Spec _SECTION 23 65 00 .pdf
PDF 155 KB Posted
- Solicitation number
- 36C25725R0097
About this file
This document is a comprehensive technical specification (Section 23 65 00) for cooling towers and fluid coolers, providing detailed requirements for design, materials, installation, and testing of HVAC cooling equipment. The specification covers multiple cooling tower and fluid cooler types, including induced draft open circuit, forced draft open circuit, induced draft closed circuit, and forced draft closed circuit configurations, with options for various materials like galvanized steel, stainless steel, and fiberglass reinforced plastic.
Key technical requirements include specific design criteria such as wind load resistance, water drift loss limitations, sound level restrictions, and performance specifications. The document outlines extensive technical requirements for components including casings, framing, fans, motors, drift eliminators, water distribution systems, collection basins, and control panels. Installation instructions emphasize proper mounting, piping, electrical connections, startup procedures, and comprehensive testing protocols. The specification is designed to ensure high-performance, reliable cooling tower systems with provisions for maintenance, safety, and operational efficiency across different environmental conditions and project requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25725R0097 0001.docx | DOCX document | |
| AHA for Dallas VA CCR Example.xlsx | XLSX spreadsheet | |
| CONSTRUCTION SAFETY PIN 2025 UPDATED 20260120sc.pdf | ||
| Final RFI Questions and Answers_36C25726R0097_01.pdf | ||
| Site Visit Sign In Sheet.pdf | ||
| 36C25725R0097.docx | DOCX document | |
| Price Breakdown Worksheet.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
03-01-23
23 65 00-1
SECTION 23 65 00
COOLING TOWERS
SPEC WRITER NOTES:
1. Delete between // ----- // if not applicable to project. Also delete any other item or paragraph not applicable in the Section and renumber the paragraphs.
2. Specify packaged cooling towers except in the rare cases where field assembled type has been selected.
3. Provide the year of latest edition to each publication given in paragraph
APPLICABLE PUBLICATIONS.
PART 1 - GENERAL
1.1 DESCRIPTION
A. A complete listing of common acronyms and abbreviations are included in
Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
B. This section covers packaged, //induced draft// //forced draft// //open circuit cooling tower// //closed circuit fluid cooler// complete with fill, fan, //inlet louvers// and associated accessories and equipment.
1.2 RELATED WORK
A. Section 01 00 00, GENERAL REQUIREMENTS.
B. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
C. Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS.
D. //Section 01 91 00, GENERAL COMMISSIONING REQUIREMENTS.//
E. Section 03 30 00, CAST-IN-PLACE CONCRETE.
F. //Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL
COMPONENTS.//
G. Section 22 11 00, FACILITY WATER DISTRIBUTION.
H. Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
I. Section 23 05 12, GENERAL MOTOR REQUIREMENTS FOR HVAC and STEAM
GENERATION EQUIPMENT.
J. Section 23 05 41, NOISE and VIBRATION CONTROL FOR HVAC PIPING and
EQUIPMENT.
K. //Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS.//
L. Section 23 21 13, HYDRONIC PIPING.
M. Section 23 25 00, HVAC WATER TREATMENT.
N. Section 23 31 00, HVAC DUCTS and CASINGS.
O. Section 26 29 11, MOTOR CONTROLLERS.
23 65 00-2
1.3 APPLICABLE PUBLICATIONS
SPEC WRITER NOTES:
1. Make material requirements agree with requirements specified in the referenced Applicable Publications.
Verify and update the publication list to that which applies to the project unless the reference applies to all HVAC systems. Publications that apply to all HVAC systems may not be specifically referenced in the body of the specification but shall form a part of this specification.
2. Insert the year of approved latest edition of the publications between the brackets // // and delete the brackets if applicable to this project.
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. Where conflicts occur these specifications and the VHA standards will govern.
B. American National Standard Institute (ANSI/ASSE):
A10.18-//2007(R2012)//..Safety Requirements for Temporary Roof and
Floor Holes, Wall Openings, Stairways, and
Other Unprotected Edges in Construction and
Demolition Operations
C. American Society of Mechanical Engineers (ASME):
PTC 23-//2003(R2014)//..Performance Test Codes on Atmospheric Water
Cooling Equipment
ASME Boiler and Pressure Vessel Code (BPVC)
BPVC Section VIII-//2019/// Rules for Construction of Pressure Vessels, Division 1
D. American Society for Testing Materials (ASTM):
A385/A385M-//2020//.....Standard Practice for Providing High-Quality
Zinc Coatings (Hot-Dip)
A653/A653M-2020.........Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron
Alloy-Coated (Galvannealed) by the Hot-Dip
Process
A666-2015...............Standard Specification for Annealed or
Cold-Worked Austenitic Stainless Steel Sheet, Strip, Plate, and Flat Bar
23 65 00-3
B117-//2019//...........Standard Practice for Operating Salt Spray
(Fog) Apparatus
B209/B209M-//2021//.....Standard Specification for Aluminum and
Aluminum-Alloy Sheet and Plate
E84-//2021a//...........Standard Test Method for Surface Burning
Characteristics of Building Materials
E. Cooling Technology Institute (CTI):
ATC 105-//2019//........Acceptance Test Code for Water Cooling Towers
ATC 105S//2011//........Acceptance Test Code for Closed Circuit Cooling
Towers
STD 201 OM-//2019//.....Operations Manual for Thermal Performance
Certification of Evaporative Heat Rejection
Equipment
F. National Electrical Manufacturers Association (NEMA):
MG 1-//2016//...........Motors and Generators (ANSI)
250-//2020//............Enclosures for Electrical Equipment (1000 Volts
Maximum)
G. National Fire Protection Association (NFPA):
70-//2020//.............National Electrical Code
H. Veterans Health Administration (VHA):
ES-2019-01//2021//......Engineering Standard Cooling Tower Water
Systems
Directive 1061-//2021//.Prevention of Health Care-Associated Legionella
Disease and Scald Injury from Water Systems
1.4 SUBMITTALS
A. Submittals, including number of required copies, shall be submitted in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND
SAMPLES.
B. Information and material submitted under this section shall be marked
“SUBMITTED UNDER SECTION 23 XX XX, SECTION TITLE”, with applicable paragraph identification.
C. Shop Drawings:
1. Sufficient information, clearly presented, shall be included to determine compliance with the contract documents.
2. Include rated capacities, pressure drop, fan performance and rating curves, dimensions, weights, mounting details, front view, side view, and equipment and device arrangement.
23 65 00-4
3. Include electrical rating, detail wiring for power, signals, and controls.
4. //Pump characteristic curve for the closed circuit fluid cooler.//
5. Sound curves and characteristics of sound attenuators if required to meet the noise criteria.
D. Certification:
1. Submit 4 copies of performance curves, for CTI certified cooling towers, showing compliance with actual conditions specified, to the
COR 2 weeks prior to delivery of the equipment.
2. Two weeks prior to final inspection, submit 4 copies of the following to the COR:
SPEC WRITER NOTE: Specify the seismic design category for the project so the cooling tower manufacturers can check/design seismic strength of their equipment. Delete the following paragraph if the seismic design category is A or B.
a. Certification from the manufacturer that the cooling tower(s), accessories, and components are suitable for seismic design category // // installations and that the unit will be fully operational after the seismic event at the project site.
b. Certification by the manufacturer that the cooling towers conform to the requirements of the contract documents.
c. Certification by the Contractor that the cooling towers have been installed, adjusted, and tested.
E. Manufacturer's Literature and Data Including: Full item description and optional features and accessories. Include dimensions, weights, materials, applications, standard compliance, model numbers, size, and capacity.
SPEC WRITER NOTE: Coordinate O&M Manual and commissioning requirements with Section 01 00 00, GENERAL REQUIREMENTS and Section 01 91 00, GENERAL COMMISSIONING REQUIREMENTS. O&M Manuals shall be submitted for content review as part of closeout documents.
F. Complete operating and maintenance manuals including wiring diagrams, technical data sheets, information for ordering replaceable parts, and troubleshooting guide:
1. Include complete list indicating all components of the systems.
23 65 00-5
2. Include complete diagrams of the internal wiring for each item of equipment.
3. Diagrams shall have their terminals identified to facilitate installation, operation, and maintenance.
G. //Completed System Readiness Checklist provided by the CxA and completed by the contractor, signed by a qualified technician, and dated on the date of completion, in accordance with the requirements of
Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS.//
H. //Submit training plans and instructor qualifications in accordance with the requirements of Section 23 08 00, COMMISSIONING OF HVAC
SYSTEMS.//
1.5 QUALITY ASSURANCE
A. Refer to paragraph QUALITY ASSURANCE of Section 23 05 11, COMMON WORK
RESULTS FOR HVAC.
B. Design Criteria:
1. Design to withstand // // Pa (// // psf) wind load.
2. Free water drift loss shall not be greater than five hundredths of one percent (0.05) of the water circulated to tower.
SPEC WRITER NOTE: Specify dB(A) level based on the project specific acoustic analysis and local ordinance.
3. Sound levels at 1.5 meters (5 feet) and 17 meters (55 feet) in any direction from the tower shall not exceed // // dB (A) and // // dB (A), respectively. Select “low Noise” model cooling towers, where available. Provide sound attenuators if necessary to meet the noise criteria.
C. Performance Criteria:
1. Manufacturer shall certify that performance of cooling towers will meet contract requirements, stating entering air wet bulb temperature, entering and leaving condenser water temperatures, water flow rates, fan kW (horsepower)// and pump head at base of tower//. Certification shall be made at the time of submittal.
SPEC WRITER NOTE: CTI STD 201 OM
certification applies only to selections with entering water temperature of 52 degrees C (125 degrees F) or less, temperature ranges of 2.2 degrees C (36 degrees F) or more, temperature approaches of 2.8 degrees C (37 degrees F) or more, and wet bulb between 15.5
23 65 00-6 degrees C to 29.5 degrees C (60 degrees F to 85 degrees F).
2. Cooling Technology Institute (CTI) Certified Towers: These towers shall have been tested, rated, and certified in accordance with CTI
STD 201 OM, and shall bear the CTI certification label, and shall be listed in the CTI directory of certified cooling towers.
3. The alignment and balancing of the fans, motors and drive shaft as installed shall operate within the vibration tolerance specified in
Section 23 05 41, NOISE and VIBRATION CONTROL FOR HVAC PIPING and
EQUIPMENT.
D. Bio-Based Materials: For products designated by the USDA’s
Bio-Preferred Program, provide products that meet or exceed USDA recommendations for bio-based content, so long as products meet all performance requirements in this specifications section. For more information regarding the product categories covered by the
Bio-Preferred Program, visit http://www.biopreferred.gov.
E. Refer to Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for additional sustainable design requirements.
1.6 AS-BUILT DOCUMENTATION
A. Comply with requirements in paragraph AS-BUILT DOCUMENTATION of Section
23 05 11, COMMON WORK RESULTS FOR HVAC.
PART 2 - PRODUCTS
2.1 INDUCED DRAFT OPEN CIRCUIT COOLING TOWER
SPEC WRITER NOTE: Induced draft open circuit cooling towers should be used on a majority of projects. In general, cross-flow type shall be used, where winter operation is required, specify counter-flow type.
A. Cooling tower shall be a factory assembled, induced draft, //cross-flow// //counter-flow// type with a vertical discharge configuration.
SPEC WRITER NOTE: Use stainless-steel for all principal panels and structural elements, hot and cold water basins, fan deck, etc. for the High-Humidity locations listed in the VA HVAC Design Manual.
B. Casing: Heavy gauge (minimum 16 gauge) //galvanized steel//
//stainless-steel// //Fiberglass Reinforced Plastic (FRP) with UV inhibitors//.
http://www.biopreferred.gov/
23 65 00-7
1. //Galvanized Steel: Hot-dip galvanized steel complying with ASTM
A653/A653M, and having G235 (Z700) coating. //
2. //Stainless-Steel: ASTM A666, Type 304. //
3. //Fiberglass Reinforced Plastic: FRP with maximum flame spread rating of five according to ASTM E84 and with UV inhibitors. //
4. Fasteners: Zinc or cadmium coated bolts or tapping screws for assembly. Use stainless-steel washers with neoprene backing where required for preventing leaks.
5. Joints and Seams: Sealed watertight.
6. Welded Connections: Continuous and watertight.
C. Framing: //Rolled structural steel shapes, hot-dip galvanized after fabrication or structural shapes cold formed from galvanized steel sheets or plates, complying with ASTM A653/A653M, and having G235
(Z700) coating.// //Rolled or formed structural stainless-steel conforming to ASTM A666, Type 304.//
D. Louvers:
1. Spaced to minimize air resistance and prevent splash out. Louver materials shall be similar to the casings or may be polyvinyl chloride (PVC) if formed integral with the fill material.
2. 13 mm (1/2 inch) inlet screen, //hot dipped galvanized steel or copper// //stainless-steel//. Attach the screen securely to air intakes.
E. Fill: //PVC// //FRP// resistant to rot, decay and biological attack;
with a maximum flame spread rating of five per ASTM E84 and fabricated, formed and installed by manufacturer to ensure that water breaks up into droplets.
F. Drift Eliminators: Same as fill material. Effectively trap water droplets entrained in discharge air stream and limit drift loss to less than 0.05 percent of the total water circulated. Sections shall be assembled into easily removable racks of the same material as the casing. Eliminators can be PVC neoprene honeycomb type.
SPEC WRITER NOTE: Eliminate the combustible materials when cooling tower is located 12 meters (40 feet) or closer to hazards such as chimneys, and incinerators, or when roof mounted.
G. Hot Water Distribution System: Open basin, flume and troughs, or a pipe system with nozzles spaced for even distribution of water over fill material. Provide access door. System shall be self-draining and
23 65 00-8 non-clogging. Spray nozzles, if used, shall be cleanable stainless-steel, bronze or high impact plastic, non-clog, removable type properly spaced for even distribution. Provide cover for entire nozzle area or flume/trough area. //Provide manufacturer's standard pre-strainer assembly and butterfly or globe valve, for cross flow tower, to balance the water flow to each basin.//
H. Cold Water Collection Basin: Heavy gauge, zinc-coated or hot-dip galvanized steel, same as the casing //stainless-steel// //FRP with UV inhibitors//. Overflow drain not less than 50 mm (2 inches), and a 304 stainless-steel strainer assembly with openings smaller than nozzle orifices and with built-in vortex baffling to prevent cavitation and air entrainment in the water basin circulating pump.
I. Accessories: Make-up water, overflow and drain connections//; equalizer connection (multiple cooling tower systems)//; Flume plate between adjacent cells (multi-cell units only)//.
SPEC WRITER NOTE: On large multiple tower systems, on small systems with a single tower 50 tons or larger, or on systems requiring remote level indication/alarm capability, provide electronic level control. Locate the sensor in the equalization line on multiple tower systems.
J. Collection Basin Water Level Control: //Mechanically operated bronze adjustable make-up water float valve.// //Electronic operated with slow closing 120V solenoid valve and NEMA MG 1, Type 4X enclosure. Solid state controls with stainless-steel electrode probes and relays factory wired to a terminal strip to provide control of makeup valve, low and high level alarms and output for shutoff of pump on low level//.
K. Fans: Heavy duty axial flow type, //belt// //gear// driven and balanced at the factory after assembly, with //cast aluminum or aluminum alloy//
//FRP// blades. Fans shall be driven by //single speed// //variable speed// motor. The fan drive and moving parts shall be completely enclosed by removable hot-dip galvanized screens and panels complying with OSHA regulations. Fan shaft bearings of the self-aligning, grease-lubricated ball or roller bearings with moisture proof seals and premium, moisture-resistant grease suitable for temperatures between minus 29 and 149 degrees C (minus 20 and plus 300 degrees F). Bearings designed for an L-10 life of //40,000// //50,000// hours and with
23 65 00-9 extended lubrication lines to an easily accessible location outside of the wet air stream. Provide access doors for inspection and cleaning.
L. Motors and Drives:
1. The alignment and balancing of the fans, motors and drive shaft as installed shall operate within the vibration limits specified in
Section 23 05 41, NOISE and VIBRATION CONTROL FOR HVAC PIPING and
EQUIPMENT.
2. In addition to the requirements of Section 23 05 11, COMMON WORK
RESULTS FOR HVAC, the following shall apply:
a. Motors: Totally enclosed or epoxy encapsulated NEMA MG 1. Protect fan, bearings, and appurtenances from damage by weather, corrosion, water spray and grit. Provide motors with severe duty rating with the rotor and stator protected with corrosion-inhibiting epoxy resin, double shielded, vacuum-degassed bearings lubricated with premium moisture-resistant grease suitable for temperatures between minus 29 and plus 149 degrees C (minus 20 and plus 300 degrees F), and an internal heater automatically energized when motor is de-energized. Provide an adjustable motor base or other suitable provision for adjusting belt tension.
b. Fans for towers of 350 kW (100 tons) and less shall be belt driven. For towers larger than 350 kW (100 tons), fan shall be driven through a gear reducer, or driven by a V-belt.
1) Gear Reducer Drive: Specially designed for cooling tower operation, with dynamically balanced drive shaft assembly or shock absorbent flexible coupling requiring no lubrication, cast-iron case with readily accessible oil drum and fill, and self-contained oil reservoir sealed against water entrance.
2) V-Belt Drive: Fan shall be driven by a one-piece, multi-groove, neoprene/polyester belt, where this is the manufacturer’s standard. Belt drives shall be "V" type as specified in Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
Belt driven fan and motor shafts shall have taper-lock sheaves fabricated from corrosion resistant material.
SPEC WRITER NOTE: Coordinate motor and starter requirements with Division 26, ELECTRICAL.
23 65 00-10
c. Motor Controllers: Provide variable speed motors and controllers, if shown in the contract documents for cooling tower fans. See
Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
d. Lubrication fittings shall be readily accessible outside the wet air stream. Provide access doors for inspection and cleaning.
e. The alignment and balancing of the fans, motors and drive shaft as installed shall operate within the vibration tolerance specified in Section 23 05 41, NOISE and VIBRATION CONTROL FOR
HVAC PIPING and EQUIPMENT.
M. Fans over 1524 mm (60 inches) in diameter include a vibration cutout switch located in a protected position to effectively monitor fan vibration. Vibration switch shall be solid-state with adjustable time delay in NEMA 250, Type 4 enclosure. It shall stop fan motor under excessive fan vibration. //Interface the vibration cut-out switch with the DDC control system to provide an alarm in the event the fans stop due to excessive vibration.//
SPEC WRITER NOTE: Designer shall show handrails, ladders, and platforms required for maintenance of cooling towers on drawings. The design shall comply with OSHA Standards. Coordinate with manufacturer’s requirements for maintenance access.
N. Safety: Provide fan guards, ladders, handrails, and platform in conformance with the ANSI A10.18 as follows:
1. Fan Guard: Removable fan discharge with a rigid framed screen guard, installed over the fan cylinder.
2. Ladders: Vertical hot-dip galvanized steel or aluminum ladder for each tower located outdoors. Ladders higher than 3.6 meters (12 feet) shall have safety cage. Ladders shall extend to within 305 mm
(1 foot) of the grade or the roof deck surface.
3. Hand Railing: Steel or aluminum hand railings not less than 1067 mm
(42 inches) high around perimeter of each fan-deck, or working surface 3.6 meters (12 feet) or more above ground, roof or other supporting construction. Handrails shall meet OSHA Standards.
4. Platform: Galvanized steel with a bar grating floor.
SPEC WRITER NOTE: Delete paragraphs O and P when winter operation is not required.
O. Electric Basin Heater: Furnish stainless-steel electric immersion heater installed in a threaded coupling on the side of the basin and
23 65 00-11 with watertight junction boxes mounted in the basin with sufficient capacity to maintain plus 4 degrees C (40 degrees F) water in the basin at // // degrees C (// // degrees F) ambient. Provide a NEMA 250, //Type 3R// //Type 4// //Type 4X// mounted on the side of each cooling tower cell with magnetic contactors controlled by a temperature sensor/controller to maintain collection basin water-temperature set point. Provide a water-level probe to monitor cooling tower water level and de-energize the heater when the water reaches low-level set point.
Provide a control-circuit transformer with primary and secondary side fuses, terminal blocks with numbered and color-coded wiring to match wiring diagram, Single-point, field-power connection to a //fused disconnect switch// //nonfused disconnect switch// //circuit breaker// and heater branch circuiting complying with NFPA 70. Provide a Metal raceway for factory-installed wiring outside of enclosures, except make connections to each electric basin heater with liquid tight conduit.
SPEC WRITER NOTE: Specify electric heat tracing if cooling tower is specified independent of HVAC Piping Systems.
P. Electric Heat Tracing: Provide in Section 23 21 13, HYDRONIC PIPING.
SPEC WRITER NOTE: Specify discharge hood, if necessary, to increase leaving air velocity to avoid recirculation.
Q. //Discharge Hood: //Tapered// //Straight// //hot-dip galvanized steel//
//stainless-steel//, same as the casing with factory-installed access door. //
2.2 FORCED DRAFT OPEN CIRCUIT COOLING TOWER
SPEC WRITER NOTE: Forced draft open circuit cooling towers should be used on projects where the tower is indoors, requires ductwork, or is operated in the winter.
A. Cooling tower shall be a factory assembled, forced draft, counter-flow type with a vertical discharge configuration.
SPEC WRITER NOTE: Use stainless-steel for all principal panels and structural elements, hot and cold water basins, etc.
for the High-Humidity locations.
inhibitors//.
23 65 00-12
1. //Galvanized Steel: Hot-dip galvanized steel complying with ASTM
A653/A653M, and having G235 (Z700) coating.//
2. //Stainless-Steel: ASTM A666, Type 304.//
3. //Fiberglass Reinforced Plastic: FRP with maximum flame spread rating of five according to ASTM E84 and with UV inhibitors.//
4. Fasteners: Zinc or cadmium coated bolts or tapping screws for assembly. Use stainless-steel washers with neoprene backing where required for preventing leaks.
5. Joints and Seams: Sealed watertight.
6. Welded Connections: Continuous and watertight.
C. Framing: //Rolled structural steel shapes, hot-dip galvanized after fabrication or structural shapes cold formed from galvanized steel sheets or plates, complying with ASTM A653/A653M, and having G235
(Z700) coating.// //Rolled or formed structural stainless-steel conforming to ASTM A666, Type 304.//
D. Fill: //PVC// //FRP// resistant to rot, decay and biological attack;
with a maximum flame spread rating of five per ASTM E84 and fabricated, formed and installed by manufacturer to ensure that water breaks up into droplets.
E. Drift Eliminators: Same as fill material. Effectively trap water droplets entrained in discharge air stream and limit drift loss to less than 0.0005 percent of the total water circulated. Sections shall be assembled into easily removable racks of the same material as the casing. Eliminators can be PVC neoprene honeycomb type.
SPEC WRITER NOTE: Eliminate the combustible materials when cooling tower is located 12 meters (40 feet) or closer to hazards such as chimneys, and incinerators, or when roof mounted.
F. Hot Water Distribution System: Open basin, flume and troughs, or a pipe system with nozzles spaced for even distribution of water over fill material. Provide access door. System shall be self-draining and non-clogging. Spray nozzles, if used, shall be cleanable stainless-steel, bronze or high impact plastic, non-clog, removable type properly spaced for even distribution. Provide cover for entire nozzle area or flume/trough area. //Provide manufacturer's standard pre-strainer assembly and butterfly or globe valve, for cross flow tower, to balance the water flow to each basin.//
23 65 00-13
G. Cold Water Collection Basin: Heavy gauge, zinc-coated or hot-dip galvanized steel, same as the casing //stainless-steel// //FRP with UV inhibitors//. Overflow drain not less than 50 mm (2inches), and a 304 stainless-steel strainer assembly with openings smaller than nozzle orifices and with built-in vortex baffling to prevent cavitation and air entrainment in the water basin circulating pump.
H. Accessories: Make-up water, overflow and drain connections, Equalizer connection (multiple cooling tower systems) Flume plate between adjacent cells (multi-cell units only).
SPEC WRITER NOTE: On large multiple tower systems, on small systems with a single tower 50 tons or larger, or on systems requiring remote level indication/alarm capability, provide electronic level control. Locate the sensor in the equalization line on multiple tower systems.
I. Collection Basin Water Level Control: //Mechanically operated bronze closing 120V solenoid valve and NEMA MG 1, Type 4X enclosure. Solid state controls with stainless-steel electrode probes and relays factory wired to a terminal strip to provide control of makeup valve, low and high level alarms and output for shutoff of pump on low level.//
J. Fans: Centrifugal double width, double inlet, forward curved blades, belt driven and statically and dynamically balanced at the factory after assembly. Hot-dip galvanized steel centrifugal fans belt driven by //single speed// //variable speed// motor. The fan drive and moving parts shall be completely enclosed by removable hot-dip galvanized screens and panels complying with OSHA regulations. Fan shaft bearings of the self-aligning, grease-lubricated ball or roller bearings with moisture proof seals and premium, moisture-resistant grease suitable for temperatures between minus 29 and 149 degrees C (minus 20 and plus
300 degrees F). Bearings designed for an L-10 life of //40,000//
//50,000// hours and with extended lubrication lines to an easily accessible location outside of the wet air stream. Provide access doors for inspection and cleaning.
K. Motors and Drives:
1. The alignment and balancing of the fans, motors and drive shaft as installed shall operate within the vibration limits specified in
23 65 00-14
Section 23 05 41, NOISE and VIBRATION CONTROL FOR HVAC PIPING and
EQUIPMENT.
2. In addition to the requirements of Section 23 05 11, COMMON WORK
RESULTS FOR HVAC, the following shall apply:
a. Motors: Totally enclosed or epoxy encapsulated NEMA MG 1. Protect fan, bearings, and appurtenances from damage by weather, corrosion, water spray and grit. Provide motors with severe duty rating with the rotor and stator protected with corrosion-inhibiting epoxy resin, double shielded, vacuum-degassed bearings lubricated with premium moisture-resistant grease suitable for temperatures between minus 29 and plus 149 degrees C (minus 20 and plus 300 degrees F), and an internal heater automatically energized when motor is de-energized. Provide an adjustable motor base or other suitable provision for adjusting belt tension.
b. V-Belt Drive: Fan shall be driven by a one-piece, multi-groove, neoprene/polyester belt, where this is the manufacturer’s standard. Belt drives shall be "V" type as specified in Section
23 05 11, COMMON WORK RESULTS FOR HVAC. Belt driven fan and motor shafts shall have taper-lock sheaves fabricated from corrosion resistant material.
SPEC WRITER NOTE: Coordinate motor and starter requirements with Division 26, ELECTRICAL.
c. Motor Controllers: Provide variable speed motors and controllers, if shown in the contract documents for cooling tower fans. See
Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
d. Lubrication fittings shall be readily accessible outside the wet air stream. Provide access doors for inspection and cleaning.
e. The alignment and balancing of the fans, motors and drive shaft as installed shall operate within the vibration tolerance specified in Section 23 05 41, NOISE and VIBRATION CONTROL FOR
HVAC PIPING and EQUIPMENT.
L. Fans with motors over 15 kW (20 hp) shall include a vibration cutout switch located in a protected position to effectively monitor fan vibration. Vibration switch shall be solid-state with adjustable time delay in NEMA 250, Type 4 enclosure. It shall stop fan motor under excessive fan vibration. //Interface the vibration cut-out switch with
23 65 00-15 the DDC control system to provide an alarm in the event the fans stop due to excessive vibration.//
SPEC WRITER NOTE: Designer shall show handrails, ladders, and platforms required for maintenance of cooling towers on drawings. The design shall comply with OSHA Standards. Coordinate with manufacturer’s requirements for
M. Safety: Provide fan guards, ladders, handrails, and platform in
1. Fan Guard: Removable rigid framed screen guard, installed over the inlet side of the fan.
2. Ladders: Vertical hot-dip galvanized steel or aluminum ladder for each tower located outdoors. Ladders higher than 3.6 meters (12 feet) shall have safety cage. Ladders shall extend to within 305 mm
(1 foot) of the grade or the roof deck surface.
3. Hand Railing: Steel or aluminum hand railings not less than 1067 mm
(42 inches) high around perimeter of each fan-deck, or working surface 3.6 meters (12 feet) or more above ground, roof or other supporting construction. Handrails shall meet OSHA Standards.
4. Platform: Galvanized steel with a bar grating floor.
SPEC WRITER NOTE: Delete paragraphs N and O when winter operation is not required.
N. Electric Basin Heater: Furnish stainless-steel electric immersion with watertight junction boxes mounted in the basin with sufficient capacity to maintain plus 4 degrees C (40 degrees F) water in the basin at // // degrees C (// // degrees F) ambient. Provide a NEMA 250, //Type 3R// //Type 4// //Type 4X// mounted on the side of each cooling tower cell with magnetic contactors controlled by a temperature sensor/controller to maintain collection basin water-temperature set point. Provide a water-level probe to monitor cooling tower water level and de-energize the heater when the water reaches low-level set point.
Provide a control-circuit transformer with primary and secondary side fuses, terminal blocks with numbered and color-coded wiring to match wiring diagram, Single-point, field-power connection to a //fused disconnect switch// //nonfused disconnect switch// //circuit breaker// and heater branch circuiting complying with NFPA 70. Provide a metal
23 65 00-16 raceway for factory-installed wiring outside of enclosures, except make connections to each electric basin heater with liquid tight conduit.
SPEC WRITER NOTE: Specify electric heat tracing if cooling tower is specified
O. Electric Heat Tracing: Provide in Section 23 21 13, HYDRONIC PIPING.
SPEC WRITER NOTE: Specify discharge hood, if necessary, to increase leaving air velocity to avoid recirculation. Provide automatic control damper on cooling towers designed to operate in the winter.
P. //Discharge Hood: //Tapered// //Straight// //hot-dip galvanized steel// door //and automatic control damper//.//
SPEC WRITER NOTE: Specify sheet metal ducts, if cooling tower is to be installed indoors.
Q. //Sheet Metal Ducts: Provide in Section 23 31 00, HVAC DUCTS AND
CASINGS.//
2.3 INDUCED DRAFT CLOSED CIRCUIT FLUID COOLER
SPEC WRITER NOTE: Induced draft closed circuit coolers will be used on projects requiring a cooler, installed outdoors and not operated in the winter.
A. Cooler shall be a factory assembled, induced draft, //cross-flow//
//counter-flow// type with a vertical discharge configuration.
SPEC WRITER NOTE: Use stainless-steel for all principal panels and structural elements, hot and cold water basins, fan deck, etc. for the High-Humidity locations listed in the VA HVAC Design Manual.
inhibitors//.
1. //Galvanized Steel: Hot-dip galvanized steel complying with ASTM
A653/A653M, and having G235 (Z700) coating.//
2. //Stainless-Steel: ASTM A666, Type 304.//
3. //Fiberglass Reinforced Plastic: FRP with maximum flame spread rating of five according to ASTM E84 and with UV inhibitors.//
23 65 00-17
4. Fasteners: Zinc or cadmium coated bolts or tapping screws for assembly. Use stainless-steel washers with neoprene backing where required for preventing leaks.
5. Joints and Seams: Sealed watertight.
6. Welded Connections: Continuous and watertight.
C. Framing: //Rolled structural steel shapes, hot-dip galvanized after fabrication or structural shapes cold formed from galvanized steel sheets or plates, complying with ASTM A653/A653M, and having G235
(Z700) coating.// //Rolled or formed structural stainless-steel conforming to ASTM A666, Type 304.//
D. Louvers:
1. Spaced to minimize air resistance and prevent splash out. Louver materials shall be similar to the casings or may be polyvinyl chloride (PVC) if formed integral with the fill material.
2. 13 mm (l/2 inch) inlet screen, //hot-dip galvanized-steel or copper// //stainless-steel//. Attach screens securely to air intakes.
E. Drift Eliminators: Same as fill material. Effectively trap water droplets entrained in discharge air stream and limit drift loss to less than 0.0005 percent of the total water circulated. Sections shall be assembled into easily removable racks of the same material as the casing. Eliminators can be PVC neoprene honeycomb type.
SPEC WRITER NOTE: Provide stainless-steel basin for the High-Humidity locations listed in the VA HVAC Design Manual.
F. Cold Water Collection Basin: Heavy gauge zinc-coated or hot-dip galvanized steel, same as the casing //stainless-steel// //FRP with UV inhibitors//. Overflow drain not less than 50 mm (2 inches), and a 304 stainless-steel strainer assembly with openings smaller than nozzle orifices and with built-in vortex baffling to prevent cavitation and air entrainment in the water basin circulating pump.
SPEC WRITER NOTE: On large systems greater than 50 tons or on systems requiring remote level indication/alarm capability, provide electronic level control.
G. Collection Basin Water Level Control: //Mechanically operated bronze closing 120V solenoid valve and NEMA MG 1, Type 4X enclosure. Solid
23 65 00-18 state controls with stainless-steel electrode probes and relays factory wired to a terminal strip to provide control of makeup valve, low and high level alarms and output for shutoff of pump on low level.//
SPEC WRITER NOTE: Use copper or stainless-steel tubes for the High- Humidity locations listed in the VA HVAC Design Manual.
H. Cooling Coil Sections: //Prime-coated steel tube and sheet with outer surface of tube and sheet hot-dip galvanized after fabrication//
//Copper tube with stainless-steel sheet// //Stainless-steel tube and sheet//, tested at 2413 kPa (350 psig) air pressure under water. Slope tubes to permit free drainage of fluid. Design and manufacture and test coils according to ASME BPVC Section VIII, and bearing ASME “U” stamp.
Design coil and casing housing section for easy removal of coil. Coil section shall be of the serpentine design type with coil tubing welded into service pipe connection header. Provide flanged piping connections suitable for field mounting on the vent, supply and return water lines to the coil.
I. Water Distribution System: Open gravity type or individual removable non-clogging spray nozzle type and specifically designed that each trough or spray nozzle extends the entire length of the cooling coil section to complete wetting of the cooling coil at all times. Construct water distribution system of hot-dip galvanized steel or Schedule 40
PVC. Provide corrosion resistant hangers and supports designed to resist movement during operation and shipment.
J. Cooler Water Distribution Circulating Pump: Close coupled bronze fitted centrifugal circulating pump with mechanical seal suitable for outdoor use, suction strainer, and flow balancing valve. Pump shall be completely piped to suction strainer and water distribution system, mounted to drain completely when tower basin is drained. Include a bleed line with valve between pump discharge and overflow pipe. For pump motor, see Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
K. Fans: Heavy duty axial flow type, //belt// //gear// driven and balanced at the factory after assembly, with //cast aluminum or aluminum alloy//
//FRP// blades. Fans shall be driven by //single speed// //variable speed// motor. The fan drive and moving parts shall be completely enclosed by removable hot-dip galvanized screens and panels complying with OSHA regulations. Fan shaft bearings of the self-aligning, grease-lubricated ball or roller bearings with moisture proof seals and
23 65 00-19 premium, moisture-resistant grease suitable for temperatures between minus 29 and 149 degrees C (minus 20 and plus 300 degrees F). Bearings designed for an L-10 life of //40,000// //50,000// hours and with extended lubrication lines to an easily accessible location outside of the wet air stream. Provide access doors for inspection and cleaning.
L. Motors and Drives:
1. The alignment and balancing of the fans, motors and drive shaft as installed shall operate within the vibration limits specified in
Section 23 05 41, NOISE and VIBRATION CONTROL FOR HVAC PIPING and
EQUIPMENT.
2. In addition to the requirements of Section 23 05 11, COMMON WORK
RESULTS FOR HVAC, the following shall apply:
a. Motors: Totally enclosed or epoxy encapsulated NEMA MG 1. Protect fan, bearings, and appurtenances from damage by weather, corrosion, water spray and grit. Provide motors with severe duty rating with the rotor and stator protected with corrosion-inhibiting epoxy resin, double shielded, vacuum-degassed bearings lubricated with premium moisture-resistant grease suitable for temperatures between minus 29 and plus 149 degrees C (minus 20 and plus 300 degrees F), and an internal heater automatically energized when motor is de-energized. Provide an adjustable motor base or other suitable provision for adjusting belt tension.
b. Fans for coolers of 350 kW (100 tons) and less shall be belt driven. For coolers larger than 350 kW (100 tons), fan shall be driven through a gear reducer, or driven by a V-belt.
1) Gear Reducer Drive: Specially designed for cooler operation, with dynamically balanced drive shaft assembly or shock absorbent flexible coupling requiring no lubrication, cast-iron case with readily accessible oil drum and fill, and self-contained oil reservoir sealed against water entrance.
2) V-Belt Drive: Fan shall be driven by a one-piece, multi-groove, neoprene/polyester belt, where this is the manufacturer’s standard. Belt drives shall be "V" type as specified in Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
Belt driven fan and motor shafts shall have taper-lock sheaves fabricated from corrosion resistant material.
SPEC WRITER NOTE: Coordinate motor and starter requirements with ELECTRICAL.
23 65 00-20
c. Motor Controllers: Provide variable speed motors and controllers, if shown in the contract documents for cooling tower fans. See
Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
d. Lubrication fittings shall be readily accessible outside the wet air stream. Provide access doors for inspection and cleaning.
e. The alignment and balancing of the fans, motors and drive shaft as installed shall operate within the vibration tolerance specified in Section 23 05 41, NOISE and VIBRATION CONTROL FOR
HVAC PIPING and EQUIPMENT.
M. Fans over 1524 mm (60 inches) in diameter include a vibration cutout switch located in a protected position to effectively monitor fan vibration. Vibration switch shall be solid-state with adjustable time delay in NEMA 250, Type 4 enclosure. It shall stop fan motor under excessive fan vibration. //Interface the vibration cut-out switch with the DDC control system to provide an alarm in the event the fans stop due to excessive vibration.//
SPEC WRITER NOTE: Delete paragraphs N and O when winter operation is not required.
N. Electric Basin Heater: Furnish stainless-steel electric immersion with watertight junction boxes mounted in the basin with sufficient capacity to maintain plus 4 degrees C (40 degrees F) water in the basin at // // degrees C (// // degrees F) ambient. Provide a NEMA 250, //Type 3R// //Type 4// //Type 4X// enclosure mounted on the side of each cooler cell with magnetic contactors controlled by a temperature sensor/controller to maintain collection basin water-temperature set point. Provide a water-level probe to monitor cooler water level and de-energize the heater when the water reaches low-level set point.
Provide a control-circuit transformer with primary and secondary side fuses, terminal blocks with numbered and color-coded wiring to match wiring diagram, Single-point, field-power connection to a //fused disconnect switch// //nonfused disconnect switch// //circuit breaker// and heater branch circuiting complying with NFPA 70. Provide a Metal raceway for factory-installed wiring outside of enclosures, except make connections to each electric basin heater with liquid tight conduit.
SPEC WRITER NOTE: Specify electric heat tracing if fluid cooler is specified
23 65 00-21
O. Electric Heat Tracing: Refer to Section 23 21 13, HYDRONIC PIPING.
SPEC WRITER NOTE: Designer shall show handrails, ladders, and platforms required for maintenance of fluid coolers on drawings. The design shall comply with OSHA Standards. Coordinate with manufacturer’s requirements for
P. Safety: Provide fan guards, ladders, handrails and platform in
1. Fan Guard: Removable fan discharge with a rigid framed screen guard, installed over the fan cylinder.
2. Ladders: Vertical hot-dip galvanized steel or aluminum ladder for each tower located outdoors. Ladders higher than 3.6 meters (12 feet) shall have safety cage. Ladders shall extend to within 305 mm
(1 foot) of the grade or the roof deck surface.
3. Hand Railing: Steel or aluminum hand railings not less than 1067 mm
(42 inches) high around perimeter of each fan-deck, or working surface 3.6 meters (12 feet) or more above ground, roof or other supporting construction. Handrails shall meet OSHA Standards.
4. Platform: Galvanized steel with a bar grating floor.
SPEC WRITER NOTE: Specify discharge hood, if necessary, to increase leaving air velocity to avoid recirculation.
Q. //Discharge Hood: //Tapered// //Straight// //hot-dip galvanized steel// door.//
2.4 FORCED DRAFT CLOSED CIRCUIT FLUID COOLER
SPEC WRITER NOTE: Forced draft closed circuit coolers will be used on projects requiring a cooler, installed indoors or outdoors and suitable to be operated in the winter.
A. Cooler shall be a factory assembled, forced draft, counter-flow type with a vertical discharge configuration.
SPEC WRITER NOTE: Use stainless-steel for all principal panels and structural elements, hot and cold water basins, etc.
for the High-Humidity locations listed in the VA HVAC Design Manual.
23 65 00-22
B. Casing: Heavy gauge (minimum 16 gauge) //galvanized steel//
//stainless-steel// //Fiberglass Reinforced Plastic (FRP) with UV inhibitors//.
1. //Galvanized Steel: Hot-dip galvanized steel complying with ASTM
A653/A653M, and having G235 (Z700) coating.//
2. //Stainless-Steel: ASTM A666, Type 304.//
3. //Fiberglass Reinforced Plastic: FRP with maximum flame spread rating of five according to ASTM E84 and with UV inhibitors.//
4. Fasteners: Zinc or cadmium coated bolts or tapping screws for assembly. Use stainless-steel washers with neoprene backing where required for preventing leaks.
5. Joints and Seams: Sealed watertight.
6. Welded Connections: Continuous and watertight.
C. Framing: //Rolled structural steel shapes, hot-dip galvanized after fabrication or structural shapes cold formed from galvanized steel sheets or plates, complying with ASTM A653/A653M, and having G235
(Z700) coating.// //Rolled or formed structural stainless-steel conforming to ASTM A666, Type 304.//
D. Drift Eliminators: Same as fill material. Effectively trap water droplets entrained in discharge air stream and limit drift loss to less than 0.0005 percent of the total water circulated. Sections shall be assembled into easily removable racks of the same material as the casing. Eliminators can be PVC neoprene honeycomb type.
E. Cold Water Collection Basin: Heavy gauge zinc-coated or hot-dip galvanized steel, same as the casing //stainless-steel// //FRP with UV inhibitors//. Overflow drain not less than 50 mm (2 inches), and a 304 stainless-steel strainer assembly with openings smaller than nozzle orifices and with built-in vortex baffling to prevent cavitation and air entrainment in the water basin circulating pump.
SPEC WRITER NOTE: On large systems greater than 50 tons or on systems requiring remote level indication/alarm capability, provide electronic level control.
F. Collection Basin Water Level Control: //Mechanically operated bronze closing 120V solenoid valve and NEMA MG 1, Type 4X enclosure. Solid state controls with stainless-steel electrode probes and relays factory
23 65 00-23 wired to a terminal strip to provide control of makeup valve, low and high level alarms and output for shutoff of pump on low level.//
SPEC WRITER NOTE: Use copper or stainless-steel tubes for the High- Humidity locations listed in the VA HVAC Design Manual.
G. Cooling Coil Sections: //Prime-coated steel tube and sheet with outer surface of tube and sheet hot-dip galvanized after fabrication//
//Copper tube with stainless-steel sheet// //Stainless-steel tube and sheet//, tested at 2413 kPa (350 psig) air pressure under water. Slope tubes to permit free drainage of fluid. Design and manufacture and test coils according to ASME BPVC Section VIII, and bearing ASME “U” stamp.
Design coil and casing housing section for easy removal of coil. Coil section shall be of the serpentine design type with coil tubing welded into service pipe connection header. Provide flanged piping connections suitable for field mounting on the vent, supply and return water lines to the coil.
H. Water Distribution System: Open gravity type or individual removable non-clogging spray nozzle type and specifically designed that each trough or spray nozzle extends the entire length of the cooling coil section to complete wetting of the cooling coil at all times. Construct water distribution system of hot-dip galvanized steel or Schedule 40
PVC. Provide corrosion resistant hangers and supports designed to resist movement during operation and shipment.
I. Cooler Water Distribution Circulating Pump: Close coupled bronze fitted centrifugal circulating pump with mechanical seal suitable for outdoor use, suction strainer, and flow balancing valve. Pump shall be completely piped to suction strainer and water distribution system, mounted to drain completely when tower basin is drained. Include a bleed line with valve between pump discharge and overflow pipe. For pump motor, see Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
J. Fans: Centrifugal double width, double inlet, forward curved blades, belt driven and statically and dynamically balanced at the factory after assembly. Hot-dip galvanized steel centrifugal fans belt driven by //single speed// //variable speed// motor. The fan drive and moving parts shall be completely enclosed by removable hot-dip galvanized screens and panels complying with OSHA regulations. Fan shaft bearings of the self-aligning, grease-lubricated ball or roller bearings with moisture proof seals and premium, moisture-resistant grease suitable
23 65 00-24 for temperatures between minus 29 and 149 degrees C (minus 20 and plus
300 degrees F). Bearings designed for an L-10 life of //40,000//
//50,000// hours and with extended lubrication lines to an easily accessible location outside of the wet air stream. Provide access doors for inspection and cleaning.
K. Motors and Drives:
1. The alignment and balancing of the fans, motors and drive shaft as installed shall operate within the vibration limits specified in
Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND
EQUIPMENT.
2. In addition to the requirements of Section 23 05 11, COMMON WORK
RESULTS FOR HVAC, the following shall apply:
a. Motors: Totally enclosed or epoxy encapsulated NEMA MG 1. Protect fan, bearings, and appurtenances from damage by weather, corrosion, water spray and grit. Provide motors with severe duty rating with the rotor and stator protected with corrosion-inhibiting epoxy resin, double shielded, vacuum-degassed bearings lubricated with premium moisture-resistant grease suitable for temperatures between minus 29 and plus 149 degrees C (minus 20 and plus 300 degrees F), and an internal heater automatically energized when motor is de-energized. Provide an adjustable motor base or other suitable provision for adjusting belt tension.
b. V-Belt Drive: Fan shall be driven by a one-piece, multi-groove, neoprene/polyester belt, where this is the manufacturer’s standard. Belt drives shall be "V" type as specified in Section
23 05 11, COMMON WORK RESULTS FOR HVAC. Belt driven fan and motor shafts shall have taper-lock sheaves fabricated from corrosion resistant material.
c. Motor Controllers: Provide variable speed motors and controllers, if shown in the contract documents for cooling tower fans. See
Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
d. Lubrication fittings shall be readily accessible outside the wet air stream. Provide access doors for inspection and cleaning.
e. The alignment and balancing of the fans, motors and drive shaft as installed shall operate within the vibration tolerance specified in Section 23 05 41, NOISE and VIBRATION CONTROL FOR
HVAC PIPING and EQUIPMENT.
23 65 00-25
L. Fans with motors over 15 kW (20 hp) shall include a vibration cutout switch located in a protected position to effectively monitor fan vibration. Vibration switch shall be solid-state with adjustable time delay in NEMA 250, Type 4 enclosure. It shall stop fan motor under excessive fan vibration. //Interface the vibration cut-out switch with the DDC control system to provide an alarm in the event the fans stop due to excessive vibration.//
SPEC WRITER NOTE: Delete paragraphs M and N when winter operation is not required.
M. Electric Basin Heater: Furnish stainless-steel electric immersion with watertight junction boxes mounted in the basin with sufficient capacity to maintain plus 4 degrees C (40 degrees F) water in the basin at // // degrees C (// // degrees…