Generator Questions and Answers.docx
DOCX document 34 KB Posted
- Attached to
- Fixed Frequency Converter System/Generator
- Solicitation number
- FA448426Q0028
About this file
This is a Questions and Answers document providing vendor clarifications for the procurement of a 180-kVA low-profile fixed frequency converter system (UFC-180H or equivalent) to support KC-46 and C-17 maintenance operations at an Air Force facility. The Government confirmed that contractors must furnish all aircraft output cables as part of the requirement, including the WIH-15 input cable (15 feet in length) and WOA-80M AC output cables (80 feet in length). Cable specifications must support input voltage of 380-480V (+10%/-15%), 3-phase, 50/60 Hz with full load input current of 186A at 480VAC, and output of 115V L-N / 200V L-L, 3-phase, 4-wire at 400 Hz on two separate outputs.
The manufacturer specifications provided detail comprehensive system requirements including input current distortion not exceeding 5% (typically 3%), acoustic noise less than 65 dBA at 5 feet, operating temperature range of -40°C to +55°C, and environmental ingress rating of Type 3SX/IP55. Output specifications include power ratings of 120, 150, or 180 kVA (to be specified), 94% efficiency at full load, voltage regulation of 3%, frequency regulation of 0.01%, and comprehensive protection against overload, short circuit, over/undervoltage conditions. Vendors are authorized to quote manufacturer-standard cables compatible with the UFC-180H system if Government-specific cable specifications do not exist. This amendment updated the quotation submission deadline to 10 August 2026 at 2:00 PM Eastern Time, and all quoters must acknowledge receipt of this amendment with their proposal.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Vendor Questions
1. Aircraft Output Cables
· Should the contractor furnish the aircraft output cables as part of this requirement, or does the Government intend to use existing output cables already on site?
Answer: The contractor should furnish the aircraft output cables as per SOW requirements.
2. Cable Type
· If the contractor is required to provide the aircraft output cables, what type of cables are required (e.g., Split-F, Non-Jumpered, or another configuration)?
Answer: Not sure what is being asked as far as type of cable. Per the requirements we need the following:
· Input: 380 to 480 V +10%/-15%, 3-phase, 50/60 Hz; full load input current 186 A (at 480 VAC)
· Output 1: 115 V L-N / 200 V L-L, 3-phase, 4-wire, 400 Hz
· Output 2: 115 V L-N / 200 V L-L, 3-phase, 4-wire, 400 Hz
3. Cable Lengths
· Please provide the required length of:
· The WIH-15 Input Cable (CLIN 0002).
Answer: Input cable length is 15 feet.
· Each WOA-80M AC Output Cable (CLIN 0003).
Answer: Output cable length is 80 feet.
4. Cable Routing Information (if exact lengths are unavailable)
· If exact cable lengths cannot be provided, please provide the approximate cable run distance from the converter's installed location at Building 2201, Main Hangar Door, to:
· The electrical connection point.
Answer: 8 feet would be acceptable.
· The aircraft servicing position.
Answer: 40 feet would be acceptable
5. Cable Specifications
· Please provide any applicable cable specifications, drawings, conductor size, connector/end-fitting details, or other technical requirements for the WIH-15 and WOA-80M cable assemblies.
Answer: Please see below for specifications directly from manufacturer quote.
GENERAL SPECIFICATIONS
INPUT:
Input Current Distortion ≤ 5%, typically 3% Voltage
Frequency Phase Rotation Protection
Inrush Current 380 to 480 volts, +10%, -15%, 3Ø, 3 or 4 wire plus ground (Alternate Voltages Available) 45 - 65 Hz ± 10% Any Over/undervoltage, loss of phase, overcurrent, short circuit. Voltage transient protection IAW IEEE C62.41.1, Location Cat. B/C No greater than 100% of full load current
ENVIRONMENTAL:
Acoustical Noise < 65 dBA maximum at 5 feet (1.5m) Temperature Range -40°C to +55°C Relative Humidity 10 - 95%, Non-Condensing Ingress of Water Type 3SX, IP55
ENERGY FACTORS:
Efficiency
Energy Efficiency Ratio 94% typical at full load; 92% typical at half load; varies depending on configuration
20.0 typical
OUTPUT:
Power Rating Power Factor Range Overload
Voltage*** Crest Factor Voltage Regulation
Voltage Transients Frequency Regulation
Frequency Transients Phase Angle Regulation
Harmonic Distortion Protection
Automatic Line Drop Compensation (ALDC) 120, 150, or 180 kVA (Specify)
0.5 lagging to 0.8 leading 100% continuous 110% for 60 min 125% for 10 min 150% for 2 min 200% for 20 sec 115/200 volts, 3Ø, 4 wire, grounded neutral
1.414 ± 3% ± 1.0% under all conditions of line, balanced loads and temperature
IAW MIL-STD-704F
400 Hz ± 0.01% under all conditions of line, load and temperature None ± 1° for balanced loads;
± 2° for unbalanced loads 2.0% maximum Overload, short circuit, over/undervoltage and safety disconnect 15%
6. Manufacturer Standard Cables
· If no Government-specific cable specifications or drawings exist, should vendors quote the manufacturer-standard WIH-15 input cable and WOA-80M output cables that are compatible with the UFC-180H or equivalent frequency converter system?
Answer: Yes, please quote the manufacturer standard cables that are compatible with the UFC-180H.