This Statement of Work (SOW) details a fiber optic and audio-visual (A/V) cabling installation project for a building at Hanscom Air Force Base in Massachusetts. The project requires installing Fiber-to-the-Desk (FTTD) and A/V cables to connect video teleconferencing systems in two conference rooms on the second floor, with a 90-calendar day period of performance. Key technical requirements include using OM4 50/125 μm multi-mode fiber optic cables with red jackets, installing an 8-strand fiber cable between the intermediate distribution frame (IDF) and data drops, and terminating each strand in 4-port surface-mounted boxes with LC connectors.

The contractor must meet extensive specifications, including using Optical Fiber® certified installers, ensuring Trade Act Agreement compliance, and performing comprehensive testing in accordance with multiple telecommunications standards (TIA-568.1, TIA-568.2, TIA-568.3). Submittal requirements include material cut sheets, personnel qualifications, telecommunications drawings, factory reel tests, performance testing, maintenance documentation, warranty information, and as-built drawings. The project involves multiple meetings, including a virtual kickoff within 5 working days of contract award, bi-weekly progress meetings before cable installation, and weekly meetings during installation, culminating in pre-final and final on-site inspections.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATEMENT OF WORK (SOW)

FOR

Building

Fiber-to-the-Desk and Audio-Visual Cabling

Prepared by AFNWC/NCO

25 July 2025

1.0 Purpose:

The intent of this contract is to install Fiber-to-the-Desk (FTTD) and audio-visual (A/V) cables that will connect video teleconferencing (VTC) systems within the conference rooms of Building

, located at Hanscom Air Force Base (HAFB), Massachusetts. If a requirement is not allowed by building codes, building codes shall take precedence.

2.0 Scope/Objectives:

The contractor shall provide all labor, materials, and equipment necessary to implement FTTD, as well as run and install all necessary A/V cables needed to connect and ensure operational VTC systems in both conference rooms located on the second floor of Building

a. Installation of fiber optic cable from the main distribution frame (MDF) of to the alcove area located between and where the Class 5 IPS container and patch panel equipment will be housed. For the purposes for this SOW, we will refer to all the equipment in this alcove as the intermediate distribution frame (IDF).

b. Installation of multimode cable from the IPS container to individual offices, rooms, conference rooms, or systems furniture workstations within the project area.

c. Installation of A/V cables for each conference room.

3.0 Attachments:

• Attachment #1: Floor Plan

4.0 Administration:

The following are the points of contact (POCs) for this delivery order:

a. Project Manager (PM)

b. Alternate Project Manager:

5.0 Project Submittals:

The following submittals shall be required under this contract. Unless otherwise specified below, the Government requires 21 calendar days for the review and approval of each submittal.

a. Pre-installation Submittal: Material Cut Sheets Provide manufacturer product information for all products provided under this contract.

Submittal Format When Material Cut Sheets Adobe PDF 30 Calendar Days from

Contract Award

b. Pre-Installation Submittal: Personnel Qualifications Provide qualifications for the Communications Installer(s). Submit documentation demonstrating that the proposed communications cabling installer meets the requirements stated in Section 8 of this SOW.

Submittal Format When Communications Installer Adobe PDF 30 Calendar Days from

c. Pre-Installation Submittal: Telecommunications Drawings Provide telecommunications drawings as stated in Section 8.

Submittal Format When Telecommunications Installer Adobe PDF 30 Calendar Days from

d. Submittal: Factory Reel Tests Provide factory reel test data for all fiber optic cabling provided.

Factory Reel Test Adobe PDF 10 work days prior to installation

e. Submittal: Performance Testing Provide the results of performance testing completed on the installed cabling.

Performance Testing Adobe PDF 10 work days prior to installation

f. Closeout Submittal: Maintenance Documentation Provide maintenance documentation for all equipment provided under this contract.

Maintenance Documentation Adobe PDF Prior to Pre-Final Inspection

g. Closeout Submittal: Warranty Information

Provide installer and manufacture warranty for all equipment provided under this contract.

Provide a summary of all manufacturer warranties that includes an item description, expiration date of warranty, and contact information to request warranty service.

Warranty Information Adobe PDF Prior to Pre-Final Inspection

h. As-built Drawings

Provide as-built drawings that details the configuration of FTTD and A/V cables installed.

As-builts Adobe PDF, AutoCAD

(Max Sheet Size ANSI D) Prior to Pre-Final Inspection

6.0 Project Management:

The Government requires that the Contractor perform all management functions required to meet the requirements of this SOW. Specifically, the contractor shall:

a. Participate in a virtual kickoff meeting within 5 working days of contract award.

b. Participate in virtual bi-weekly progress meetings between contract award and the start of fiber optic cable installation.

c. Participate in virtual weekly progress meetings upon commencement of fiber optic cable installation.

d. Participate in an on-site pre-final inspection.

e. Participate in an on-site final inspection.

7.0 Period of Performance:

The Period of Performance (POP) for this contract shall be 90 calendar days. If the Contractor cannot perform the work within the proposed POP, the contractor shall submit a proposed POP. The POP shall include:

a. Pre-Installation Submittals

b. Government Reviews

c. Material Lead Time

d. Pre-Final & Final Inspections

e. Project Closeout activities

The contractor shall assume that fiber optic cable installation will commence between [TBD] and [TBD].

The contractor shall begin installation within 30 days of notification from the Government. The Contractor shall coordinate with the to coordinate schedules and deconflict work.

8.0 Cable Specifications / Requirements:

a. Common Requirements:

• All installers shall be Optical Fiber® (INSTF®) certified.

• Install all cabling through raceways suspended from ceiling (installed by others), through a metal conduit (installed by others) where they penetrate secure walls and finally terminate inside of a compact surface mount box.

• Optical fiber cables shall be non-conductive optical fiber plenum (OFNP).

• Any CAT 5e/6 cables utilized shall be plenum/shielded (STP).

• Optical fiber cables shall be OM4 50/125 µm multi-mode and the jacket color shall be red.

• Terminate optical fiber cables using unkeyed duplex LC connectors and adaptors by fusion splicing at both ends. Pre-terminated fiber optic cables are also acceptable.

• Ensure all cabling used for this project is Trade Act Agreement (TAA) compliant.

• Provide telecommunication drawings prepared by a registered communications distribution designer (RCDD) in accordance with TIA-606 for Government approval prior to starting installation. The identifier for each termination and cable shall appear on the drawings. Drawings shall depict final telecommunications wiring infrastructure in accordance with TIA-606. The drawings should provide details required to prove that the distribution system shall properly support connectivity from the MDF to the alcove equipment, and finally to the data port location(s). Provide a laminated plastic schematic of the as-installed telecommunications cable system.

• Cabling, equipment, and hardware manufacturers shall have a minimum of 3 years’ experience in the manufacturing, assembly, and factory testing of components which comply with TIA-568.1, TIA-568.2 and TIA-568.3.

• Provide a complete and detailed test plan for the telecommunications cabling system including a complete list of test equipment for the components and accessories for each cable type specified, 60 days prior to the proposed test date. Include procedures for certification, validation, and testing. Security shall grant final acceptance.

• In accordance with ICEA S-83-596, TIA-568.3, UL 1666 and NFPA 70. Cable shall be imprinted with fiber count, fiber type and aggregate length at regular intervals not to exceed 40 inches.

• Provide labeling in accordance with TIA-606.

b. Wall Penetrations

• Use existing wall penetration to the greatest extent possible.

• After all communications wires have been pulled, seal each penetration using firestopping system that complies with ASTM E814 or UL 1479.

• For workstations along walls, the contractor shall install surface mounted conduit.

• Only the cable trays shown on the attached drawings will be provided by others. The Contractor shall extend cable trays as required.

• Construct new wall penetrations using details shown on in Attachment #1.

c. Patch Panel Enclosure Cabinet:

Provide the equipment below meeting the following requirements:

• 19U lockable wall-mount cabinet with a low-decibel dual-fan kit similar to the Chatsworth Products CUBE-iT™ Wall-Mount Cabinet (cabinet part no. 11900-736 and fan kit part no. 40975-001) and the blocking necessary to support the cabinet on the EAST wall in the alcove of the corner of

• Install patch panel dedicated to the 96-strand trunk cables. The patch panel shall not use more than 8Us of cabinet space.

d. Private offices, conference rooms and systems furniture locations:

• Install one 8-strand 50/125 μm OM4 multi-mode plenum rated fiber optic fiber cable between the associated IDF and the data drop.

• Terminate each strand at the data drop locations shown on the attached floor plan in a 4 port, surface mounted boxes using LC connectors.

e. Testing requirements:

• Provide documentation of the testing and verification (Factory Reel Tests) actions taken by manufacturer to confirm compliance with TIA-568.1, TIA-568.2, TIA-568.3, TIA- 526-7 for single mode optical fiber, and TIA-526-14 for multimode optical fiber cables.

• Perform telecommunications cabling inspection, verification, and performance tests in accordance with TIA-568.1, [TIA-568.2], [TIA-568.3]. Test equipment shall conform to

TIA-1152. Perform optical fiber field inspection tests via attenuation measurements on factory reels and provide results along with manufacturer certification for factory reel tests. Remove failed cable reels from project site upon attenuation test failure.

• For multimode optical fiber, perform optical fiber end-to-end attenuation tests in accordance with TIA-568.3 and TIA-526-14 using Method B, OTDR for multimode optical fiber. For single-mode optical fiber, perform optical fiber end-to-end attenuation tests in accordance with TIA-568.3 and TIA-526-7 using Method B, OTDR for single-mode optical fiber.

• For each port, perform optical fiber end-to-end link tests in accordance with TIA-568.3.