The document is a Statement of Work (SOW) for the VA Pittsburgh Healthcare System's Medical Air Compressor Replacement project at the University Drive Medical Center. The urgent project involves replacing two medical air compressor systems located in different areas (2A130 and 7W139), where existing systems have reached end-of-life and replacement parts are obsolete. The scope includes complete demolition of existing compressors, storage tanks, dryers, and associated electrical and piping infrastructure, followed by installation of new NFPA 99 compliant AMICO Tri-Plex medical air systems.

Specific equipment requirements include a 7.5 scroll medical air system for 2A130 and a 20HP scroll medical air system for 7W139, both featuring premium HMI controllers with BACnet, CO and dewpoint monitors, dual desiccant dryers, and filtration packages. Installation must be performed by Certified ASSE 6010 medical gas installers, potentially during off-hours and weekends to minimize disruption. The project requires a 2-inch crossover pipe to interconnect both medical air systems, ensuring continuous medical air supply during the replacement process. All electrical connections, wiring, alarms, and system certifications are part of the contractor's responsibilities.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Statement of Work VA Pittsburgh Healthcare System

University Drive Medical Center

Medical Air Compressor Replacement 2A130/7W139

This is an urgent and compelling need for the Medical Center to replace two (2) medical air compressor systems at two (2) different locations within the University Drive Medical Center. These medical air systems have reached their life’s expectancy and repair parts are obsolete or very hard to find for both these medical air systems.

There will be a need to install a 2-inch crossover pipe to interconnect both medical air systems from 2A130 and 7W139 to prevent any disruption of medical air while this work is being conducted to any medical Air System.

2A130 Medical Air Compressor System

• Demo to consist of removal of existing Medical Air compressors, storage tank, and dryers. All electrical power wiring and low voltage control wiring. Any associated piping.

• All existing housekeeping pads to be reused and modified as needed to support the installation of the new equipment.

• All demo of the existing medical air compressor system or any debris associated with the demo to be removed from the building and disposed of by the contractor.

• Demolition of the existing medical air system may need to be performed off hours and weekends.

NEW EQUIPMENT SPECIFICATIONS

• Freight, receiving, rigging, Installation, start up and verification/certification of new NFPA99 AMICO Tri-Plex 7.5 scroll

(Brand Name or Equal) medical air system. Premium HMI controller with BACnet. CO and dewpoint monitors. Dual desiccant dryers, filtration and regulation package. Installation of new medical air compressor system to be performed by Certified

ASSE 6010 medical gas installers.

• The installation of this medical air system may need to be performed on off hours and weekends as needed.

• Piping connections to existing intake, exhaust and main piping.

Existing source valve and main line switch to kept in service if needed. All final piping connections for the medical air compressor system and dryers and filtration package

• All electrical power wiring connections. BACnet wiring and setup and all low voltage wiring and alarms.

• Certification of the installation and testing all alarms before the system can be put into normal operation.

7W139 Medical Air Compressor System

• Demo to consist of removal of existing Medical Air compressors, storage tank, and dryers. All electrical power wiring and low voltage control wiring. Any associated piping.

• All existing housekeeping pads to be reused and modified as needed to support the installation of the new equipment.

• All demo of the existing medical air compressor system or any debris associated with the demo to be removed from the building and disposed of by the contractor.

• Demolition of the existing medical air system may need to be performed off hours and weekends.

New Equipment Specifications

• Freight, Receiving, Rigging, Installation, Startup and

Verification/Certification of NFPA 99 Amico Triplex 20HP scroll

Medical Air System, Premium HMI controller with BACnet and CO and dew point monitors, Dual Desiccant Dryer, Filtration and

Regulation Package. Installation of the new medical Air

Compressor System to be performed by Certified ASSE 6010 medical Gas installers.

• The installation of this medical air system may need to be performed on off hours and weekends as needed.

• Piping connections to existing intake, exhaust and main piping.

Existing source valve and main line switch to kept in service if needed. All final piping connections for the medical air compressor system and dryers and filtration package

• All electrical power wiring connections. BACnet wiring and setup and all low voltage wiring and alarms.

• Certification of the installation and testing all alarms before the system can be put into normal operation.