This document is a Statement of Work (SOW) for the installation of two new tilt-down antenna towers to replace three existing towers at the Red Bluff Remote Communications Outlet (RCO) located near the Red Bluff Municipal Airport in Red Bluff, California.
The SOW outlines the scope of work, which includes excavation, concrete foundation work, installation of underground conduit, assembly of the antenna system, and integration of lightning protection, obstruction lights, and power/RF cabling. The contractor is responsible for providing all labor, materials, and transportation, while the FAA will furnish the antenna system components, pull boxes, and cables. The work must comply with all applicable federal, state, and local regulations, as well as FAA safety and security requirements. The contractor is required to commence work within 21 calendar days of the notice to proceed and complete the project within 15 calendar days. The SOW also includes details on site visits, utilities availability, project supervision, and inspection and acceptance of the work.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 6973GH-24-Q-00127 Amendment 00001 - Site Visit.pdf | ||
| 6973GH-24-Q-00127 Red Bluff CA SAM.gov.pdf | ||
| Wage Determination CA20240007 as of 05.24.24.pdf | ||
| ATTACHMENT B RBL RCO CONDUITE AND PULL BOXES.pdf | ||
| ATTACHMENT A JAQUITH DWG CD-D-7778.pdf | ||
| Antenna Foundation Plan.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RBL RCO NEW ANTENNA TOWER
WSTERN SERVICE AREA – AWP
ENGINEERING SERVICES
AJW-2W15U
SPECIFICATIONS & STATEMENT OF WORK
INSTALL NEW RCO TILT-DOWN ANTENNA TOWERS
RED BLUFF, CALIFORNIA
Coordinate: 40° 09’ 99 N 122° 15’ 1.74”W
FEBRUARY 2022
PROJECT LOCATION:
Red Bluff Municipal Airport
1800 Airport Blvd.
Red Bluff, CA 96080
FACILITY MANAGER:
Christopher Bauman FAA Red Bluff SSC Office: (530) 527-7920 Mobile: (530) 736-8050 Christopher.Bauman@faa.gov
POINT OF CONTACT
Michael Kwong Office 530-527-7920 Cell 530-308 7527 michael.kwong@faa.gov
PROJECT ENGINEER:
Ira Farnoush, AJW-2W15F FAA WSA Los Angeles, California Telephone: 424 405-7548 Cell: 310 880 0462 ira.farnoush@faa.gov
1.0 INTRODUCTIONS
The RBL RCO is located in vicinity of Red Bluff Municipal Airport, at Red Bluff, California. The purpose of this project is to install 2 new TILT-DOWN Antenna Towers to replace 3 existing antenna towers.
2.0 SCOPE OF WORK
Provide all labors, materials, transportations, and other services necessary to dig foundations and install 3 concrete pull boxes, install new tilt-down antenna masts and install trenchless underground conduits and pull power and Coax cable.
All pull boxes and antenna components, coax cables, connectors and power cables will be provided by the FAA. The contractor must pick up all items from a FAA storage area nearby and transport them to the job site. The location of the antenna foundations and trenching rout is shown on the attached sketch but the exact locations shall be field determined.
The project includes but it is not limited to following:
• Pick up and transport to the site a set of Frangible Antenna System, pull boxes from storage area located in administration building. Each pull box weigh about 2000 Lbs which may require a crane for installation.
• Layout and mark the location the antenna foundation as shown on the attached schematic sketch.
The exact location of the foundations must be field determined.
mailto:michael.kwong@faa.gov
• Saw cut concrete slab, an asphalt paving from the building to the pull box as shown on the project sketch.
• Excavate a trench 9’x9’, 24’ deep and install a concrete foundation for each antenna system, Refer to the attached Sketches for the concrete foundation and drawing CD-D-7778 for detail information for the antenna foundation and mast installations. The antenna masts shall be aligned in north-south track and in direction of each other.
• Excavate and install 3 pull boxes.
• Provide and install Polyethylene – PVC Conduit to AS/NZS 2053 Heavy duty conduits for underground cables by Horizontal Directional Drilling. The conduits shall be 1-1/2” for the power and 4” for the RF cables. The conduits must be extended to the power panel and equipment racks inside the equipment room. The point of access into the equipment room will be field determined.
**See note below.
• Install and assemble the antenna system.
• Provide and install lightning protection systems, consists of 30” long x ½” blunt tip, nickel plated air terminal and adapter, 7/16” braded cooper wire down conductor & fasteners. In addition provide and install ground counterpoise around the antenna mast including four (4) ½” cooper ground rods 10’ long at the corners of the platform and connected to #4/O cooper conductors. All conductors must be exothermically welded to the ground rods.
• Install RF and power cables from equipment room to the antenna masts. Final termination of the RF cables ends and power cable at the power panel will be terminated by the FAA.
• Provide and install lightning terminal at the top of the mast and down conductor to grounding counterpoise. Install Lightning conductor outside antenna mast.
• Install new obstruction lights and connect the circuit to the power disconnect circuit breaker inside the equipment room.
• Schedule a facility outage with POCC for RCO and disconnect all circuits.
**NOTES:
1- Prior to start of the work the contractor shall identify and mark all underground utilities along the route to prevent damage to property and provide clearance required to those services. The correct fittings, conduit alignment, route depth to be used for cable pulling pits.
2- The polyethylene pipe conduit specified has proved to be adequate for the minimum depths required.
However, deeper installations including crossing under built-up roads, may require a thicker wall conduit due to the deformation caused by factors such as the high bearing pressure of the ground water. The Contractor is responsible for assessing whether or not the specified conduit is adequate for the particular application and is to provide a conduit of sufficient wall thickness to ensure undue deformation does not occur. As a minimum, conduit shall be polyethylene pressure pipe complying with AS/NZS 4130, having minimum performance equivalent to PE80 material, classification PN10.
3.0 TECHNICAL REQUIREMENTS
• The contractor shall verify in the field all conditions, elevations and dimensions before starting work.
• All structural and civil works shall be in full compliances with the requirements of the International Building Code.
• All electrical work must comply with the requirements of FAA-STD-1217G, FAA-STD-019f and
2020 NEC.
• All concrete works must comply with American Concrete Institute (ACI).
• All structural steels and sheet metal works must comply with the criteria set in the American
Institute for Structural Construction (AISC).
• The contractor must adhere to all Occupational, Safety & Health Administration (OSHA) safety and health rules and guidance.
• Contractor shall be responsible for compliance with the local construction safety orders and any other applicable local, state or federal regulations.
• Concrete shall have a minimum compressive strength in 28 days equal to 4000 psi, and shall be normal weight (145 PCF). Portland cement: ASTM C150 type I or type II, low alkali. Coarse aggregate shall be normal weights hard, durable crushed stone or gravel graded and conform to ASTM C33. Sand shall be clean, hard, durable, washed, and free from silt loan or clay. Mixing water shall be clean and free from injurious amounts of oil, acids, alkalizes, organic materials or other deleterious substances.
• Reinforcing bars ASTM A615, grade 60, grade 40 for #3 bars.
• All reinforcing steel shall be free of loose flaky crust and scale, grease or other substances, which might affect or impair proper bonding.
• All reinforcing shall be accurately placed and adequately supported before concrete is placed and shall be secured against displacement.
• All anchor bolts, nuts and locking devices shall be stainless steel, or hot-deep galvanized A307 steel.
4.0 EXECUTION OF WORK
The RBL RCO is a secure facility and thus, the contractor shall comply with all security and safety requirements and regulations of the FAA while working at this site. All works shall be performed in a way not to disturb the normal operation of the facility. The contractor is not allowed to enter any area which is outside of scope of this project. The contractor will be escorted while working in secure areas.
Contractor shall assume full responsibility for the protection and safekeeping of products stored on the site.
The Contractor and his Subcontractors shall maintain the job site in a neat and orderly condition; this includes the daily removal of rubbish, waste and tools, equipment, and materials not required for the work in progress. The contractor shall be cautious when working inside the building and provide adequate protection for safeguarding the equipment.
All existing equipment and materials removed from the project area shall become property of the contractor, which must be removed immediately. This includes the daily removal of rubbish, waste and tools, equipment, and materials not required for the work in progress.
Contractor shall not damage any FAA property. Contractor will be held liable for any damage and will be required to make repairs immediately.
All materials and equipment shall be installed in accordance with the contract drawings and the recommendations of the manufacturer as approved by the Resident Engineer. The installation shall be accomplished by skilled workmen regularly engaged in this type of work. Where required by local regulations, the workmen shall be properly licensed.
Minor departures from dimensions shown in electrical plans may be permitted where required to avoid conflict or unnecessary difficulty in placement of a dimensioned item, provided all contract requirements are met. The Contractor shall promptly obtain approval from the Resident Engineer prior to undertaking any such proposed departure.
The Contractor shall furnish all materials not specifically shown on the Government Furnished Property List.
Materials and equipment must comply with all contract requirements. Materials to be furnished by the Contractor under this specification shall be new, the standard products of manufacturer's latest designs that comply with the specification requirements
5.0 SECURITY REQUIREMENTS:
The job site is located in the secure area of the FAA which contain equipment that are part of the NAS.
Therefore, the Contractor shall comply with all instructions, rules, security, and safety requirements of the FAA. Work performed at this site shall be done under FAA personal and or Contracting Officer Representative (COR) at all times.
The contractor shall coordinate all works with the COR at all times.
6.0 PERFORMANCE TIME:: The Contractor shall be required to (a) Commence work under this contract within twenty one (21) calendar days after the date he/she receives the notice to proceed, (b) prosecute the work diligently, and (c) complete the entire work ready for use not later than 15 Calendar days after receipt of notice to proceed. The time stated for completion shall include final cleanup of the premises.
7.0 EMERGENCY CONTACT LIST:
The contractor shall provide an emergency contact list of names and telephone numbers for at least the foreman and a backup person so that contact can be made during non-working hours in case of an emergency.
8.0 PROJECT SUPERVISION:
The Contractor shall have a designated project superintendent at the project site at all times during the course of work. Superintendent shall be an employee of the Contractor.
9.0 AVAILABILITY OF UTILITIES:
Electricity is available at the site for contractor use. Telephone and lavatory shall be provided by the contractor.
10.0 SITE VISIT PRIOR TO BIDDING:
The contracting officer (CO) will schedule a job site visit for the contractor to assess the site conditions and get familiar with the site and surrounding environment. The date will determine on later date. Contractors are strongly encouraged to visit the site prior to bidding on the project.
The project engineer for this project is Ira Farnoush, phone number (424) 405-7543, cell (310) 880 0462 email: ira.farnoush@faa.gov. . Any technical questions should be directed to him through the Contracting Officer.
11.0 STORAGE AND CLEAN UP
mailto:ira.farnoush@faa.gov
The contractor shall provide storage at the job site for storing the tools, supplies and materials. The location of the storage must be coordinated with the FAA The contractor is required to maintain the job site in a neat and orderly condition during the progress of the work. Upon completion, remove all debris, trash, surplus materials.
12.0 INSPECTION AND ACCEPTANCE OF WORK
The FAA will reject any work, which is not performed to the scope of the contract, including industry standards related to the project.
The contractor shall promptly replace the rejected material and/or workmanship.
13.0 GOVERNMENT FURNISHED MATERIAL
• Jaquith Tilt-down Antenna System
• RF cables and connectors,
• 3 Pull BOXES
All other materials needed for the project must be provided by contractor.
14.0 LIST OF DRAWINGS & SKETCHES
ATTACHMENT A : JAQUITH DRAWING: CD-D 7778
ATTACHMENT B: SITE PLAN PULLBOXES & UNDERGROUND CONDUITS
ATTACMENT C: ANTENNA TOWER FUNDATION
| The RBL RCO is a secure facility and thus, the contractor shall comply with all security and safety requirements and regulations of the FAA while working at this site. All works shall be performed in a way not to disturb the normal operation of the fa... |
| Contractor shall assume full responsibility for the protection and safekeeping of products stored on the site. The Contractor and his Subcontractors shall maintain the job site in a neat and orderly condition; this includes the daily removal of rubbi... |
| 5.0 SECURITY REQUIREMENTS: |
| The job site is located in the secure area of the FAA which contain equipment that are part of the NAS. Therefore, the Contractor shall comply with all instructions, rules, security, and safety requirements of the FAA. Work performed at this site shal... |
6.0 PERFORMANCE TIME:: The Contractor shall be required to (a) Commence work under this contract within twenty one (21) calendar days after the date he/she receives the notice to proceed, (b) prosecute the work diligently, and (c) complete the entir...