Pre-Award Q and A.pdf
PDF 126 KB Posted
- Attached to
- DSCR B54 HVAC Condenser Replacement Project
- Solicitation number
- SP470326Q0002
- Issued by
-
Defense Logistics Agency
About this file
This document is a Questions & Answers (Q&A) addendum for a Defense Logistics Agency (DLA) HVAC Condenser Replacement Project at the Defense Supply Center Richmond (DSCR), Solicitation SP470326Q0002. The Q&A addresses three key contractor inquiries: vehicle parking, ductwork replacement, and humidity control requirements. Contractors are permitted to park vehicles directly behind Building 54A, can potentially reuse existing ductwork if it is compatible with the new system and in good condition, and must maintain specific humidity control parameters of 37% to 45% relative humidity (RH) at 66 to 70 degrees F during heating, and 45% to 53% RH at 70 to 74 degrees F during cooling.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Photo-3.jpg | JPG image | |
| Photo-5.jpg | JPG image | |
| Photo-4.jpg | JPG image | |
| Photo-2.jpg | JPG image | |
| Photo-1.jpg | JPG image | |
| Movie-1.mov | MOV file | |
| Photo-6.jpg | JPG image | |
| DSCR Building 54 AC unit meeting location_.pdf | ||
| SF1442 SP470326Q0002.pdf | ||
| DSCR-B54A-SOW-AC_CondensingUnit_rev1.pdf | ||
| Wage Determination.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Defense Logistics Agency(DLA)
Defense Supply Center Richmond(DSCR)
Building 54A – HVAC Condenser Replacement Project
Solicitation SP470326Q0002
Questions & Answers
1. Q: Will the contractor be allowed to park their vehicles directly behind DSCR Building
54A, directly behind the jobsite, for convenience?
A: Yes, parking directly behind DSCR B54A is allowed.
2. Q: Does all the duct work need to be replaced?
A: Not necessarily. As long as the current duct work is compatible with the new system, is in good condition, and the two rooms have their own independent system, the existing duct work can be reused.
3. Q: Is there any specific type of humidity control required for the rooms?
A: For heating the range is 37% to 45% RH at 66 to 70 degrees F and 45% to 53% RH at 70 to 74 degrees F for cooling.