Text version

U.S Department of State (DOS)

Bureau of International Narcotics and Law Enforcement Affairs (INL)

U.S. Embassy – Tegucigalpa, Honduras

Medium Tension Equipment and Installation in Choluteca in support the Forensic Medicine Directorate and Public Ministry

SECTION 1

SOLICITATION CONSIDERATIONS

1.1 SYSTEM FOR AWARD MANAGEMENT

This solicitation requires registration with the System for Award Management (SAM) prior to award, pursuant to FAR 4.1102 and other applicable regulations and guidelines. Information can be found at www.sam.gov.

1.2 TRADE AGREEMENTS ACT (19 U.S.C. 2512(A)) (TAA)

Pursuant to the Trade Agreements Act (19 U.S.C. 2512(a)) (TAA), Federal acquisitions of supplies may be made only from offerors that shall supply products of an eligible country under any of the free trade agreements entered into pursuant to the TAA. An article is considered a product of a country only if it is wholly a product of that country or if it has been, substantially transformed, in that country into a new and different article of commerce with a name, character, or use distinct from that of the original article(s). Note that any item that is a discreet article as it is sold in commerce, regardless of its ultimate function or use, cannot be considered, substantially transformed, and based solely on its integration into IT or other systems

1.3 UNAUTHORIZED DISCLOSURE

The Contractor and its employees shall exercise the utmost discretion concerning all matters relating to their duties and functions. They shall not communicate to any person any information known to them by reason of their performance of services under this contract, which has not been made public, except in the necessary performance of their duties or upon written authorization of the Contracting Officer.

All documents and records (including photographs) generated during the performance of work under this contract shall be for the sole use and become the exclusive property of the U.S Government. Furthermore, no article, book, pamphlet, email, recording, broadcast, speech television appearance, film or photograph concerning any aspect of work performed under this contract shall be published or disseminated through any media without the prior written authorization of the Contracting Officer. These obligations do no cease upon the expiration or termination of this contract. The Contractor shall include the substance of this provision in all contracts of employment and in all subcontracts hereunder.

See FAR 3.104 for additional information.

(Rest of Page Intentionally Left Blank)

SECTION 2 (Instruction to Offerors)

INSTRUCTIONS, CONDITIONS, AND NOTICES TO OFFERORS/RESPONDENTS

SUBMISSION INFORMATION PERTAINING TO REQUEST FOR QUOTE

2.1 INFORMATION TO CONTRACTOR

Contractors are reminded that information furnished under this Request for Quote (RFQ) may be subject to disclosure under the Freedom of Information Act (FOIA). Therefore, all items that are confidential to business or that contain trade secrets or proprietary or personnel information shall be clearly marked. Marking of items shall not necessarily preclude disclosure when Department of State (DOS) determines disclosure is warranted by FOIA. However, if such items are not marked, all information contained within the submitted documents shall be deemed releasable.

2.2 QUESTIONS CONCERNING THE REQUEST FOR PROPOSAL

Offerors are warned against contacting any INL personnel other than the Contracting Officer and Contract Specialist prior to award of the Contract resulting from this RFQ. If such a contact occurs and found to be prejudicial to competing vendors, the vendor making such a contact may be excluded from award consideration.

No information concerning this RFQ shall be provided in response to telephone calls. All such requests shall be submitted in writing to the Contracting Officer and Contract Specialist.

2.3 NOTICE OF SAM.GOV SYNOPSIS CLOSING DATE AND TIME

All offers shall be submitted to the designated Government Representative via email.

Any communications in reference to this RFQ shall cite the reference section title and page number, and directed to the following individuals:

Name: Kelly L. Byers Title: Contracting Officer E-mail: byerskl@state.gov

Name: Hermann Tinoco Title: Contracting Officer Representative E-mail: TinocoHO@state.gov

Closing Date and Time:

• 5:00 P.M. (local Washington D.C. time) on the following date: 24 February 2023

2.4 CONTRACTOR RELATIONSHIPS

The Department of State (DOS) encourages the use of subcontractors. In addition, the Department requires that any potential Organization Conflict of Interest be identified in the proposal to ensure proper firewalls established prior to award.

2.5 MULTIPLE PROPOSALS/ALTERNATIVE SOLUTIONS

Contractors shall not submit, nor shall the Government accept or evaluate, multiple proposals offering alternative solutions. Contractors shall not submit, nor shall the Government accept or evaluate, multiple solutions within one proposal.

2.6 PERIOD OF ACCEPTANCE OF OFFERS

Contractors shall agree, if the proposal is accepted within ninety (90) calendar days (unless a greater period is inserted by the contractor) from the date specified in the solicitation for receipt of proposals, to furnish any or all of the requirements upon which prices are proposed at the price set opposite each item, performed and/or delivered at the designated point(s) within the time specified.

2.7 SPECIFIC SUBMISSION INSTRUCTIONS

Vendors shall limit the number of pages to no more than fifteen (15), 12 Point Font, Times New Roman, pdf.

(Rest of Page Intentionally Left Blank)

SECTION 3

DESCRIPTION OF REQUIREMENTS

BACKGROUND

The Bureau of International Narcotics and Law Enforcement Affairs (INL) is an instrumental leader in the development of policies and programs to combat international narcotics and crime. INL programs support two of the Department of States' strategic goals: (1) to reduce the entry of illegal drugs into the United States; and (2) to minimize the impact of international crime on the United States and its citizens. One of the many ways to effectively meet these goals is to partner with allied governments both directly and indirectly to promote the modernization of and support the enforcement operations of their foreign criminal justice systems and law enforcement agencies.

The International Narcotics Affairs Section (INL - U.S. Embassy, Honduras) requires the purchase and one-time installation of Medium Tension Electric Equipment in Choluteca, Choluteca, Honduras, as provided in the specifications attached.

The “Centro Integrado - CEIN” or Integrated Center from the Forensic Medicine Directorate and Public Ministry, includes offices for administrative, prosecutors, investigators and forensic personnel in Choluteca, Honduras. In plans the CEIN includes: and Electrical Room with I-Line and Electric Panels; Module A1, A2, A3, D; and an Electric Backup Room where an electric generator will be installed in the future.

As of now, the CEIN has four existing panels and one I-Line of 800A. They can be found in the plans as panel CC1, CC2, CC3 found in the electrical room; and panel CC4 found in Module D.

There is electric transformer bank (3x50KVA) located on the South-West Side of the Building at street level, at approximately 69 LM from the Electrical Room with I-Line and Electric Panels. The Electric Backup Room will be located at approximately 48LM from the Electrical Room.

The Medium Tension Electric Equipment will support the load for the IT equipment, illumination, interior output circuits, air conditioning, allowing the personnel to move into the facilities, and the CEIN to start operating. Once in full capacity the total Electric Charge will be 289,036W.

All details regarding the single-line diagram, existing panels, new panels, trench ways, register boxes, can be found in the plans and annex below, in pages 15-26.

The Medium Tension Electric Equipment and Installation is intended to:

1) Replace the existing three electric transformer bank of 150KVA (3x50 KVA) and increase the electrical load capacity to a new three electric transformers bank of 300KVA (3x100KVA). The location for the new bank remains the same.

2) Replace the existing electrical connection for panel CC1, CC2, CC3, and CC4 with new 3x1/0 cable awg+1#2 awg Neutral +1#4 awg ground on 1-1/2''" emt pipe.

3) Install a new Three-phase Panel for CC5 for air conditioning circuits, including the breakers according to plans IE005.

4) Replace panels CC2 and CC3 with new Three-phase Panels, including the breakers according to plans IE005.

5) Disconnect the existing electrical circuit of panel CC2 and CC3 from the “Honduran Supreme Court” Electric Circuit, and connect it to existing I-Line in electrical room, with 1 1/2 emt pipe and 3x1/0 thhn+1x2 thhn+1x4 ground cable.

6) Add the electrical conduit only, for a future backup electric generator to the ATS.

This will result in the capacity enhancement of the forensic and investigation services provided, which include: Reception of Criminal Complaints, Interviews with Prosecutors, Forensic Evaluations, and Evaluations in the Gesell Chamber. Additionally, it will provide a one-stop for citizens to have access to such services. The CEIN will receive cases from the southern region of Honduras, including the departments of Choluteca and Valle.

The contractor shall provide all the Medium Tension Electric Equipment, materials, labor, transportation, and testing that will be needed to supply and install the Medium Tension Electric Equipment stated in this document and in accordance to Section 3.1 and plans in Annex 1.

The equipment to be provided shall be from an accredited dealer that can provide accessories and spare parts, and maintenance (if needed) in Honduras.

THE SCHEDULE

1. ACQUISITION METHOD

The U.S. Government is conducting this acquisition as a Simplified Acquisition Procedure with Full and Open Competition.

1.1 TYPE OF CONTRACT

This requirement will result in the award of a Firm Fixed Price (FFP) contract in accordance with the specifications in Section 3 of this Statement of Work (SOW). No additional sums will be payable due to any escalation in the cost of materials, equipment, or labor, or because of the Contractor’s failure to properly estimate or accurately predict the prices or difficulty of achieving the results required by this contract. Nor will the contract price be adjusted on account of fluctuations in the currency exchange rates. This purchase request is under NAICS Code: 238210 Electrical equipment and appliance installation

2. EFFECTIVE PERIOD OF CONTRACT

This contract shall be effective on the date of the Contracting Officer's signature and shall remain in full force and effect until all furniture is received and accepted by the U.S. Government in accordance with the contract delivery date NLT than ninety (90) calendar days after from receipt of the award notification

3. SUPPLIES AND PRICING

The Contractor shall provide to the U.S. Government the Medium Tension Equipment and Installation in strict compliance with the specifications at the agreed upon firm fixed price. In the event of non-compliance with the specifications, the U.S. Government reserves the right to demand correction(s) or reject this requirement in its entirety. Additionally, the Contractor shall perform the pre-delivery inspection of the equipment and deliver them to the location set forth in Section 8, Place of Delivery, of this SOW. The firm fixed price shall include the electrical units, transportation, delivery and installation and warranty certificates and any other documentation mandated by the destination country.

3.1 SPECIFICATIONS

CLIN Description Quantity Unit of Measurement

1 40 foot Concrete Post / Poste de Concreto de 40 pies 2 each

Structure for mounting transformers of 3x100 KVA, in wooden crosshead of 5''x6''x240'' /Burra para montaje de transformarmadores de 3x100 KVA,en cruceta de madera de 5''x6''x240'' 1 each

Structure A-III-6, at 34.5 KV/ Estructura A-III-6, en

34.5 KV 1 each

Structure A-III-4, in 34.5 KV/Estructura A-III-4, en

34.5 KV 2 each

5 Retention R-01/ Retenida R-01 1 each 6 Retention R-04/ Retenida R-04 1 each

Primary line extension 3x1/0 ACSR+1#2 ACSR Neutral/Extension de linea primaria 3x1/0 ACSR+1#2 ACSR Neutro Distance: 10 linear meters 1 lot

Transformer Bank 3x100 KVA, in 34.5 KV, output 120- 208V brand name or equal to PROLEC GE/Banco de transformadores 3x100 KVA, en 34.5 KV, salida 120- 208V marca similar o igual a PROLEC GE 1 lot

Electrical connection with cable 3x(3x500

MCM+3#350

MCM+3X1/0 AWG) IN 3X4 PVC/IMC DUCT from bank of transformers to main panel in electrical room/ Acometida eléctrica con cable 3x(3x500 MCM+3#350 MCM+3X1/0 AWG) EN DUCTO 3X4 PVC/IMC desde banco de transformadores hasta panel principal en cuarto eléctrico Distance: 69 linear meters 1 lot

Electrical conduit for backup electric generator to ATS in 3X4 PVC/IMC Duct, no cable needed /Canalizado en ducto 3X4 PVC/IMC desde generador hacia ATS, cableado no es necesario incluirlo.

Distance: 9 linear meters 1 lot

Electrical conduit from Main Panel in Electric Room to ATS in Backup Electric Room in 3X4 PVC/IMC Duct/Canalizacion en ducto 3X4 PVC/IMC desde panel principal en cuarto eléctrico hasta ATS en cuarto de respaldo electrico Distance: 48 linear meters 1 lot

Electrical connection for panel CC1 with 3x1/0 cable awg+1#2 awg Neutral +1#4 awg ground on 1-1/2''" emt pipe/Acometida eléctrica para panel CC1 con cable 3x1/0 awg+1#2 awg Neutro +1#4 awg tierra en tubería emt de 1-1/2'' Distance: 6 linear meters 1 lot

Electrical connection for panel CC2 with 3x1/0 cable awg+1#2 awg Neutral +1#4 awg ground on 1-1/2''" emt pipe/Acometida eléctrica para panel CC2 con cable 3x1/0 awg+1#2 awg Neutro +1#4 awg tierra en tubería emt de 1-1/2'' Distance: 8 linear meters 1 lot

Electrical connection for panel CC3 with 3x1/0 cable awg+1#2 awg Neutral +1#4 awg ground on 1-1/2''" emt pipe/Acometida eléctrica para panel CC3 con cable 3x1/0 awg+1#2 awg Neutro +1#4 awg tierra en tubería emt de 1-1/2'' Distance: 10 linear meters 1 lot

Electrical connection for panel CC4 with 3x1/0 cable awg+1#2 awg Neutral +1#4 awg ground on 1-1/2'' emt pipe, from electrical room to Module D *Panel CC4 is superficial /Acometida eléctrica para panel CC4 con cable 3x1/0 awg+1#2 awg Neutro +1#4 awg tierra en tubería emt de 1-1/2'', desde cuarto eléctrico a Modulo D *Panel CC4 es superficial Distance: 44 linear meters 1 Lot

Electrical connection for panel CC5, in electrical room ,with (3x4/0awg+1x2/0awg+1x2T awg ground) in 2x2 1/2" emt pipe /Acometida eléctrica con (3x4/0awg+1x2/0awg+1x2T awg tierra) en tubería emt de 2x2 1/2 para panel CC5 en cuatro electrico Distance: 8 linear meters 1 Lot

Register box, size: 60x60x80 cm, block and concrete construction, polished, basin type, with water drain according to plans named EG2 and EG3/Caja de registro de 60x60x80 cms, de bloque y concreto, pulido tipo pila, sumidero de agua, de acuerdo a planos son las cajas EG2 y EG3 3 each

Register box, size: 10"X10"X4" , block and concrete construction, polished, basin type, with water drain according to plans in Electrical Backup Room /Caja de registro de 10"X10"X4" cms, de bloque y concreto, pulido tipo pila, sumidero de agua de acuerdo a planos en el Cuarto de Respaldo Electrico 1 each

Three-phase Panel (CC5) for air conditioning circuits,42 spaces, 225 amp bars, with 225 amp main breaker, brand name or equal to Square D, with the following breakers:

Thirteen (13) 2 poles 40 amp breaker Six (6) 2 pole 30 amp breaker One (1) 2 poles 20 amp breaker" /Panel Trifásico, CC5, para circuitos de aire acondicionado, 42 espacios, barras de 225 amp, con main breaker de 225 amp, de marca similar o igual a Square D con los breaker siguientes:

Trece (13) breakers de 2 polos 40 amp Seis (6) breakers de 2 polos 30 amp Un (1) breaker de 2 polos 20 amp 1 set

Three-phased panel (CC2), 42 spaces, 225 amp bars, with 225 main breaker amp, three phased, brand name or equal to Square D with the following breakers:

Four (4) 2 pole, 20amp breaker Six (6) 3 pole, 30amp breaker /Panel trifasico (CC2) 42 espacios, barras de 225 amp, con main breaker de 225 amp, similar marca o igual a Square D, con los siguientes breakers:

Cuatro (4) breakers de 2 polo, 20 Amp Seis (6) breakers de 3 polo, 30 Amp 1 set

Three-phased panel (CC3) , 42 spaces, 225 amp bars, with 225 main breaker , brand name or equal to Square D/with the following breakers:

Fourteen (14) 2 pole, 20 amp breaker /Panel trifasico (CC3) 42 espacios, barras de 225 amp, con main breaker de 225 amp, similar o igual a la marca Square D con los breaker siguientes:

Catorce (14) breakers de 2 polos, 20 amp 1 set

22 Labor and Installation

See Annex A.1 for detail on Installation Activities.

1 lot

Earth network, with 8 rods of 5/8 and 1/0 awg cable, exothermic welding/Red de tierra, con 8 varillas de 5/8 y cable 1/0 awg, soldadura exotermica 1 set

ENEE design approval process and reception/Tramite de aprobacion de diseño y recepcion ENEE 1 lot

Shipping to Choluteca, Choluteca, Honduras./ Transporte a Choluteca, Choluteca, Honduras 1 lot

Note: Plans can be found in pages 14-31. Additional PDF files can be provided upon request.

Juzgados Unificados de Choluteca Centro Integrado del Ministerio Publico y Medicina Forense Choluteca, Choluteca, Honduras

3.3 OPTIONAL EQUIPMENT REQUIRED:

- N/A

3.4 ADDITIONAL REQUIREMENTS

Manuals of use and care should be provided in PDF & Print-Spanish.

4. WARRANTY

In accordance with the Contractor’s proposal, the vendor’s offer should include one (1) year minimum warranty from final installation date. It should cover any paint defects or deficiency that may occur during normal use, as well as defect and deficiencies.

A written warranty should be provided.

to

5. PREPARATION FOR DELIVERY

The Contractor shall consolidate the entire shipment to prevent loss and misdirection. Any lost or damaged items during shipment shall be replaced by the contractor upon notification.

The contractor must request all needed information from the US Embassy and the Government of Honduras, for the ENEE design approval process and reception process, within ten (10) calendar days after receipt of award order.

The electric components, conduit, and cable shall be clean, in new condition and must be in the normal operating ranges. No grey market or refurbished products.

6. MARKING AND SUBMISSION OF DOCUMENTS

6.1 All items shall be clearly marked as follows:

Embajada Americana Order No. (provided upon award) Item #___of ___ (if applicable) Attention: Ana Carcamo Phone:+504 94510604 Email: carcamoag@state.gov

6.2 Consignee Address:

Consignee: Embajada Americana Order No. (provided upon award) Col. San Carlos, Avenida La Paz Tegucigalpa M.D.C., Honduras Ana Carcamo Email: Carcamoag@state.gov

7. DELIVERY SCHEDULE

All Medium Tension Equipment shall be delivered and installed to location set forth in section 8, in up to ninety (90) calendar days after from receipt of the award notification.

mailto:carcamoag@state.gov mailto:Carcamoag@state.gov

8. PLACE OF DELIVERY AND INSTALLATION

The Medium Tension Equipment will be delivered and installed to the following address:

Juzgados Unificados de Choluteca Centro Integrado del Ministerio Publico y Medicina Forense

Choluteca, Choluteca, Honduras

Installation shall commence within fourteen (14) calendar days after the design approval is granted.

9. CUSTOMS CLEARANCE AND TAX EXEMPTIONS

The U.S. Government will assist the Contractor in obtaining customs clearance and tax exemption certificates from the Government of Honduras

The Contractor shall comply with Sections 38-40 of the Arms Export Control Act (AECA) (22 U.S.C. 2778-2780) and the International Traffic in Arms Regulations (ITAR) (22 CFR Parts 120-

130) as required, for the prosecution of work under this contract at no additional cost to the Government. Failure to be in compliance with AECA and ITAR by date planned for commencement of contract performance as well as during the entire performance of work under this contract may result in contract termination. Any penalties rendered to the Contractor, as a direct result of being found non-compliance with AECA and ITAR, shall be the responsibility of the Contractor. For additional information on AECA and ITAR, see http://www.pmddtc.state.gov/.

The Contractor shall comply with license requirements of the Commerce Control List and any Export Administrative Regulations (EAR), which may apply

The Contractor’s must include and arrange all local, port handling and other fees associated with delivery to the destination.

9.1. EXPORT LICENSE

If an export license is required, delivery shall be forty five (45) days after receipt of export license, and export license application shall be accomplished expeditiously after award.

10. INSPECTION AND ACCEPTANCE

The Contractor shall ensure professional installation to original equipment manufacturer (OEM) standards for all components and accessories. Contractor must ensure all equipment is assembled and working properly.

Contractor must do a cleanup and dispose of all packaging and debris.

The inspection and acceptance of the Medium Tension Equipment shall be performed by the U.S.

Government upon the installation in Choluteca, Choluteca, Honduras.

The payment(s) to the Contractor shall be made following satisfactory inspection and acceptance of products by the Office of INL in Tegucigalpa. All equipment delivered and installation performed shall conform exactly to the standard described in Section 3.

Contractor may submit an invoice for equipment once all items are delivered. Afterwards, a second invoice for labor and installation may be submitted once installation is completed.

If the items or some item does not fulfill requested technical specifications, INL shall return the items to vendor with no cost to INL Honduras. The vendor shall evaluate and replace returned items with no transportation cost to INL.

The Contractor shall notify the U.S. Government five (5) business days before the completion of the installation. INL will have two (2) day to inspect and accept all items. The designated representative of the US Embassy in Honduras will be responsible for carrying out at least the following checks of the required elements:

i. Quantities

ii. Compliance with the offered technical specifications

iii. Correct operation of the required elements

12. EVALUATION FACTORS FOR OFFERORS

The following are the evaluation factors for proposals sent by the bidders:

a) DESCRIPTION: Description/nomenclature of the item being quoted; Compliance with the requested technical specifications and warranty period as per Statement of Work.

b) TECHNICAL PROPOSAL: Vendor must include in its quotation, the technical proposal plans for the installation of Medium Tension Equipment.

c) PRICE: For evaluation purposes, the price will be determined by multiplying the offered prices times the quantities stated in the schedule, and arriving at a grand total, including all options, if any.

• Award will be made to the lowest priced, technically acceptable, responsible quoter.

• The Government reserves the right to reject quotations that are incomplete, non-compliant with the terms of this solicitation, or that are unreasonably high in price.

d) DELIVERY DATE: The Government will evaluate the proposed delivery time frame.

e) PAST PERFORMANCE: A list of contracts within the last two (2) years for the provision of Electric Installations. The list shall include contact information (name, organization, email, and phone) and limited to no more than five (5) references.

• The Government will determine quoter responsibility by analyzing whether the apparent successful quoter complies with the requirements of FAR 9.1.

f) SAM: Unless an exception in FAR 4.1102 applies, a quoter must be registered in SAM (www.sam.gov) in order to be eligible for award. If the quoter does not become registered in the SAM database in the time prescribed by the Contracting Officer, the Contracting Officer will proceed to award to the next otherwise successful registered quoter.

13. ADDITIONAL CONSIDERATIONS

1. Additional PDF Plans of the location can be provided upon request.

http://www.sam.gov/

Appendix A

Annex A.1 Installation Activities

A. Labor for Dismantling existing 3x50 KVA transformer bank / Mano de Obra para Desmontaje de banco de transformadores de 3x50 KVA existente

B. Installation of 40 foot concrete post / Instalacion de poste de concreto de 40 pies C. Installation of structure for mounting transformers of 3x100 KVA, in wooden crosshead of

5''x6''x240'' /Instalacion de burra para montaje de transformarmadores de 3x100 KVA,en cruceta de madera de 5''x6''x240''

D. Installation of Structure A-III-6, at 34.5 KV/ Instalacion de Estructura A-III-6, en 34.5 KV

E. Installation of structure A-III-4, in 34.5 KV/ Instalacion de estructura A-III-4, en 34.5 KV

F. Installation of retention R-01/Instalacion de retenida R-01

G. Installation of retention R-04/Instalacion de retenida R-04

H. Installation of Primary line extension 3x1/0 ACSR+1#2 ACSR Neutral/Instalacion de la Extension de linea primaria 3x1/0 ACSR+1#2 ACSR Neutro

I. Installation of Transformer Bank 3x100 KVA, in 34.5 KV, output 120-208V brand name or equal to PROLEC GE/ Instalacion de Banco de transformadores 3x100 KVA, en 34.5 KV, salida 120-208V marca similar o igual a PROLEC GE

J. Installation of electrical connection with cable 3x(3x500 MCM+3#350 MCM+3X1/0 AWG) IN 3X4 PVC/IMC DUCT from bank of transformers to main panel in electrical room/Instalación de acometida eléctrica con cable 3x(3x500 MCM+3#350 MCM+3X1/0 AWG) EN DUCTO 3X4 PVC/IMC desde banco de transformadores hasta panel principal en cuarto eléctrico

K. Installation of Electrical conduit for backup electric generator to ATS in 3X4 PVC/IMC Duct, no cable needed /Instalacion del canalizado en ducto 3X4 PVC/IMC desde generador hacia ATS, cableado no es necesario incluirlo.

L. Installation of Electrical conduit from Main Panel in Electric Room to ATS in Backup Electric Room in 3X4 PVC/IMC Duct/Instalacion de Canalizacion en ducto 3X4 PVC/IMC desde panel principal en cuarto eléctrico hasta ATS en cuarto de respaldo electrico

M. Installation of electrical connection for panel CC1 with 3x1/0 cable awg+1#2 awg Neutral +1#4 awg ground on 1-1/2''" emt pipe/Instalación de acometida eléctrica para panel CC1 con cable 3x1/0 awg+1#2 awg Neutro +1#4 awg tierra en tubería emt de 1-1/2''

N. Installation of electrical connection for panel CC2 with 3x1/0 cable awg+1#2 awg Neutral +1#4 awg ground on 1-1/2''" emt pipe/Instalación de acometida eléctrica para panel CC2 con cable 3x1/0 awg+1#2 awg Neutro +1#4 awg tierra en tubería emt de 1-1/2''

O. Installation of electrical connection for panel CC3 with 3x1/0 cable awg+1#2 awg Neutral +1#4 awg ground on 1-1/2''" emt pipe/Instalación de acometida eléctrica para panel CC3 con cable 3x1/0 awg+1#2 awg Neutro +1#4 awg tierra en tubería emt de 1-1/2''

P. Installation of electrical connection for panel CC4 with 3x1/0 cable awg+1#2 awg Neutral +1#4 awg ground on 1-1/2'' emt pipe, from electrical room to Module D *Panel CC4 is superficial /Instalación de acometida eléctrica para panel CC4 con cable 3x1/0 awg+1#2 awg Neutro +1#4 awg tierra en tubería emt de 1-1/2'', desde cuarto eléctrico a Modulo D *Panel CC4 es superficial

Q. Installation of electrical connection for panel CC5, in electrical room ,with (3x4/0awg+1x2/0awg+1x2T awg ground) in 2x2 1/2" emt pipe /Instalación de acometida eléctrica con (3x4/0awg+1x2/0awg+1x2T awg tierra) en tubería emt de 2x2 1/2 para panel CC5 en cuatro electrico

R. Labor for disconecting the existing electrical connection from panel CC2 and CC33 to the Judicial Power and connecting it to existing I-Line in electrical room, with 1 1/2 emt pipe and 3x1/0 thhn+1x2 thhn+1x4 earth cable / Mano de obra para desconectar la acometida eléctrica existente del panel CC2 y CC33 del Poder Judicial y conectarlo al I-Line existente en cuarto eléctrico, con tubería de 1 1/2 emt y cable de tierra 3x1/0 thhn+1x2 thhn+1x4

S. Labor for dismantling the existing electrical connection with 3#3/0 awg+1#1/0awg/Mano de obra por desmontaje de acometida eléctrica existente con 3#3/0 awg+1#1/0awg Length: 75 Linear Meters

T. Labor for main connection trench from transformer bank to ATS and to electrical room/Mano de obra para zanjo de acometida principal desde banco de transformadores hasta ATS y hacia cuarto eléctrico Length: 66 linear Meters

U. Labor for Sidewalk grooving and sidewalk patching/Ranurado de Cera y resane de cera.

Length" 19 Linear Meters

V. Labor for Filling and compacting of Trench /Relleno y compactado de Zanjo length: 66 Linear Meters

W. Installation of Three-phase Panel (CC5) for air conditioning circuits,42 spaces, 225 amp bars, with 225 amp main breaker, brand name or equal to Square D, with the following breakers:

Thirteen (13) 2 poles 40 amp breaker Six (6) 2 pole 30 amp breaker One (1) 2 poles 20 amp breaker" /Instalación de Panel Trifásico, CC5, para circuitos de aire acondicionado, 42 espacios, barras de 225 amp, con main breaker de 225 amp, de marca similar o igual a Square D con los breaker siguientes:

Trece (13) breakers de 2 polos 40 amp Seis (6) breakers de 2 polos 30 amp Un (1) breaker de 2 polos 20 amp

X. Installation of three-phased panel (CC2), 42 spaces, 225 amp bars, with 225 main breaker amp, three phased, brand name or equal to Square D with the following breakers:

Four (4) 2 pole, 20amp breaker Six (6) 3 pole, 30amp breaker /Instalacion de panel trifasico (CC2) 42 espacios, barras de 225 amp, con main breaker de amp, similar marca o igual a Square D, con los siguientes breakers:

Cuatro (4) breakers de 2 polo, 20 Amp Seis (6) breakers de 3 polo, 30 Amp

Y. Installation of three-phased panel (CC3) , 42 spaces, 225 amp bars, with 225 main breaker , brand name or equal to Square D/with the following breakers:

Fourteen (14) 2 pole, 20 amp breaker /Instalacion de panel trifasico (CC3) 42 espacios, barras de 225 amp, con main breaker de 225 amp, similar o igual a la marca Square D con los breaker siguientes:

Catorce (14) breakers de 2 polos, 20 amp

Z. Ground network test, includes OHM test results (Electric Resistance and Conductivity)/Prueba de red de tierra incluye lectura de los OHMS (Resistencia Eléctrica y Conductividad)

Annex A.2 Plan 1 - IE001

Annex A.3 Plan 1.1 - IE001 – electric transformer bank, trench route, register box

Annex A.4 Plan 1.2 - IE001 – Electric Room

Annex A.6 Plan 1.3 - IE001 – Panel CC4 in Module D

Annex A.7 Plan 2- IE002

Annex A.8 Plan 3- IE003

Annex A.9 Plan 4 – IE004

Annex A.10 Plan 5- IE005

Annex A.11- Single line Diagram - Diagrama Unifilar

Annex A.12 – I-Line

Annex A.13 – Existing Panel CC1

Annex A.14 – Existing panel CC2

Annex A.15 – Existing Panel CC3

Annex A.16- Existing Panel CC4

Annex A.17– New panel CC5

File details come from the government source that posted it. Updated .