SOW_Roofing_and_Liners_for_242.docx

DOCX document 35 KB Posted

Attached to
Insulated Metal Roof and Liners
Solicitation number
140R3023Q0061
Issued by

About this file

This document is a scope of work for a federal solicitation requiring insulated metal roofs and liners to be installed at 12 wellfield buildings located along the 242 lateral well field. The Bureau of Reclamation, Lower Colorado Region, Yuma Area Office seeks to purchase roof panels measuring 18' 2" L x 15' 8" W with an R-25 rating, and interior liners measuring 13' 5" W x 12.5' H with an R-5.7 rating, to cover the dimensions specified for each building. Proposals must include installation hardware, trim, and accessories to provide a complete assembly for all 12 buildings. Deliveries shall be made to the Bureau of Reclamation Yuma Area Office warehouse between 6:00 A.M. and 3:00 P.M., Monday through Thursday. The solicitation number for this opportunity is 140R3023Q0061.

View the file

Other files

File Type Posted
Sol_140R3023Q0061_Amd_0002.pdf PDF
Clauses_Amendment_0002_0002.docx DOCX document
WBR_1419_7_-_Template_1_Subcontracting_Plan_Template_9-2022_0002.docx DOCX document
Provisions_Amendment_0002_0002.docx DOCX document
Sol_140R3023Q0061_Amd_0001.pdf PDF
140R3023Q0061_Questions_0001.docx DOCX document
Roof_Top_View_0001.pdf PDF
Floor_and_Roof_Plan.pdf PDF
Clauses.docx DOCX document
Sol_140R3023Q0061.pdf PDF
Provisions.docx DOCX document
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFQ No. 140R3023Q0061

FOR OFFICIAL USE ONLY

Roofing and Liners for the 242 Wellfield Buildings

GENERAL

DESCRIPTION

The Bureau of Reclamation, Lower Colorado Region, Yuma Area Office (YAO) has a requirement to purchase insulated metal roofs and liners to support the building climate control at 12 well sites along the 242 lateral well field. This requirement is to keep cool, the electrical panels and components controlling the new upgraded 400-HP well motors.

Each building design includes a 4” insulated metal roof with the dimensions of 18’ 2” L x 15’ 8” W, totalling 287 sq ft per building. The roof panels must have a radiation rating of no less than R-25 and cover the dimensions for all sites, as a minimum requirement to be technically acceptable.

Each building’s interior design includes 2” insulated liners that covers four walls with dimensions of 13’ 5” W x 12.5’ H, totalling 675 sq ft per building. The liners must have a radiation rating of no less than R-5.7 and cover the dimensions for all walls in each building, as a minimum requirement to be technically acceptable.

Roof insulations should not be exposed. Roofs requiring specialized metal fascia trim must be provided for all building sides, for the dimensions provided, and must be included in the proposals as a separate line item. All roofs and liners must include in the proposal, the required installation hardware, trim, and any other accessories to have a complete assembly. All material shall construct 12 buildings.

PRODUCTS

Roofing and Liner Material See Floor and Roof Plan

CONTRACTOR SERVICES

DELIVERY

All roofing and liner materials shall be delivered to the Bureau of Reclamation Yuma Area Office. The contractor must coordinate the delivery with the Bureau of Reclamation YAO warehouse. Contact the warehouse at 928-343-8525 to coordinate delivery. Delivery shall be made to: US Bureau of Reclamation, 7301 S. Calle Agua Salada, Yuma, AZ 85364. Monday though Thursday 6:00 A.M. to 3:00 P.M.

The contractor must protect all parts/equipment from corrosion, deformation, dents, dings, scratches, ruptures, breaks, punctures, abrasions, cuts, and other types of damage during storage, handling, transport, and delivery.