ATTACHMENT_5_-_Drawings_UPS_Upgrade_Bldg_100.pdf
PDF 5 MB Posted
- Attached to
- Replace Transformer and UPS Upgrade Building 100 Federal contract opportunity
- Solicitation number
- SP3300-17-B-0011
- Issued by
- Defense Logistics Agency Distribution
About this file
ATTACHMENT 5 - UPS DRAWINGS
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SP330017B0011_A0003_PAGE_1.pdf | ||
| SP330017B0011_A0002_PAGE_1.pdf | ||
| SP330017B0011_AMENDMENT_0001.pdf | ||
| B100_UPS_Transformer_Site_Visit_Roster.pdf | ||
| ATTACHMENT_7_-_Submittal_Register_UPS_Upgrade_Bldg_100.pdf | ||
| Attachment_1_-_construction_wage_determination.pdf | ||
| ATTACHMENT_4_-_Drawings_Xfmr_Repl_Bldg_100.pdf | ||
| SP330017B0011.pdf | ||
| ATTACHMENT_9-__SF25_(Performance_Bond).pdf | ||
| ATTACHMENT_3_-_Specifications_UPS_Upgrade_Bldg_100.pdf | ||
| ATTACHMENT_10_-__SF24_-_Bid_Bond.pdf | ||
| ATTACHMENT_2_-_Specifications_Xfmr_Repl_Bldg_100.pdf | ||
| ATTACHMENT_6_-_Submittal_Register_Xfmr_Repl_Bldg_100.pdf | ||
| ATTACHMENT_8-__SF25A_(Payment_Bond).pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SP330017B0011
ATTACHMENT 5 - UPS DRAWINGS
tjc0831 Typewritten Text
BUILDING 100 REPLACE TRANSFORMER AND UPGRADE UPS - DDJC TRACY
tjc0831 Typewritten Text E 0.0
DAK0013
Typewritten Text
PROJECT LOCATION
DAK0013
Line
BUILDING 100 REPLACE TRANSFORMER AND UPGRADE UPS
DDJC - TRACY, CA
REPLACE EXISTING MBP
NEW BATTERY
EXISTING
EXISTING
BUILDING 100 UPS ROOM LAYOUT
(not to scale)
NEW UPS
NEW 800AF/700AT, NEMA 12 CIRCUIT BREAKER
BUILDING 100 REPLACE TRANSFORMER
AND UPGRADE UPS
DRWG E 5.1
SP330017B0011
ATTACHMENT 5 - UPS DRAWINGS
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Line
Rectangle
BU
IL
D
IN
G
R
EP
LA
C E
TR
A
N
SF
O
RM
ER
A
N D
U
PG
RA
D
E U
PS
D
D
JC
TR
A C
Y, C
A
EX
IS
TI
N
G U
PS
S
IN
G
LE
L
IN
E
D
IA
G
RA
M
BUILDING 100 REPLACE
TRANSFORMER AND UPGRADE UPS
DRWG # E 5.2
SP330017B0011
ATTACHMENT 5 - UPS DRAWINGS
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
DAK0013
Rectangle
Rectangle
K2
MBS INPUT
FROM UPS-2
(3Ø,4W,G)
MAINTENANCE
BYPASS INPUT
480vac, 60Hz (3Ø,4W,G)
For 2xSG-225kva UPS, 480Vac, 3Ø/4W/G p/n: PH021317-01SP
K1/2/3
SKRU
K1
OUTPUT TO
CRITICAL LOAD
480vac, 60Hz (3Ø, 4W,G)
Existing UPS INPUT SWITHBOARD (ISB)
480Vac, 3Ø/4W/G, 60Hz
UIS INPUT
480vac, 60Hz (3Ø,4W,G)
MIB-1
350AT
400AF
MIB-2
350AT
400AF
SIB
700AT
800AF
MBB
700AT
800AF
NEUTRAL
GROUND K1/2/3 K1/2
K2 K1
K2K1
GE
Critical Power
Drawing Title:
Drawing No.:
Issued by: Issued date:
Released by: Revised date:
Scale:
Sheet No.:
PH
PH 02/27/17 NONE
MI, RPAP-PC w/SKRU, 3ø/4W/G, for 2x SG-225kva, in PC system
PH021317-03GEMI
Rev. No.:
1.0
Project Name: Point of Contact:
Kahlon Amarjeet Equipment Part Number:
PH021317-01SP DLA
MBS INPUT
FROM UPS-1
(3Ø,4W,G)
BATTERY
CABINET
(EXISTING)
BATTERY
CABINET
(NEW)
K4
F8, 9
K7
K6
SSM
IN
V E R T E R
R E C T
IF
IE
R
FROM
BATTERY
(+, -, G)
RECTIFIER
INPUT
(3Ø, 3W,G)
BYPASS
INPUT
(3Ø, 4W,G)
UPS-1
SG-225KVA
480VAC, 60Hz
(EXISTING)
VR1 VR2
L3
L1 L50
K50
R50/ C50
5th THD filter (Option)
TR1
Customer Interface
Card (CIC)
F2
F3 F4
CP
K8
Q1
K3
R
P
A
K4
F8, 9
K7
K6
SSM
IN
V E R T E R
R E C T
IF
IE
R
FROM
BATTERY
(+, -, G)
RECTIFIER
INPUT
(3Ø, 3W,G)
BYPASS
INPUT
(3Ø, 4W,G)
UPS-2
SG-225KVA
480VAC, 60Hz
(EXISTING)
VR1 VR2
L3
L1
L50
K50
R50/
C50
5th THD filter (Option)
TR1
Customer Interface
Card (CIC)
F2
F3 F4
CP
K8
Q1 Q2
K3
R
P
A
RIB-1
400AT
400AF
RIB-2
400AT
400AF
MMB
700AT
800AF
BIB-1
350AT
400AF
BIB-2
350AT
400AF
MMB-TEMP
350AT
400AF
K2
K1/2/3
SKRU
K1
MBB
350AT
400AF
K1/2/3K1/2
K2 K1
K2K1
MIB
350AT
400AF
xxx xxxxx xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx xxxx xxxxxx xx x xxxxxxxxxxxxxxxxxx xxxxxxxxxxxxxxxxxxxxxxxxxxx x x x x x x x x
Existing UPS OUTPUT SWITCHBOARD (OSB)
480Vac, 3Ø/4W/G, 60Hz
FB-1
300AT
400AF
FB-4
20AT
2P
FB-2
350AT
400AF
MAIN
700AT
800AF
FB-3
350AT
400AF
FB-5
20AT
2P
FB-6
20AT
2P
FB-7
20AT
2P
SPACE
20AT
2P
SPACE
20AT
2P
TEMPORARY
OUTPUT TO
CRITICAL LOAD
Modification Instructions:
1. Additional items required:
1.1. Existing Input Swbd (ISB)
1.1.1. MMB breaker, 3P, 700AT/800AF, MCCB, manually operated breaker.
1.2. Existing Output Swbd (OSB)
1.1.1. MAIN breaker, 3P, 700AT/800AF, MCCB, manually operated breaker.
2. Modification Instructions:
2.1. Initial condition:
2.1.1. On ISB switchboard:
MMB-TEMP, RIB-1 and BIB-1 breaker are closed.
All remaining breakers are open.
2.1.2. On OSB switchboard:
MAIN breaker must be open.
All remaining breakers are closed to support the critical load
2.1. Install the 2
nd UPS and RPAP unit
2.1. Transfer to critical from UPS-1 to
Maintenance bypass mode via existing MBP. Now the critical load is supported by utility.
See power flows in RED
2.2. Disconnect the power cable from
UPS-1 to existing MBP, MIB breaker.
See power flow in BLUE.
2.3. Shut down the UPS-1 module.
2.4. Connect UPS-2 input and RPAP MBB
breaker to existing ISB switchboard.
25. Connect RPAP input to both UPS outputs and OSB switchboard MAIN,
2.6. Connect RPA control cables.
2.7. Connect SKRU control and MIB
breakers aux contact from RPAP to each UPS module
2.8. Run the RPA system to make sure it
works correctly with MAIN breaker in the OSB open.
Existing MBP 480Vac, 3Ø/4W/G, 60Hz
NEW 800AF/700AT MCCB
NEMA 12 ENCLOSURENEW 3/4" C
NEW RPA CARD
NEW BATTERY
NEW 3/4"C
REMOVE
NEW 3/4"C
GOVT. SUPPLIED UPS
NEW 2- 4#500,1#4GRD
NEW MBP RPAP-PC
EXISTING
RACK
NEW 2- 4#500,1#4GRD
REMOVE 4#350, 1#4 GRD
4#350, 1#4 GRD
REMOVE EXISTING MBP
NEW 3"C 4#350, 1#4 GRD
NEW 4#350, 1#4GRD
NEW 3"C, 4#350, 1#4GRD
il
BUILDING 100 UPS NEW SINGLE LINE
REMOVE EXISTING CABEL
SP330017B0011
ATTACHMENT 5 - UPS DRAWINGS
DAK0013
Rectangle
DAK0013
Line
DAK0013
Rectangle
DAK0013
Line
DAK0013
Rectangle
DAK0013
Line
DAK0013
Rectangle
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Rectangle
DAK0013
Line
DAK0013
Rectangle
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Line
DAK0013
Rectangle
DAK0013
Typewritten Text
BUILDING 100 REPLACE TRANSFORMER
AND UPGRADE UPS - DDJC TRACY
DRWG # E 5.3
DAK0013
Typewritten Text
BUILDING 100 REPLACE TRANSFORMER AND UPGRADE UPS - DDJC TRACY
Line
BUILDING 100 REPLACE TRANSFORMER AND UPGRADE UPS DDJC - TRACY, CA
ANNEXURE 1
BUILDING 100 EXISTING UPS LAYOUT
SP330017B0011
ATTACHMENT 5 - UPS DRAWINGS
| Annexure 1 - Existing UPS layout |
| E 0.0 General Project Location |
| E5.1 UPS-LayOut |
| E5.2 UPS-ExistingSingleLine |
| E5.3 UPS- NewSingleLine |
File details come from the government source that posted it. Updated .