SOW Attachment 10- Narrative-min_Part2 - HVAC Resolicit.pdf
PDF 20 MB Posted
- Attached to
- Z1DZ--402-22-755 Replace Laundry HVAC
- Solicitation number
- 36C24124R0062
About this file
The provided document is a Statement of Work (SOW) attachment for a federal contract opportunity to replace the HVAC system in the laundry rooms of the VA Medical Center in Maine, Togus Campus.
The key details include:
- The contract is a 100% set-aside for small businesses.
- The required services include labor, materials, and services to perform the HVAC system repair and replacement.
- Proposals must be submitted via email to Andrew Baker at Andrew.baker@va.gov no later than June 6, 2024 at 5:00 PM EST.
- The contracting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1.
- No compressed .ZIP files will be accepted.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Model: Grilles and Registers -- Supply / Return Airflow Measurements Procedure
1. Place anemometer type probe against outlet or inlet as shown.
Note: For the rotating vane anemometer, an average reading is obtained by moving the anemometer over the grille face at a uniform rate or by holding the anemometer at various spots for an equal amount of time. Anemometer readings are to be for at least a one-minute period. Be sure the anemometer is held against the vanes.
2. Repeat Step 1 for a number of readings in equal areas of the grille face.
3. Average these readings.
4. Calculate the flow rate using the following equation.
Note: Refer to the appropriate factor (supply or return) table for the flow factor and the Core Area Table for the core area factor.
Air Flow Factors 272-FF 03-24-04
Supply Outlet Factors
Dwyer Air Velocity Meter
#460-7
Supply
6060 or 2220-A Jet
Anemotherm Model 60 Supply
6070 or 2220-A Jet
6070 or 2220-A Jet
Anemotherm Model 60
All rights reserved. No part of this work may be reproduced or transmitted in any form or any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air Distribution Technologies
605 Shiloh Road Plano, Texas 972-212-4800
Air Flow Factors 272-FF 03-24-04
Refer to the Balancing Application Guide for more information about balancing air systems.
Alnor Anem RVA Alnor Anem RVA
23 45 0.33 1.05 0.75 50 0 0.61 1.07 0.81
25 30 0.44 1.11 0.79 T-700 0.35 1.06 0.74
30 0 0.61 1.27 0.84 CT-700 0.37 0.94 0.71
33 30 0.48 1.12 0.79 34 45 0.37 1.22 0.76 3 45 0.29 1.14 0.73 4 45 0.36 1.19 0.74 8 0 0.43 1.12 0.86 355 35 0.50
Core Defl.
Anemometer
350RL
350FL
350RS
350FS
0.52
Return Inlet Factors
Core Defl.
Anemometer
Core Area, Square Feet Factors
6 0.12 0.19 8 0.16 0.26 0.37
10 0.21 0.34 0.47 0.59 12 0.25 0.41 0.57 0.72 0.88 14 0.30 0.48 0.67 0.85 1.04 1.22 16 0.34 0.57 0.77 0.98 1.19 1.40 1.62 18 0.39 0.63 0.88 1.11 1.35 1.59 1.83 2.07 20 0.43 0.72 0.97 1.24 1.50 1.77 2.04 2.31 2.57 22 0.48 0.77 1.07 1.37 1.66 1.96 2.25 2.55 2.84 24 0.52 0.88 1.17 1.49 1.82 2.14 2.46 2.79 3.11 3.75 26 0.57 0.92 1.27 1.62 1.97 2.32 2.67 3.02 3.38 4.08 28 0.62 0.99 1.37 1.75 2.13 2.51 2.89 3.26 3.64 4.40 30 0.66 1.11 1.47 1.88 2.29 2.69 3.10 3.50 3.91 4.72 5.94 32 0.71 1.14 1.57 2.01 2.44 2.88 3.31 3.74 4.18 5.05 6.35 34 0.75 1.21 1.67 2.14 2.60 3.06 3.52 3.98 4.44 5.37 6.75 36 0.80 1.29 1.77 2.26 2.75 3.24 3.73 4.22 4.71 5.69 7.16 8.63 38 0.84 1.36 1.88 2.39 2.91 3.43 3.94 4.46 4.98 6.01 7.57 9.12 40 0.89 1.43 1.98 2.52 3.07 3.61 4.16 4.70 5.25 6.34 7.97 9.61 42 0.93 1.50 2.08 2.65 3.22 3.80 4.37 4.94 5.51 6.66 8.38 10.10 48 1.07 1.72 2.38 3.04 3.69 4.35 5.00 5.66 6.32 7.63 9.60 11.57 15.50 54 1.20 1.94 2.68 3.42 4.16 4.90 5.64 6.38 7.12 8.60 10.82 13.04 17.47 60 1.34 2.16 2.98 3.81 4.63 5.45 6.27 7.10 7.92 9.57 12.04 14.50 19.44 66 1.47 2.38 3.29 4.19 5.10 6.00 6.91 7.82 8.72 10.54 13.25 15.97 21.41 72 1.61 2.60 3.59 4.58 5.57 6.56 7.55 8.54 9.52 11.50 14.47 17.44 23.38
Core Area = Nominal Duct Size - 3/4 inch
All rights reserved. No part of this work may be reproduced or transmitted in any form or any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air Distribution Technologies
Notes:
• Detail A-A is used for vertical joints. The frames of both vertical sides of the joint are sheared and then butted together. Alignment tabs serve to keep the face surfaces parallel.
• Detail B-B is used for horizontal joining. Horizontal frames are installed full width with an aluminum mullion in between each frame.
• This page is for Border Type 1 grilles only.
CB
A
STEEL FRAME ALUMINUM FRAME
1-150.16 • OCTOBER, 2019
STEAM/HOT WATER UNIT HEATERS
MODEL HSB/HC MODEL V/VN
MODEL GLW
MODEL PT/PTN
MODEL HCH
TABLE OF CONTENTS
As Modine Manufacturing Company has a continuous product improvement program, it reserves the right to change design and specifications without notice.
Table of Contents Page
I. Design Benefits
Performance Data
TM
Dimensional Data
IV. Model Identification
V. Specifications
Refer to page 9 for information regarding the BreezeTM AccuSpec Sizing and Selection Program
Canadian Registered heat exchangers
CRN
OH 9234.5C
*Does not apply to V/
PT 952
Wide Product Selection
Application Flexibility
Ease of Installation/Maintenance = Reliability
Blends with the Environment
DESIGN BENEFITS
Unit Features - Horizontal Delivery Unit Heaters
In addition to the features noted on page 2, features that enhance the popularity of the horizontal delivery unit heater are:
Connections
Vertical Fins
Coil
Motor
Fan
Deflector Blades
Safety Fan Guard
Casings
Figure 4.1 - Unit Features
Unit Features - Vertical Delivery Unit Heaters
In addition to the features noted on page 2, features that enhance the popularity of the vertical delivery unit heater are:
Motor-Cooling Cone
Coil
Motor
Fan
Junction Box
Motor Easily Removable
Vertical Fins
Casings
Figure 5.1 - Unit Features
Unit Features - Power-ThrowTM Horizontal Delivery Unit Heaters
In addition to the features noted on page 2, features that enhance the popularity of the Power-Throw� horizontal delivery unit heater are:
Unit Features - Low Water Temperature Greenhouse Heating Units
Standard features include:
Unit Sizing
Example:
Dimensions and Specifications - Model GLW660S, GLW330S
Figure 6.2 - Top View Figure 6.3 - Discharge and Side Views
Figure 6.1 - Model GLW Performance Curves
Table 7.1 Factory Mounted Options
Factory Mounted Option Description
Table 7.2 Field Installed Accessories for Horizontal Models
Field Installed Accessories Description
Table 7.3 Field Installed Accessories for Vertical Models
Field Installed Accessories Description
Table 7.4 Field Installed General Accessories
Field Installed Accessories Description
Options and Accessories
Power Code Descriptions & Control Sequence
Control Sequence
Intermittent Fan Operation - Hot Coil
Continuous Fan Operation - Intermittent Hot/Cold Coil
Intermittent Fan Operation - Intermittent Hot/Cold Coil
Supply Voltage Motor Enclosure Motor Type Motor Starter
Table 8.1 Power Code Descriptions
Power Thermal Overload Code Protection
PERFORMANCE DATA
Modine Breeze AccuSpec Sizing and Selection Program
[HSB/HC/V/VN/PT/PTN] [HSB/HC/V/VN/PT/PTN]
Steam Conversion Tables
Table 10.1 Steam Heating Capacity Conversion Factors
Unit Steam Entering Air Temperature (°F) Heater Pressure Type (PSIG)
BtuA = BtuS x Heating Capacity Factor
BtuS = BtuA ÷ Heating Capacity Factor
Ho riz on ta l D el iv er y Ve rti ca l D el iv er y an d Po w er
-T hr ow
-10 0 10 20 30 40 50 60 70 80 90 100
Steam Conversion Tables
Table 11.1 Air Temperature Rise Conversion Factors
Unit Steam Entering Air Temperature (°F) Heater Pressure Type (PSIG)
ATRA = (FATS - EATS ) x Air Temperature Rise Factor
FATA = EATA + ATRA
Ho riz on ta l D el iv er y Ve rti ca l D el iv er y an d Po w er
-T hr ow
-10 0 10 20 30 40 50 60 70 80 90 100
Steam Conversion Tables
Table 12.1 Steam Unit Heater Mounting Height Correction Factors
Steam Pressure, PSIG 2 5 10 15 20 30 40 50 60 70 80 90 100 125 150 175 200 225 250 Correction Factor
Max. Mounting HeightA = Max. Mounting HeightS x Correction Factor
Table 12.2 Properties of Steam
Gauge Latent Gauge Latent Gauge Latent Gauge Latent Pressure Temp Heat Pressure Temp Heat Pressure Temp Heat Pressure Temp Heat (PSIG) (°F) (Btu/lb.) (PSIG) (°F) (Btu/lb.) (PSIG) (°F) (Btu/lb.) (PSIG) (°F) (Btu/lb.)
0 34 70 109
2 36 72 112 4 38 74 115 5 40 76 118 6 42 78 121 8 44 80 124 10 46 82 125 12 48 84 127 14 50 86 130 16 52 88 133 18 54 90 136 20 56 92 139 22 58 94 142 24 60 96 145 26 62 98 150 28 64 100 175 30 66 103 200 32 68 106 225
Condensate rate = BtuA ÷ Latent Heat of Steam
Steam Performance Data - Standard Models
Type Model No. Btu/hr Sq. Ft. EDR
Air Data Motor Data
Maximum Mounting Height (ft.)
Heat Throw or Spread @ Max.
Height
CFM Outlet Velocity (Fpm)
Final Air Temp. (°F)
Condensate lb/hr Hp Approx.
RPM
Horizontal Delivery
HSB/HC 18
HSB/HC 24
HSB/HC 33
HSB/HC 47
HSB/HC 63
HSB/HC 86
HSB/HC 108
HSB/HC 121
HSB/HC 165
HSB/HC 193
HSB/HC 258
HSB/HC 290
HSB/HC 340
Power Throw�
PT/PTN 279
PT/PTN 333
PT/PTN 385
PT/PTN 500
PT/PTN 610
PT 952
Vertical Delivery
V/VN 42 15 11
V/VN 59 19 14
V/VN 78 20 15
V/VN 95 20 15
V/VN 139 24 18
V/VN 161 27 20
V/VN 193 30 22
V/VN 212 30 22
V/VN 247 34 26
V/VN 279 37 30
V/VN 333 37 30
V/VN 385 36 30
V/VN 500 44 37
V/VN 610 43 36
V 952
Table 13.1 - Performance Data for Standard Units at Standard Conditions of 2 lb. Steam and 60°F Entering Air High Motor Speed
Table 13.2 - Performance Data for Standard Units at Standard Conditions of 2 lb. Steam and 60°F Entering Air Reduced Motor Speed
Type Model No. Btu/hr Sq. Ft.
EDR
Air Data Motor Data
Maximum Mounting Height (ft.)
Heat Throw or Spread @
Max. Height CFM Outlet
Velocity (Fpm)
Final Air Temp.
(°F)
Condensate lb/hr Hp Approx.
RPM
Horizontal Delivery
HSB/HC 18
HSB/HC 24
HSB/HC 33
HSB/HC 47
HSB/HC 63
HSB/HC 86
HSB/HC 108
Steam Performance Data - Low Outlet Temperature Models
Table 14.2 - Performance Data for Low Outlet Temperature Units at Standard Conditions of 2 lb. Steam and 60°F Entering Air Reduced Motor Speed
Table 14.1 - Performance Data for Low Outlet Temperature Units at Standard Conditions of 2 lb. Steam and 60°F Entering Air High Motor Speed
Type Model No. Btu/hr Sq. Ft. EDR
Air Data Motor Data
Maximum Mounting Height (ft.)
Heat Throw or Spread @ Max.
Height
CFM Outlet Velocity (Fpm)
Final Air Temp. (°F)
Condensate lb/hr Hp Approx.
RPM
Horizontal Delivery
HSB/HC 18L
HSB/HC 24L
HSB/HC 33L
HSB/HC 47L
HSB/HC 63L
HSB/HC 86L
HSB/HC 108L
HSB/HC 121L
HSB/HC 165L
HSB/HC 258L
HSB/HC 290L
HSB/HC 340L
Power Throw� PT/PTN 610L
Vertical Delivery
V 42L 17 13 V 59L 22 16 V 78L 26 19 V 95L 26 19
V/VN 139L 31 23
V/VN 161L 35 26
V/VN 193L 36 27
V/VN 212L 36 27
V/VN 247L 42 32
V/VN 279L 45 36
V/VN 333L 45 36
V/VN 385L 43 36
V/VN 500L 54 45
V/VN 610L 52 44
V 952L - -
Type Model No. Btu/hr Sq. Ft. EDR
Air Data Motor Data
Maximum Mounting Height (ft.)
Heat Throw or Spread @ Max.
Height
CFM Outlet Velocity (Fpm)
Final Air Temp. (°F)
Condensate lb/hr Hp Approx.
RPM
Horizontal Delivery
HSB/HC 18L
HSB/HC 24L
HSB/HC 33L
HSB/HC 47L
HSB/HC 63L
HSB/HC 86L
HSB/HC 108L
Steam Conversion Tables - Example Calculations
Conversion factor example #1:
Solution:
Conversion factor example #2:
Solution:
Alternate Solution:
Table 16.1 Hot Water Heating Capacity Conversion Factors Entering Water Entering Air Temperature (°F) Temp. (°F) 0 10 20 30 40 50 60 70 80 90 100
BtuA = BtuS x Heating Capacity Factor
BtuS = BtuA ÷ Heating Capacity Factor
Hot Water Conversion Tables
Hot Water Conversion Tables
Table 17.2 - Ethylene Glycol Correction Factors
BtuAG = BtuS (or BtuA) x Glycol Correction Factor
BtuS (or BtuA) = BtuAG ÷ Glycol Correction Factor
Table 17.3 - Hot Water Unit Heater Mounting Height Correction Factors
Max. Mounting HeightA = Max. Mounting HeightS x Correction Factor
Ethylene Glycol Solution % Solution Temperature (°F) 20% 30% 40% 50% 60% 70% 80%
Table 17.1 - Minimum Water Flow and Water Volume (gallons)
Entering Water Correction Entering Water Correction Entering Water Correction Temperature, °F Factor Temperature, °F Factor Temperature, °F Factor
140 230 320 150 240 330 160 250 340 170 260 350 180 270 360 190 280 370 200 290 380 210 300 390 220 310 400
Table 18.1 Correction Factors for Varying Water Temperature Drop
Water Temperature Drop, °F 5 10 15 20 25 30 35 40 45 50 55 60
Btu Correction Factor GPM Correction Factor WPD Correction Factor
BtuA = BtuS x Btu Correction Factor
GPMA = GPMS x GPM Correction Factor
WPDA = WPDS x WPD Correction Factor
BtuS = BtuA ÷ Btu Correction Factor
FATA = EATA + [(460 + EATA) x (BtuA) ÷ (573 x Cfms)] for HSB and HC units only
FATA = EATA + [(460 + EATA) ÷ ((573 x Cfms ÷ BtuA) - 1)] for V/VN and PT/PTN units only
WTDA = BtuA ÷ (480 x GPMA)
Hot Water Conversion Tables - Miscellaneous Formulas
Hot Water Performance Data - Standard Models
Table 19.1 - Performance Data for Standard Units at Standard Conditions of 200°F Entering Water and 60°F Entering Air High Motor Speed
Table 19.2 - Performance Data for Standard Units at Standard Conditions of 200°F Entering Water and 60°F Entering Air Reduced Motor Speeds
Type Model No. Btu/hr
Water Data Air Data Motor Data
GPM
Pressure Drop (Ft. of Water)
Min/Max
GPM
Maximum Mounting Height (ft.)
Heat Throw or Spread @ Max.
Height CFM Outlet
Velocity (Fpm)
Final Air Temp.
(°F) Hp Approx.
RPM
Horizontal Delivery
HSB/HC 18
HSB/HC 24
HSB/HC 33
HSB/HC 47
HSB/HC 63
HSB/HC 86
HSB/HC 108
HSB/HC 121
HSB/HC 165
HSB/HC 193
HSB/HC 258
HSB/HC 290
HSB/HC 340
Power Throw�
PT/PTN 279
PT/PTN 333
PT/PTN 385
PT/PTN 500
PT/PTN 610
PT 952
Vertical Delivery
V/VN 42 16 12
V/VN 59 20 15
V/VN 78 22 16
V/VN 95 22 16
V/VN 139 26 19
V/VN 161 29 22
V/VN 193 32 24
V/VN 212 32 24
V/VN 247 37 28
V/VN 279 40 32
V/VN 333 40 32
V/VN 385 39 32
V/VN 500 47 40
V/VN 610 46 39
V 952 - -
Type Model No. Btu/hr
Water Data Air Data Motor Data
GPM
Pressure
Drop (Ft. of Water)
Maximum Mounting
Height (ft.)
Heat Throw or Spread @ Max.
Height
CFM Outlet Velocity (Fpm)
Final Air Temp. (°F) Hp Approx.
RPM
Horizontal Delivery
HSB/HC 18
HSB/HC 24
HSB/HC 33
HSB/HC 47
HSB/HC 63
HSB/HC 86
HSB/HC 108
Hot Water Performance Data - Low Outlet Temperature Models Table 20.1 - Performance Data for Low Outlet Temperature Units at Standard Conditions of 200°F Entering Water and 60°F Entering Air � High Motor Speed
Table 20.2 - Performance Data for Low Outlet Temperature Units at Standard Conditions of 200°F Entering Water and 60°F Entering Air � Reduced Motor Speeds
Type Model No. Btu/hr
Water Data Air Data Motor Data
GPM
Pressure Drop (Ft. of Water)
Min/Max GPM Maximum Mounting
Height (ft.)
Heat Throw or Spread @ Max.
Height CFM Outlet
Velocity (Fpm)
Final Air Temp. (°F) Hp Approx.
RPM
Horizontal Delivery
HSB/HC 18L
HSB/HC 24L
HSB/HC 33L
HSB/HC 47L
HSB/HC 63L
HSB/HC 86L
HSB/HC 108L
HSB/HC 121L
HSB/HC 165L
HSB/HC 258L
HSB/HC 290L
HSB/HC 340L
Power Throw� PT/PTN 610L
Vertical Delivery
V 42L 18 14 V 59L 23 17 V 78L 28 21 V 95L 28 21
V/VN 139L 33 25
V/VN 161L 37 28
V/VN 193L 38 29
V/VN 212L 38 29
V/VN 247L 45 35
V/VN 279L 48 39
V/VN 333L 48 39
V/VN 385L 46 49
V/VN 500L 57 49
V/VN 610L 55 48
V 952L
Type Model No. Btu/hr
Water Data Air Data Motor Data
GPM Pressure Drop (Ft. of Water)
Maximum Mounting Height (ft.)
Heat Throw or Spread @ Max.
Height
CFM Outlet Velocity (Fpm)
Final Air Temp.
(°F) Hp Approx.
RPM
Horizontal Delivery
HSB/HC 18L
HSB/HC 24L
HSB/HC 33L
HSB/HC 47L
HSB/HC 63L
HSB/HC 86L
HSB/HC 108L
Hot Water Performance Data � High Efficiency Low EWT Models
Table 21.1 - Performance Data for Low Outlet Temperature Units at Standard Conditions of 140°F Entering Water and 60°F Entering Air � High Motor Speed
Type Model No. Btu/hr
Water Data Air Data Motor Data
GPM
Pressure Drop (Ft. of Water)
Min/Max GPM Maximum Mounting
Height (ft.)
Heat Throw or Spread @ Max.
Height CFM Outlet
Velocity (Fpm)
Final Air Temp. (°F) Hp Approx.
RPM
Horizontal Delivery
HCH 22
HCH 39
HCH 67
HCH 104
HCH 170
HCH 195
Hot Water Conversion Tables - Example Calculations
Conversion factor example #1:
Solution:
Conversion factor example #2:
Solution:
Maximum Mounting Heights for Vertical Outlet Accessories, Dimensions
Table 23.1 Mounting Height/Spread for Vertical Unit Air Outlet Accessories
HH
HH H
S S S S S
Table 23.2 - Vertical Air Outlet Accessories Dimensions Model Cone-Jet Truncone Louvers
Number L T M X P Z V 42, V 59 V 78, V 95
V 139, V 212 V 247, V 279
V 333 V 385, V 500
V 610 V-952
Figure 23.2 - Vertical Air Outlet Accessories
L
T
X Z
P M
CONE-JET TRUNCONE LOUVER
Cone-Jet Truncone One Way Louvers Two Way Louvers
Standard L.O.T. Standard L.O.T. Standard L.O.T. Standard L.O.T.
Model H S H S H S H S H S H S H S H S
V/VN 42
V/VN 59
V/VN 78
V/VN 95
V/VN 139
V/VN 161
V/VN 193
V/VN 212
V/VN 247
V/VN 279
V/VN 333
V/VN 385
V/VN 500
V/VN 610
V 952
Motor Data, Step-Down Transformer Accessory Data
Table 24.1 - Motor Data
Figure 24.1 Field Installed Transformer Accessory
Table 24.2 - Step-Down Transformer Accessory Selection
208V/60Hz/1 230/460V/ 575V/60Hz/ or 3 phase 60Hz/3 phase 3 phase Model Number kVA kVA kVA
HSB/HC 18-63
HSB/HC 86-121
HSB/HC 165-193
HSB/HC 258-340
V/VN 42-59
V/VN 78-139
V/VN 161-212
V/VN 247-333
PT/PTN 279-333
kVA Size Ship Wt. (Lb.)
Available Motor Type, Voltage and Power Code
115/60/1 208/60/1 230/60/1 208/60/3 230/460/3 575/60/3 115/60/1 230/460/60/3 Model Number Motor HP 01 N/A 02 04 05 10 06 09
HSB/HC 18
HSB/HC/HCH 22, 39, 24, 33
HSB/HC 47, 63
HSB/HC/HCH 67, 104, 86, 108 ,
HSB/HC 121
HSB/HC/HCH 165, 170, 193, 195
HSB/HC 258-340
V/VN 42, 59
V/VN 78, 95
V/VN 139
V/VN 161-212
V/VN 247
V/VN, PT/PTN 279
V/VN, PT/PTN 333
V/VN, PT/PTN 385
V/VN, PT/PTN 500, 610
V, PT 952
Explosion-proofTotally Enclosed
DIMENSIONAL DATA
Dimensions - Horizontal Air Delivery Models
D Female Approx.
Model 115 Std. 115V Exp. Connections Fan Shipping Number A B C Motor Motor E F G H NPT Diameter Wt. lb.
HSB 18
HSB 24
HSB 33
HSB 47
HSB 63
HSB 86
HSB 108
HSB 121
HSB 165
HSB 193
HSB 258
HSB 290
HSB 340
HC 18
HC 24
HC 33
HC 47
HC 63
HC 86
HC 108
HC 121
HC 165
HC 193
HC 258
HC 290
HC 340
Figure 25.1 - Model Dimensions HSB 18-193
Figure 25.3 - Model Dimensions HC 18-165
Table 25.1 - Model HSB and HC Dimensions
Figure 25.2 - Model Dimensions HSB 258-340
Figure 25.4 - Model Dimensions HC 193-340
Dimensions - Horizontal Air Delivery Models
Table 26.2- Model Dimensions HCH 22-195
Figure 26.1 - Model Dimensions HCH 22-195
Model Number A B C
D
E
F
G H Connections Copper Tube
OD (in.)
Fan Diameter
(in.)
Shipping
Wt. lb.
115V Std.
Motor Exp.
Motor Inlet Outlet
HCH 22
HCH 39
HCH 67
HCH 104
HCH 170
HCH 195
Dimensions - Vertical Air Delivery Models
Figure 27.1 - Model V/VN and PT/PTN Dimensions
Table 27.2 - Model V/VN and PT/PTN Dimensions Male
Connections Approx.
Model Fan NPT Shipping Number A B C D E F G Diameter Top Bottom Wt. (lb.)
V/VN 42
V/VN 59
V/VN 78
V/VN 95
V/VN 139
V/VN 161
V/VN 193
V/VN 212
V/VN 247
V/VN 279
V/VN 333
V/VN 385
V/VN 500
V/VN 610
V 952
PT/PTN 279
PT/PTN 333
PT/PTN 385
PT/PTN 500
PT/PTN 610
PT 952
Vertical Air Delivery Power-Throw� Air Delivery
C
C
DMALE
RETURN
MALE
SUPPLY
WVC/WVN 42 THROUGH V/WVN 279
MALE SUPPLY
MALE RETURN
WVC/WVN 333,
WVC/WVN 385,
WVC/WVN 500
C
D
WVC/WVN 333 THROUGH WVC 952
MALE RETURN
WVC/WVN 610/952
8-MOUNTING HOLES
5/8" DIA. IN ANGLE
IRON BRACKET4-MOUNTING
HOLES
1/2"-13 TAP
G
MODEL IDENTIFICATION
Model Identification
Figure 28.1 Model Number Designation
Figure 28.2 Serial Number Designation
Figure 27.3 Model Identification Plate
05 01 12 98 - 0007 Motor
Fan
Year of Manufacture
Week of Manufacture
Sequence Number
HSB 108 S B 01 S A
Model Type
HC / HSB / PT /
PTN / V / VN
MBH Input @ 2 lbs. steam 60°F E.A.T.
Coil Type S - Standard L - Low Outlet Temperature
Development Sequence B - Current
Power Code 01 - 115V/60Hz/1ø 02 - 230V/60Hz/1ø etc.
Fan Guard Type S - Standard F - Finger Proof
Factory Installed Option A - None
SPECIFICATIONS
Specification for Horizontal, Vertical and Power-Throw� Models
General
Casing HSB and HC Models
Vertical and Power-Throw� Models
All Models -
Condenser
Horizontal Models -
Vertical and Power-Throw� Models
Motors
Fans/Fan Guards
Air Deflectors �
Products from Modine are designed to provide indoor air-comfort and ventilation solutions for residential, commercial, institutional and industrial applications.
Whatever your heating, ventilating and air conditioning requirements, Modine has the product to satisfy your needs, including:
HVAC
• Unit Heaters:
– Gas
– Hydronic
– Electric
– Oil
• Ceiling Cassettes
• Duct Furnaces
• Hydronic Cabinet Unit Heaters, Fin Tube, Convectors
• Infrared Heaters
• Make-up Air Systems
• Unit Ventilators
Ventilation
• Packaged Rooftop Ventilation
School Products
• Vertical Packaged Classroom HVAC:
– DX Cooling/Heat Pump
– Water/Ground Source Heat Pump
– Horizontal/Vertical Unit Ventilators
Specific catalogs are available for each product. Catalogs 75-136 and 75-137 provide details on all Modine HVAC equipment.
Modine Manufacturing Company
1500 DeKoven Avenue
Racine, Wisconsin 53403-2552
Phone: 1.800.828.4328 (HEAT) www.modinehvac.com
© Modine Manufacturing Company 2019
The Modine brand has been the industry standard since Arthur B.
Modine invented and patented the first lightweight, suspended hydronic unit heater in 1923.
No other manufacturer can provide the combined application flexibility, technical expertise and fast delivery found at Modine.
Consult your local Modine distributor for help in solving your indoor air problems.
TITUS Metric Performance Data TMS 7/21/98
Note: All dimensions are nominal • product will be built to the closest inch equivalent dimension unless specially ordered to true metric
• contact factory for availability of sizes •
990 Security Row • Richardson, Texas 75081TITUS
Telephone 972-699-1030 • FAX 972-918-8880 G104-S All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying, or by an information storage system, without permission in writing from TITUS
TMS
600mm x 600mm Module Size
Neck Velocity 2.0 2.5 3.0 3.5 4.0 5.0 6.0 7.0 8.0
Velocity Pressure, Pa 2 4 6 8 10 16 22 30 40
Air Flow, Liters/s 37 46 56 65 74 93 111 130 148
150mm Total Pressure, Pa 4 6 9 12 16 25 35 48 63
Dia. NC ( Noise Criteria) - - - 12 16 22 28 32 36
Throw , m 0.3 - 0.5 - 1.3 0.3 - 0.5 - 1.3 0.5 - 1 - 1.5 0.5 - 1 - 1.8 0.5 - 1.3 - 2.3 1 - 1.3 - 2.8 1.3 - 1.5 - 3.3 1.3 - 1.8 - 3.8 1.5 - 2.3 - 4
Air Flow, Liters/s 66 82 99 115 132 165 198 231 264
200mm Total Pressure, Pa 4 6 9 12 16 25 36 49 64
Dia NC ( Noise Criteria) - - 11 15 19 26 31 36 40
Throw , m 0.5 - 1 - 1.5 0.5 - 1 - 2.3 1 - 1.3 - 2.5 1 - 1.5 - 2.8 1.3 - 1.5 - 3.3 1.3 - 2.3 - 4 1.5 - 2.5 - 4.3 1.8 - 2.8 - 5 2.3 - 3.3 - 5.3
Air Flow, Liters/s 103 129 154 180 206 257 309 360 412
250mm Total Pressure, Pa 4 6 9 13 16 26 37 50 66
Dia NC ( Noise Criteria) - - 14 18 22 29 34 39 43
Throw , m 0.5 - 1.3 - 2.3 1 - 1.5 - 2.8 1.3 - 1.5 - 3.3 1.3 - 1.8 - 4 1.5 - 2.3 - 4.3 1.8 - 2.8 - 5.3 2.3 - 3.3 - 5.5 2.5 - 4 - 6 3 - 4.3 - 6.5
Air Flow, Liters/s 148 185 222 259 297 371 445 519 593
300mm Total Pressure, Pa 4 7 10 13 17 26 38 52 68
Dia NC ( Noise Criteria) - 11 16 21 24 31 36 41 45
Throw , m 1 - 1.5 - 2.8 1.3 - 1.8 - 3.3 1.5 - 2.3 - 4.3 1.5 - 2.5 - 5 1.8 - 2.8 - 5.5 2.5 - 3.3 - 6 2.8 - 4.3 - 6.8 3.3 - 5 - 7 3.8 - 5.5 - 7.5
Air Flow, Liters/s 202 252 303 353 404 505 605 706 807
350mm Total Pressure, Pa 4 7 10 13 18 27 39 54 70
Dia NC ( Noise Criteria) - 13 18 22 26 33 38 43 47
Throw , m 1.3 - 1.5 - 3.3 1.5 - 2.3 - 4.3 1.5 - 2.5 - 5 1.8 - 3 - 5.8 2.3 - 3.3 - 6.5 2.8 - 4.3 - 7 3.3 - 5 - 7.5 4 - 5.8 - 8.3 4.3 - 6.5 - 8.8
Air Flow, Liters/s 232 290 348 405 463 579 695 811 927
375mm Total Pressure, Pa 4 7 10 14 18 28 40 55 72
Dia NC ( Noise Criteria) - 13 19 23 27 34 39 44 48
Throw , m 1.3 - 1.8 - 3.8 1.5 - 2.3 - 4.5 1.8 - 2.8 - 5.5 2.3 - 3 - 6.5 2.5 - 3.8 - 6.8 3 - 4.5 - 7.5 3.8 - 5.5 - 8.3 4.3 - 6.5 - 8.8 5 - 6.8 - 9.5
· Throw values are given for terminal velocities of .8, .50, and .3 m/s.
· Throw Values are given for Isothermal Conditions
· N.C. values are based on Octave Band 2 - 7 sound power levels minus a room absorption of 10dB.
· Dash (-) in space denotes an N.C. value of less than 10.
· Data were obtained from test conducted in accordance with ANSI / ASHRAE Standard 70-1991.
Note: Refer to the Air Balancing Application Guide for more information about balancing air systems.
Air Flow Factors TMS-FF 06-13-07
TMS Air Flow Factors
Neck Diameter Size
Factor Neck Diameter
Size Factor
4-inch 0.07 8-inch 0.28
5-inch 0.11 10-inch 0.43
6-inch 0.16 12-inch 0.62
7-inch 0.19 14-inch 0.85
8-inch 0.28 15-inch 0.97
12 x 12-inch Face 24 x 24-inch Face
Alnor 6070, 6000, 2220, or 2220-A Probe
Locations
Model: TMS Air Flow Measurements:
1. Center the probe on each side of the upper cone as shown to measure air flow.
2. Record and average the four velocity readings.
3. Calculate the flow rate using the following equation.
Flow Rate: CFM = Factor x Average Measured Velocity
Note: Select and use the applicable factor from the following table.
All rights reserved. No part of this work may be reproduced or transmitted in any form or any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air Distribution Technologies
T it u s-
H V
C
S h il o h R o a d
P la n o
T ex as
.2
2.
Gu ide lin es fo r S ur fa ce -M ou nt ing Ce ilin g D iffu se rs
Gu ide lin es fo r S ur fa ce -M ou nt ing Ce ilin g D iffu se rs
O ne o f th e m or e fr eq ue nt ly a sk ed q ue st io ns w e re ce iv e in a pp li ca ti on e ng in ee ri ng r eg ar ds s ur fa ce m ou nt in g
T it us d if fu se rs
. W h en a c ei li ng g ri d is n ot p re se nt
, s ur fa ce m ou nt in g is s pe ci fi ed a nd th e in st al la ti on q ue st io ns a ri se . L in ea r di ff us er s ar e av ai la bl e w it h co nc ea le d m ou nt in g, s qu ar e an d re ct an gu la r di ff us er s w it h sq ua re o r ro un d in le ts a re n ot . T he m os t i m po rt an t t hi ng to k no w a bo ut s ur fa ce m ou nt in g is th at it n or m al ly r eq ui re s ad di ti on al f ra m in g to w h ic h th e un it s w ill b e se cu re d.
O ft en w e re ce iv e ca ll s fo r m ou nt in g in st ru ct io ns a ft er th e sh ee t r oc k ha s be en in st al le d w hi ch is to o la te to p ro vi de f ra m in g w it ho ut r em ov in g th e in st al le d su rf ac e.
F ra m in g re qu ir em en ts w il l va ry f ro m o ne jo b to th e ne xt b ut th er e ar e so m e ge ne ra l g ui de li ne s an d te rm in ol og y w e us e.
O bv io us ly in st al li ng s cr ew s in th e fa ce o f a di ff us er w il l w or k as it d oe s fo r gr il le s bu t d uc t r et ur n fl an ge s be hi nd th e ed ge s of d if fu se rs a re g en er al ly n ot a va ila bl e to p ro vi de a s ec ur e m ou nt in g ba se i nt o w hi ch a s cr ew c an b e ru n.
A nd m an y su rf ac e m ou nt f ra m es d o no t h av e a fl at s ur fa ce n or is th er e a sc re w h ol e fa st en in g op tio n av ai la bl e.
F ur th er
, s cr ew f as te ni ng c er ta in ly d oe s no t e nh an ce th e ae st he ti cs o f th e in st al le d di ff us er ll s he et ro ck is m ou nt ed to c ei lin g jo is ts
. T he se jo is ts a re u su al ly p ar al le l t o ea ch o th er a nd s pa ce d at tw o to th re e fe et a pa rt d ep en di ng o n lo ca l b ui ld in g co de s.
T he f ra m in g fo r th e di ff us er in m os t c as es c an b e m ou nt ed to th e to p of
, a nd p er pe nd ic ul ar to th e jo is ts . S cr ew s ar e th en u se d to m ou nt t he b ac k pa n to th e fr am in g.
T he f ra m in g m em be rs sh ou ld b e ce nt er ed o n th e di ff us er lo ca ti on a nd s ho ul d al lo w s uf fi ci en t c le ar an ce f or th e di ff us er in le t a nd a ss oc ia te d du ct
A dd it io na l c ar e m us t b e ta ke n to a vo id a ny pr ot ru si on s or f ea tu re s th at w il l o cc up y th e sp ac e ne ce ss ar y fo r th e fr am in g on th e re ar s id e of th e di ff us er . T he y sh ou ld a ls o be a t a d ep th th at w il l a ll ow th e di ff us er to fi rm ly s ea t a ga in st th e sh ee t r oc k.
M os t d if fu se r ba ck p an h ei gh ts a re le ss th an th e de pt h of th e jo is t.
T he s he et r oc k or c ei li ng s ur fa ce is in st al le d le av in g an o pe ni ng p ro vi de d fo r th e di ff us er . T he d if fu se r co re s ho ul d be r em ov ed p ri or to in st al la ti on to a ll ow f or s cr ew s to b e in st al le d in th e to p of th e ba ck p an tr an si ti on
; t hi s is th e fl at p or ti on o n th e re ar o f th e ba ck p an
. S cr ew s ar e th en u se d to s ec ur e th e ba ck p an to th e fr am in g.
I t i s he lp fu l t o us e w as he rs to p re ve nt th e sc re w h ea ds f ro m b ei ng d ri ve n th ro ug h th e ba ck p an if th e fr am in g is n ot f lu sh to th e re ar o f th e pa n.
I n m os t c as es th e sc re w s ca n be p la ce d so a s to n ot b e vi si bl e fr om th e oc cu pi ed s pa ce a ft er th e di ff us er c or e or f ac e is r e-in st al le d.
Metric Performance Data DL 7/21/98
M47-S
Model DL NC 20 NC 30 NC 40 rev 09/05/97
Min. Duct L is ted Duct Velocity
Area Size m /s 1.5 2.0 2.5 3.0 3.6 4.1 4.6 5.1 m 2 Vel .Press , Pa 1 2 4 6 8 10 13 16 l /s 61 81 102 122 142 162 183 203
0.04 25 0m m x 15 0mm NC (Noise Criteria) <10 <10 17 23 29 34 38 42
Total Press. , Pa 11 20 32 45 62 81 102 126
T h r o w , m 1.5 - 1.8 - 5 2.3 - 3.3 - 6.8 2.8 - 4.3 - 8 3.3 - 5 - 8.8 4 - 5.8 - 9.5 4.5 - 6.8 - 10 5 - 7.5 - 10.8 5.5 - 8 - 11.3 l /s 118 157 196 236 275 314 354 393
0.08 45 0m m x 15 0mm NC (Noise Criteria) <10 11 19 25 31 35 40 43
Total Press. , Pa 11 20 32 45 62 81 102 126
T h r o w , m 3.3 - 5 - 8.5 4.3 - 6.5 - 10 5.5 - 8 - 11.3 6.5 - 8.5 - 12.3 7.5 - 9.5 - 13 8.3 - 10 - 14 8.5 - 10.8 - 15 9.3 - 11.3 - 15.8 l /s 194 258 323 388 452 517 582 646
0.13 75 0m m x 15 0mm NC (Noise Criteria) <10 10 18 24 29 34 38 42
Total Press. , Pa 11 20 32 45 62 81 102 126
T h r o w , m 5.3 - 8 - 11.3 7 - 9.3 - 12.8 8.3 - 10 - 14.3 9.3 - 11.3 - 15.8 9.8 - 12 - 17 10.3 - 12.8 - 18.3 11.3 - 13.8 - 19.3 11.5 - 14.3 - 20.5 l /s 384 512 640 767 895 1023 1151 1279
0.32 1500m m x 150m m NC (Noise Criteria) <10 16 23 30 35 40 44 48
Total Press. , Pa 11 20 32 45 62 81 102 126
T h r o w , m 9.3 - 11 - 15.5 10.3 - 12.8 - 18 11.5 - 14.3 - 20 12.8 - 15.5 - 22.3 13.8 - 16.8 - 23.8 14.8 - 18 - 25.5 15.5 - 19.3 - 27.3 16.5 - 20 - 28.8 l /s 207 275 344 413 482 551 620 689
0.14 50 0m m x 25 0mm NC (Noise Criteria) <10 13 20 26 31 36 40 44
Total Press. , Pa 8 14 21 31 42 54 69 85
T h r o w , m 5.5 - 8.3 - 11.5 7.5 - 9.5 - 13.5 8.5 - 10.3 - 15 9.5 - 11.5 - 16.3 10 - 12.5 - 17.8 11 - 13.5 - 19 11.5 - 14 - 19.8 12.3 - 15 - 21 l /s 507 676 845 1014 1183 1352 1521 1690
0.33 1250m m x 250m m NC (Noise Criteria) <10 16 23 29 35 40 44 48
Total Press. , Pa 8 14 21 31 42 54 69 85
T h r o w , m 10.3 - 12.8 - 18 12 - 14.8 - 20.8 13.5 - 16.5 - 23.3 14.8 - 18 - 25.5 15.8 - 19.5 - 27.5 17 - 20.8 - 29.3 18 - 22 - 31 19 - 23.3 - 33 l /s 707 943 1179 1415 1651 1886 2122 2358
0.46 1750m m x 250m m NC (Noise Criteria) <10 18 25 31 36 41 45 49
Total Press. , Pa 8 14 21 31 42 54 69 85
T h r o w , m 12.3 - 15 - 21.3 14.3 - 17.3 - 24.8 15.8 - 19.5 - 27.5 17.3 - 21.3 - 30.3 19 - 22.8 - 32.5 20 - 24.8 - 34.8 21.3 - 26 - 37 22.5 - 27.5 - 38.8 l /s 247 330 412 494 577 659 741 824
0.16 50 0m m x 30 0mm NC (Noise Criteria) <10 13 20 27 32 37 41 45
Total Press. , Pa 7 13 20 29 39 51 64 79
T h r o w , m 6.8 - 8.8 - 12.5 8.3 - 10.3 - 14.8 9.5 - 11.5 - 16.3 10.3 - 12.5 - 17.8 11 - 13.8 - 19.3 12 - 14.8 - 20.5 12.5 - 15.3 - 21.8 13 - 16.3 - 22.8 l /s 487 649 811 974 1136 1298 1460 1623
0.32 1000m m x 300m m NC (Noise Criteria) <10 16 23 29 35 39 44 47
Total Press. , Pa 7 13 20 29 39 51 64 79
T h r o w , m 10 - 12.5 - 17.8 12 - 14.3 - 20.5 13 - 16.3 - 22.8 14.3 - 17.8 - 25 15.5 - 19 - 26.8 16.8 - 20.5 - 28.8 17.8 - 21.8 - 30.5 18.5 - 22.8 - 32.3 l /s 846 1128 1411 1693 1975 2257 2539 2821
0.56 1750m m x 300m m NC (Noise Criteria) <10 19 26 32 37 42 46 50
Total Press. , Pa 7 13 20 29 39 51 64 79
T h r o w , m 13.5 - 16.5 - 23.3 15.5 - 19 - 26.8 17.3 - 21.3 - 29.8 19 - 23.3 - 33 20.5 - 25 - 35.8 22 - 26.8 - 38 23.3 - 28.3 - 40.3 24.5 - 29.8 - 42.3 l /s 233 311 389 467 544 622 700 778
0.15 40 0m m x 40 0mm NC (Noise Criteria) <10 13 20 27 32 37 41 45
Total Press. , Pa 6 11 17 24 33 43 54 67
T h r o w , m 5.8 - 8.5 - 12.3 7.5 - 10 - 14 9.3 - 11.3 - 15.8 10 - 12.3 - 17.3 10.8 - 13 - 18.5 11.5 - 14 - 19.8 12.3 - 15 - 21 12.8 - 15.8 - 22.3 l /s 756 1008 1260 1512 1764 2016 2268 2520
0.50 1250m m x 400m m NC (Noise Criteria) <10 18 25 31 36 41 45 49
Total Press. , Pa 6 11 17 24 33 43 54 67
T h r o w , m 12.8 - 15.5 - 22 14.8 - 18 - 25.3 16.5 - 20 - 28.3 18 - 22 - 31 19.5 - 23.8 - 33.5 20.8 - 25.3 - 36 22 - 26.8 - 38 23.3 - 28.3 - 40.3 l /s 1055 1406 1758 2109 2461 2812 3164 3515
0.69 1750m m x 400m m NC (Noise Criteria) 10 19 27 32 38 43 47 51
Total Press. , Pa 6 11 17 24 33 43 54 67
T h r o w , m 15 - 18.3 - 26 17.3 - 21.3 - 29.8 19.3 - 23.8 - 33.5 21.3 - 26 - 36.5 22.8 - 28 - 39.5 24.5 - 29.8 - 42.3 26 - 31.8 - 45 27.5 - 33.5 - 47.3
Data Notes: NC 50
- All data is based on tests conducted in accordance with ASHRAE 70-91
- Throw is based on iso-thermal air, 0.8, 0.5, 0.3 m/s terminal velocities
- Velocity Pressures are based on nominal duct velocity.
- Each NC value represents the noise criterion w hich will not be exceeded by the sound pressure in any of the octave bands, 2nd through 7th. Each NC value is based on a room absorption of 10 dB, re 10 -12 w atts.
- Throw is based on a 15o upward deflection. For 0o multiply throws shown by 1.2, for 30o multiply by 0.8.
Note: All dimensions are nominal • product will be built to the closest inch equivalent dimension unless specially ordered to true metric
• contact factory for availability of sizes •
All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying, or by an information storage system, without permission in writing from Air Distribution Technologies.
605 Shiloh Road • Plano, Texas 75074 • 972-212-4800®
Model: Rectangular Drum Louver (DL) Air Flow Measurements:
1. Position the Alnor velometer 2220A probe at blade
Note: Probe position is always blade center, regardless of spread.
2. Select appropriate area factor from the table below.
3. Calculate flow rate using the following equation.
Flow Rate: CFM = A x Average Velocity
Air Flow Factors DL-FF 03-24-04
Rectangular Drum Louver AK Factors
All rights reserved. No part of this work may be reproduced or transmitted in any form or any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air Distribution Technologies
(L)
(T)
(B)
(L)
(R)
(S)
(T)
(B)
(L)
(R)