Energy QAP C16.67-2.pdf

PDF 140 KB Posted

Attached to
RFQ SPE60524Q0045 DRAWSKO POMORSKI, POLAND 32, 000 GALS DIESEL FUEL (SFD) RDD 19 SEPT 2024
Solicitation number
SPE60524Q0045
Issued by

About this file

This document is a Diesel Fuel Specification (SFD) for the Defense Logistics Agency Energy (DLA Energy) that outlines the product requirements for diesel fuel to be delivered to locations in Kosovo, Afghanistan, and other general locations.

The key details are:

  • Diesel fuel must conform to the latest revision of the EN 590 commercial specification, including a maximum sulfur content of 10 mg/kg.
  • For Kosovo, there are additional requirements for color, acid number, haze rating, sediment, and water content. Diesel fuel must also meet seasonal grade requirements.
  • For Afghanistan, the diesel fuel must meet a maximum cold filter plugging point of -15°C.
  • Contractors must obtain written exceptions or deviations from DLA Energy if they are unable to meet any of the specification requirements.
  • This specification applies to a related federal contract opportunity, Solicitation Number SPE60524Q0045, for 32,000 gallons of diesel fuel delivery to Drawsko Pomorski, Poland with a delivery date of September 19, 2024.

View the file

Other files

File Type Posted
ATTN REQ RFQ SPE60524Q0045.pdf PDF
RFQ SPE60524Q0045.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEFENSE LOGISTICS AGENCY ENERGY Page 1 of 1

8725 JOHN J. KINGMAN ROAD

FORT BELVOIR, VIRGINIA 22060-6222

Signature

Prepared by:

Quality/Technical Support Office Approval

Contracting Approval:

DISTRIBUTION STATEMENT – A: APPROVED FOR PUBLIC RELEASE. DISTRIBUTION IS UNLIMITED

C16.67-2 DIESEL FUEL SPECIFICATION (SFD) (PC&S) (EUROPE) (MIDDLE EAST) (DLA ENERGY NOV 2018)

NATIONAL STOCK NUMBER PRODUCT NOMENCLATURE DLA ENERGY PRODUCT CODE

9140-01-556-9156 Diesel Fuel SFD

Supplies delivered under this contract shall conform to all National environmental requirements applicable to the geographic location of the receiving activity on the date of delivery. The list of such requirements contained in this contract is not intended to be a complete list and the Contractor shall be responsible for determining the existence of all such requirements. In the event that a National environmental requirement is more stringent than a specification contained in this contract, the Contractor shall deliver product that complies with the more stringent requirement. Product that fails to meet the more stringent requirement will be considered a nonconforming supply. Product(s) supplied shall fully meet the requirements of the applicable specification(s) as cited below.

Product shall conform to the latest revision of commercial specification EN 590. Product shall be visually free of undissolved water, sediment, and suspended matter. Product classification is shown above. Maximum sulfur content, as stated in EN 590, is 10 mg/kg (0.0010 wt%).

a) FOR LOCATIONS IN KOSOVO:

(1) TESTING REQUIREMENTS: The following additional tests shall be performed and results reported:

i. Color: ISO 2049/ASTM D1500

ii. Acid Number: ISO 6618/ASTM D974

(2) In addition to the EN 590 specification requirement for water content of 200 mg/kg or ppm (0.0200 wt%) maximum, and particulate content of 24 mg/kg or ppm (0.0024 wt%) maximum, the diesel fuel shall have a maximum haze rating of 2 when tested in accordance with ASTM D4176, Procedure 2. In case of dispute, the haze rating shall be determined at 25 °C (77 °F) with a maximum haze rating of 2 and shall contain no more than 24 mg/kg (0.0024 wt%) sediment and no more than 200 mg/kg (0.0200 wt%) water.

(3) Diesel during the summer months, May 1st to September 30th, shall comply with Grade A of Table 2 in EN 590.

(4) Diesel during winter months, October 1 to April 30th, shall comply with the Class 1 limits set in Table 3 of EN 590.

b) FOR LOCATIONS IN AFGHANISTAN: Diesel fuel delivered to all locations in Afghanistan shall meet the Grade E, -

15°C maximum cold filter plugging point, as detailed in EN 590 Section 5.6.1, Table 2 – Climate Related Requirements and Test Methods – Temperate Climates.

c) FOR ALL LOCATIONS: Written exception(s) or deviation(s) must be submitted to DLA Energy contracting officer if the Contractor is unable to meet any of the characteristic requirements of the above listed specification(s). Exception(s) and/or deviation(s) must state the reason why the contractor is unable to meet requirements, if this will be for the entirety of the performance period, if it is source specific, the Contractor’s course of action on how they plan on resolving this issue, and any proposed changes to specification requirement limit(s) for that product.

2018-11-16T10:10:12-0500
ATKINS.RENRICK.L.1024389320
2018-11-16T10:25:11-0500
BANISZEWSKI.DANIEL.J.1287388698
2018-11-16T21:11:17-0500
PETERSON.DAVID.W.1074069483

File details come from the government source that posted it. Updated .