Statement of Work Summary: Frequency Converter Generator Procurement & Commissioning
This is a Statement of Work (SOW) for the procurement, delivery, and commissioning of a frequency converter generator system to support the 305th Maintenance Squadron at Joint Base McGuire-Dix-Lakehurst, New Jersey. The contractor must procure and deliver one (1) UFC-180H, 180-kVA Low Profile fixed frequency converter system or equivalent that meets or exceeds specified technical requirements. The unit shall accept input voltage of 380 to 480 V (+10%/-15%), 3-phase, 50/60 Hz with a full load input current of 186 A at 480 VAC, and provide dual outputs of 115 V L-N / 200 V L-L, 3-phase, 4-wire at 400 Hz to support KC-46 and C-17 aircraft maintenance operations. The contractor is responsible for all transportation and materials required for delivery to Building 2201, providing technical data and installation manuals to Base Civil Engineering, commissioning the unit following CE installation, training government personnel on operation and troubleshooting, and delivering as-built documentation, user manuals, and maintenance instructions.
The work shall begin within 30 days of contract award and be completed within 180 days of Notice to Proceed, including delivery and commissioning pending CE coordination. The place of performance is Main Hangar Building 2201, located at 2201 Grissom Road, Joint Base McGuire-Dix-Lakehurst, New Jersey. All work must comply with the National Electrical Code (NEC), OSHA Safety Standards, Unified Facilities Criteria (UFC), and JB MDL engineering directives. The contractor must submit a Job Safety Analysis (JSA) or Activity Hazard Analysis (AHA) prior to on-site work and ensure all electrical commissioning is performed by licensed technicians. Base Civil Engineering will provide physical installation, mounting, electrical connections, site access coordination through the 305th MXS, and access to technical drawings and base utility maps. Primary point of contact is Michael Ford (609-754-0094, Michael.Ford.5@us.af.mil), with alternate contact Scott Rayner (609-754-1868, Scott.rayner@us.af.mil).
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Combo Synopsis Solicitation- FA448426Q0028-0001-Reducted.pdf | ||
| Generator Questions and Answers.docx | DOCX document | |
| Combine Synopsis Solicitation-FA448426Q0028_Redacted.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF WORK (SOW)
Frequency Converter Generator Procurement & Commissioning
305th Maintenance Squadron (305 MXS) Joint Base McGuire-Dix-Lakehurst (JB MDL)
1.0 SCOPE
This Statement of Work (SOW) defines the requirements for the procurement, delivery, and commissioning of a frequency converter generator system. The unit will support electrical requirements at the main hangar door of the 305th Maintenance Squadron (305 MXS), located at Joint Base McGuire-Dix-Lakehurst (JB MDL).
Note: Physical installation, mounting, and electrical integration into the facility will be performed by Base Civil Engineering (CE).
2.0 BACKGROUND
The existing electrical infrastructure at the main hangar door does not provide adequate support for mission-essential equipment. A frequency converter generator is required to provide reliable 400 Hz power to support KC-46 and C-17 aircraft maintenance operations and ensure mission readiness.
3.0 REQUIREMENTS
3.1 Contractor Deliverables
• Procurement: Procure and deliver one (1) UFC-180H, 180-kVA Low Profile™ fixed frequency converter system/ or equal that meets or exceed the technical specification.
• Technical Specifications:
• Input: 380 to 480 V +10%/-15%, 3-phase, 50/60 Hz; full load input current 186 A (at 480 VAC).
• Output 1 & 2: 115 V L-N / 200 V L-L, 3-phase, 4-wire, 400 Hz.
• Logistics: Provide all transportation and materials required for delivery to Bldg 2201.
• CE Coordination: Provide technical data, wiring diagrams, and installation manuals to Base CE to facilitate their installation process.
• Commissioning: Following installation by CE, the Contractor shall test and commission the unit to ensure full operational functionality and compliance with safety codes.
• Training: Train designated government personnel in basic operation, safety, and troubleshooting.
• Documentation: Provide as-builts (reflecting final configuration), user manuals, standard manufacturer warranty information, and maintenance instructions.
3.2 Performance Standards
All work and equipment shall comply with:
• National Electrical Code (NEC)
• OSHA Safety Standards
• Unified Facilities Criteria (UFC)
• JB MDL engineering and safety directives
4.0 PERIOD OF PERFORMANCE
• Project Initiation: Work shall begin within 30 days of contract award/approved credit.
• Total Completion: Total project completion shall not exceed 180 days from Notice to Proceed
(NTP), including delivery and commissioning, pending coordination with CE and safety.
5.0 PLACE OF PERFORMANCE
Main Hangar Bldg 2201 305th Maintenance Squadron Joint Base McGuire-Dix-Lakehurst, NJ 2201 Grissom Rd
6.0 GOVERNMENT FURNISHED SUPPORT
The Government (specifically Base Civil Engineering) will provide:
• Physical Installation: Mounting and securing the unit at the designated location.
• Electrical Connection: Connection of all electrical components and utility integration from the building to the generator.
• Site Access provided by 305 MXS : Escorts and location access for delivery and commissioning.
• Technical Data: Access to technical drawings and base utility maps (if available).
7.0 SAFETY AND ENVIRONMENTAL
• The Contractor must comply with JB MDL safety regulations during delivery and commissioning and submit a Job Safety Analysis (JSA) or Activity Hazard Analysis (AHA) prior to on-site work.
• All electrical commissioning work must be performed by licensed technicians.
• Waste materials generated during delivery/unboxing must be disposed of in accordance with EPA and base environmental guidelines.
8.0 OPSEC
“OPSEC - The contractor shall be responsible for safeguarding military information as outlined by the JB MDL Commander. Contractor personnel will not take photographs of military facilities, equipment or personnel unless cleared through the proper channels.”
9.0 POINTS OF CONTACT
Primary POC:
Name: Michael Ford Phone: 609-754-0094 Email: Michael.Ford.5@us.af.mil
Alternate POC:
Name: Scott Rayner Phone: 609-754-1868 Email: Scott.rayner@us.af.mil
GENERAL SPECIFICATIONS
INPUT:
Input Current Distortion ≤ 5%, typically 3%
Voltage
Frequency
Phase
Rotation
Protection
Inrush Current
380 to 480 volts, +10%, -15%, 3Ø, 3 or 4 wire plus ground (Alternate Voltages Available)
45 - 65 Hz ± 10%
Any
Over/undervoltage, loss of phase, overcurrent, short circuit. Voltage transient protection IAW IEEE C62.41.1, Location Cat. B/C
No greater than 100% of full load current
ENVIRONMENTAL:
Acoustical Noise < 65 dBA maximum at 5 feet (1.5m)
Temperature Range -40°C to +55°C
Relative Humidity 10 - 95%, Non- Condensing
Ingress of Water Type 3SX, IP55
ENERGY
FACTORS:
Efficiency
Energy Efficiency Ratio
94% typical at full load; 92% typical at half load; varies depending on configuration
20.0 typical
OUTPUT:
Power Rating
Power Factor Range
Overload
Voltage**
* Crest
Factor
Voltage Regulation
Voltage Transients
Frequency
Regulation
Frequency Transients
Phase Angle
Regulation
Harmonic
Distortion
Protection
Automatic Line Drop Compensation
(ALDC)
120, 150, or 180 kVA (Specify)
0.5 lagging to 0.8 leading
100% continuous
110% for 60 min
125% for 10 min
150% for 2 min
200% for 20 sec
115/200 volts, 3Ø, 4 wire, grounded neutral
1.414 ± 3%
± 1.0% under all conditions of line, balanced loads and temperature
IAW MIL-STD-704F
400 Hz ± 0.01% under all conditions of line, load and temperature
None
± 1° for balanced loads;
± 2° for unbalanced loads
2.0% maximum
Overload, short circuit, over/undervoltage and safety disconnect
15%