUYS AND TIE-DOWNS NECESSARY FOR
THE ERECTION PROCESS.
6. IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO FOLLOW THE APPLICABLE SAFETY CODES
AND REGULATIONS DURING ALL PHASES OF CONSTRUCTION.
7. CONTRACTOR'S CONSTRUCTION AND ERECTION SEQUENCE SHALL CONSIDER THE EFFECTS OF
THERMAL MOVEMENTS OF THE STRUCTURAL ELEMENTS DURING THE CONSTRUCTION PERIOD.
8. EXISTING CONDITIONS:
A. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL DIMENSIONS AND CONDITIONS
RELATING TO EXISTING CONSTRUCTION AND EXISTING SERVICES ON SITE. THE
CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND LOCATIONS OF EXISTING COLUMNS,
WALLS, OPENINGS, ETC, WITH THE ARCHITECTURAL DRAWINGS PRIOR TO PROCEEDING
WITH THE WORK. ANY DISCREPANCIES WITH THE CONTRACT DOCUMENTS SHALL BE
REPORTED TO THE ARCHITECT AND ENGINEER BEFORE PROCEEDING WITH THE AFFECTED
PART OF THE WORK.
B. DURING CONSTRUCTION THE CONTRACTOR MAY ENCOUNTER EXISTING CONDITIONS WHICH
ARE NOT KNOWN OR ARE AT VARIANCE WITH PROJECT DOCUMENTATION (DISCOVERY).
SUCH CONDITIONS MAY INTERFERE WITH THE NEW CONSTRUCTION OR REQUIRE
PROTECTION AND/OR SUPPORT OF EXISTING WORK DURING CONSTRUCTION. IT MAY ALSO
CONSIST OF DAMAGED OR DETERIORATION OF STRUCTURAL MATERIALS OR COMPONENTS
WHICH COULD JEOPARDIZE THE STRUCTURAL INTEGRITY OF THE BUILDING(S). THE
CONTRACTOR SHALL NOTIFY THE ENGINEER OF ALL DISCOVERIES WHICH MAY INTERFERE
WITH THE PROPER EXECUTION OF THE WORK OR JEOPARDIZE THE STRUCTURAL INTEGRITY
OF THE BUILDING(S) PRIOR TO PROCEEDING WITH THE WORK RELATED TO SUCH
DISCOVERIES.
C. DURING THE CONSTRUCTION PROCESS, IT SHALL BE SOLELY THE CONTRACTOR'S
RESPONSIBILITY TO MAINTAIN THE INTEGRITY OF THE EXISTING STRUCTURE AND TO
PROTECT IT FROM DAMAGE ANY PORTIONS THAT ARE TO REMAIN.
D. CONTRACTOR SHALL INVESTIGATE THE SITE DURING EARTHWORK OPERATIONS FOR FILL
MATERIAL OR BURIED STRUCTURES. IMMEDIATELY, NOTIFY THE ENGINEER IF ANY SUCH
MATERIALS OR STRUCTURES ARE DISCOVERED.
9. STRUCTURAL COORDINATION
A. MECHANICAL, ELECTRICAL OR PLUMBING LOADS, OPENINGS AND SUPPORT FRAMING ARE
SHOWN FOR BIDDING PURPOSES ONLY. CONTRACTOR SHALL OBTAIN APPROVAL OF THE
MECHANICAL, ELECTRICAL OR PLUMBING CONTRACTOR BEFORE PROCEEDING WITH SUCH
PORTION OF THE WORK.
B. THE CONTRACTOR SHALL VERIFY THE SIZE AND LOCATION OF ALL OPENINGS, HOLES AND
SLEEVES THROUGH FOUNDATIONS AND OTHER STRUCTURAL ELEMENTS WITH THE
MECHANICAL, ELECTRICAL AND PLUMBING CONTRACTORS. NO OPENINGS SHALL PASS
THROUGH STRUCTURAL MEMBERS UNLESS SHOWN ON THE DRAWINGS OR APPROVED BY
THE ENGINEER.
C. EXCESS COST DUE TO VARIATION IN THE STRUCTURE TO ACCOMMODATE A SUBSTITUTION
OR ALTERNATE MANUFACTURER(S) FROM THE LISTED BASIS OF DESIGN SHALL BE BORNE
BY THE CONTRACTOR.
10. BEFORE SUBMITTING A BID, EACH BIDDER SHALL VISIT THE SITE AND BECOME FULLY
ACQUAINTED WITH THE EXISTING CONDITIONS, CONSTRUCTION REQUIREMENTS,
RESTRICTIONS, QUANTITIES AND EQUIPMENT NECESSARY TO COMPLETE THE WORK. THE BID
SHALL INCLUDE ALL ITEMS REQUIRED TO COMPLETE THE WORK WITHIN THE EXISTING
CONDITIONS. DISRUPTION OF THE OWNERS NORMAL ACTIVITIES AROUND THE CONSTRUCTION
SITE SHALL BE KEPT TO A MINIMUM.
11. THE COST OF ADDITIONAL DESIGN WORK DUE TO ERRORS AND OMISSIONS BY THE
CONTRACTOR DURING CONSTRUCTION SHALL BE BORNE BY THE RESPONSIBLE CONTRACTOR.
12. ANY ENGINEERING DESIGN PROVIDED BY OTHER AND SUBMITTED FOR REVIEW OR RECORD
SHALL BEAR THE STAMP AND SIGNATURE OF A PROFESSIONAL STRUCTURAL ENGINEER
REGISTERED IN THE STATE WHERE THE PROJECT EXISTS.
13. CONTRACTOR SHALL COORDINATE WORK SCHEDULES WITH THE OWNER TO ESTABLISH
CONSTRUCTION SEQUENCING AROUND ANY OCCUPIED AREAS. CONTRACTOR SHALL NOT
PROCEED TO OCCUPIED AREAS UNTIL AUTHORIZED BY THE OWNER.
14. ALL ELEMENTS AND SURFACES DAMAGED BY DEMOLITION, BUT NOT SCHEDULED FOR REMOVAL
SHALL BE REPAIRED AND REFINISHED TO MATCH THE ADJACENT SURFACES AT NO ADDITIONAL
COST TO THE OWNER.
15. CONTRACTOR SHALL REMOVE ALL DEBRIS AND WASTE MATERIALS RESULTING FROM
CONSTRUCTION FROM THE SITE, UNLESS NOTED OTHERWISE.
16. CONTRACTOR SHALL MINIMIZE CREATION OF DUST, DIRT AND WINDBORNE DEBRIS FROM
BLOWING ACROSS THE SITE AND ONTO ADJACENT SITES.
17. CONTRACTOR SHALL COVER ANY EXTERIOR OPENING WITH TEMPORARY CLOSURES WHEN NOT
WORKING ON SITE TO PROTECT THE INTERIOR SPACES FROM WEATHER, INSECTS, RODENTS
AND INTRUDERS.
STRUCTURAL STEEL
1. STRUCTURAL STEEL SHALL CONFORM TO THE REFERENCED EDITION OF THE AISC
"SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS".
2. STRUCTURAL STEEL MATERIAL STANDARDS
WIDE FLANGE SECTIONS ASTM A992 Fy = 50 KSI ANGLES, CHANNELS & PLATES ASTM A36 Fy = 36 KSI SQUARE AND RECTANGULAR HSS ASTM A500, GR C Fy = 50 KSI ROUND HSS ASTM A500, GR C Fy = 46 KSI STANDARD PIPE SECTIONS ASTM A53, GR B Fy = 35 KSI
3. STRUCTURAL STEEL CONNECTION STANDARDS:
HIGH STRENGTH BOLTS ASTM F3125 GRADE A325
TENSION CONTROL BOLT/NUT/WASHER ASTM F1852
HEAVY HEX NUT ASTM A563
WASHERS ASTM F436
ANCHOR RODS ASTM F1554 GRADE 36
HEADED WELDED STUDS ASTM A108 TYPE B
WELDING ELECTRODES (CARBON STEEL) AWS 5.1, E70XX
4. WELDING SHALL BE IN ACCORDANCE WITH STRUCTURAL WELDING CODE, AWS D1.1, LATEST
EDITION, AND SHALL BE PERFORMED BY CERTIFIED WELDERS ONLY USING PROPER
ELECTRODES FOR MATERIAL BEING WELDED. PROVIDE WELD SIZE IN ACCORDANCE WITH AISC
SPECIFICATIONS, BUT NOT LESS THAN 3/16" FILLET, CONTINUOUS UNLESS OTHERWISE NOTED.
5. ALL HIGH STRENGTH BOLTS SHALL BE INSTALLED IN ACCORDANCE WITH RCSC -
"SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS." SEE DRAWINGS
FOR BOLTS SIZES. USE 3/4" DIAMETER, A325 BOLTS UNLESS NOTED OTHERWISE.
6. WHEN TENSION CONTROL BOLTS ARE INDICATED "TC" ON THE DRAWINGS, PROVIDE HIGH
STRENGTH "TENSION CONTROLLED" BOLTS MEETING ASTM F1852, TYPE 1.
7. ALL BOLTED CONNECTIONS ARE BEARING TYPE, UNLESS INDICATED AS TENSION CONTROLLED
(TC) OR SLIP CRITICAL (SC). PROVIDE STANDARD HOLES FOR BEARING TYPE CONNECTION
WHICH ARE 1/16" WIDER DIAMETER THAN THE BOLT.
8. ALL EXTERIOR EXPOSURE STEEL FRAMING, STEEL LINTEL ASSEMBLIES, BRICK RELIEF ANGLES
AND CONNECTORS SHALL BE HOT DIPPED GALVANIZED. ITEMS INDICATED TO BE GALVANIZED
SHALL BE HOT-DIP GALVANIZED IN COMPLIANCE WITH ASTM A123.
9. AFTER FABRICATION, ALL STEEL SHALL BE CLEANED OF ALL RUST, LOOSE MILL SCALE AND
OTHER FOREIGN MATERIALS. STEEL SHALL BE HAND TOOLED CLEANED (SSPC-SP2) OR POWER
TOOL CLEANED (SSPC-SP3).
10. ALL STRUCTURAL STEEL WILL HAVE ONE COAT OF FABRICATOR'S STANDARD LEAD AND
CHROMATE-FREE RUST INHIBITIVE PRIMER APPLIED PRIOR TO DELIVERY TO THE JOB SITE
UNLESS NOTED OTHERWISE. ALL AREAS OF STRUCTURAL STEEL MEMBERS IN WHICH THE
PRIMER COATED SURFACE IS DAMAGED DURING CONSTRUCTION SHALL BE TOUCHED UP WITH
MATCHING PRIMER.
11. THERE SHALL BE NO FIELD CUTTING OF STRUCTURAL STEEL MEMBERS FOR THE WORK OF
OTHER TRADES WITHOUT PRIOR WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER OF
RECORD.
12. ALL MISCELLANEOUS STEEL AS SHOWN OR REFERENCED ON THE ARCHITECTURAL DRAWINGS
SHALL BE FABRICATED AND INSTALLED AS PART OF THE STRUCTURAL STEEL.
13. CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORES, GUYS, BRACES AND OTHER
SUPPORTS DURING ERECTION TO KEEP STRUCTURAL STEEL SECURE, PLUMB AND IN
ALIGNMENT AGAINST TEMPORARY CONSTRUCTION LOADS AND LOADS EQUAL TO DESIGN
LOADS. REMOVE ALL TEMPORARY SUPPORTS WHEN PERMANENT STRUCTURAL STEEL
FRAMING AND CONNECTIONS ARE COMPLETED.
14. MAINTAIN ERECTION TOLERANCES OF STRUCTURAL STEEL WITHIN AISC 303, "CODE OF
STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES."
15. DO NOT ENLARGE MISALIGNED BOLT HOLES BY BURNING OR THERMAL CUTTING. REAM HOLES
THAT MUST BE ENLARGED TO INSTALL BOLTS.
FOUNDATIONS
1. ALL EXCAVATIONS SHALL BE PROPERLY AND SAFELY BACKFILLED. DO NOT PLACE BACKFILL
BEHIND BASEMENT WALLS OR RETAINING WALLS UNTIL CONCRETE HAS ATTAINED THE
SPECIFIED COMPRESSIVE STRENGTH. BASEMENT WALLS SHALL NOT BE BACKFILLED UNTIL
SUPPORTING FLOOR IS COMPLETED AND ATTAINED FULL STRENGTH. CONTRACTOR SHALL
PROTECT ALL BELOW GRADE WALLS FROM LATERAL EARTH PRESSURES UNTIL SUPPORTING
FLOOR STRUCTURE IS COMPLETED. CONTRACTOR PROVIDE FOR DESIGN, PERMITS AND
INSTALLATION OF LATERAL SHORING TO BRACE WALLS IN LIEU OF WAITING FOR FLOOR SLAB
COMPLETION.
2. FOOTING SHALL BE CENTERED UNDER WALLS AND COLUMNS UNLESS NOTED OTHERWISE.
3. CONTRACTOR SHALL ACCOUNT FOR PUMPING OF WATER FROM THE EXCAVATION DUE TO
SURFACE WATER, GROUND WATER AND SEEPAGE.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN AND INSTALLATION OF ALL SHEETING, SHORING AND CRIBBING REQUIRED TO SAFELY RETAIN THE EARTH BANK AROUND THE
EXCAVATIONS.
5. ALL FOOTINGS SHALL BE PLACED ONTO FIRM UNDISTURBED SOIL OR ACCEPTABLE COMPACTED
BACKFILL AS OUTLINED IN THE SOIL REPORT AND PROJECT SPECIFICATIONS.
6. FOOTING ELEVATIONS SHOWN DESIGNATE THE MINIMUM DEPTH OF THE FOOTING WHERE THE
ALLOWABLE SOIL BEARING IS EXPECTED. LOCALIZED AREAS OF UNACCEPTABLE SOILS OR
POOR COMPACTION MAY BE DISCOVERED DURING THE EXCAVATION PROCESS REQUIRING
OVEREXCAVATION AND BACKFILL WITH ACCEPTABLE FILL. FOOTING EXCAVATIONS SHALL BE
LOWERED TO REACH SOIL MEETS THE DESIGN BEARING PRESSURE AND APPROVED BY THE
GEOTECHNICAL SPECIAL INSPECTION AGENCY.
7. ACCEPTABLE BACKFILL MATERIAL SHALL BE PLACED IN LIFTS NOT TO EXCEED EIGHT (8) INCHES
IN LOOSE THICKNESS.
8. FOR FOOTING AND FOUNDATIONS, THE SUBGRADE OR FILL MATERIAL SHALL BE COMPACTED
AND VERIFIED TO MEET 98% STANDARD PROCTOR MAXIMUM DRY DENSITY ACCORDANCE WITH
ASTM D698. FOR RELATIVELY COHESIONLESS GRANULAR FILL WHICH HAS A PERCENT PASSING
THE #200 SIEVE LESS THAN 10 PERCENT AND HAS ONLY A SLIGHT SENSITIVITY TO MOISTURE
CHANGES, COMPACTION SHALL BE 75 PERCENT RELATIVE DENSITY IN ACCORDANCE WITH
ASTM D4253 AND D4254. IF COMPACTION DOES NOT COMPLY, CONTRACTOR SHALL RECOMPACT
AREA AND UNTIL TEST RESULTS ARE PASSING. AN AREA EXHIBITING WEAKNESS SUCH AS
RUTTING OR PUMPING SHALL BE REMOVED AND REPLACED WITH COMPACTED GRANULAR FILL.
9. FOOTING EXCAVATIONS SHALL BE INSPECTED AND APPROVED BY THE GEOTECHNICAL SPECIAL
INSPECTION AGENCY BEFORE CONCRETE IS PLACED. CONTRACTOR SHALL NOTIFY INSPECTION
AGENCY WHEN EXCAVATION IS READY FOR TESTING. INSPECTION AGENCY SHALL PROVIDE A
WRITTEN REPORT OF TEST RESULTS AND COMPLIANCE TO THE OWNER.
10. ACCEPTABLE SOIL SHALL BE DEFINED AS MEETING ASTM D2487 SOIL CLASSIFICATION GROUPS
GW, GP, GM, SW, SP, SM OR A COMBINATION OF THESE TYPES.
11. UNACCEPTABLE SOILS SHALL BE DEFINED AS MEETING ASTM D2487 SOIL CLASSIFICATION GROUPS GC, SC, ML, MH, CL, CH, OL, OH, PT OR A COMBINATION OF THESE TYPES. GROUPS CL AND ML MAY BE ACCEPTABLE IF THE LIQUID LIMIT IS LESS THAN 45 AND THE PLASTICITY INDEX IS
LESS THAN 20.
12. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY MEASURES TO PREVENT ANY FROST OR
ICE FROM PENETRATING ANY FOOTING OR SLAB SUBGRADES BEFORE AND AFTER PLACING THE
CONCRETE AND UNTIL SUCH SUBGRADE IS FULLY PROTECTED BY THE PERMANENT BUILDING
ENCLOSURE AND THE SPACE IS CONDITIONED TO REMAIN ABOVE FREEZING.
13. CONCRETE FOOTINGS AND SLABS SHALL NOT BE PLACED ON OR AGAINST SUBGRADES
CONTAINING FROST, SNOW OR ICE. FROZEN SUBGRADES SHALL BE COMPLETELY THAWED AND
RECONDITIONED BEFORE CONCRETE MAY BE PLACED.
14. REPEATED HEAVY CONSTRUCTION TRAFFIC OVER EXPOSED SUBGRADE WILL CAUSE RUTTING
AND PUMPING WHEN SOIL IS ABOVE THE OPTIMUM MOISTURE CONTENT. AVOID EXCESS
CONSTRUCTION ACTIVITY ON WET SOILS. IF SUBGRADE IS ABOVE THE OPTIMUM MOISTURE
CONTENT DURING CONSTRUCTION, THEN DRYING OF THE SOIL SHALL BE CONDUCTED BY
DISKING, SCARIFICATION, AND AERATION.
15. SOILS WITH A MOISTURE CONTENT ABOVE THE OPTIMUM LEVEL SHALL BE REMOVED AND
REPLACED WITH COMPACTED GRANULAR FILL.
16. CONTRACTOR SHALL NOTIFY THE ARCHITECT AND ENGINEER OF ANY UNUSUAL SOIL
CONDITIONS THAT ARE IN VARIANCE WITH THE SOIL REPORT.
17. CONTRACTOR SHALL NOTIFY THE ARCHITECT AND ENGINEER IMMEDIATELY IF THE EXISTING
FOUNDATIONS VARY FROM THAT SHOWN ON THE DRAWINGS.
18. CONTRACTOR SHALL VERIFY OPENINGS AND SLEEVES THROUGH FOUNDATION WALLS WITH
THE ARCHITECTURAL, MECHANICAL AND ELECTRICAL REQUIREMENTS. CHANGES IN SIZE,
LOCATION AND NUMBER SHALL NOT BE PERMITTED WITHOUT WRITTEN APPROVAL BY THE
ENGINEER.
DESIGN INFORMATION
1. CODES:
A. INTERNATIONAL BUILDING CODE (IBC) 2015
B. AMERICAN CONCRETE INSTITUTE - BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE (ACI 318)
C. AMERICAN INSTITUTE OF STEEL CONSTRUCTION - SPECIFICATION FOR STRUCTURAL
STEEL BUILDINGS (AISC 360)
ALLOWABLE STRENGTH DESIGN (ASD)
D. AMERICAN SOCIETY OF CIVIL ENGINEERS AND STRUCTURAL ENGINEERING INSTITUTE
(ASCE/SEI 7) - MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
E. AMERICAN WELDING SOCIETY D1.1
2. DESIGN LOADS PER THE 2015 IBC (RISK CATEGORY II)
A. DEAD LOADS
STRUCTURE SELF WEIGHT AS SHOWN
B. LIVE LOADS
JIB CRANE LIVE LOAD - 2000 POUNDS
3. SOILS INFORMATION BASED ON ASSUMED SOILS PER THE IBC 2015.
NET ALLOWABLE SOIL BEARING PRESSURES:
SPREAD FOOTINGS 1500 PSF
MIN
3'-6" 6'-6"
M
IN
3' -6
6'
-6
FASTEN JIB CRANE TO
NEW FOUNDATION PER
MANUFACTURER'S
RECOMMENDATIONS
JIB ARM SWING
JIB
APPROVED SUBGRADE, IF
SAND ENCOUNTERED,
REPLACE W/ 6" GRANULAR FILL
C
LR3"
6'-6"x6'-6"x2'-0" FTG w/ #7 AT 12" O.C., EW, TOP, & BOTTOM
#5x1'-0" DOWEL AT 24" O.C.
AROUND PERIMETER OF FTG,
DRILL & GROUT 4" MIN
EXISTING SLAB2'
-0
BA D E
FC G
Io w a
Il lin oi s
In di an a
N eb ra sk a
D R
AW
N
AP
PR
O
VE
D
IS
SU
ED
F
O R
D
AT
E:
FI
EL
D B
O O
K:
PR
O
JE
C
T N
O
H
Pr in te d:
En te r O ffi ce N um be r i n
G lo ba l P ar am et er s Ph on e w w w
.s hi ve -h at te ry .c om
BA D E FC G H
Autodesk Revit 2020
N
EW
J
IB
C R
AN
E
FO
U
N D
AT
IO
N
IO
W
A D
EP
AR
TM
EN
T O
F
TR
AN
SP
O R
TA
TI
O N
LI
N
C O
LN
W
AY
AM
ES
, I
O W
A
S100
JI
B
FO
U
N D
AT
IO
N
PL
AN
D
ET
AI
L
O W
N
ER
R
EV
IE
W
C R
M
C R
K
5/ 8/
NORTH
1/4" = 1'-0"A3 JIB FOUNDATION PLAN
6'
01" = 1'-0"A6 JIB DETAIL
1'-6"
PAGES, SHEETS OR DIVISIONS COVERED BY THIS SEAL:
PRINTED OR TYPED NAME
SIGNATURE
MY LICENSE RENEWAL DATE IS DECEMBER 31,
DATE
LICENSE NUMBER
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS
OF THE STATE OF IOWA.
Christopher R. Marvin
ALL
27417
STRUCTURAL ENGINEER
10-10-2025