140R3023Q0061_Questions_0001.docx

DOCX document 15 KB Posted

Attached to
Insulated Metal Roof and Liners
Solicitation number
140R3023Q0061
Issued by

About this file

This document contains questions and answers regarding solicitation number 140R3023Q0061 from the Department of the Interior Bureau of Reclamation for an insulated metal roof and wall liners. The solicitation requests quotes for 4-inch insulated metal panels for the roof and 2-inch panels for the walls of a 170-foot tall building. It seeks pricing for panels from either Kingspan Insulated Panels or All Weather Insulated Panels including necessary fasteners, closures, and trim. The answer clarifies that the roof will be fastened to a single purlin running midway along the building, with additional purlins potentially added if needed off the purlin. The trim will be a 4-inch metal strip around the roof edges to cover exposed insulation material.

View the file

Other files

File Type Posted
Sol_140R3023Q0061_Amd_0002.pdf PDF
Clauses_Amendment_0002_0002.docx DOCX document
WBR_1419_7_-_Template_1_Subcontracting_Plan_Template_9-2022_0002.docx DOCX document
Provisions_Amendment_0002_0002.docx DOCX document
Sol_140R3023Q0061_Amd_0001.pdf PDF
Roof_Top_View_0001.pdf PDF
Floor_and_Roof_Plan.pdf PDF
Clauses.docx DOCX document
SOW_Roofing_and_Liners_for_242.docx DOCX document
Sol_140R3023Q0061.pdf PDF
Provisions.docx DOCX document
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

140R3023Q0061 Questions Question 1: The package is missing a building elevation along with what the framing substrate is we are attaching the insulated panels too. We can quote the square footage of the 4” IMP roof and the 2” IMP walls. As for the required fasteners, closures and trim are unclear. We represent both Kingspan Insulated Panels and All Weather Insulated Panels……….a sister company. We can quote both manufactured panels, fasteners, and trim complete with the requested information.

Answer 1: The photo attached shows the one purlin that is placed midway from North to South (side to side) of the building. This is assumed to be where the panels will be fastened to. No other purlins are required for the roof install. If fasteners are needed where the purlin is not, then additional purlins may be added, if required. For the trim, this is basically a 4” metal strip that wraps around the sides of the roof that covers any exposed insulation material (Styrofoam?). Elevation is 170 feet.